Questions and Answers #1

Solicitation Number: HSCG85-16-Q-P45279 - DRY DOCK REPAIRS FY2016 FOR USCGC WIRE (WYTL-65612) Q: Item O-007 Please, provide QTY of FT:

A: APPROXIMATELY 6 FT TOTAL, NON-LINEAR

Q: Item D-027 Under paragraph 3.1.2 there is no Tech. Rep required but paragraph 3.2 & 3.3 calls for a Technical Rep to supervise work. Please, clarify. Also, piano wire is acceptable for alignment or laser alignment is required?

A: NO TECH REP IS NECESSARY UNLESS THE CONTRACTOR CANNOT COMPLETE THE WORK IN HOUSE. LASER ALIGNMENT IS REQUIRED.

Q: Item D-030 Scope calls for 18 sqft and paragraph 3.2 for 10 sqft. Is 18 sqft a typo mistake? Please, clarify.

A: 18 ft…the 10 ft is the typo mistake.

Q: For items 003, 004, 005 & 006 repair up to 8 sqft of steel plate and 030, 031 & 032 repair up to 10 sqft of steel plate – will the repairs be done in one increment? If there are small increments, what is the minimum plating size?

A: They are small increments; the smallest being approximately 6”x6” of each item.

Q: For item 029: Please, provide minimum sqft of spot abatement of lead-based paint

A: 140 sq ft is the minimum.