1.0 Statement of Need.

This requirement is for the acquisition of nine (9) 4’ x 6’ Downdraft tables to be used by the Aviation Logistics Center. These downdraft tables will be used to provide a cleaner, safer, and healthier work environment by capturing hazardous dust particles during grinding and sanding operations on parts and assemblies. The contractor shall provide the Downdraft tables at the firm fixed price(s) specified in the resultant Purchase Order.

2.0 Requirements.

Dimensions
4 feet x 6 feet
Table Top
Fully Ventilated
Sides
Removable
Side Height
Between 15 and 20 inches
Table Height from Floor
Between 36 and 44 inches with casters included
Airflow
At least 205 (FPM)
Power Requirement
Single Phase, 230 volt
Safety Rating
Units must be UL “Class 2” (spark resistant)
Motor
Must be mounted externally and cannot contain any components capable of producing a spark which can come into contact with dust generated from sanding and/or grinding operations
Casters
Units must contain lockable casters
Paint
Units must have a durable industrial paint finish
Construction
Units must be all welded construction
Bearings
All bearings must be sealed with no requirements to grease
Filtration
Units must use HEPA filtration system MERV 14 high efficiency main filters or higher and MERV 9 high capacity pre-filters
Filter Access
Should include tool-less quick open access door(s)
Gauge
Units must include an easily readable Magnehelic type filter pressure monitor gauge
Hazardous Dust Capture
Units must meet all standards for capturing Hexavalent Chromium and other hazardous dust
Operation
Units must be direct drive with no belts to inspect or replace
Motor Compartment
Units must include an acoustic lined blower motor compartment
Electrical Connections
Connections must be 18 or more inches from the floor
Table Access
Workers must be able to utilize all 4 sides of the table
Cleaned Air
Discharge must be at bottom of the unit to allow for access to all 4 sides
Sound Level
Must be 85 decibels or below at 5 feet (1.52 meters)