HOFU_237580-FINAL CD_ COMBINED DRAWINGS-120919.pdf

PDF 4 MB Posted

Attached to
HOFU UPGRADE HVAC, PAINT STORE MUSEUM COLLECTTION
Solicitation number
140P4220R0061
Issued by

About this file

This solicitation is for HVAC replacement, interior and exterior painting, window and door repair, deck repair, and collection storage services at the HOFU site. The National Park Service Northeast Region is seeking these services to upgrade the HVAC system, paint interior display rooms and the exterior, and properly store the museum collection. Offerors should propose pricing to remove the existing HVAC system, install a new high-efficiency system, paint all interior spaces designated for display and the building exterior, repair windows and doors, refurbish exterior decks, and remove and store the collection according to federal standards. The response deadline is not provided. The period of performance and award date are also unspecified.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/3

/2

:0

:2

A

M P

\1

H

O F

U I ro n m a s te r' s H o u s e H

V A

C \R e v it \I R

O N

M A

S T

E R

'S H

O U

S E

.r v t

Designer

Author

Checker

10/30/2019

G-0.1

DRAWING INDEX

DRAWING INDEX

G - 0.0

G - 0.1

G - 0.2

A - 1.0

A - 1.1

A - 1.2

A - 1.3

A - 2.1

A - 2.2

H - 0.0

H - 1.1

H - 2.1

H - 3.1

H - 3.2

H - 3.3

H - 3.4

H - 5.0

H - 7.0

H - 8.0

E - 0.0

E - 2.1

E - 4.1

E - 4.2

E - 4.4

E - 7.1

COVER SHEET

DRAWING INDEX

SITE PLAN

BASEMENT FLOOR PLAN

FIRST FLOOR PLAN

SECOND FLOOR PLAN

ATTIC PLAN

REFLECTED CEILING PLAN - FIRST FLOOR

REFLECTED CEILING PLAN - SECOND FLOOR

HVAC COVER SHEET

HVAC ZONING PLANS

HVAC DEMOLITION PLANS

HVAC BASEMENT FLOOR NEW WORK PLAN

HVAC FIRST FLOOR NEW WORK PLAN

HVAC SECOND FLOOR NEW WORK PLAN

HVAC ATTIC NEW WORK PLAN

HVAC SECTIONS AND ENLARGED PLANS

HVAC SCHEDULES

HVAC DETAILS

ELECTRICAL COVER SHEET

ELECTRICAL DEMOLITION PLANS

ELEC POWER & SYSTEMS PLAN - BASEMENT

ELEC POWER & SYSTEMS PLAN - 1ST FLOOR

ELEC POWER & SYSTEMS PLAN - ATTIC

ELECTRICAL SCHEDULES

2 25

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/3

/2

:0

:2

A

M P

\1

H

O F

U I ro n m a s te r' s H o u s e H

V A

C \R e v it \I R

O N

M A

S T

E R

'S H

O U

S E

.r v t

Designer

AT

AW

10/30/2019

G-0.2

SITE PLAN

TO

ENTRANCE TO VALLEY

IRONMASTER'S

VISITOR CENTER

TO READING

F R

E N

C H

C R

E E

K

VILLAGE

BARN

APPROPRIATE

STAGING AREA

SITE PLAN

NOT TO SCALE

MAINTENANCE

PARKING

(PAVED)

GRAVEL ROADS,

TYPICAL

VEHICLE ACCESS,

TYPICAL

STORE &

OFFICE

WALKWAY

& STEPS

FURNACE

3 25

DN

UP

UP

MOULDERS

DINING ROOM

KITCHEN

STAGING AREA; PROTECT GROUND

SURFACE& WALLS FROM DAMAGE;

PROTECT OR REPLACE RED SHALE

HVAC UNIT

REMOVE & REINSTALL

EXISTING WOOD FASCIA CONDENSING UNIT AND

CONCRETE PAD

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-1.0

BASEMENT FLOOR PLAN

1/4" = 1'-0"1 BASEMENT FLOOR PLAN

0 4 84

SCALE OF FEET

4 25

DN

UP

DN

UP

DN

NORTHWEST

PARLOR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

STAIR

HVAC UNIT

HVAC PIPING UP & DOWN; PARK TO

PROVIDE FALSE BACK AT FIREBOX

ADJUST LOCATION OF FLOOR GRILLES AS

NECESSARY TO FIT IN FLOOR BOARD AND

AVOID EXISTING FRAMING. TYPICAL FOR ALL.

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-1.1

FIRST FLOOR PLAN

1/4" = 1'-0"1 FIRST FLOOR PLAN

0 4 84

5 25

DNDN

DN

UP

DN

HVAC PIPING UP & DOWN IN FLUE

BATHROOM

BEDROOM

BEDROOM

209STAIR HALL

BEDROOM

CLOSET HALL

BEDROOM

BEDROOM

BEDROOM

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-1.2

SECOND FLOOR PLAN

1/4" = 1'-0"1 SECOND FLOOR PLAN

0 4 84

6 25

HVAC PIPING DOWN

303 304

TRUSS BRACING THIS AREA

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-1.3

ATTIC PLAN

1/4" = 1'-0"1 ATTIC FLOOR PLAN

0 4 84

7 25

104 105

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-2.1

REFLECTED CEILING PLAN -

FIRST FLOOR

1/4" = 1'-0"1 RCP - FIRST FLOOR

0 4 84

8 25

203 202

208 209

ADJUST REGISTER AND GRILLE LOCATIONS TO

AVOID EXISTING FRAMING. TYPICAL FOR ALL

REGISTERS AND GRILLES.

SUPPLY REGISTER

RETURN GRILLE

LEGEND

RETURN AIR GRILLE ABOVE

PAINTING SCOPE

1. TOUCH UP ALL PAINT DAMAGED BY THIS WORK. PAINT

ANY NEW WOOD INSTALLED. COR TO PROVIDE PAINT

COLOR AND TYPE INFORMATION.

2. AT ROOMS 001, 002 & 003, TOUCH UP ANY PAINT AT STEEL

STRUCTURE, DOORS, DOOR FRAMES, OR STAIRS

DAMAGED BY THIS WORK.

3. AT ROOMS 004 AND 005, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

4. AT ROOMS 101, 102, 103, 104 & 105, ALL SURFACES TO BE

PAINTED IN ACCORDANCE WITH THE HISTORIC FINISHES

REPORT.

5. AT ROOM 204, ALL SURFACES TO BE PAINTED IN

ACCORDANCE WITH THE HISTORIC FINISHES REPORT.

6. IN ROOMS WITH NEW CEILING GRILLES, REPAINT

SURROUNDING CEILING SURFACE TO A NATURAL

SURFACE BREAK - TRIM, CHANGE IN PLANE, ETC.

PAINTING IS NOT REQUIRED IF THERE IS NO DAMAGE TO

EXISTING PAINT OR PLASTER

1/4" = 1'-0"1 RCP - SECOND FLOOR

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

REPLACE RADIANT HEATING SYSTEM

AT IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENTS

HOFU 237580

/9

/2

3:

:2

PM

P:

\1

8\

H

O

FU

Ir on m as te r's

H ou se H

VA

C

\R ev it\

IR

O N

M

AS

TE

R

'S H

O U

SE

.rv t

AW

AT

AW

10/30/2019

A-2.2

REFLECTED CEILING PLAN -

SECOND FLOOR

0 4 84

9 25

HVAC ABBREVIATIONS

COMPRESSED AIR PIPING

AUTOMATIC AIR VENT

AIR COMPRESSOR

AIR CONDITIONING FAN (AIR HANDLING UNIT)

DUCT ACCESS DOOR

ABOVE FINISHED FLOOR

ACCESS PANEL

AIR PRESSURE DROP

AIR SEPARATOR

AUTOMATIC TEMPERATURE CONTROLS

BOILER

BRANCH CONTROLLER

BACKDRAFT DAMPER

BOTTOM OF DUCT

BOTTOM OF PIPE

BRITISH THERMAL UNIT

BTU PER HOUR

CONDENSATE

CEILING DIFFUSER

CEILING EXHAUST GRILLE

CEILING EXHAUST REGISTER

CUBIC FEET PER HOUR

CUBIC FEET PER MINUTE

CHILLER

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CLEAN OUT

CONDENSATE

CONTINUED

CONDENSATE PUMP

CEILING RETURN GRILLE

CEILING RETURN REGISTER

CEILING SUPPLY GRILL

COOLING TOWER

CONDENSING UNIT

CABINET UNIT HEATER

CONSTANT VOLUME

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

COOLING CONDENSATE DRAIN PIPING

DRY BULB/DECIBEL

A-WEIGHTED DECIBEL

DIRECT DIGITAL CONTROLS

DIAMETER

DOWN

DUCT MOUNTED SUPPLY GRILLE

DIRECT EXPANSION

EXHAUST AIR

ENTERING AIR TEMPERATURE

ELECTRIC BASEBOARD RADIATOR

ELECTRICAL CONTRACTOR

EXHAUST FAN

ENERGY RECOVERY WHEEL

EXTERNAL STATIC PRESSURE

EXPANSION TANK

ENTERING WATER TEMPERATURE

EXISTING

FURNACE/FAHRENHEIT

FORCED CONDENSATE

FLOOR DRAIN

FLEXIBLE

SPRINKLER/FIRE PROTECTION CONTRACTOR

FEET PER MINUTE

FLOOR RETURN GRILL

FLOOR SUPPLY REGISTER

FOOT/FEET

FIN-TUBE CONVECTOR

GAS

GRAVITY CONDENSATE

GROUND COUPLED RETURN

GROUND COUPLED SUPPLY

GALLONS PER MINUTE

A

AAV

AC

AHU

AD

AFF

AP

APD

AS

ATC

B

BC

BDD

BOD

BOP

BTU

BTUH

C

CD

CEG

CER

CFH

CFM

CH

CHWR

CHWS

CO

COND

CONT

CP

CRG

CRR

CSG

CT

CU

CUH

CV

CWR

CWS

D

DB

DBA

DDC

DIA

DN

DSG

DX

EA

EAT

EBR

EC

EF

ERW

ESP

ET

EWT

(E) F

FC

FD

FLEX

FPC

FPM

FRG

FSR

FT

FTC

G

GC

GCR

GCS

GPM

HEAT PUMP/HORSE POWER

HOT WATER

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

HEAT EXCHANGER

LEAVING AIR TEMPERATURE

LINEAR DIFFUSER - RETURN

LINEAR BAR GRILLE

LINEAR DIFFUSER

LOW PRESSURE STEAM SUPPLY

LINEAR SUPPLY REGISTER

LINEAR RETURN GRILLE

LEAVING WATER TEMPERATURE

MAXIMUM

1000 BTUH

MECHANICAL CONTRACTOR

MINIMUM FUSE AMPACITY

MOTORIZED DAMPER

MINIMUM

MAXIMUM OVER-CURRENT PROTECTION SIZE

NEW WORK

NOT APPLICABLE

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

OUTSIDE AIR

OPPOSED BLADE DAMPER

OPEN ENDED DUCT

PUMP

PLUMBING CONTRACTOR/ PUMPED CONDENSATE

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH

PACKAGED TERMINAL AIR CONDITIONER

REFRIGERANT GAS RETURN LINE

RETURN AIR

RELATIVE HUMIDITY

REFRIGERANT RETURN

RADIANT PANEL

REVOLUTIONS PER MINUTE

REFRIGERANT SUPPLY

ROOF TOP UNIT

SLOPE

SANITARY/SLOPE

SUPPLY AIR

SECONDARY CHILLED WATER SUPPLY OR RETURN

SQUARE FEET

TESTING, ADJUSTING & BALANCING

TRANSFER AIR GRILLE

TERTIARY CHILLED WATER SUPPLY OR RETURN

TOTAL DEVELOPED HEAD(DYNAMIC)

TEMPERED OUTSIDE AIR

TOP OF DUCT

TRANSITION

TOTAL STATIC PRESSURE

TYPICAL

UNIT HEATER

UNLESS NOTED OTHERWISE

VARIABLE AIR VOLUME

VOLUME DAMPER

VARIABLE FREQUENCY DRIVE

VERIFY IN FIELD

VARIABLE REFRIGERANT FLOW

WET BULB

WALL EXHAUST GRILLE

WALL EXHAUST REGISTER

WATER PRESSURE DROP

WALL RETURN REGISTER

WALL SUPPLY GRILLE

WATER SOURCE HEAT PUMP

WALL SUPPLY REGISTER

WIRE MESH SCREEN

HP

HW

HWS

HWR

HTX

LAT

LDR

LBG

LD

LPS

LSR

LRG

LWT

MAX

MBH

MC

MCA

MD

MIN

MOCP

(N) N/A

NC

NIC

NO

NTS

OA

OBD

OED

P

PC

PRV

PSI

PTAC

R

RA

RH

RL

RP

RPM

RS

RTU

s=02'

S

SA

SCHWS/R

SF

TAB

TAG

TCHWS/R

TDH

TOA

TOD

TR

TSP

TYP

UH

U.N.O.

VAV

VD

VFD

VIF

VRF

WB

WEG

WER

WPD

WRR

WSG

WSHP

WSR

WMS

HVAC PLAN SYMBOLS

AIRFLOW DIRECTION

SYMBOL

UNDERCUT DOOR

EQUIPMENT TAG

SECTION MARKER

DIAMETER

CONNECT NEW TO EXISTING

CUT AND CAP

EXISTING TO REMAIN

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

HUMIDITY SENSOR / HUMIDISTAT

TEMPERATURE SENSOR / THERMOSTAT

SMOKE DETECTOR

(E)

(R)

(RL)

H

T

EQUIPMENT

NUMBER

EQUIPMENT TYPE

DESIGNATOR

SHEET NUMBER

SECTION NUMBER

X

XX

S

CARBON DIOXIDE SENSORCO2

PIPE ANCHOR

PIPE GUIDE

PIPE CAP

EXISTING TO REMAIN

EXISTING TO BE REMOVED

(DEMO PLANS)

NEW WORK

PIPE UP

PIPE DOWN

PIPE DROP

PIPE UNION

PIPE TAKE-OFF UP

RETURN PIPING

(NEW WORK

PLANS)

U

LOUVERED DOOR L

XX

XXX

"CRR OR FRG" TYPE RETURN AIR GRILLE

"CD OR FSR" TYPE SUPPLY AIR DIFFUSER

BALL VALVE

HVAC VALVE SYMBOLS HVAC GRILLE SYMBOLS

PLAN

SECTION

DETAILS

VOLUME DAMPER

HVAC DUCT SYMBOLS

RETURN, EXHAUST, MAKEUP,

OR OUTSIDE AIR INTAKE

SUPPLY AIRFLOW

DUCT SIZE - RECTANGULAR

DUCT SIZE - ROUND

DUCT SIZE - FLAT OVAL

## x ##

## Ø

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H0.0

HVAC COVER SHEET

EXAMINE JOB SITE AND VERIFY ALL SITE

CONDITIONS PRIOR TO SIGNING CONTRACT. BRING

ANY DISCREPANCY BETWEEN THE CONTRACT

DOCUMENTS AND THE ACTUAL FIELD CONDITIONS

TO THE ATTENTION OF THE CONTRACTOR OF

RECORD.

THE DRAWINGS ARE DIAGRAMMATIC. COORDINATE

IN THE FIELD, WITH THE CONTRACTOR OF RECORD

AND WITH ALL TRADES, THE EXACT LOCATION OF

EQUIPMENT, DUCTWORK, AND PIPING.

PERFORM WORK IN ACCORDANCE WITH RULES,

REGULATIONS, STANDARDS, CODES, ORDINANCES,

AND LAWS OF LOCAL, STATE, AND FEDERAL

GOVERNMENTS, AND OTHER AUTHORITIES HAVING

JURISDICTION AND BE RESPONSIBLE FOR

COMPLIANCE THEREWITH.

OBTAIN ALL NECESSARY APPROVALS, PERMITS AND

INSPECTIONS. PAY ALL ASSOCIATED FEES.

CONTRACTOR’S SHALL MAINTAIN A NOTATED SET OF

“AS-BUILT” DRAWINGS ONSITE SHOWING ALL

DEVIATIONS FROM THE CONTRACT DRAWINGS AND

SHALL TURN THEM OVER TO THE CONTRACTOR OF

RECORD UPON SUBSTANTIAL COMPLETION.

ALL MATERIALS SHALL BE NEW AND OF

COMMERCIAL GRADE AND BEAR THE

UNDERWRITER'S LABEL WHERE APPLICABLE.

OBTAIN APPROVAL FROM THE PARK SERVICE

REPRESENTATIVE PRIOR TO ANY INTERRUPTION OF

BUILDING SYSTEMS. COORDINATE ACCEPTABLE

WORKING HOURS WITH SAME.

1.

2.

3.

4.

5.

6.

7.

HVAC GENERAL NOTES:

HVAC DRAWING SCHEDULE

SHEET

NUMBER SHEET NAME

100% CD

10/30/19

H0.0 HVAC COVER SHEET ●

H1.1 HVAC ZONING PLANS ●

H2.1 HVAC DEMOLITION PLANS ●

H3.1 HVAC BASEMENT FLOOR NEW WORK PLAN ●

H3.2 HVAC FIRST FLOOR NEW WORK PLAN ●

H3.3 HVAC SECOND FLOOR NEW WORK PLAN ●

H3.4 HVAC ATTIC NEW WORK PLAN ●

H5.0 HVAC SECTIONS AND ENLARGED PLANS ●

H7.0 HVAC SCHEDULES ●

H8.0 HVAC DETAILS ●

UP

UP

DN

UP

DN

UP

DNDN

UP

DN

MOULDERS

DINING RM.

KITCHEN

VRF 0-3

VRF 0-4

NORTHWEST

PARLOR

STAIR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

VRF 0-5

VRF 0-2

VRF 0-1

VRF 0-6 VRF 1-1

BEDROOM

BEDROOM

STAIR HALL

CLOSET HALL

BEDROOM

BEDROOM

BEDROOM

BEDROOM

VRF 2-1 VRF 2-2

VRF 2-3 VRF 2-4

VRF 2-6

VRF 2-5

VRF 0-2

NO CONDITIONING PROVIDED

303 304

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H1.1

HVAC ZONING PLANS

1/8" = 1'-0"H1.1

1 HVAC BASEMENT ZONING PLAN

1/8" = 1'-0"H1.1

2 HVAC FIRST FLOOR ZONING PLAN

1/8" = 1'-0"H1.1

3 HVAC SECOND FLOOR ZONING PLAN

1/8" = 1'-0"H1.1

4 HVAC ATTIC ZONING PLAN

0 4 84

UP

UP

DN

UP

DN

UP

DNDN

UP

DN

MOULDERS

DINING RM.

KITCHEN

(E) 14"

OPENING

(R) CABINET

UNIT HEATER(S)

(E) DEHUMIDIFIER

TO REMAIN

(E) UH TO

REMAIN

(E) UH TO

REMAIN

(E) UH TO

REMAIN

(E) WOODEN REVEAL

NORTHWEST

PARLOR

STAIR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

NOTES:

IN FLOOR ELECTRIC RADIANT HEAT TO BE ABANDONED IN

PLACE WHERE NO PLASTER, PATCH.

(E) FLOOR

GRILLE TO

REMAIN

(E) FLOOR

GRILLE TO

REMAIN

BEDROOM

BEDROOM

STAIR HALL

CLOSET HALL

BEDROOM

BEDROOM

BEDROOM

BEDROOM

NOTES:

NO DEMOLITION SCOPE ON THIS FLOOR.

FLOOR SHOWN FOR REFERENCE ONLY.

303 304

NOTES:

NO DEMOLITION SCOPE ON THIS FLOOR.

FLOOR SHOWN FOR REFERENCE ONLY.

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H2.1

HVAC DEMOLITION PLANS

1/8" = 1'-0"H2.1

1 HVAC BASEMENT DEMOLITION PLAN

1/8" = 1'-0"H2.1

2 HVAC FIRST FLOOR DEMOLITION PLAN

1/8" = 1'-0"H2.1

3 HVAC SECOND FLOOR DEMOLITION PLAN

1/8" = 1'-0"H2.1

4 HVAC ATTIC DEMOLITION PLAN

UP

UP

MOULDERS

DINING RM.

KITCHEN

(E) DEHUMIDIFIER

TO REMAIN

(E) UH TO

REMAIN

(E) UH TO

REMAIN

(E) UH TO

REMAIN

(E) WOODEN

REVEAL

BC

VRF

0-5

12"ø RA UP

8ø SA UP

VRF

0-1

COND UP

14ø SA UP

8ø SA UP

8"ø SA UP

8ø SA UP

VRF

0-2

VRF

0-4

VRF

0-6

16ø RA UP

20x10 RA x

R

A

EACH LINE REPRESENTS 2 SETS

OF REFRIGERANT LINES (RS/RL)

BETWEEN BC AND VRF UNITS

CU

REFRIGERANT MAIN

DROP TO 24" AFF

SOUND ATTENUATORS

LINE OF

STRUCTURE

ABOVE

H5.0

DRIP LINE OF ROOF ABOVE

COND SPILL TO GRADE

RS/RL UP

CONDENSATE UP

REFRIGERANT SUCTION,

GAS, MIXTURE UP TO BC-2

14ø RA20x10 SA

10ø SA

10ø SA

H5.0

H5.0

10ø SA 10ø SA

18x16 SA

10x10 RA

VRF

0-3

T

T

VRF

0-6

VRF

0-3

CORE

THROUGH WALL

42"x110" CONCRETE PAD

CO

RACK PIPES ON

STONE WALL

H5.0

Sim

1 1/4" GC

1 1/4" GC

26x8 SA

SG

410 CFM

12x12

WSR9

H5.0

RG ABOVE

PROVIDE 10 GPH CONDENSATE PUMP WITH 20FT

OF HEAD. BASIS OF DESIGN IS LITTLE GIANT

VCMX-2OULS. PROVIDE PUMP WITH CORD AND

PLUG.

TEMPERATURE SENSOR/ THERMOSTAT

LOCATIONS SHALL BE COORDINATED WITH COR.

(TYP. FOR ALL).

HVAC NEW WORK KEYED NOTES:

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H3.1

HVAC BASEMENT FLOOR

NEW WORK PLAN

1/4" = 1'-0"H3.1

1 HVAC BASEMENT NEW WORK AND PIPING PLAN

NOTES:

1. ALL PIPING, EQUIPMENT AND DUCTWORK SHALL BE LOCATED TIGHT TO OVERHEAD STRUCTURE.

UP

DN

UP

NORTHWEST

PARLOR

STAIR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

(E) 12" ø VENT (RA)

360 CFM

VRF

1-1

(E) 14" ø VENT (RA)

860 CFM

REFRIGERANT SUCTION,

LIQUID, MIX UP/DN TO BC 1

COND UP/DN

RS/RL DN

CONDENSATE DN.

T

T

T

VRF

0-5

VRF

0-2

VRF

0-1

T

T

VRF

0-6

VRF

1-1

HVAC CONTROL PANEL

1 1

H5.0

FRR

410 CFM

(12"Ø)

FSR

410 CFM

(12"Ø)

FSR

180 CFM

(8"Ø) TYP. FOR TWO

FSR

500 CFM

(12"Ø)

FSR

180 CFM

(8"Ø)

FSR

180 CFM

(8"Ø)

COORDINATE NEW DIFFUSER LOCATIONS WITH

BEAMS AND JOISTS.

TEMPERATURE SENSOR/ THERMOSTAT

LOCATIONS SHALL BE COORDINATED WITH COR.

(TYP. FOR ALL).

HVAC NEW WORK KEYED NOTES:

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H3.2

HVAC FIRST FLOOR NEW

WORK PLAN

1/4" = 1'-0"H3.2

1 HVAC FIRST FLOOR NEW WORK PLAN

DNDN

BEDROOM

BEDROOM

STAIR HALL

CLOSET HALL

BEDROOM

BEDROOM

BEDROOM

BEDROOM

CSG

350 CFM

CSG

350 CFM

14x6 CRG

350 CFM

CSG

125 CFM

CRG

700 CFM

CSG

350 CFM

1-1/4" COND

UP/DN

CSG

350 CFM

CRG

700 CFM

CRG

700 CFM

CSG

225 CFM

CSG

350 CFM

CSG

350 CFM

CSG

350 CFM

CRG

350 CFM

CRG

350 CFM

14x6 CSG

350 CFM

REFRIGERANT SUCTION,

LIQUID, MIX DN TO BC 1

SA UP (TYP.)

RA UP (TYP.)

TT

VRF

2-4

VRF

2-3

T

VRF

2-6

T

VRF

2-5

T

VRF

2-2

T

VRF

2-1

H5.0

1 1 1 1

COORDINATE NEW DIFFUSER LOCATIONS WITH

BEAMS AND JOISTS.

TEMPERATURE SENSOR/ THERMOSTAT

LOCATIONS SHALL BE COORDINATED WITH COR.

(TYP. FOR ALL).

HVAC NEW WORK KEYED NOTES:

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :0

P

M

SAW

DAI

CSA

10/30/19

H3.3

HVAC SECOND FLOOR NEW

WORK PLAN

1/4" = 1'-0"H3.3

1 HVAC SECOND FLOOR NEW WORK PLAN

VRF

2-1

VRF

2-6

VRF

2-3

VRF

2-4

H5.0

VRF

2-2

VRF

2-5

BC

REFRIGERANT SUCTION,

LIQUID, MIX DN TO BC 1

CO

EACH LINE REPRESENTS 2 REFRIGERANT LINES

(RS/RL) TO EACH INDOOR UNIT (TYP.) BETWEEN

BC AND VRF UNITS

1 1/4" GC

1 1/4" GC

1 1/4" GC

1 1/4" GC

1 1/4" GC

1 1/4" GC

1-1/4" CONDENSATE DN.

CO

12ø SA DN (TYP.)

12ø RA DN. (TYP.)

10ø SA DN TO GRILLE 10ø SA DN TO GRILLE

H5.0

H5.0

16x12 RA DN TO GRILLE.

10" ø SA DN TO GRILLE. (TYP)

12ø RA

10ø SA

12" ø SA DN TO GRILLE. (TYP)

20x10 SA

12ø SA

12ø SA

14ø SA

12ø SA

12ø SA

14ø SA

12ø SA

BELOW

12ø SA

12ø SA

12ø RA

12ø RA

10ø RA DN TO GRILLE

12ø SA10ø SA

10ø SA DN TO GRILLE

12ø SA 10ø SA DN TO GRILLE

10ø RA DN TO GRILLE

12ø SA

16x12 RA DN

TO GRILLE.

COORDINATE NEW DIFFUSER LOCATIONS WITH

BEAMS AND JOISTS.

TEMPERATURE SENSOR/ THERMOSTAT

LOCATIONS SHALL BE COORDINATED WITH COR.

(TYP. FOR ALL).

HVAC NEW WORK KEYED NOTES:

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :1

P

M

SAW

DAI

CSA

10/30/19

H3.4

HVAC ATTIC NEW WORK

PLAN

1/4" = 1'-0"H3.4

1 HVAC ATTIC NEW WORK PLAN

NOTES:

1. ALL PIPING, EQUIPMENT AND DUCTWORK SHALL BE LOCATED TIGHT TO OVERHEAD STRUCTURE.

BASEMENT

-8' - 6"

FIRST FLOOR

0' - 0"

2' - 0"

CU

UNIT DISCHARGE

SOUND ATTENUATOR

RACK REF

PIPING ON WALL

H8.0

UNIT SOUND

ATTENUATOR PANELS

BASEMENT

-8' - 6"

FIRST FLOOR

0' - 0"

VRF

0-6

VRF

1-1

3/4" GC

3/4" REF

3/4" REF

3/4" REF

3/4" REF

3/4" REF

FSR

VRF

0-3

CONDESATE

PUMP

18x18 RA700 CFM 14x14

SG

410 CFM

12x12

WSR

BASEMENT

-8' - 6"

FIRST FLOOR

0' - 0"

VRF

0-2

10x10 RA

16x18 SA

14ø SA

FSR

500 CFM

12" ø

H5.0

VRF

0-4

VRF

0-6

VRF

0-3

CP

ATTIC FLOOR

18' - 10"

ROOF PLAN

27' - 9"

VRF

2-1 VRF

2-2

10ø SA

12ø SA

ATTIC FLOOR

18' - 10"

ROOF PLAN

27' - 9"

VRF

2-3

12ø SA

12ø SA

12x16 RA

ATTIC FLOOR

18' - 10"

ROOF PLAN

27' - 9"

VRF

2-5

12ø SA

10ø SA

10ø RA

10ø SA

CSG

350 CFM

14x6

CRG

700 CFM

14x6

CRG

350 CFM

14x6

VRF

0-6

VRF

0-4

18x18 RA

10x12 SA

SG

410 CFM

12x12

OPEN ENDED

DUCT W/ WMS

410 CFM

14x14

FSR

410 CFM

(12"Ø)

BASEMENT

-8' - 6"

FIRST FLOOR

0' - 0"

STAIR

NORTHWEST

PARLOR

(E)14" VENT

14ø RA

20x10 RA

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :1

P

M

SAW

DAI

CSA

10/30/19

H5.0

HVAC SECTIONS AND

ENLARGED PLANS

3/8" = 1'-0"H5.0

2 HVAC SECTION AT CU-1

1/4" = 1'-0"H5.0

3 HVAC SECTION AT VRF 0-6

3/8" = 1'-0"H5.0

1 HVAC SECTION AT VRF 0-2

3/8" = 1'-0"H5.0

4 HVAC BASEMENT NEW WORK AND PIPING PLAN

3/8" = 1'-0"H5.0

5 HVAC SECTION AT VRF 2-1 & 2-2

3/8" = 1'-0"H5.0

6 HVAC SECTION AT VRF 2-3

3/8" = 1'-0"H5.0

7 HVAC SECTION AT VRF 2-5

H5.0

8 ISOMETRIC VIEW OF VRF 0-4 & 0-6

1/4" = 1'-0"H5.0

9 SECTION 102

AIR DEVICE SCHEDULE

FINISHMATERIALDESIGNATION

FACE/

SLOTS/

SPACING

REMARKS

CSG

BORDER BASIS

FRG

NOTES:

1. REFER TO FLOOR PLANS FOR BALANCING CFM AND THE TAKE-OFF SCHEDULE FOR THE NECK SIZE OF EACH DEVICE.

2. CONTRACTOR TO COORDINATE AIR DEVICE BORDER TYPE WITH STRUCTURE. REFER TO ARCHITECTURAL DRAWINGS FOR MORE INFORMATION.

FSR CUSTOM GRILLE PROVIDE VOLUME DAMPER IN DUCT SERVING GRILLEBLACK INTEGRAL

VINTAGE

HARDWARE

ZM-IR

CAST IRON

CRG

VINTAGE

HARDWARE

ZM-IR

REGGIO

REGISTERS

CAST IRON

CAST IRON

CAST IRON

BLACK

WHITE

WHITE

CUSTOM GRILLE

CUSTOM GRILLE

"SCROLL"

CUSTOM GRILLE

"SCROLL"

INTEGRAL

INTEGRAL

INTEGRAL

PROVIDE VOLUME DAMPER IN DUCT SERVING GRILLE

PROVIDE VOLUME DAMPER IN DUCT SERVING GRILLE

PROVIDE VOLUME DAMPER IN DUCT SERVING GRILLE

REGGIO

REGISTERS

SG STEEL WHITE 3/4" DOUBLE DEFLECTION 1-1/4" PROVIDE WITH FOAM GASKETTITUS 300 RL

MINIMUM INSERTION LOSS FOR DUCT

SILENCER FOR CONDENSING UNIT SCHEDULE

OCTAVE BAND CENTER FREQUENCY (HZ)

PATHSILENCER

NOTES: COORDINATE PRESSURE DROP WITH MANUFACTURER REQUIREMENTS

DS-1

CU-1

DISCHARGE

1K

2K

4K

8K

MANUFACTURER SOUND PRESSURE LEVELS

FOR MECHANICAL UNITS SCHEDULE

SOUND PRESSURE LEVELS (DB RE. 20 µPA)

MODEL

NOTES:

PEFY-P12NMAU-E

63 HZ

125 HZ

250 HZ

500 HZ

1 KHZ

2 KHZ

4 KHZ

8 KHZ

PEFY-P30NMAU-E 43 42 39 37 34 29 22 24

PVFY-P18NAMU-E 44 43 41 39 35 31 28 24

PFFY-P12NMAU-E 40 43 41 42 34 29 20 17

CU-1 71 68 64 57.5 54 46.5 48.5 45

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :1

P

M

SAW

DAI

CSA

10/30/19

H7.0

HVAC SCHEDULES

BRANCH CONTROLLER SCHEDULE

SYMBOL

LOCATION

INDOOR UNITS SERVED

(VRF-#)

CONNECTED

CONDENSING

UNIT

NUMBER OF

PORTS

PHYSICAL CHARACTERISTICS ELECTRICAL BASIS OF DESIGN

REMARKS

TAG NO.

LENGTH

(IN.)

WIDTH

(IN.)

HEIGHT

(IN.)

WEIGHT

(LBS.)

V/PH/HZ MCA MOCP MANUFACTURER MODEL NO

BC 1 RM 001 0-1, 0-2, 0-3, 0-4, 0-5, 0-6, 1-1 CU-1 8 43-3/4 20-1/2 11-7/16 124 230/1/60 1.45 15 MITSUBISHI ELECTRIC CMB-P108NU-HA1 SEE NOTES BELOW

BC 2 ATTIC 301 2-1, 2-2, 2-3, 2-4, 2-5, 2-6 CU-1 8 23-1/2 15-11/16 9-7/8 69 230/1/60 0.87 15 MITSUBISHI ELECTRIC CMB-P108NU-KB1 SEE NOTES BELOW

VARIABLE REFRIGERANT FLOW INDOOR UNIT SCHEDULE

SYMBOL

LOCATION TYPE

CAPACITY MBH ELECTRICAL FAN ELECTRICAL DIMENSIONS

OPER

WEIGHT

BASIS OF DESIGN

REMARKSTAG NO COOLING HEATING V/PH/HZ CFM

POWER

(WATTS) MCA MOCP L W H MANUFACTURER MODEL NO

VRF 0-1 RM 003 DUCTED HORIZONTAL 12 13.5 230/1/60 211-282-370 96 1.2 15 27-9/16" 31-1/8" 7-7/8" 46 MITSUBISHI ELECTRIC PEFY-P12NMAU SEE NOTES BELOW

VRF 0-2 RM 002 DUCTED VERTICAL 18 20 230/1/60 410-497-585 110 3 15 17" 21-5/8" 50-1/4" 113 MITSUBISHI ELECTRIC PVFY-P18NAMU SEE NOTES BELOW

VRF 0-3 RM 004 FLOOR STANDING 12 13.5 230/1/60 247-317 90 0.38 15 46-3/32" 8-11/16" 24-13/16" 50 MITSUBISHI ELECTRIC PFFY-P12NEMU SEE NOTES BELOW

VRF 0-4 KITCHEN 005 DUCTED VERTICAL 18 20 230/1/60 410-497-585 110 3 15 17" 21-5/8" 50-1/4" 113 MITSUBISHI ELECTRIC PVFY-P18NAMU SEE NOTES BELOW

VRF 0-5 RM 001 DUCTED HORIZONTAL 12 13.5 230/1/60 211-282-370 96 1.2 15 27-9/16" 31-1/8" 7-7/8" 46 MITSUBISHI ELECTRIC PEFY-P12NMAU SEE NOTES BELOW

VRF 0-6 KITCHEN 005 DUCTED VERTICAL 18 20 230/1/60 410-497-585 110 3 15 17" 21-5/8" 50-1/4" 113 MITSUBISHI ELECTRIC PVFY-P18NAMU SEE NOTES BELOW

VRF 1-1 KITCHEN 105 FLOOR STANDING 12 13.5 230/1/60 247-317 90 0.38 15 46-3/32" 8-11/16" 24-13/16" 50 MITSUBISHI ELECTRIC PFFY-P12NEMU SEE NOTES BELOW

VRF 2-1 ATTIC 302 DUCTED HORIZONTAL 12 13.5 230/1/60 211-282-370 96 1.2 15 27-9/16" 31-1/8" 7-7/8" 46 MITSUBISHI ELECTRIC PEFY-P12NMAU SEE NOTES BELOW

VRF 2-2 ATTIC 302 DUCTED HORIZONTAL 12 13.5 230/1/60 211-282-370 96 1.2 15 27-9/16" 31-1/8" 7-7/8" 46 MITSUBISHI ELECTRIC PEFY-P12NMAU SEE NOTES BELOW

VRF 2-3 ATTIC 303 DUCTED HORIZONTAL 30 34 230/1/60 512-636-742 140 2.50 15 28-7/8" 43-5/16" 9-13/16" 71 MITSUBISHI ELECTRIC PEFY-P30NMAU SEE NOTES BELOW

VRF 2-4 ATTIC 304 DUCTED HORIZONTAL 30 34 230/1/60 512-636-742 140 2.50 15 28-7/8" 43-5/16" 9-13/16" 71 MITSUBISHI ELECTRIC PEFY-P30NMAU SEE NOTES BELOW

VRF 2-5 ATTIC 301 DUCTED HORIZONTAL 12 13.5 230/1/60 211-282-370 96 1.2 15 27-9/16" 31-1/8" 7-7/8" 46 MITSUBISHI ELECTRIC PEFY-P12NMAU SEE NOTES BELOW

VRF 2-6 ATTIC 301 DUCTED HORIZONTAL 30 34 230/1/60 512-636-742 140 2.50 15 28-7/8" 43-5/16" 9-13/16" 71 MITSUBISHI ELECTRIC PEFY-P30NMAU SEE NOTES BELOW

AIR COOLED HEAT PUMP CONDENSING UNIT SCHEDULE

SYMBOL

LOCATION SERVICE TYPE EER IEER

NOM

CAPACITY

(MBH)

MIN

AMBIENT

TEMP

FAN ELECTRICAL

OPERATING

WEIGHT

BASIS MANUFACTURER

REMARKSTAG NO. QTY V/PH/HZ MCA MOCP NAME MODEL NO

CU 1 GRADE ALL VRF UNITS HEAT RECOVERY 12.1 23.9 192 23 2 230/3/60 (2)33 (2)45 1100 MITSUBISHI PURY-192TSLNU SEE NOTES BELOW

NOTES:

PROVIDE PAINTED INLET AND DISCHARGE SOUND ATTENUATORS, COORDINATE COLOR WITH COR.

ELECTRICAL TRADES CONTRACTOR SHALL PROVIDE DISCONNECTS MATCHED TO THE EQUIPMENT.

NOMINAL COOLING AND HEATING CAPACITIES ARE BASED ON INDOOR AIR COIL EAT OF 80/67 °F (DB/WB), OUTDOOR OF 95°F.

NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 54°F (DB), OUTDOOR OF 5°F(DB).

EFFICIENCY VALUES FOR EER, IEER, COP ARE BASED ON AHRI 1230 TEST METHOD FOR MIXTURE OF DUCTED & NON-DUCTED INDOOR UNITS. FOR SYSTEMS WITH MULTIPLE MODULES, REFRIGERANT PIPE DIMENSIONS INDICATE TOTAL SYSTEM

COMBINED PIPING DOWNSTREAM OF MODULE TWINNING.

ADDED REFRIGERANT FIELD CHARGE IS IN ADDITION TO FACTORY CHARGE, THIS MUST BE UPDATED BASED UPON FINAL AS-BUILT PIPING LAYOUT.

PROVIDE WITH CENTRAL CONTROLLER (AE-200), SEE DWGS.

UNIT IS DESIGNED TO PROVIDE NOMINAL HEATING TO MAINTAIN SPACE AT 55°F DURING WINTER DESIGN CONDITIONS.

NOTES:

ELECTRICAL TRADES CONTRACTOR SHALL PROVIDE NON-FUSED DISCONNECTS MATCHED TO THE EQUIPMENT.

NOMINAL COOLING AND HEATING CAPACITIES ARE BASED ON INDOOR AIR COIL EAT OF 80/67 °F (DB/WB), OUTDOOR OF 95 °F.

NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 70°F (DB), OUTDOOR OF 43°F(DB).

SEE OUTDOOR UNIT SCHEDULE FOR OUTDOOR AMBIENT CONDITIONS, CONNECTED CAPACITY, AND OTHER FACTORS ASSOCIATED WITH CORRECTED UNIT CAPACITIES.

SEE SCHEMATIC PIPING/ CONTROL DIAGRAM FOR INDICATION OF REQUIRED INDOOR UNIT REMOTE CONTROLLERS, SYSTEM CONTROLLERS, AND INTEGRATION DEVICES.

CONTROLS FOR EACH AC UNIT BY UNIT MANUFACTURER.

UNIT SHALL BE CONTROLLED BY WALL MOUNTED WIRELESS CONTROLLER

PROVIDE HORIZONTAL UNITS WITH INTEGRAL CONDENSATE LIFT DEVICES

PROVIDE HORIZONTAL DUCTED UNITS WITH FILTER BOXES TO ACCOMODATE A 2" FILTER

1.

2.

3.

4.

5.

6.

7.

8.

9.

1.

2.

3.

4.

5.

6.

7.

8.

NOTES:

ELECTRICAL TRADES CONTRACTOR SHALL PROVIDE ALL DISCONNECTS MATCHED TO THE EQUIPMENT.

PROVIDE REFRIGERANT ISOLATION BALL VALVES FOR ALL REFRIGERANT LIQUID AND SUCTION PIPING. SPARE PORTS TO BE PROVIDED WITH VALVES AND SEALED PER

MANUFACTURER'S RECOMMENDATIONS.

1.

2.

NOTE:

VRF SYSTEM IMAGE IS DIAGRAMMATIC IN NATURE AND IS REPRESENTATIVE ONLY OF THE OVERALL SYSTEM DESIGN INTENT. ALL DETAILS, INCLUDING BUT NOT LIMITED TO REFRIGERANT PIPING LENGTHS AND REFRIGERANT CHARGE VOLUMES, ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO DETERMINE IN ACCORDANCE

WITH MANUFACTURER'S INSTALLATION REQUIREMENTS.

SA (SIZE VARIES)

UNIT

ISOLATOR

(TYP OF (4))

CLIP ANGLE

(TYP)

CINCH BOLT

(TYP)

FLEXIBLE CONNECTION

FLEXIBLE

CONNECTION

ROD

PLASTIC

SECONDARY

DRAIN PAN

TO CONDENSATE DRAIN

CONDENSATE DRAIN CONNECTION

BELOW CONNECTION TO DRAIN PAN.

MUST BE A MINIMUM OF ONE INCH

1.

NOTES:

1/2" PUMPED

CONDENSATE

(REFER TO PLANS

FOR ROUTING)

BALL VALVE

CHECK VALVE

CONDENSATE

RECEIVER

& PUMP

M

IN

UNIT WITH

COOLING COIL

1.

NOTES:

REFER TO PLANS FOR QUANTITY OF PIPING RUNOUTS TO HEAT PUMP UNITS.

R S

R L

R S

R L

R S

R L

RS

RL

GAS PIPE PORT TO

INDOOR UNITS

(TYP)LIQUID PIPE PORT

TO INDOOR UNITS

(TYP)REFRIGERANT LINE

INSULATION (TYP)

SUSPENSION

BRACKET (TYP)

BRANCH SELECTOR/HEAT

RECOVERY BOX

CONTROL BOX

12" MINIMUM SERVICE

CLEARANCE

MINIMUM 18"x18"

SERVICE ACCESS

PLAN VIEW

SHUTOFF VALVE

(TYP)

LIQUID PORT

SUCTION GAS PORT

REFRIGERANT

BALL VALVE

CONDENSATE

DRAINAGE

VRF CONDENSING

UNIT

NOTES:

STAND SHALL MEET ASCE 7 REQUIREMENTS

FOR OVER TURNING.

45°

CHAMFER

GRADE

STEEL STAND

FEET

HEAVY GAUGE

STEEL SUPPORT

STAND

CONCRETE EQUIPMENT

PAD. SEE ARCH DWGS.

1.

24"

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/6

/2

:5 :1

P

M

SAW

DAI

CSA

10/30/19

H8.0

HVAC DETAILS

N.T.S.H8.0

1 SUSPENDED EQUIPMENT DETAIL

N.T.S.H8.0

2 CONDENSATE PUMP DETAIL

N.T.S.H8.0

4 BRANCH SELECTOR BOX PLAN VIEW

N.T.S.H8.0

3 VRF CONDENSING UNIT SUPPORT STAND DETAIL

NIC - DEVICES, WIRING, AND RACEWAY SHALL BE

EXISTING TO REMAIN, UNLESS NOTED OTHERWISE

WORKING CLEARANCE FOR

ELECTRICAL EQUIPMENT

1P 2P 3P 4P A

AB

AC

AFCI

AFF

AIC

AFG

ARCH

ATS

ATC

AV

BAS

BLDG

BDF

C

CATV

CB

CD

CKT

CMT

CP

C.T.

DISC

DO

DWG

(E)

EBB

EC

ELI

(ER)

EWC

FA

FAAP

FACP

FBO

FLA

FT

FTL

GC

GFCI

GND

HP

HV

Hz

IDF

IG

JB

KCMIL

KVA

KW

LED

ONE POLE

TWO POLE

THREE POLE

FOUR POLE

AMPERE

ABOVE CEILING

ABOVE COUNTER

ARC FAULT CURRENT INTERRUPTER

ABOVE FINISHED FLOOR

AMPS INTERRUPTING CURRENT

ABOVE FINISHED GRADE

ARCHITECT

AUTOMATIC TRANSFER SWITCH

AUTOMATIC TEMPERATURE CONTROL SYSTEM

AUDIO VISUAL

BUILDING AUTOMATION SYSTEM

BUILDING

BUILDING DISTRIBUTION FRAME (IT)

CONDUIT

CABLE TELEVISION

CIRCUIT BREAKER

CANDELA

CIRCUIT

EMPTY CONDUIT, WITH PULL STRING

CORD AND PLUG

CURRENT TRANSFORMER

DISCONNECT

DRAWOUT TYPE

DRAWING

EXISTING TO REMAIN

ELECTRIC BASE BOARD HEATER

ELECTRICAL CONTRACTOR

EMERGENCY LIGHTING INTERFACE

EXISTING TO BE RELOCATED

ELECTRIC WATER COOLER

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY OWNER

FULL LOAD AMPS

FIXED TEMPERATURE

FEED THROUGH LUGS

GENERAL CONTRACTOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUNDED

HORSEPOWER

HIGH VOLTAGE

HERTZ (CYCLE) PER SECOND

INTERMEDIATE DISTRIBUTION FRAME (IT)

ISOLATED GROUND

JUNCTION BOX

THOUSAND CIRCULAR MILS

KILOVOLT AMPERE

KILOWATT

LIGHT EMITTING DIODE

LP

LTG

MCB

MCC

MDP

MDF

(ME)

MISC

MLO

MOA

MOD

MTD

MTG

MTS

(N) N/A

NAC

NEC

N/E

NIC

NL

NTS

OCPD

P

PB

PH

PNL

PVC

PWR

(R)

(RE)

REC

ROR

SCP

SFL

SLC

SWBD

SYS

TC

TEL/DATA

TEL

TTB

TVSS

TYP

UON

UL

V W

WP

WR

XFMR

#1/E5.1

LIGHTING PANEL

LIGHTING

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MAIN DISTRIBUTION FRAME (IT)

MODIFY EXISTING

MISCELLANEOUS

MAIN LUGS ONLY

MULTI-OUTLET ASSEMBLY

MOTOR OPERATED DISCONNECT SWITCH

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

NEW

NOT APPLICABLE

NOTIFICATION APPLIANCE CIRCUIT (FAS)

NATIONAL ELECTRICAL CODE

NORMAL/EMERGENCY

NOT IN CONTRACT

NIGHT LIGHT

NUMBER

NOT TO SCALE

OVERCURRENT PROTECTIVE DEVICE

POLE

PULL BOX

PHASE

PANEL

POLYVINYL CHLORIDE CONDUIT

POWER

REMOVE EXISTING

RELOCATE EXISTING

RECESSED

RATE OF RISE

SECURITY CONTROL PANEL

SUB FEED LUGS

SIGNALING LINE CIRCUIT (FAS)

SWITCHBOARD

CONNECTION TO SYSTEMS FURNITURE

TIME CLOCK

TELEPHONE/DATA

TELEPHONE

TELEPHONE TERMINAL BOARD

TRANSIENT VOLTAGE SURGE SUPPRESSION

TYPICAL

UNLESS OTHERWISE NOTED

UNDERWRITERS LABORATORY

VOLT

WATT

WEATHERPROOF

WEATHER RESISTANT

TRANSFORMER

INDICATES MOUNTED ABOVE CENTER

OR AS NOTED ON DWG.

DETAIL NUMBER/DRAWING NUMBER

ABBREVIATIONS

POWER

ELECTRICAL SYMBOL LIST

BRANCH CIRCUIT WIRING (WHERE SHOWN)

BRANCH CIRCUIT WIRING AND/OR CONDUIT WITH WIRE, CONCEALED IN FLOOR

OR BELOW GRADE.

BRANCH CIRCUIT WIRING AND/OR CONDUIT WITH WIRE, CONCEALED IN CEILING

OR WALL.

BRANCH CIRCUIT WIRING AND/OR CONDUIT WITH WIRE, EXPOSED

BRANCH CIRCUIT WIRING TO PANEL

DENOTES CIRCUIT NUMBER AT PANELBOARD

5RP

DENOTES PANELBOARD IDENTITY (NAME)

OBSERVER

BRANCH CIRCUIT WIRE AND/OR CONDUIT WITH WIRE, TURNING UP TOWARD

OBSERVER

BRANCH CIRCUIT WIRE AND/OR CONDUIT WITH WIRE, TURNING AWAY FROM

NEW WORK

EXISTING TO REMAIN

DEMOLITION

ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE (N.E.C.), NATIONAL FIRE

PROTECTION ASSOCIATION (N.F.P.A.), AND APPLICABLE LOCAL CODES.

REFER TO MECHANICAL DRAWINGS TO COORDINATE WITH ALL AREAS OF DEMOLITION & NEW WORK.

VERIFY ALL FIELD CONDITIONS AND LOCATIONS OF EQUIPMENT, LIGHTING, DEVICES, CIRCUITING & FEEDERS, INCLUDING WITH OTHER

TRADES, PRIOR TO ANY ELECTRICAL WORK. DO NOT SCALE DRAWINGS.

CONTRACTOR TO TRACE OUT ALL WIRING, CABLES, CIRCUITING, FEEDERS, & CONTROL WIRING PRIOR TO ANY REMOVAL, RELOCATION, &

MODIFICATIONS. CONTRACTOR TO TAG WITH IDENTIFICATION & MAINTAIN WRITTEN RECORD.

THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AS NECESSARY FOR THE ENTIRETY OF DEMOLITION & CONSTRUCTION PHASES, AND COMPLY WITH UTILITY, STATE, LOCAL, AND REGULATING AUTHORITIES.

REMOVE ALL AFFECTED ELECTRICAL EQUIPMENT, DEVICES, LIGHTING, WIRING & CONDUIT, ETC. TO COORDINATE WITH THE NEW RENOVATIONS & WORK UNLESS OTHERWISE NOTED. WHERE THE DEMOLITION & REMOVAL OR RELOCATION OF SUCH EQUIPMENT AFFECTS THE CONTINUITY OF CIRCUIT(S) WHICH SERVE OTHER ITEMS DOWNSTREAM NOT TO BE REMOVED OR RELOCATED, THE CONTRACTOR SHALL REMOVE THE CIRCUIT WIRING BACK TO THE SOURCE (PANEL, BREAKER, SWITCH, ETC.). PROVIDE NEW WIRING AND RACEWAY, &

CONNECT TO THE UNAFFECTED DOWNSTREAM DEVICE TO MAINTAIN CONTINUITY.

COORDINATE WITH MECHANICAL CONTRACTOR FOR THE REMOVAL OR MODIFICATION OF THEIR EQUIPMENT, DISCONNECT, RECONNECT OR MODIFY CIRCUITING, INTERLOCKING, SWITCHING, ETC. TO COORDINATE WITH THE NEW WORK & ALTERATIONS FOR THE NEXT PHASE.

THE ELECTRICAL CONTRACTOR SHALL, AS PART OF THEIR WORK, PERFORM ALL RELATED DEMOLITION (TO CLEAR THE AREA OF THIS CONTRACT OF EXISTING SYSTEMS OR PARTS THEREOF), MODIFICATIONS, RELOCATION OF SERVICES AND RELATED WORK, INCLUDING NEW

WORK NECESSARY TO COMPLETE THE PROJECT.

ITEMS REMOVED SHALL BE OFFERED TO THE OWNER FOR THEIR USE. IF NOT ACCEPTED BY THE OWNER, DISPOSE OF THE MATERIAL FROM

THE SITE.

EACH TRADE CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION AND MODIFICATIONS OF SERVICES, EQUIPMENT AND MATERIALS

RELATING TO EACH TRADE RESPECTIVELY.

ELECTRICAL GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

MISCELLANEOUS

JUNCTION BOX (FLOOR, CEILING, WALL)

PULL BOX

MOTOR

T TRANSFORMER

J J J

PB

CIRCUIT PROTECTION

DISCONNECT SWITCH, UNFUSED TYPE

DISCONNECT SWITCH, FUSED TYPE

PANELBOARDS

SURFACE MOUNTED ELECTRICAL PANELBOARD

RECESSED MOUNTED ELECTRICAL PANELBOARD

SYSTEMS PANEL OR TERMINAL CABINET (AS INDICATED ON DRAWING)

MANUAL MOTOR STARTERS

COMBINATION MOTOR STARTER

M

ENCLOSED CIRCUIT BREAKERCB

TAG

EQUIPMENT CONNECTION

GROUND ROD

XX/##

CIRCUIT NUMBER

CIRCUIT DESIGNATION

PANEL NAME

DUPLEX RECEPTACLE

QUADRAPLEX RECEPTACLE

DUPLEX GROUND FAULT RECEPTACLE

OR AS INDICATED ON DRAWINGS

DUPLEX RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT, BACKSPLASH,

BACKSPLASH, OR AS INDICATED ON DRAWINGS

DUPLEX GROUND FAULT RECEPTACLE - MOUNTED ABOVE COUNTER HEIGHT,

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :0

P

M

KL

PLB

JH

10/30/19

E0.0

ELECTRICAL COVER SHEET

ELECTRICAL DRAWING SCHEDULE

SHEET

NUMBER SHEET NAME

100% CD

10/30/19

E0.0 ELECTRICAL COVER SHEET ●

E2.1 ELECTRICAL DEMOLITION PLANS ●

E4.1 ELEC POWER & SYSTEMS PLAN - BASEMENT ●

E4.2 ELEC POWER & SYSTEMS PLAN - 1ST FLOOR ●

E4.4 ELECTRICAL POWER & SYSTEMS PLAN - ATTIC ●

E7.1 ELECTRICAL SCHEDULES ●

UP

UP

DN

UP

DN

UP

MOULDERS

DINING RM.

(R) CABINET

UNIT HEATER

(E) WOODEN REVEAL PATHWAY

KITCHEN

(E) DEHUMIDIFIER

(E) UH

(E) UH

(E) UH

(E)PANEL PP

(E)FACP

(E)

PANEL HP

EXISTING CEILING

PATH UP

(E) UNDERGROUND 200A, 240V,

3 PHASE, 3W FROM VISITOR

CENTER BUILDING

(E) 200A/200A/3P

240V SWITCH

NORTHWEST

PARLOR

STAIR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

PANEL CH (E)

WIRE TROUGH

(E)

REMOVE EXISTING

STARTERS & WIRING

FROM TROUGH

ASSOCIATED WITH

MECHANICAL

EQUIPMENT BEING

DEMOLISHED BY

MECHANICAL

CONTRACTOR

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :0

P

M

KL

PLB

JH

10/30/19

E2.1

ELECTRICAL DEMOLITION

PLANS

1/8" = 1'-0"E2.1

1 ELECTRICAL DEMOLITION PLAN - BASEMENT

1/8" = 1'-0"E2.1

2 ELECTRICAL DEMOLITION PLAN - FIRST FLOOR

GENERAL NOTES:

ALL LIGHTING, POWER, EQUIPMENT, SYSTEMS, DEVICES, ETC. ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

VERIFY ALL FIELD CONDITIONS, LOCATIONS, WIRING, LIGHTING, EQUIPMENT AND DEVICES WITH OTHER TRADES PRIOR TO INSTALLATION OF

ELECTRICAL WORK. DO NOT SCALE DRAWINGS.

CONTRACTOR TO TRACE OUT ALL WIRING, CIRCUITING, FEEDERS & CONTROL WIRING PRIOR TO ANY REMOVAL, RELOCATION &

MODIFICATIONS. CONTRACTOR TO TAG WITH IDENTIFICATION & MAINTAIN WRITTEN RECORD.

REFER TO MECHANICAL DRAWINGS FOR ALL AREAS OF DEMOLITION & NEW WORK.

REMOVE, RELOCATE OR MODIFY ELECTRICAL WORK TO COORDINATE WITH ALTERATIONS AND NEW WORK. WHERE THE REMOVAL OF SUCH EQUIPMENT AFFECTS THE CONTINUITY OF CIRCUIT(S) WHICH SERVE OTHER ITEMS DOWNSTREAM NOT TO BE REMOVED, THE CONTRACTOR SHALL REMOVE THE CIRCUIT WIRING BACK TO THE UPSTREAM DEVICE CLOSEST TO THE SOURCE, OR IF REQUIRED, BACK TO THE SOURCE (PANEL, BREAKER, SWITCH, ETC.). PROVIDE NEW WIRING AND RACEWAY, CONNECT TO THE UNAFFECTED DOWNSTREAM

DEVICE TO MAINTAIN CONTINUITY.

UNLESS OTHERWISE NOTED, UTILIZE EXISTING 240V & 120/240V ELECTRICAL PANELS FOR CIRCUITING EXISTING & NEW ELECTRIC, SYSTEMS

& MECHANICAL. REFER TO NEW WORK PLANS.

WHERE EXISTING ELECTRICAL FEEDERS, WIRING, CONDUIT, LIGHTING FIXTURES, SYSTEM DEVICES OR EQUIPMENT INTERFERES WITH THE REMOVAL OF EXISTING, AND INSTALLATION OF NEW CONSTRUCTION OF ANY TRADE, THE CONTRACTOR SHALL RE-ROUTE THE EXISTING ELECTRICAL FEEDER, WIRING, CONDUIT OR RELOCATE THE EQUIPMENT IN AN APPROVED INSTALLATION OF THE NEW CONSTRUCTION. THE CONTRACTOR SHALL WORK WITH THE BUILDING MAINTENANCE ENGINEER TO IDENTIFY CABLES OR SYSTEMS TO BE RELOCATED.

WHERE THE EXISTING CEILING AND FINISHES ARE BEING REMOVED TO INSTALL NEW FINISHES, THE ELECTRICAL CONTRACTOR SHALL TEMPORARILY REMOVE ANY EXISTING ELECTRIC TO COORDINATE WITH THE RENOVATION AND MODIFICATIONS. REINSTALL ANY EXISTING

ELECTRIC TO REMAIN AT THE NEW FINISH SURFACE AS REQUIRED.

COORDINATE WITH MECHANICAL CONTRACTOR FOR THE REMOVAL OR MODIFICATION OF THEIR EQUIPMENT. DISCONNECT, RECONNECT OR MODIFY CIRCUITING, INTERLOCKING, SWITCHING, ETC. TO COORDINATE WITH NEW WORK & ALTERATIONS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

UP

UP

S

MOULDERS

DINING RM.

KITCHEN

(E) DEHUMIDIFIER

(E) UH

(E) UH

(E) UH

(E)PANEL PP

(E)FACP

(E)

PANEL HP

(E) WOODEN REVEAL

PATHWAY

EXISTING CEILING

PATH UP

(E) UNDERGROUND 200A, 240V,

3 PHASE, 3W FROM VISITOR

CENTER BUILDING

(E) 200A/200A/3P

240V SWITCH

VRF

0-1 BC

VRF

0-2

VRF

0-5

CU

VRF

0-3

VRF

0-4

CP

PP/17

WP WR

PROVIDE WEATHERPROOF HUBBELL

LIGHT, SWITCH & WEATHER

RESISTANT DUPLEX GFCI

RECEPTACLE WITH "WHILE IN USE"

COVER MOUNTED ON UNISTRUT

RACK. CIRCUIT TO EXISTING PANEL

PP-16.

MOD 1 MOD 2

VRF

0-6

COORDINATE LOCATION OF SURFACE

MOUNTED RACEWAY AND BOX WITH COR.

CORE, SLEEVE & SEAL

VERTICAL RACK ON WALL

FOR HVAC & ELECTRIC

SHARED PATHWAY UP

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :1

P

M

KL

PLB

JH

10/30/19

E4.1

ELEC POWER & SYSTEMS

PLAN - BASEMENT

1/4" = 1'-0"E4.1

1 ELECTRICAL POWER & SYSTEMS PLAN - BASEMENT

GENERAL NOTES:

ALL EQUIPMENT & DEVICES SHALL BE NEW UNLESS OTHERWISE NOTED.

VERIFY ALL FIELD CONDITIONS AND LOCATIONS OF EQUIPMENT, DEVICES & WIRING WITH COR, INCLUDING OTHER TRADES PRIOR TO INSTALLATION OF ELECTRICAL WORK. DO NOT SCALE

DRAWINGS.

COORDINATE WITH MECHANICAL CONTRACTOR FOR ALL MECHANICAL WORK, EQUIPMENT,

CHARACTERISTICS, LOCATIONS & QUANTITIES PRIOR TO ANY ROUGH-INS. REFER TO MECHANICAL

DRAWINGS FOR FURTHER INFORMATION.

ELECTRICAL CONTRACTOR TO VERIFY IN FIELD WITH MECHANICAL CONTRACTOR FOR ANY

CONTROLS, SWITCHING & INTERFACING PRIOR TO ANY ROUGH-IN. PROVIDE EMPTY BOXES &

RACEWAYS. POWER CIRCUITS & CONTROL RACEWAYS SHALL FOLLOW MECHANICAL.

WIRE TROUGH, PULL & JUNCTION BOXES ARE SIZED BY THE ELECTRICAL CONTRACTOR TO MEET

FIELD CONDITIONS & CODE REQUIREMENTS.

REFER TO ELECTRICAL CONNECTION SCHEDULE ON DRAWING E7.1 FOR MECHANICAL EQUIPMENT &

CIRCUITING. REFER MECHANICAL DRAWINGS & SCHEDULES FIR EQUIPMENT QUANTITIES &

LOCATIONS.

ELECTRICAL CONTRACTOR SHALL SLEEVE & SEAL ALL CONDUITS AT ALL POINTS OF PENETRATION INTO EARTH, MASONRY, OR STRUCTURE IN BUILDING. PROVIDE FIRE RATED THRU-WALL, CEILING &

FLOOR SEALS TO ASSURE LEAK FREE INSTALLATION AND PREVENTION OF GAS OR OTHER FUME

SEEPAGE INTO BUILDING.

1.

2.

3.

4.

5.

6.

7.

DN

UP

NORTHWEST

PARLOR

STAIR

SOUTHWEST

PARLOR

DINING ROOM

KITCHEN

PANEL CH

(E)

WIRE TROUGH

(E)

VRF

1-1

SHARED PATHWAY UP

J

120V CKT FOR

TOUCH SCREEN

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :1

P

M

KL

PLB

JH

10/30/19

E4.2

ELEC POWER & SYSTEMS

PLAN - 1ST FLOOR

1/4" = 1'-0"E4.2

1 ELECTRICAL POWER & SYSTEMS PLAN - FIRST FLOOR

GENERAL NOTES:

ALL EQUIPMENT & DEVICES SHALL BE NEW UNLESS OTHERWISE NOTED.

VERIFY ALL FIELD CONDITIONS AND LOCATIONS OF EQUIPMENT, DEVICES & WIRING WITH COR, INCLUDING OTHER TRADES PRIOR TO INSTALLATION OF ELECTRICAL WORK. DO NOT SCALE

DRAWINGS.

COORDINATE WITH MECHANICAL CONTRACTOR FOR ALL MECHANICAL WORK, EQUIPMENT,

CHARACTERISTICS, LOCATIONS & QUANTITIES PRIOR TO ANY ROUGH-INS. REFER TO MECHANICAL

DRAWINGS FOR FURTHER INFORMATION.

ELECTRICAL CONTRACTOR TO VERIFY IN FIELD WITH MECHANICAL CONTRACTOR FOR ANY

CONTROLS, SWITCHING & INTERFACING PRIOR TO ANY ROUGH-IN. PROVIDE EMPTY BOXES &

RACEWAYS. POWER CIRCUITS & CONTROL RACEWAYS SHALL FOLLOW MECHANICAL.

WIRE TROUGH, PULL & JUNCTION BOXES ARE SIZED BY THE ELECTRICAL CONTRACTOR TO MEET

FIELD CONDITIONS & CODE REQUIREMENTS.

REFER TO ELECTRICAL CONNECTION SCHEDULE ON DRAWING E7.1 FOR MECHANICAL EQUIPMENT &

CIRCUITING. REFER MECHANICAL DRAWINGS & SCHEDULES FIR EQUIPMENT QUANTITIES &

LOCATIONS.

ELECTRICAL CONTRACTOR SHALL SLEEVE & SEAL ALL CONDUITS AT ALL POINTS OF PENETRATION INTO EARTH, MASONRY, OR STRUCTURE IN BUILDING. PROVIDE FIRE RATED THRU-WALL, CEILING &

FLOOR SEALS TO ASSURE LEAK FREE INSTALLATION AND PREVENTION OF GAS OR OTHER FUME

SEEPAGE INTO BUILDING.

1.

2.

3.

4.

5.

6.

7.

303 304BC

VRF

2-6

VRF

2-5

VRF

2-1

VRF

2-2

VRF

2-3

VRF

2-4

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :1

P

M

KL

PLB

JH

10/30/19

E4.4

ELECTRICAL POWER &

SYSTEMS PLAN - ATTIC

1/4" = 1'-0"E4.4

1 ELECTRICAL POWER & SYSTEMS PLAN - ATTIC

GENERAL NOTES:

ALL EQUIPMENT & DEVICES SHALL BE NEW UNLESS OTHERWISE NOTED.

VERIFY ALL FIELD CONDITIONS AND LOCATIONS OF EQUIPMENT, DEVICES & WIRING WITH

ARCHITECT, INCLUDING OTHER TRADES PRIOR TO INSTALLATION OF ELECTRICAL WORK. DO NOT

SCALE DRAWINGS.

COORDINATE WITH MECHANICAL CONTRACTOR FOR ALL MECHANICAL WORK, EQUIPMENT,

CHARACTERISTICS, LOCATIONS & QUANTITIES PRIOR TO ANY ROUGH-INS. REFER TO MECHANICAL

DRAWINGS FOR FURTHER INFORMATION.

ELECTRICAL CONTRACTOR TO VERIFY IN FIELD WITH MECHANICAL CONTRACTOR FOR ANY

CONTROLS, SWITCHING & INTERFACING PRIOR TO ANY ROUGH-IN. PROVIDE EMPTY BOXES &

RACEWAYS.

WIRE TROUGH, PULL & JUNCTION BOXES ARE SIZED BY THE ELECTRICAL CONTRACTOR TO MEET

FIELD CONDITIONS & CODE REQUIREMENTS.

REFER TO ELECTRICAL CONNECTION SCHEDULE ON DRAWING E7.1 FOR MECHANICAL EQUIPMENT &

CIRCUITING. REFER MECHANICAL DRAWINGS & SCHEDULES FIR EQUIPMENT QUANTITIES &

LOCATIONS.

ELECTRICAL CONTRACTOR SHALL SLEEVE & SEAL ALL CONDUITS AT ALL POINTS OF PENETRATION INTO EARTH, MASONRY, OR STRUCTURE IN BUILDING. PROVIDE FIRE RATED THRU-WALL, CEILING &

FLOOR SEALS TO ASSURE LEAK FREE INSTALLATION AND PREVENTION OF GAS OR OTHER FUME

SEEPAGE INTO BUILDING.

1.

2.

3.

4.

5.

6.

7.

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF 25

REPLACE RADIANT HEATING SYSTEM AT

IRONMASTER'S MANSION

100% CONSTRUCTION DOCUMENT DRAWINGS

HOFU 237580

/3

/2

:4 :1

P

M

KL

PLB

JH

10/30/19

E7.1

ELECTRICAL SCHEDULES

ELECTRICAL CONNECTION SCHEDULE- MECHANICAL EQUIPMENT

TAG NUMBER

ELECTRICAL CHARACTERISTICS LOCAL DISCONNECT DEVICE STARTER WIRING

REMARKS V/PH/HZ MCA MOCP KW HP

NONFUSED

SWITCH

FUSIBLE

SWITCH

MAN MOTOR SWITCH

DIV TYPE SIZE

COMBINATION TYPE ACCESSORIES

DIV WIRE PANEL

CIRCUIT

NUMBERW/O OL W/ OL SWITCH MCP HOA PILOT

BC 1 240/1/60 .47 15A X 26 2 #12, 1 #12 GND. - 3/4"C. HP 10,12

BC 2 240/1/60 .47 15A X 26 2 #12, 1 #12 GND. - 3/4"C. HP 14,16

CP 1 CORD & PLUG 120/1/60 FRACTIONAL 26 2 #12, 1 #12 GND. - 3/4"C. PP 17

CU 1 MODULE 1 240/3/60 33 45A 60/40/3 26 3 #6, 1 #10 GND. - 1"C. CH 1,3,5

CU 1 MODULE 2 240/3/60 33 45A 60/40/3 26 3 #6, 1 #10 GND. - 1"C. CH 7,9,11

VRF 0-1 240/1/60 1.2 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 13,15

VRF 0-2 240/1/60 3 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 13,15

VRF 0-3 240/1/60 .38 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 17,19

VRF 0-4 240/1/60 3 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 21,23

VRF 0-5 240/1/60 1.2 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 25,27

VRF 0-6 240/1/60 3 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 21,23

VRF 1-1 240/1/60 .38 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 6,8

VRF 2-1 240/1/60 1.2 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 10,12

VRF 2-2 240/1/60 1.2 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 14,16

VRF 2-3 240/1/60 2.5 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 18,20

VRF 2-4 240/1/60 2.5 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 22,24

VRF 2-5 240/1/60 1.2 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 26,28

VRF 2-6 240/1/60 2.5 15A X 26 2 #12, 1 #12 GND. - 3/4"C. CH 2,4

SCHEDULE NOTES:

TOTAL KVA B: 3.68 TOTAL CONNECTED AMPS: 38.15 A

TOTAL KVA A: 4.44 TOTAL CONNECTED KVA: 8.12 KVA

17 20 A 1 (N) RCPTL - CP-1 & TOUCH SCREEN 0.06 0.00 SPACE WITH BUS -- -- 18

15 20 A 1 (E) RCPTL - RM 002 0.36 0.20 (N) LTG & GFCI OUTDOOR 1 20 A 16

13 20 A 1 (E) FIRE ALARM & SECURITY 0.30 0.54 (E) RCPTL - RM 004, 005 1 20 A 14

11 20 A 1 (E) RCPTL - RM 003 0.36 0.72 (E) RCPTL - RM 208, 209, 304 1 20 A 12

9 20 A 1 (E) LTG & RCPTLS 0.50 0.54 (E) RCPTL - RM 201, 204 1 20 A 10

7 20 A 1 (E) RCPTL & LTG - BASEMENT 0.50 0.54 (E) RCPTLS - 101-103 1 20 A 8

5 20 A 1 (E) LTG - BASEMENT 0.50 1.00 (E) RCPTL - DEDICATED RM 204 1 20 A 6

3 20 A 1 (E) BARN & STORE 1.00 0.00 -- -- -- 4

1 20 A 1 (E) BARN & STORE 1.00 0.00 MAIN CIRCUIT BREAKER 2 100 A 2

CKT TR P DESCRIPTION A B A B DESCRIPTION P TR CKT

LOCATION: 003

ISOL. GRD. BUS:

GRD. BUS: X

10 KAIC NEUT. BUS X

MAINS: 2P/100A

208/120V 1 PHASE 3 WIRE MAIN BUS RATING: 100 A

ELECTRICAL PANEL SCHEDULE (E) PANEL PP

SCHEDULE NOTES:

TOTAL KVA C: 7.85

TOTAL KVA B: 7.89 TOTAL CONNECTED AMPS: 63.17 A

TOTAL KVA A: 10.45 TOTAL CONNECTED KVA: 26.18 KVA

17 -- -- -- 0.00 0.00 SPACE WITH BUS -- -- 18

15 -- -- -- 0.00 0.05 -- -- -- 16

13 100 A 3 MAIN CIRCUIT BREAKER 0.00 0.05 (N) BC-2 2 15 A 14

11 -- -- -- 2.60 0.05 -- -- -- 12

9 30 A 2 (E) UH - RM 005 2.60 0.05 (N) BC-1 2 15 A 10

7 -- -- -- 2.60 2.60 -- -- -- 8

5 30 A 2 (E) UH - RM 003 2.60 2.60 (E) UH - RM 004 2 30 A 6

3 -- -- -- 2.60 2.60 -- -- -- 4

1 30 A 2 (E) UH - RM 001 2.60 2.60 (E) UH - RM 002 2 30 A 2

CKT TR P DESCRIPTION A B C A B C DESCRIPTION P TR CKT

LOCATION: 003

ISOL. GRD. BUS:

GRD. BUS: X

10 KAIC NEUT. BUS X

MAINS: 3P/100A

240V 3 PHASE 3 WIRE MAIN BUS RATING: 100 A

ELECTRICAL PANEL SCHEDULE (E) PANEL HP

SCHEDULE NOTES:

TOTAL KVA C: 7.92

TOTAL KVA B: 8.66 TOTAL CONNECTED AMPS: 59.27 A

TOTAL KVA A: 7.97 TOTAL CONNECTED KVA: 24.55... KVA

29 -- -- SPACE WITH BUS 0.00 0.00 SPACE WITH BUS -- -- 30

27 -- -- -- 0.12 0.12 -- -- -- 28

25 15 A 2 VRF-0-5 0.12 0.12 VRF-2-5 2 15 A 26

23 -- -- -- 0.65 0.24 -- -- -- 24

21 15 A 2 VRF-0-4 & VRF-0-6 0.65 0.24 VRF-2-4 2 15 A 22

19 -- -- -- 0.04 0.24 -- -- -- 20

17 15 A 2 VRF-0-3 0.04 0.24 VRF-2-3 2 15 A 18

15 -- -- -- 0.48 0.12 -- -- -- 16

13 15 A 2 VRF-0-1 & VRF-0-2 0.48 0.12 VRF-2-2 2 15 A 14

11 -- -- -- 3.30 0.12 -- -- -- 12

9 -- -- -- 3.30 0.12 VRF-2-1 2 15 A 10

7 50 A 3 CU-1 (MODULE 2) 3.30 0.04 -- -- -- 8

5 -- -- -- 3.30 0.04 VRF-1-1 2 15 A 6

3 -- -- -- 3.30 0.24 -- -- -- 4

1 50 A 3 CU-1 (MODULE 1) 3.30 0.24 VRF-2-6 2 15 A 2

CKT TR P DESCRIPTION A B C A B C DESCRIPTION P TR CKT

LOCATION: KITCHEN 105

ISOL. GRD. BUS:

GRD. BUS: X

10 KAIC NEUT. BUS X

MAINS: 3P/200A

240V 3 PHASE 3 WIRE MAIN BUS RATING: 200 A

ELECTRICAL PANEL SCHEDULE (E) PANEL CH

GENERAL NOTES:

FACTORY SUPPLIED EQUIPMENT CONTROL PANEL WITH CONTROL

TRANSFORMERS, ETC. U.O.N.

PROVIDE HACR CIRCUIT BREAKERS FOR HEATING, AIR CONDITIONING &

REFRIGERATION EQUIPMENT UNLESS OTHERWISE RECOMMENDED BY

THE EQUIPMENT MANUFACTURER. PROVIDE STANDARD CIRCUIT

BREAKER IN PANEL FOR UNIT EQUIPMENT WITH FUSE DISCONNECT

SWITCH.

REFER MECHANICAL & PLUMBING DRAWINGS FOR ACTUAL PHYSICAL

LOCATION & QUANTITIES OF EQUIPMENT LISTED IN SCHEDULE.

COORDINATE ELECTRICAL WORK WITH MECHANICAL, PLUMBING, FIRE

PROTECTION AND CONTROLS CONTRACTORS FOR ALL EQUIPMENT

CHARACTERISTICS, CONTROL/INTERLOCKING CONDUIT ROUTING AND

LOCATIONS PRIOR TO ANY ROUGH-INS. CONTROL AND INTERLOCKING

WIRING (INCLUDING TERMINATIONS), AND CONTROL TRANSFORMERS

ARE BY MECHANICAL, PLUMBING OR CONTROLS…

This is the start of the file's text. The full file is on GovTribe.