This is a set of engineering drawings from the Ohio Department of Natural Resources (ODNR) Division of Engineering for the construction of New Well #3 at Hocking Hills State Park in Hocking County, Ohio (Project DNR-230117, PWS #OH3736411). The project involves installing a new water well, including associated waterline connections, electrical work, and infrastructure to integrate it with the existing water system. The drawings detail site plans, well construction specifications, electrical installations, and connection details for the new well. The project is designed by Verdantas LLC of Dublin, Ohio and requires coordination between civil and electrical contractors.

The drawings specify technical requirements including a well depth of 460 feet, 1-1/4" Schedule 80 conduit for electrical connections, and detailed specifications for waterline trenching, concrete work, and electrical systems integration with the existing Motor Control Center (MCC-1). The plans include provisions for a double throw disconnect switch system to allow operation of either Well #2 or Well #3, indicating this is an expansion of existing water infrastructure. The project requires specialized construction methods for both the well drilling/installation and the supporting electrical infrastructure, with particular attention paid to proper grounding, conduit installation, and pump control integration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WILLIAMS

FULTON LUCAS

HENRY

PAULDING

DEFIANCE

PUTNAM

HANCOCK

WOOD

OTTAWA

SANDUSKY ERIE

HURONSENECA

LORAIN

VAN WERT

ALLEN

HARDIN

WYANDOT CRAWFORD

RICHLAND

ASHLAND WAYNE

MEDINA

MERCER

DARKE

AUGLAIZE

LOGAN

UNION

MARION

MORROW

KNOX

HOLMES

SHELBY

DELAWARE COSHOCTON

ASHTABULALAKE

GEAUGA

CUTAHOGA

PORTAGE

SUMMIT

TRUMBULL

MAHONING

COLUMBIANA

CARROLL

JEFFERSON

HARRISON

TUSCARAWAS

STARK

BELMONT

GUERNSEY

MUSKINGUM

LICKING

FRANKLIN

MADISON

MIAMI

CHAMPAIGN

CLARK

PREBLE MONTGOMERY

GREENE

FAYETTE

PICKAWAY

FAIRFIELD

MORGAN

NOBLE

MONROE

WASHINGTON

ATHENS

HOCKING

VINTON

JACKSON

MEIGS

GALLIASCIOTO

PIKE

ROSS

HIGHLAND

BUTLER WARREN

HAMILTON

CLERMONT

BROWN ADAMS

CLINTON

LAWRENCE

PERRY

TITLE SHEET 1 1

D I V I S I O N O F E N G I N E E R I N G

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY, OHIO

DNR - 230117

PWS # OH3736411

CHECKED BY: TM

DRAWN BY: DJH

DESIGNED BY: AB

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 19856

DATE: 12/19/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY

6397 EMERALD PKWY, SUITE 200

DUBLIN, OH 43016

TEL. 614.793.8777

FAX 614.360.0023

APPROVED BY: ODNR REVISED DATE:

NOT TO SCALE SCALE: 1" = 1000'

PROJECT SITE

FOR OFFICIAL USE ONLY - Infrastructure Record This document is an infrastructure record pursuant to Ohio Revised Code 149.433(A). Therefore, it is not a public record and its authorized use, copying or distribution is prohibited.

N O

RT

H

N O

RT

H

LOCATION MAPVICINITY MAP

OHIO DEPARTMENT OF NATURAL RESOURCES (ODNR)

2045 MORSE ROAD, BUILDING E-3

COLUMBUS, OH 43229

PHONE: 614-265-6948

OWNER:

ENGINEER: VERDANTAS LLC

6397 EMERALD PARKWAY, SUITE 200

DUBLIN, OH 43016

PHONE: 614-793-8777

HOCKING HILLS

STATE PARK

SHEET INDEX

Sheet Title Sheet Number

TITLE SHEET 1

GENERAL NOTES 2

SITE PLAN 3

WELL DETAILS 4

ELECTRICAL SITE PLAN 5

ELECTRICAL ONE-LINE DIAGRAM AND DETAILS 6

CHECKED BY: TM

DRAWN BY: DJH

DESIGNED BY: AB

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 19856

DATE: 12/19/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY

6397 EMERALD PKWY, SUITE 200

DUBLIN, OH 43016

TEL. 614.793.8777

FAX 614.360.0023

APPROVED BY: ODNR REVISED DATE:

GENERAL NOTES 2 2

GENERAL NOTES

G00 - SPECIFICATIONS

G01 - UTILITY OWNERS

G02 - UTILITY LOCATIONS

G03 - SURVEYS

G04 - MODIFICATIONS

G05 - SAFETY

G06 - REVIEW OF PROJECT SITE

G07 - IRON PINS AND MONUMENTS

G08 - PRIOR TO COMMENCEMENT OF WORK

G09 - SANITARY FACILITIES

G10 - USE OF FIRE HYDRANTS

G11 - LEGAL DIMENSIONS AND WEIGHT LIMITS

G12 - EMERGENCY PHONE NUMBERS

G13 - INCLUSIVE BID

G14 - WORKING HOURS

G15 - RECORD DRAWINGS

G16 - NON-RUBBER TIRE VEHICLES

G17 - PROTECTION AND RESTORATION OF PROPERTY

G18 - WORK LIMITS

G19 - MISCELLANEOUS WORK

G20 - FINAL CLEANUP

G21 - INDEMNIFICATION

G22 - PAVEMENT CLEANING

G23 - WEATHER CONDITIONS

G24 - WORK IN PAVEMENT

G25 - WORK WITHIN ROAD RIGHT-OF-WAY

G26 - STORM WATER BMPS

G27- AIR AND NOISE CONTROL

G28 - PROHIBITED CONSTRUCTION ACTIVITIES

WATERLINE NOTES

W00 - WATERLINE WORK

W01 - CONFLICTS

W02 - LINE CROSSING

W03 - DISINFECTION

W04 - TESTING

W06 - CROSS-CONNECTIONS

LEGEND

DRAWING SCALE

1" = 40'

40' 10' 20'

CHECKED BY: TM

DRAWN BY: DJH

DESIGNED BY: AB

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 19856

DATE: 12/19/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY

6397 EMERALD PKWY, SUITE 200

DUBLIN, OH 43016

TEL. 614.793.8777

FAX 614.360.0023

APPROVED BY: ODNR REVISED DATE:

SITE PLAN 3 3

WATERLINE TRENCH DETAIL IN GRASSY AREA2

D

CONNECTION DETAIL1

TYPICAL WELL DETAIL

PLAN VIEW SECTION VIEW

TYPICAL WELL APRON DETAIL

WELL DETAILS 4 4

CHECKED BY: TM

DRAWN BY: DJH

DESIGNED BY: AB

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 19856

DATE: 12/19/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY

6397 EMERALD PKWY, SUITE 200

DUBLIN, OH 43016

TEL. 614.793.8777

FAX 614.360.0023

APPROVED BY: ODNR REVISED DATE:

DETAIL B - CONDUIT TRENCH DETAIL

WARNING RIBBON

POWER CONDUIT

A. THE BOTTOM OF THE TRENCH SHALL BE RELATIVELY

SMOOTH, UNDISTURBED EARTH, WELL-TAMPERED EARTH, OR

SAND, WHICH IS FREE OF ROCK, CINDERS, OR SHARP

OBJECTS.

B. CONTRACTOR SHALL BACKFILL AROUND ALL CONDUIT WITH

SIX (6) INCHES OF GRADED SAND, STONE DUST, LIMESTONE

DUST, ROCK FREE (1/4" OR LESS DIAMETER STONES) EARTH,

OR TOPSOIL. THE REMAINDER OF THE TRENCH SHALL BE

BACKFILLED WITH NATIVE SOIL, NOT CONTAINING LARGE

ROCKS. AN ADDITIONAL SIX INCHES OF MOUNDED BACKFILL

SHALL BE ADDED FOR SETTLING.

NOTES A&B

3. EXPANSION FITTINGS TO BE INSTALLED A MINIMUM EVERY 200 FEET

AND AT ALL BUILDING ENTRANCE LOCATIONS.

FINISHED GRADE

FROM MCC AT

PUMP HOUSE

INTERCEPT EXISTING

1" CONDUIT NEAR PUMP#2

AND EXTEND TOWARDS DS.

REFEED PUMP #2

FROM DISCONNECT.

INSTALL SCHED. 80 1-1/4"

INSTALL SCHED. 80 1-1/4"

CONDUIT T0 PUMP #3

CONCRETE ENCASED

POSTS, 42" DEPTH

2"x2" GALVANIZED

UNISTRUT CHANNEL

(2) SUPPORT POST - 3" RGS CONDUIT

CAPPED AND CONCRETE ENCASED.

DOUBLE THROW

DISCONNECT SWITCH.

3P, 60A, NEMA 4X.

SEE NOTE 6.

SCHEDULE 80 CONDUIT

ABOVE GROUND, TYP.

EXPANSION FITTINGS.

TYPICAL.

DETAIL A- SWICTH RACK DETAIL

CHECKED BY: RJC

DRAWN BY: RJC

DESIGNED BY: RJC

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 160084

DATE: 12/18/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY, OH APPROVED BY: ODNR REVISED DATE:

ELECTRICAL SITE PLAN 5 5

NOTE 1: CALL 811 BEFORE EXCAVATION.

NOTE 2: REFEED EXISTING PUMP #2 FROM NEW PROPOSED DISCONNECT SWITCH.

INSPECT AND SALVAGE EXISTING WIRE, FEEDING PUMP #2. ACCOUNT FOR LENGTH

REQUIRED TO TERMINATE CONDUCTORS ON NEW DISCONNECT SWITCH LOCATION.

INSTALL SCHEDULE 80 1-1/4" CONDUIT WITH CONDUIT EXPANSION FITTING ON WELL

CONDUIT RISER.

NOTE 3: PROVIDE WEATHER PROOF PLACARD AT DISCONNECT SWITCH STATING,

"DE-ENERGIZE PUMP #2 & #3 FEEDER CIRCUIT AT MCC-1 IN PUMP HOUSE BEFORE

SWITCHING PUMPS".

NOTE 4: BOND ALL EQUIPMENT GROUNDS, ENCLOSURE, AND ENCLOSURE RACK

STRUCTURE AT DISCONNECT LOCATION.

NOTE 5: VERIFY EXISTING UNDERGROUND CONDUIT BETWEEN MCC-1 AND EXISTING

PUMP #2 IS 1" PVC SCHEDULE 40. THIS IS THE MINIMALLY REQUIRED CONDUIT SIZE FOR

THE NEW SPECIFIED FEEDER CONDUCTORS. IF SCHEDULE 80 1" CONDUIT IS

DISCOVERED UNDERGROUND, NOTIFY THE ENGINEER. SCHEDULE 80 WALL THICKNESS,

COMPARED TO SCHEDULE 40, WILL NOT ACCOMMODATE NEW FEEDERS PER 40% FILL

REQUIREMENT. SCHEDULE 40 WAS DISCOVERED WHILE ON SITE IN BUILDING. THIS IS

JUST A VERIFICATION FOR THE REMAINDER OF EXISTING UNDERGROUND

INSTALLATION.

NOTE 6: PROVIDE SAFETY SWITCH, DOUBLE THROW, NON-FUSIBLE, 60A, 600V, 3 POLE,

NEMA 4X, SQUARE-D DTU362DS OR EQUIVALENT (EATON, SIEMENS, ETC.).

NOTE 7: PROVIDE AND INSTALL LISTED SPLICES FOR SUBMERSIBLE PUMP ELECTRICAL

CONNECTIONS..

NOTE 8: ALL ELECTRICAL EQUIPMENT SHALL BE RATED WITH MINIMUM 75 DEGREE C

TERMINATIONS.

NOTE 9: GROUND EQUIPMENT PER NEC ARTICLE 250.

NOTE 10: WHEN PULLING WIRE, DO NOT PULL BEYOND THE WIRE MANUFACTURER'S

MAXIMUM PULLING TENSION BETWEEN PULL POINTS. INSTALL PULL BOXES AS

NECESSARY TO ADHERE TO THIS NOTE. NOT MORE THAN 360 DEGREES OF TOTAL

BENDS BETWEEN PULL POINTS.

NOTE 8: CONDUIT SHALL BE SIZED ACCORDING TO NOTED ELECTRICAL DETAILS ON

THIS DRAWING. SCHEDULE 80 SHALL BE USED THROUGH OUT NEW INSTALLATION. THIS

INCLUDES BETWEEN PUMPS 2 AND 3, ABOVE GRADE AND UNDER DRIVEWAYS AND

WALKWAYS, AS APPLICABLE. CONDUIT ELBOW SWEEPS SHALL BE SCHEDULE 80.

SCHEDULE 80 CONDUIT, FOR PROPOSED NEW INSTALLATION, IS SIZED ADEQUATELY

FOR PROPOSED FEEDERS. SEE NOTE 5 FOR EXISTING CONDUIT NOTE.

NOTE 9: INSTALL CONDUIT EXPANSION FITTINGS WITH A MINIMUM OF 6" TRAVEL.

NOTE 10: INSTALL WARNING TAPE 12" ABOVE EACH UNDERGROUND CONDUIT. TAPE

SHALL BE AT LEAST 3" WIDE.

A: ALL ELECTRICAL WORK SHALL CONFORM TO LATEST EDITION OF THE NATIONAL

ELECTRICAL CODE ADOPTED BY OHIO, AND OWNER STANDARDS, AS APPLICABLE.

B: THE ELECTRICAL CONTRACTOR SHALL TEST ALL WIRING FOR CONTINUITY AND

PROPER GROUNDING BEFORE COMPONENT INSTALLATION, AND SHALL TEST THE ENTIRE

INSTALLATION UPON COMPLETION TO ENSURE THE ABSENCE OF SHORT CIRCUITS AND

ACCIDENTAL GROUNDS.

C: THE ELECTRICAL CONTRACTOR SHALL REVIEW MANUFACTURER'S PRODUCT

LITERATURE AND INSTALLATION INSTRUCTIONS ON ALL EQUIPMENT REQUIRING

ELECTRICAL CONNECTIONS.

D. COORDINATE ALL WORK WITH OWNER AND OTHER CONTRACTORS, AS APPLICABLE.

NOTIFY/COORDINATE WITH OWNER OF PLANNED POWER OUTAGES BEFORE SUCH

OUTAGES FOR APPROVAL.

E. PROTECT ALL BRANCH CIRCUIT WIRING AGAINST OVERCURRENT AS REQUIRED BY NEC

240.4. CONDUCTOR AMPACITY TO BE DETERMINED BY NEC 310.15 BASED ON 75°C

RATINGS. UNLESS SPECIFICALLY NOTED OTHERWISE IN CONTRACT DOCUMENTS, ALL

CONDUCTORS SHALL BE INSTALLED IN APPROVED, SPECIFIED RACEWAYS.

F. FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE STRANDED COPPER WITH 600

VOLT INSULATION. SIZES #12 THROUGH #2 SHALL BE THHN/THWN. SIZES #1 AND LARGER

SHALL BE XHHW-2, UNLESS NOTED OTHERWISE.

G. COORDINATE WITH OWNER ON STAGING OF EQUIPMENT.

H. COORDINATE WITH OWNER ON TEMPORARY STAGING SITE OR REMOVAL OF ANY

EXCAVATION SPOILS. DISPOSE BY PROPER AND LEGAL METHODS AND/OR DIRECTED BY

OWNER.

I. ALL NEW DEVICES SHALL BE FURNISHED WITH A MINIMUM OF 75°C TERMINALS. THE

CONTRACTOR SHALL SIZE THE WIRE FOR 60°C IF THE DEVICE CANNOT BE FURNISHED

WITH 75°C TERMINALS.

GENERAL ELECTRICAL NOTES

CONSTRUCTION NOTES:

ELECTRICAL ONE-LINE

DIAGRAM & DETAILS 6 6

CHECKED BY: RJC

DRAWN BY: RJC

DESIGNED BY: RJC

E N

W

S

NGINEERING

Ohio Department of Natural Resources

JOB NUMBER: DNR- 160084

DATE: 12/18/2024

SCALE: AS NOTED

HOCKING HILLS STATE PARK

NEW WELL #3

HOCKING COUNTY, OH APPROVED BY: ODNR REVISED DATE:

EXISTING ONE LINE DIAGRAM

NOTE 1: REFER TO ELECTRICAL SITE PLAN FOR ADDITIONAL INSTALLATION NOTES AND

REQUIREMENTS.

NOTE 2: AT MCC-1, RELABEL "WELL PUMP #2" MCC BUCKET AS "WELL PUMP #2 & #3

DISCONNECT", WITH AN ADDITIONAL LABEL STATING "DISCONNECT PUMP TRANSFER

SWITCH LOCATED AT PUMP #2".

NOTE 3: ADJUST EXISTING OVERLOADS HEATER SETTING DIALS BASED ON PUMP

MOTOR FLA AND SERVICE FACTOR. CONSULT WITH ENGINEER AS NECESSARY. BOTH

PUMPS #2 AND #3 ARE ASSUMED TO BE IDENTICAL, CONSULT WITH ENGINEER OF

RECORD IF THIS IS NOT THE CASE. IF DIFFERENT, AN OVERLOAD ADJUSTMENT WILL

HAVE TO BE COMPLETED DURING MANUAL TRANSFERS OF PUMPS.