This is a set of engineering drawings from the Ohio Department of Natural Resources (ODNR) Division of Engineering for the construction of New Well #3 at Hocking Hills State Park in Hocking County, Ohio (Project DNR-230117, PWS #OH3736411). The project involves installing a new water well, including associated waterline connections, electrical work, and infrastructure to integrate it with the existing water system. The drawings detail site plans, well construction specifications, electrical installations, and connection details for the new well. The project is designed by Verdantas LLC of Dublin, Ohio and requires coordination between civil and electrical contractors.
The drawings specify technical requirements including a well depth of 460 feet, 1-1/4" Schedule 80 conduit for electrical connections, and detailed specifications for waterline trenching, concrete work, and electrical systems integration with the existing Motor Control Center (MCC-1). The plans include provisions for a double throw disconnect switch system to allow operation of either Well #2 or Well #3, indicating this is an expansion of existing water infrastructure. The project requires specialized construction methods for both the well drilling/installation and the supporting electrical infrastructure, with particular attention paid to proper grounding, conduit installation, and pump control integration.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WILLIAMS
FULTON LUCAS
HENRY
PAULDING
DEFIANCE
PUTNAM
HANCOCK
WOOD
OTTAWA
SANDUSKY ERIE
HURONSENECA
LORAIN
VAN WERT
ALLEN
HARDIN
WYANDOT CRAWFORD
RICHLAND
ASHLAND WAYNE
MEDINA
MERCER
DARKE
AUGLAIZE
LOGAN
UNION
MARION
MORROW
KNOX
HOLMES
SHELBY
DELAWARE COSHOCTON
ASHTABULALAKE
GEAUGA
CUTAHOGA
PORTAGE
SUMMIT
TRUMBULL
MAHONING
COLUMBIANA
CARROLL
JEFFERSON
HARRISON
TUSCARAWAS
STARK
BELMONT
GUERNSEY
MUSKINGUM
LICKING
FRANKLIN
MADISON
MIAMI
CHAMPAIGN
CLARK
PREBLE MONTGOMERY
GREENE
FAYETTE
PICKAWAY
FAIRFIELD
MORGAN
NOBLE
MONROE
WASHINGTON
ATHENS
HOCKING
VINTON
JACKSON
MEIGS
GALLIASCIOTO
PIKE
ROSS
HIGHLAND
BUTLER WARREN
HAMILTON
CLERMONT
BROWN ADAMS
CLINTON
LAWRENCE
PERRY
TITLE SHEET 1 1
D I V I S I O N O F E N G I N E E R I N G
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY, OHIO
DNR - 230117
PWS # OH3736411
CHECKED BY: TM
DRAWN BY: DJH
DESIGNED BY: AB
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 19856
DATE: 12/19/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY
6397 EMERALD PKWY, SUITE 200
DUBLIN, OH 43016
TEL. 614.793.8777
FAX 614.360.0023
APPROVED BY: ODNR REVISED DATE:
NOT TO SCALE SCALE: 1" = 1000'
PROJECT SITE
FOR OFFICIAL USE ONLY - Infrastructure Record This document is an infrastructure record pursuant to Ohio Revised Code 149.433(A). Therefore, it is not a public record and its authorized use, copying or distribution is prohibited.
N O
RT
H
N O
RT
H
LOCATION MAPVICINITY MAP
OHIO DEPARTMENT OF NATURAL RESOURCES (ODNR)
2045 MORSE ROAD, BUILDING E-3
COLUMBUS, OH 43229
PHONE: 614-265-6948
OWNER:
ENGINEER: VERDANTAS LLC
6397 EMERALD PARKWAY, SUITE 200
DUBLIN, OH 43016
PHONE: 614-793-8777
HOCKING HILLS
STATE PARK
SHEET INDEX
Sheet Title Sheet Number
TITLE SHEET 1
GENERAL NOTES 2
SITE PLAN 3
WELL DETAILS 4
ELECTRICAL SITE PLAN 5
ELECTRICAL ONE-LINE DIAGRAM AND DETAILS 6
CHECKED BY: TM
DRAWN BY: DJH
DESIGNED BY: AB
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 19856
DATE: 12/19/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY
6397 EMERALD PKWY, SUITE 200
DUBLIN, OH 43016
TEL. 614.793.8777
FAX 614.360.0023
APPROVED BY: ODNR REVISED DATE:
GENERAL NOTES 2 2
GENERAL NOTES
G00 - SPECIFICATIONS
G01 - UTILITY OWNERS
G02 - UTILITY LOCATIONS
G03 - SURVEYS
G04 - MODIFICATIONS
G05 - SAFETY
G06 - REVIEW OF PROJECT SITE
G07 - IRON PINS AND MONUMENTS
G08 - PRIOR TO COMMENCEMENT OF WORK
G09 - SANITARY FACILITIES
G10 - USE OF FIRE HYDRANTS
G11 - LEGAL DIMENSIONS AND WEIGHT LIMITS
G12 - EMERGENCY PHONE NUMBERS
G13 - INCLUSIVE BID
G14 - WORKING HOURS
G15 - RECORD DRAWINGS
G16 - NON-RUBBER TIRE VEHICLES
G17 - PROTECTION AND RESTORATION OF PROPERTY
G18 - WORK LIMITS
G19 - MISCELLANEOUS WORK
G20 - FINAL CLEANUP
G21 - INDEMNIFICATION
G22 - PAVEMENT CLEANING
G23 - WEATHER CONDITIONS
G24 - WORK IN PAVEMENT
G25 - WORK WITHIN ROAD RIGHT-OF-WAY
G26 - STORM WATER BMPS
G27- AIR AND NOISE CONTROL
G28 - PROHIBITED CONSTRUCTION ACTIVITIES
WATERLINE NOTES
W00 - WATERLINE WORK
W01 - CONFLICTS
W02 - LINE CROSSING
W03 - DISINFECTION
W04 - TESTING
W06 - CROSS-CONNECTIONS
LEGEND
DRAWING SCALE
1" = 40'
40' 10' 20'
CHECKED BY: TM
DRAWN BY: DJH
DESIGNED BY: AB
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 19856
DATE: 12/19/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY
6397 EMERALD PKWY, SUITE 200
DUBLIN, OH 43016
TEL. 614.793.8777
FAX 614.360.0023
APPROVED BY: ODNR REVISED DATE:
SITE PLAN 3 3
WATERLINE TRENCH DETAIL IN GRASSY AREA2
D
CONNECTION DETAIL1
TYPICAL WELL DETAIL
PLAN VIEW SECTION VIEW
TYPICAL WELL APRON DETAIL
WELL DETAILS 4 4
CHECKED BY: TM
DRAWN BY: DJH
DESIGNED BY: AB
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 19856
DATE: 12/19/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY
6397 EMERALD PKWY, SUITE 200
DUBLIN, OH 43016
TEL. 614.793.8777
FAX 614.360.0023
APPROVED BY: ODNR REVISED DATE:
DETAIL B - CONDUIT TRENCH DETAIL
WARNING RIBBON
POWER CONDUIT
A. THE BOTTOM OF THE TRENCH SHALL BE RELATIVELY
SMOOTH, UNDISTURBED EARTH, WELL-TAMPERED EARTH, OR
SAND, WHICH IS FREE OF ROCK, CINDERS, OR SHARP
OBJECTS.
B. CONTRACTOR SHALL BACKFILL AROUND ALL CONDUIT WITH
SIX (6) INCHES OF GRADED SAND, STONE DUST, LIMESTONE
DUST, ROCK FREE (1/4" OR LESS DIAMETER STONES) EARTH,
OR TOPSOIL. THE REMAINDER OF THE TRENCH SHALL BE
BACKFILLED WITH NATIVE SOIL, NOT CONTAINING LARGE
ROCKS. AN ADDITIONAL SIX INCHES OF MOUNDED BACKFILL
SHALL BE ADDED FOR SETTLING.
NOTES A&B
3. EXPANSION FITTINGS TO BE INSTALLED A MINIMUM EVERY 200 FEET
AND AT ALL BUILDING ENTRANCE LOCATIONS.
FINISHED GRADE
FROM MCC AT
PUMP HOUSE
INTERCEPT EXISTING
1" CONDUIT NEAR PUMP#2
AND EXTEND TOWARDS DS.
REFEED PUMP #2
FROM DISCONNECT.
INSTALL SCHED. 80 1-1/4"
INSTALL SCHED. 80 1-1/4"
CONDUIT T0 PUMP #3
CONCRETE ENCASED
POSTS, 42" DEPTH
2"x2" GALVANIZED
UNISTRUT CHANNEL
(2) SUPPORT POST - 3" RGS CONDUIT
CAPPED AND CONCRETE ENCASED.
DOUBLE THROW
DISCONNECT SWITCH.
3P, 60A, NEMA 4X.
SEE NOTE 6.
SCHEDULE 80 CONDUIT
ABOVE GROUND, TYP.
EXPANSION FITTINGS.
TYPICAL.
DETAIL A- SWICTH RACK DETAIL
CHECKED BY: RJC
DRAWN BY: RJC
DESIGNED BY: RJC
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 160084
DATE: 12/18/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY, OH APPROVED BY: ODNR REVISED DATE:
ELECTRICAL SITE PLAN 5 5
NOTE 1: CALL 811 BEFORE EXCAVATION.
NOTE 2: REFEED EXISTING PUMP #2 FROM NEW PROPOSED DISCONNECT SWITCH.
INSPECT AND SALVAGE EXISTING WIRE, FEEDING PUMP #2. ACCOUNT FOR LENGTH
REQUIRED TO TERMINATE CONDUCTORS ON NEW DISCONNECT SWITCH LOCATION.
INSTALL SCHEDULE 80 1-1/4" CONDUIT WITH CONDUIT EXPANSION FITTING ON WELL
CONDUIT RISER.
NOTE 3: PROVIDE WEATHER PROOF PLACARD AT DISCONNECT SWITCH STATING,
"DE-ENERGIZE PUMP #2 & #3 FEEDER CIRCUIT AT MCC-1 IN PUMP HOUSE BEFORE
SWITCHING PUMPS".
NOTE 4: BOND ALL EQUIPMENT GROUNDS, ENCLOSURE, AND ENCLOSURE RACK
STRUCTURE AT DISCONNECT LOCATION.
NOTE 5: VERIFY EXISTING UNDERGROUND CONDUIT BETWEEN MCC-1 AND EXISTING
PUMP #2 IS 1" PVC SCHEDULE 40. THIS IS THE MINIMALLY REQUIRED CONDUIT SIZE FOR
THE NEW SPECIFIED FEEDER CONDUCTORS. IF SCHEDULE 80 1" CONDUIT IS
DISCOVERED UNDERGROUND, NOTIFY THE ENGINEER. SCHEDULE 80 WALL THICKNESS,
COMPARED TO SCHEDULE 40, WILL NOT ACCOMMODATE NEW FEEDERS PER 40% FILL
REQUIREMENT. SCHEDULE 40 WAS DISCOVERED WHILE ON SITE IN BUILDING. THIS IS
JUST A VERIFICATION FOR THE REMAINDER OF EXISTING UNDERGROUND
INSTALLATION.
NOTE 6: PROVIDE SAFETY SWITCH, DOUBLE THROW, NON-FUSIBLE, 60A, 600V, 3 POLE,
NEMA 4X, SQUARE-D DTU362DS OR EQUIVALENT (EATON, SIEMENS, ETC.).
NOTE 7: PROVIDE AND INSTALL LISTED SPLICES FOR SUBMERSIBLE PUMP ELECTRICAL
CONNECTIONS..
NOTE 8: ALL ELECTRICAL EQUIPMENT SHALL BE RATED WITH MINIMUM 75 DEGREE C
TERMINATIONS.
NOTE 9: GROUND EQUIPMENT PER NEC ARTICLE 250.
NOTE 10: WHEN PULLING WIRE, DO NOT PULL BEYOND THE WIRE MANUFACTURER'S
MAXIMUM PULLING TENSION BETWEEN PULL POINTS. INSTALL PULL BOXES AS
NECESSARY TO ADHERE TO THIS NOTE. NOT MORE THAN 360 DEGREES OF TOTAL
BENDS BETWEEN PULL POINTS.
NOTE 8: CONDUIT SHALL BE SIZED ACCORDING TO NOTED ELECTRICAL DETAILS ON
THIS DRAWING. SCHEDULE 80 SHALL BE USED THROUGH OUT NEW INSTALLATION. THIS
INCLUDES BETWEEN PUMPS 2 AND 3, ABOVE GRADE AND UNDER DRIVEWAYS AND
WALKWAYS, AS APPLICABLE. CONDUIT ELBOW SWEEPS SHALL BE SCHEDULE 80.
SCHEDULE 80 CONDUIT, FOR PROPOSED NEW INSTALLATION, IS SIZED ADEQUATELY
FOR PROPOSED FEEDERS. SEE NOTE 5 FOR EXISTING CONDUIT NOTE.
NOTE 9: INSTALL CONDUIT EXPANSION FITTINGS WITH A MINIMUM OF 6" TRAVEL.
NOTE 10: INSTALL WARNING TAPE 12" ABOVE EACH UNDERGROUND CONDUIT. TAPE
SHALL BE AT LEAST 3" WIDE.
A: ALL ELECTRICAL WORK SHALL CONFORM TO LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE ADOPTED BY OHIO, AND OWNER STANDARDS, AS APPLICABLE.
B: THE ELECTRICAL CONTRACTOR SHALL TEST ALL WIRING FOR CONTINUITY AND
PROPER GROUNDING BEFORE COMPONENT INSTALLATION, AND SHALL TEST THE ENTIRE
INSTALLATION UPON COMPLETION TO ENSURE THE ABSENCE OF SHORT CIRCUITS AND
ACCIDENTAL GROUNDS.
C: THE ELECTRICAL CONTRACTOR SHALL REVIEW MANUFACTURER'S PRODUCT
LITERATURE AND INSTALLATION INSTRUCTIONS ON ALL EQUIPMENT REQUIRING
ELECTRICAL CONNECTIONS.
D. COORDINATE ALL WORK WITH OWNER AND OTHER CONTRACTORS, AS APPLICABLE.
NOTIFY/COORDINATE WITH OWNER OF PLANNED POWER OUTAGES BEFORE SUCH
OUTAGES FOR APPROVAL.
E. PROTECT ALL BRANCH CIRCUIT WIRING AGAINST OVERCURRENT AS REQUIRED BY NEC
240.4. CONDUCTOR AMPACITY TO BE DETERMINED BY NEC 310.15 BASED ON 75°C
RATINGS. UNLESS SPECIFICALLY NOTED OTHERWISE IN CONTRACT DOCUMENTS, ALL
CONDUCTORS SHALL BE INSTALLED IN APPROVED, SPECIFIED RACEWAYS.
F. FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE STRANDED COPPER WITH 600
VOLT INSULATION. SIZES #12 THROUGH #2 SHALL BE THHN/THWN. SIZES #1 AND LARGER
SHALL BE XHHW-2, UNLESS NOTED OTHERWISE.
G. COORDINATE WITH OWNER ON STAGING OF EQUIPMENT.
H. COORDINATE WITH OWNER ON TEMPORARY STAGING SITE OR REMOVAL OF ANY
EXCAVATION SPOILS. DISPOSE BY PROPER AND LEGAL METHODS AND/OR DIRECTED BY
OWNER.
I. ALL NEW DEVICES SHALL BE FURNISHED WITH A MINIMUM OF 75°C TERMINALS. THE
CONTRACTOR SHALL SIZE THE WIRE FOR 60°C IF THE DEVICE CANNOT BE FURNISHED
WITH 75°C TERMINALS.
GENERAL ELECTRICAL NOTES
CONSTRUCTION NOTES:
ELECTRICAL ONE-LINE
DIAGRAM & DETAILS 6 6
CHECKED BY: RJC
DRAWN BY: RJC
DESIGNED BY: RJC
E N
W
S
NGINEERING
Ohio Department of Natural Resources
JOB NUMBER: DNR- 160084
DATE: 12/18/2024
SCALE: AS NOTED
HOCKING HILLS STATE PARK
NEW WELL #3
HOCKING COUNTY, OH APPROVED BY: ODNR REVISED DATE:
EXISTING ONE LINE DIAGRAM
NOTE 1: REFER TO ELECTRICAL SITE PLAN FOR ADDITIONAL INSTALLATION NOTES AND
REQUIREMENTS.
NOTE 2: AT MCC-1, RELABEL "WELL PUMP #2" MCC BUCKET AS "WELL PUMP #2 & #3
DISCONNECT", WITH AN ADDITIONAL LABEL STATING "DISCONNECT PUMP TRANSFER
SWITCH LOCATED AT PUMP #2".
NOTE 3: ADJUST EXISTING OVERLOADS HEATER SETTING DIALS BASED ON PUMP
MOTOR FLA AND SERVICE FACTOR. CONSULT WITH ENGINEER AS NECESSARY. BOTH
PUMPS #2 AND #3 ARE ASSUMED TO BE IDENTICAL, CONSULT WITH ENGINEER OF
RECORD IF THIS IS NOT THE CASE. IF DIFFERENT, AN OVERLOAD ADJUSTMENT WILL
HAVE TO BE COMPLETED DURING MANUAL TRANSFERS OF PUMPS.
ONE-LINE CONSTRUCTION NOTES: