30 JUL 2012
TECHNICAL ADDENDUM NO. 4
New Commissary & Navy Exchange NSA Annapolis, Maryland
Incorporate the following items in the Contract Documents.
TO THE SPECIFICATIONS:
1. Add the following to Section 15651, immediately following paragraph 2.9.1.3:
2.9.1.3.a 1D02-2, 3, 4, 5 Case, Refrigerated, 2, 3, 4 or 5 Glass Doors, Medium Temperature, Upright:
a. Salient Characteristics:
(1) Nominal Dimensions:
(a) Length:
1D02-2: 2 Dr, 62 inches L, w/o ends (1 inch to 2 inch each end panel).
1D02-3: 3 Dr, 92-1/2 inches L, w/o ends (1 inch to 2 inch each end panel).
1D02-4: 4 Dr, 122-7/8 inches L, w/o ends (1 inch to 2 inch each end panel).
1D02-5: 5 Dr, 153-5/16 inches L, w/o ends (1 inch to 2 inch each end panel).
(b) Height: 83-1/2 inches.
(c) Depth: 39-3/4 inches.
(d) Door Width: 30 inches.
(e) Upper Shelves: 22 inches deep.
(f) Sill Height: 16 inches (max).
(2) Designed to maintain a product temperature of 30 to 36 deg F.
(3) Lights: Vertical lighting assembly, one at each end and one between all doors.
(4) Shelves: Five solid adjustable upper shelves per door section with price tag molding. One bottom epoxy coated wire rack per door section with price tag molding.
(5) Doors: Constructed per paragraph 2.10.A.29, 67 inches high with magnetic gaskets, automatic door closures, doors hinged on left side.
(6) Maximum refrigeration load for parallel system 1250 B/hr/lf.
TO THE DRAWINGS:
1. Sheet A1.1.0 and A1.1.2: Revise display case designations from 1G10-4 and 1G10-5 to read
1G12-4 and 1G12-5.
2. Sheet R3.2 - Refrigeration Equipment and Piping Schedule: Change the equipment number for system CU3 from "1G10" to "1G12."
3. Sheet E2.1 – Add an Isolated Ground (IG) electrical receptacle at counter for cash register. Refer to Supplemental drawing SD-E2.1.
nicholka Typewritten Text nicholka Typewritten Text HDEC03-12-R-0006 Amend 04 Attachment 2
4. Sheet E2.2 –
Change installed location of the Isolated Ground (IG) electrical receptacle. Refer to Supplemental drawing SD-E2.2 for new location.
Revise Sheet Keyed notes #1 to state: Install Power devices under floor in casework. Coordinate actual location with casework contractor.
5. Sheet E2.3 –
Add two isolated Ground (IG) electrical receptacles at counter in room 600. Refer to Supplemental drawing SD-E2.3 for locations.
Add Sheet Keynotes #24 to drawing E2.3. Note #24 – provide pedestal type duplex receptacles
(2) for #2 underfloor duct with 120 V power. Branch circuits fed from UPS electrical panel “LY”.
Replace Sheet keynotes Note #13 shown in room 101 with this new note #24.
6. Sheet E2.4 –
Change installed location of Isolated Ground (IG) electrical receptacle. Refer to Supplemental drawing SD-E2.4.
Add two Isolated Ground (IG) electrical receptacles at counter in room 103. Refer to Supplemental drawing SD-E2.4.
7. Sheet E3.7 – Provide cash register communication devices and sheet Keynote #1 in room 200.
Refer to Supplemental drawing SD-E3.7
8. Sheet E3.10 - Provide cash register communication devices (two locations) and sheet Keynote #1 in room 103. Refer to Supplemental drawing SD-E3.10.
9. Sheet E7.4 – Revise panel schedules for electrical panels “LX”, “LY”, and “LZ”. Refer to Supplemental drawing SD-E7.4 – Panel LX, SD-E7.4 – Panel LY, and SD-E7.4 – Panel LZ.
END OF TECHNICAL ADDENDUM NO. 4
PANEL 'LX' LOAD TYPES
PROJECT : ANNAPOLIS EXCHANGE FED FROM : 55 KVA UPS ENCLOSURE : NEMA 1 0 RECPT 5 HEAT
PROJECT # : FDWD3303 MAINS RATING (A): 150A MCB MOUNTING : SURFACE 1 LTG 6 A/C
LOCATION : ELECT. RM. 124 BUSSING (A): 225 CB TYPE : BOLT-ON 2 EQUIP 7 KITCH
NOTES : 1 VOLTAGE : 208/120V, 3PH, 4W PROVIDE : NEUTRAL BUS 3 MTR 8 ELEV
INTERRUPTING : 10 kAIC RMS SYM GROUND BUS 4 COMP 9 125%
CKT AMPS POLE CIRCUIT DESCRIPTION LOAD TYPE PH TYPE LOAD CIRCUIT DESCRIPTION POLE AMPS CKT 1 20 1 CCTV QUAD RECEPTS (4) 1440 0 A 4 180 CUSTOMER SERVICE - CASH REGISTER 1 20 2 3 20 1 LPS OFFICE RECEPTS. (5) 1080 0 B 4 180 CUSTOMER SERVICE - CASH REGISTER 1 20 4
5 20 1 LPS OFFICE RECEPTS. (2) 360 0 C 0 360 TELEPHONE QUAD RECEPT. 1 20 6
7 20 1 DOOR EXIT ALARM - DOCK DOOR 200 2 A 0 360 TELEPHONE QUAD RECEPT. 1 20 8
9 20 1 RPS POWER 200 2 B 0 360 TELEPHONE QUAD RECEPT. 1 20 10
11 20 1 MNCP POWER 200 2 C 2 200 FA TRANSMITTER POWER 1 20 12
13 20 1 CASH REGISTER - IG AT SHOE DEPT. 180 2 A 2 200 DOOR EXIT ALARM - DOUBLE DOORS 1 20 14 15 20 1 QUAD RECEPT - IG AT IT EQUIP. RM 360 2 B 2 360 QUAD RECEPT. - IG AT LPS OFFICE 1 20 16 17 20 1 QUAD RECEPT - IG AT IT EQUIP. RM 360 2 C 2 1080 QUAD & DUPLEX RECEPTS - IG AT LPS RM. 1 20 18 19 20 1 QUAD RECEPT - IG AT IT EQUIP. RM 360 2 A 2 1440 QUAD RECEPTS. - IG AT CASH COUNT RM 1 20 20 21 20 1 CASH REGISTER -IG AT SALES AREA 180 2 B 2 200 UPS REMOTE INDICATOR PANEL 1 20 22 23 20 1 CCTV CAMERA AT REAR EXT. OF BLDG. 1200 4 C 0 360 TELEPHONE QUAD RECEPT. 1 20 24 25 20 1 CCTV CAMERA AT REAR EXT. OF BLDG. 1200 4 A 0 360 TELEPHONE QUAD RECEPT. 1 20 26 27 20 1 TWISTLOCK 30A RECEPT- MDF RM 117 2880 2 B 2 1760 TWISTLOCK 20A RECEPT- MDF RM 117 2 20 28
29 20 1 TWISTLOCK 30A RECEPT- MDF RM 117 2880 2 C 2 1760 - - 30
31 20 1 QUAD RECEPT - IG AT IT EQUIP. RM 360 2 A 4 840 EAS J BOX BACK DOORS 1 20 32
33 20 1 CASH REGISTER 180 2 B SPARE 1 20 34
35 20 1 SPARE C SPARE 1 20 36
37 90 3 PANEL LZ 5040 A BUSSED SPACE ONLY 1 20 38
39 4460 B BUSSED SPACE ONLY 1 20 40
41 7400 C BUSSED SPACE ONLY 1 20 42
PANEL SUB FEED TOTAL TOTAL DEMAND NOTES:
VA FEED THRU CONN VA AMPS 1. PROVIDE PANELBOARD WITH AN ISOLATED GROUND BUS.
PHASE A 7,120 5,040 0 12,160 12,160 101
PHASE B 7,740 4,460 0 12,200 12,200 102
PHASE C 8,760 7,400 0 16,160 16,160 135
TOTAL 23,620 16,900 0 40,520 40,520 113 REVISIONS:
PANEL 'LY' LOAD TYPES
PROJECT : ANNAPOLIS EXCHANGE FED FROM : PANEL 'LZ' ENCLOSURE : NEMA 1 0 RECPT 5 HEAT
PROJECT # : FDWD3303 MAINS RATING (A): MLO MOUNTING : SURFACE 1 LTG 6 A/C
LOCATION : LAYAWAY 300 BUSSING (A): 100 CB TYPE : BOLT-ON 2 EQUIP 7 KITCH
NOTES : 1 VOLTAGE : 208/120V, 3PH, 4W PROVIDE : NEUTRAL BUS 3 MTR 8 ELEV
INTERRUPTING : 10 kAIC RMS SYM GROUND BUS 4 COMP 9 125%
CKT AMPS POLE CIRCUIT DESCRIPTION LOAD TYPE PH TYPE LOAD CIRCUIT DESCRIPTION POLE AMPS CKT 1 20 1 SECURITY PEDESTAL - EAS 840 4 A 4 180 MAIN CASH REGISTER - IG POWER 1 20 2 3 20 1 SECURITY PEDESTAL - EAS 840 4 B 4 180 MAIN CASH REGISTER - IG POWER 1 20 4 5 20 1 SECURITY PEDESTAL - EAS 720 2 C 4 180 MAIN CASH REGISTER - IG POWER 1 20 6 7 20 1 MAIN CASH REGISTER - IG POWER 180 4 A 4 180 MAIN CASH REGISTER - IG POWER 1 20 8 9 20 1 MAIN CASH REGISTER - IG POWER 180 4 B 4 180 MAIN CASH REGISTER - IG POWER 1 20 10
11 20 1 MAIN CASH REGISTER - IG POWER 180 4 C 4 180 CHECKOUT/LAUNDRY CASH REGISTER 1 20 12 13 20 1 MAIN CASH REGISTER - IG POWER 180 4 A 4 180 GARDEN CENTER CASH REGISTER 1 20 14 15 20 1 MAIN CASH REGISTER - IG POWER 180 4 B 4 180 GARDEN CENTER CASH REGISTER 1 20 16
17 20 1 HUMIDOR CASH REGISTER 180 4 C 2 720 SECURITY PEDESTAL - EAS 1 20 18
19 20 1 HUMIDOR CASH REGISTER 180 4 A 4 180 CASH REGISTER 1 20 20
21 20 1 SPARE B SPARE 1 20 22
23 20 1 GARDEN - SECURITY PEDESTAL - EAS 720 2 C SPARE 1 20 24
25 20 1 GARDEN - SECURITY PEDESTAL - EAS 840 2 A 0 360 GARDEN SECURITY RECEPTS (2) - EAS 1 20 26
27 20 1 SPARE B 4 180 CHECKOUT/LAUNDRY CASH REGISTER 1 20 28
29 20 1 SECURITY PEDESTAL - EAS 720 2 C 4 180 CHECKOUT/LAUNDRY CASH REGISTER 1 20 30
31 20 1 SPARE A 4 180 ISLAND CASH REGISTER 1 20 32
33 20 1 CCTV CAMERA AT GARDEN SHOP 600 4 B 4 600 CCTV CAMERA AT GARDEN SHOP 1 20 34 35 20 1 CCTV CAMERA AT BANK TENANT EXT. 600 4 C 4 600 CCTV CAMERA AT GARDEN SHOP 1 20 36
37 20 1 SPARE A SPARE 1 20 38
39 20 1 SPARE B SPARE 1 20 40
41 20 1 SPARE C SPARE 1 20 42
PANEL SUB FEED TOTAL TOTAL DEMAND NOTES:
VA FEED THRU CONN VA AMPS 1. PROVIDE PANELOBARD WITH AN ISOLATED GROUND BUS.
PHASE A 3,480 0 0 3,480 3,480 29
PHASE B 3,120 0 0 3,120 3,120 26
PHASE C 4,980 0 0 4,980 4,980 42
TOTAL 11,580 0 0 11,580 11,580 32 REVISIONS:
PANEL 'LZ' LOAD TYPES
PROJECT : ANNAPOLIS EXCHANGE FED FROM : PANEL 'LX' ENCLOSURE : NEMA 1 0 RECPT 5 HEAT
PROJECT # : FDWD3303 MAINS RATING (A): MLO MOUNTING : RECESSED 1 LTG 6 A/C
LOCATION : DOCTOR'S OFFICE 802 BUSSING (A): 100A CB TYPE : BOLT-ON 2 EQUIP 7 KITCH
NOTES : 1 VOLTAGE : 208/120V, 3PH, 4W PROVIDE : NEUTRAL BUS 3 MTR 8 ELEV
INTERRUPTING : 10 kAIC RMS SYM GROUND BUS 4 COMP 9 125%
CKT AMPS POLE CIRCUIT DESCRIPTION LOAD TYPE PH TYPE LOAD CIRCUIT DESCRIPTION POLE AMPS CKT
1 20 1 BARBER SHOP CASH REGISTER 180 4 A 4 180 OPTICAL SHOP CASH REGISTER 1 20 2
3 20 1 BARBER SHOP CASH REGISTER 180 4 B 4 180 JEWELRY SHOP CASH REGISTER 1 20 4
5 20 1 EAS J BOX FRONT DOORS 1260 4 C 4 180 JEWELRY SHOP CASH REGISTER 1 20 6
7 20 1 EAS J BOX FRONT DOORS 840 4 A SPARE 1 20 8
9 20 1 SPARE B 2 200 DOOR EXIT ALARM - DOUBLE DOORS 1 20 10
11 20 1 SPARE C 4 200 EAS J BOX - FOOD COURT SIDE DOORS 1 20 12
13 20 1 SPARE A 2 360 JEWELRY SHOP CASH REGISTERS (2) 1 20 14
15 20 1 OPTOMETRY STORE CASH REGISTER 180 4 B 4 600 CCTV EXTERIOR CAMERA - ON POLE 1 20 16
17 20 1 CCTV EXTERIOR CAMERA - ON POLE 600 4 C 4 180 CASH REGISTER 1 20 18
19 20 1 SPARE A SPARE 1 20 20
21 20 1 SPARE B SPARE 1 20 22
23 20 1 SPARE C SPARE 1 20 24
25 20 1 BUSSED SPACE ONLY A BUSSED SPACE ONLY 1 20 26
27 20 1 BUSSED SPACE ONLY B BUSSED SPACE ONLY 1 20 28
29 20 1 BUSSED SPACE ONLY C BUSSED SPACE ONLY 1 20 30
31 20 1 BUSSED SPACE ONLY A BUSSED SPACE ONLY 1 20 32
33 20 1 BUSSED SPACE ONLY B BUSSED SPACE ONLY 1 20 34
35 20 1 BUSSED SPACE ONLY C BUSSED SPACE ONLY 1 20 36
37 20 1 BUSSED SPACE ONLY A 3480 PANEL 'LY' 3 60 38
39 20 1 BUSSED SPACE ONLY B 3120 40
41 20 1 BUSSED SPACE ONLY C 4980 42
PANEL SUB FEED TOTAL TOTAL DEMAND NOTES:
VA FEED THRU CONN VA AMPS 1. PROVIDE PANELBOARD WITH AN ISOLATED GROUND BUS.
PHASE A 1,560 3,480 0 5,040 5,040 42
PHASE B 1,340 3,120 0 4,460 4,460 37
PHASE C 2,420 4,980 0 7,400 7,400 62
TOTAL 5,320 11,580 0 16,900 16,900 47 REVISIONS:
| Technical Addendum No. 4 |
| SD - E2.1 |
| SD - E2.2 |
| SD - E2.3 |
| SD - E2.4 |
| SD - E3.7 |
| SD - E7.4 Panel LX |
| SD - E7.4 Panel LY |
| SD - E7.4 Panel LZ |
| SD - E3.10 |