IQO INQUIRY

FM: PL8211

TO: Contractors

DATE (MM/DD/YYYY): 5/1/2018

SUBJECT: HC101317QA905-0005 Amend: 0005

A. TYPE ACTION: AMEND

1. PURPOSE: THE PURPOSE OF THIS AMENDMENT TO SOLICITATION HC101317QA905 IS

TO:

1. CHANGE THE SERVICE DATE TO BE MET TO 01 SEP 18 SIP;

2. CHANGE LOCATION Z FROM FORT GEORGE G MEADE, MD TO MECHANICSBURG, PA,

17055.

3. ADD NEW PARAGRAPH 9 AT PURPOSE STATEMENT TO CLARIFY THAT 50 METERS

PHYSICAL SEPARATION REQUIREMENT STILL APPLIES TO THIS REQUIREMENT, BUT THE

DIVERSITY REQUIREMENT IS WAIVED ONLY AS TO THE PART OF THE REQUIREMENT

ROUTE THAT PASSES THROUGH DOWNTOWN PHILADELPHIA, PA.

4. ADD NEW CIRCUIT PARAMETERS AND TESTING REQUIREMENTS.

5. ADD SP 52.

RECAP

1. SUBMIT A QUOTE TO PROVIDE, INSTALL AND MAINTAIN AN UNPROTECTED OC-48C

LEASED IP BACKBONE TRUNK BETWEEN DISA IE1 PROVIDED CISCO ASR-9010 ROUTER

(UJEWMCG030) (IPT-PEX1) BLDG 1901, ROOM 14, 1901 EAST 3RD STREET; MCGUIRE AFB, NJ

08641, AND DISA IE1 PROVIDED CISCO ASR-9010 ROUTER (UJEWMEC030) (IPT-PE1) BLDG

308, ROOM 203, 5450 CARLISLE PIKE, MECHANICSBURG, PA 17055.

A. CONTRACTORS SHALL MEET RTD OF 10 MILLISECONDS.

B. VENDOR MUST DELIVER OC-48C SERVICE 2W (UNPROTECTED) FROM COML DEMARC TO

GOVERNMENT SERVICE DELIVERY POINT AT BOTH LOCATIONS.

C. VENDOR MUST PROVIDE LIGHT LEVEL READINGS (DB LOSS) ON EXTENSION FROM

COMMERCIAL POP TO GOVERNMENT SERVICE DELIVERY POINT (SDP) AT BOTH

LOCATIONS PRIOR TO CIRCUIT TURN UP TO THE GOVERNMENT ENSURING LEVELS ARE

WITHIN SPECS. LIGHT LEVELS MUST BE ADJUSTED TO -5 TO -13.

D. VENDOR MUST CONDUCT WALK-THROUGH SITE SURVEY PRIOR TO INSTALLATION AT

BOTH LOCATIONS.

E. VENDOR MUST CONTACT DISA GOC IP BACKBONE ENGINEERING AND IMPLEMENTATION

GROUP UPON RECEIPT OF A VALID ORDER TO ESTABLISH THE COORDINATION AND

ACTIVATION PROCESS. (C) 618-220-8627 (D) 770-8627

F. VENDOR MUST CONDUCT A SATISFACTORY 24 HOUR END TO END TEST PRIOR TO TURN

OVER TO THE GOVERNMENT FOR ACCEPTANCE TESTING.

HC101317QA905-0005

G. OC-48C SERVICE MUST PASS A DOCUMENTED SATISFACTORY 24 HOUR END TO END

TEST IAW ITU STANDARD M.2101 PRIOR TO TURN UP TO THE GOVERNMENT

2. EACH CONTRACTOR IS RESPONSIBLE FOR READING AND COMPLYING WITH ALL

TECHNICAL ASPECTS OF THIS SOLICITATION, TO INCLUDE READING AND AGREEING

WITH THE STANDARD PROVISIONS, ATTACHMENTS LISTING SPECIFIC TECHNICAL

REQUIREMENTS, PRICE QUOTE REQUIREMENTS, AND REQUESTED SERVICE DATE.

FAILURE TO READ AND ADHERE TO ANY PORTION OF THE INQUIRY SHALL RENDER THE

QUOTE NON-COMPLIANT AND RESULT IN IT BEING EXCLUDED FROM EVALUATION AND

AWARD.

3. THE SERVICE DATE TO BE MET IS: 01 SEP 18 (SIP). THE GOVERNMENT ASSUMES THAT

CONTRACTORS HAVE CONSIDERED ALL ISSUES THAT MAY IMPACT THE SERVICE DATE.

THE GOVERNMENT MAY CANCEL, TERMINATE, OR REQUEST CONSIDERATION IAW

STANDARD PROVISION 42 FOR FAILURE TO MEET CONTRACTUAL SERVICE DATE OR

COMPLY WITH ANY CONTRACT TERMS OR CONDITIONS.

4. CONTRACTORS SHALL SUBMIT QUOTES IAW STANDARD PROVISION 04. QUOTES SHALL

INCLUDE SUFFICIENT DETAIL FOR EFFECTIVE EVALUATION AND SHOULD NOT SIMPLY

REPHRASE OR RESTATE THE GOVERNMENT REQUIREMENTS. RATHER, THEY MUST

PROVIDE CONVINCING RATIONALE TO ADDRESS HOW THE CONTRACTOR INTENDS

TO MEET THE REQUIREMENT. IN RESPONSE TO THIS SOLICITATION, NO TERMS OR

CONDITIONS PLACED UPON THE GOVERNMENT, NOR ASSUMPTIONS WILL BE ACCEPTED.

RESPONSES TO CONTRACTORS ARE ENCOURAGED TO SUBMIT QUESTIONS AND REQUEST

CLARIFICATIONS OF THE REQUIREMENT (S) BEFORE SUBMITTING QUOTES. QUESTIONS

SHALL BE SUBMITTED TO CONTRACT SPECIALIST AND CONTRACTING OFFICER DURING

THE SOLICITATION PHASE ONLY, AND RESPONSES FOR ALL INTERESTED PARTIES WILL

BE POSTED TO FEDBIZOPPS. . QUOTES MUST BE UPLOADED TO IDEAS AND A COURTESY

COPY MAY BE SENT TO THE FOLLOWING MAILBOX. DISA SCOTT AFB DITCO MAILBOX

VENDOR QUOTES . THIS MAILBOX MAY ALSO BE USED WHEN HAVING ISSUES UPLOADING

QUOTES IN IDEAS.

5. THIS REQUIREMENT MUST BE WORKED IN CONJUNCTION WITH SOLICITATION

HC101317QA885/TSR RU15FEB175128.

6. CONTRACTOR SHALL PROVIDE COLOR POWERPOINT DRAWINGS SHOWING THE ROUTES

FROM THE COMMERCIAL DEMARKS TO THE SUPPORTING CENTRAL OFFICES AND/OR

WIRING CENTERS, ENSURING THE PHYSICAL END TO END DIVERSITY REQUIREMENTS ARE

BEING MET. DRAWINGS MUST INCLUDE SEPARATION DISTANCES, TOTAL FIBER MILES

AND ROUND TRIP DELAY BASED ON ACTUAL DISTANCE IN MILES. REFER TO STANDARD

PROVISION 39 FOR SPECIFIC DOCUMENTATION REQUIREMENTS. SAMPLE DRAWINGS ARE

INCLUDED IN THE ATTACHMENTS.

7. ESTABLISH TSP: TSP0GKVND-01

8. THIS REQUIREMENT MUST BE ENGINEERED AND PROVISIONED TOTALLY DIVERSE

END TO END TO GOVERNMENT'S SERVICE DELIVERY POINTS (SDP'S) FROM TSR

RU15FEB175128 (HC101317QA885); MEANING THAT PHYSICAL PATHS ARE TOTALLY

SEPARATE INCLUDING MAN HOLES, CONDUIT, (CENTRAL OFFICE LOCATIONS), AND FIBER

BUILDS. ADDITIONALLY AS A MINIMUM MUST HAVE 50 METERS PHYSICAL SEPARATION

FROM TSR RU15FEB175128.

9. THE DIVERSITY REQUIREMENT STATED ABOVE OF 50 METERS MINIMUM PHYSICAL

SEPARATION FROM TSR RU15FEB175128 IS WAIVED IN DOWNTOWN PHILADELPHIA, PA,

BUT REMAINS IN PLACE FOR THE REST OF THE PATH OF THIS REQUIREMENT.

M. ADDITIONAL INFORMATION:

3. TSR NUMBER: RU15FEB175129E

4. CCSD: XXXXBSE4

Z. DITCO CONTACT:

Christopher OConnor

618-229-9712 christopher.t.oconnor2.civ@mail.mil

Paul A. Heard

DITCO Contracting Officer

Add the following:

LOCATION OF TERMINATION A:

ADDRESS: (BLDG) 1901; 1901 EAST 3RD STREET; MC GUIRE AIR FORCE BASE, NJ, 08641

ROOM: 14; NA FL

LOCATION: ACC

EXTENSION OF TELECOMMUNICATIONS SERVICE: All facilities between vendor's commercial communications interface point and termination location shall be provided by vendor. All cables shall be run in accordance with local site standards

INTERFACE: INTERFACE: ELECTRICAL: OPTICAL; PHYSICAL: SC;; (PHYSICAL)

DEMARK: BLDG 1901, RDP (REMOTE DEMARC POINT) ROOM,

1901 CAN DO WAY, MCGUIRE AFB, NJ 08641

PRI: TSGT ROBERT MIXON, D650-2244/2777, C609-754-2244/2777

EMAIL: ROBERT.MIXON@US.AF.MIL

NPA/NXX: 609/754

UNIQUE INSTALLATION FACTORS: (1) OPTICAL INTERFACE CARD (GFE)(DISA IE1 PROVIDED)

OC48C / PO0/0/0; RESERVATION: 17785

(2) FIBER CABLE X-CONNECT, IN-HOUSE, INSIDE WIRE,

SINGLE-MODE, 1310NM, DISA IE4

(3) FIBER TERMINATING PATCH PANEL (GFE)(DISA IE1

PROVIDED)

(4) FIBER CABLE X-CONNECT, IN-HOUSE, INSIDE WIRE,

SINGLE-MODE, 1310NM, TELCO

(5) CONFIG:

IP ADDRESS: 33.20.15.78

SUBNET MASK: 255.255.255.252

(6) FIBER CABLE X-CONNECT, IN-HOUSE, INSIDE WIRE,

SINGLE-MODE, 1310NM, TELCO

(7) COMMERCIAL FIBER POINT OF PRESENCE

AMPLIFYING INFO:

A. DISA IE4 IS RESPONSIBLE FOR INSTALLATION AND GSM-O FOR MAINTENANCE OF CISCO ASR-9010 ROUTER, OPTICAL INTERFACE CARD BLDG 1901, ROOM 14.

B. DISA IE4 IS RESPONSIBLE FOR INSTALLATION AND GSM-O FOR

SINGLE MODE FIBER FROM OPTICAL INTERFACE CARD INSTALLED IN CISCO ASR-9010 ROUTER TO DROP SIDE OF

DISA IE1 PROVIDED FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO ASR-9010 ROUTER. COORDINATE

TYPE OF CONNECTORS.

C. VENDOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF SINGLE MODE FIBER FROM LINE SIDE OF

DISA IE1 PROVIDED FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO ASR-9010 ROUTER SUITE

(UJEWMCG030) BLDG 1901, ROOM 14 TO DROP SIDE OF COMMERCIAL FIBER POINT OF PRESENCE FIBER

DISTRIBUTION PANEL BLDG 1901, RDP (REMOTE DEMARCATION POINT) ROOM. COORDINATE TYPE CONNECTORS

FOR TERMINATION TO DISA PROVIDED PATCH PANEL.

D. VENDOR MUST PROVIDE FIBER STRANDS FROM CISCO ASR-9010

ROUTER SUITE FIBER PATCH PANEL TO THE COMMERCIAL POINT OF PRESENCE (FIBER DISTRIBUTION PANEL)

WITHOUT SPLICING AND OR USE OF CONNECTORS TO CONNECT 2 OR MORE FIBER STRANDS MEANING THE FIBER

CANNOT BE BROKEN IN THE MIDDLE AND MUST BE CONTINUOUS.

E. CIRCUIT MUST BE TAGGED WITH LOCAL CIRCUIT ID AND LONG

HAUL CIRCUIT NO. AT LINE SIDE OF DISA PROVIDED FIBER TERMINATING PATCH PANEL BLDG 1901, ROOM 14 AND

AT DROP SIDE OF VENDOR'S FIBER DISTRIBUTION PANEL INSTALLED IN THEIR COMMERCIAL FIBER POINT OF

PRESENCE.

F. VENDOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE

OF SINGLE MODE FIBER FROM LINE SIDE OF DISA IE1 PROVIDED FIBER TERMINATING PATCH PANEL INSTALLED IN

CISCO ASR-9010 ROUTER SUITE (UJEWMCG030) BLDG 1901, ROOM 14 TO DROP SIDE OF COMMERCIAL FIBER POINT

OF PRESENCE FIBER DISTRIBUTION PANEL BLDG 1901, RDP (REMOTE DEMARCATION POINT) ROOM. COORDINATE

TYPE CONNECTORS FOR TERMINATION TO DISA PROVIDED PATCH PANEL.

G. VENDOR MUST COORDINATE WITH GOVERNMENT SITE PERSONNEL TO CONDUCT WALK THROUGH SITE

SURVEY FOR EXACT CABLE FT. FROM DISA PROVIDED FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO

ASR-9010 ROUTER SUITE BLDG 1901, ROOM 14 TO COMMERCIAL FIBER POINT OF PRESENCE BLDG 1901, ROOM 25.

H. VENDOR MUST PROVIDE FIBER STRANDS FROM DISA PROVIDED

FIBER PATCH PANEL INSTALLED IN CISCO ASR-9010 ROUTER TO COMMERCIAL DEMARC LOCATION WITHOUT

SPLICING AND OR USE OF CONNECTORS TO CONNECT 2 OR MORE FIBER STRANDS MEANING THE FIBER CANNOT

BE BROKEN IN THE MIDDLE AND MUST BE CONTINUOUS.

I. CIRCUIT MUST BE TAGGED WITH LOCAL CIRCUIT ID AND LONG

HAUL CIRCUIT NO. AT LINE SIDE OF DISA IE1 PROVIDED FIBER

PATCH PANEL BLDG 1901, ROOM 14 AND DROP SIDE OF COMMERCIAL DEMARC BLDG 1901, RDP (REMOTE

DEMARCATION POINT) ROOM. ADDITIONALLY, VENDOR MUST SHOW SITE PERSONNEL LISTED ON THIS ORDER THE

EXACT TERMINATION POINT WHEN INSTALLATION IS COMPLETE.

J. VENDOR MUST SCHEDULE/COORDINATE WITH POC'S LISTED ON THIS ORDER 72 HOURS IN ADVANCE PRIOR TO

SITE SURVEYS OR

INSTALLATIONS.

INSIDE WIRE INSTALLATION / MAINTENANCE REQUIRED: YES/ YES

CONTACT: (PMRY POC) MR. RAYMOND MANSFIELD;

(UNCLASS USER) RAYMOND.MANSFIELD.2@US.AF.MIL;

(CMCL) 609-754-2244; (DSN) 650-2777

(ALT POC) CIRCUIT ACTIONS;

(UNCLASS ORG) CIRCUIT_ACTIONS@US.AF.MIL;

(CMCL) 609-754-2244; (DSN) 312-650-2777

Add the following:

LOCATION OF TERMINATION B:

ADDRESS: (BLDG) 308, 5450 CARLISLE PIKE, MECHANICSBURG, PA 17055

ROOM: 203

LOCATION: BCC

EXTENSION OF TELECOMMUNICATIONS SERVICE: All facilities between vendor's commercial communications interface point and termination location shall be provided by vendor. All cables shall be run in accordance with local site standards

INTERFACE: INTERFACE: ELECTRICAL: OPTICAL; PHYSICAL: LC; (PHYSICAL) LC; (ELECTRICAL) OPTICAL

DEMARK: (BLDG) 308

(RM) 203

5450 CARLISLE PIKE

MECHANICSBURG, PA 17055

NPA/NXX: 717/605

UNIQUE INSTALLATION FACTORS: (1) FIBER CABLE X-CONNECT, IN-HOUSE, INSIDE WIRE,

SINGLE-MODE, 1310NM, TELCO

(2) FIBER TERMINATING PATCH PANEL (GFE)(DISA IE1 PROVIDED)

(3) FIBER CABLE X-CONNECT, IN-HOUSE, INSIDE WIRE,

SINGLE-MODE, 1310NM, DISA IE4

(4) OPTICAL INTERFACE CARD (GFE)(DISA IE1 PROVIDED); OC48C

/ PO0/0/0 RESERVATION: 17786

(5) CISCO ASR-9010 ROUTER (GFE)(DISA IE1 PROVIDED); NODE

ID: UJEWMEC030

AMPLIFYING INFO:

A. VENDOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE

OF SINGLE MODE FIBER FROM COMMERCIAL FIBER POINT OF

PRESENCE FIBER DISTRIBUTION PANEL BLDG 308, ROOM 203 TO

LINE SIDE OF DISA IE1 PROVIDED FIBER TERMINATING PATCH

PANEL INSTALLED IN CISCO ASR-9010 ROUTER SUITE (UJEWMEC030)

BLDG 308, ROOM 203. COORDINATE TYPE CONNECTORS FOR

TERMINATION TO DISA IE1 PROVIDED PATCH PANEL.

B. VENDOR MUST PROVIDE FIBER STRANDS FROM COMMERCIAL FIBER

POINT OF PRESENCE FIBER DISTRIBUTION PANEL BLDG 308, ROOM

203 TO DISA IE1 PROVIDED FIBER PATCH PANEL INSTALLED IN

CISCO ASR-9010 ROUTER SUITE BLDG 308, ROOM 203 WITHOUT

SPLICING AND OR USE OF CONNECTORS TO CONNECT 2 OR MORE

FIBER STRANDS MEANING THE FIBER CANNOT BE BROKEN IN THE

MIDDLE AND MUST BE CONTINUOUS.

C. CIRCUIT MUST BE TAGGED WITH LOCAL CIRCUIT ID AND LONG

HAUL CIRCUIT NO. AT COMMERCIAL FIBER POINT OF PRESENCE

FIBER DISTRIBUTION PANEL BLDG 308, ROOM 203 AND LINE SIDE

OF DISA IE1 PROVIDED FIBER TERMINATING PATCH PANEL BLDG

308, ROOM 203.

D. DISA IE4 IS RESPONSIBLE FOR INSTALLATION AND GSM-O FOR

MAINTENANCE OF SINGLE MODE FIBER FROM DROP SIDE OF DISA IE1

PROVIDED FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO

ASR-9010 ROUTER SUITE TO OPTICAL INTERFACE CARD INSTALLED

IN CISCO ASR-9010 ROUTER SUITE. COORDINATE TYPE OF

CONNECTORS.

E. VENDOR MUST SCHEDULE/COORDINATE WITH POC'S LISTED ON

THIS ORDER 72 HOURS IN ADVANCE PRIOR TO SITE SURVEYS OR

INSTALLATIONS.

F. DISA IE4 IS RESPONSIBLE FOR INSTALLATION AND GSM-O FOR

MAINTENANCE OF CISCO ASR-9010 ROUTER, OPTICAL INTERFACE

CARD BLDG 308, ROOM 203.

G. DISA IE4 IS RESPONSIBLE FOR INSTALLATION AND GSM-O FOR

SINGLE MODE FIBER FROM OPTICAL INTERFACE CARD INSTALLED IN

CISCO ASR-9010 ROUTER TO DROP SIDE OF DISA IE1 PROVIDED

FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO ASR-9010

ROUTER. COORDINATE TYPE OF CONNECTORS.

H. VENDOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE

OF SINGLE MODE FIBER FROM LINE SIDE OF DISA IE1 PROVIDED

FIBER TERMINATING PATCH PANEL INSTALLED IN CISCO ASR-9010

ROUTER SUITE (UJEWMCG030) BLDG 308, ROOM 203. TO DROP SIDE

OF COMMERCIAL FIBER POINT OF PRESENCE FIBER DISTRIBUTION

PANEL BLDG 308, ROOM 203. COORDINATE TYPE CONNECTORS FOR

TERMINATION TO DISA PROVIDED PATCH PANEL.

I. VENDOR MUST PROVIDE FIBER STRANDS FROM CISCO ASR-9010

ROUTER SUITE FIBER PATCH PANEL TO THE COMMERCIAL POINT OF

PRESENCE (FIBER DISTRIBUTION PANEL) WITHOUT SPLICING AND OR

USE OF CONNECTORS TO CONNECT 2 OR MORE FIBER STRANDS

MEANING THE FIBER CANNOT BE BROKEN IN THE MIDDLE AND MUST

BE CONTINUOUS.

J. CIRCUIT MUST BE TAGGED WITH LOCAL CIRCUIT ID AND LONG

HAUL CIRCUIT NO. AT LINE SIDE OF DISA PROVIDED FIBER

TERMINATING PATCH PANEL BLDG 308, ROOM 203. AND AT DROP

SIDE OF VENDOR'S FIBER DISTRIBUTION PANEL INSTALLED IN

THEIR COMMERCIAL FIBER POINT OF PRESENCE.

INSIDE WIRE INSTALLATION / MAINTENANCE REQUIRED: YES/ YES

CONTACT: PRI: DAN BRAMBLEY

D322-918-6200

C717-918-6200

PAGER C717-410-0055

EMAIL: DANIEL.S.BRAMBLEY.CIV@MAIL.MIL

ALT: FRED MURPHEY

D322-918-6610

C717-918-6610

PAGER C717-230-4103

EMAIL: FREDERICK.H.MURPHEY.CIV@MAIL.MIL

ORG EMAIL: DISA.MECHANICSBURG.EIS.MBX.CIRCUITS-CKTS@MAIL.MIL