Handlon Grinder Building - Bid Drawings 3.pdf

PDF 5 MB Posted

Attached to
472/20205. SMD; Handlon CF - Bar Screen and Grinder Upgrades
Solicitation number
RFQ - 171 - 230000000448
Issued by
Ionia County, Michigan

About this file

This document is a set of bid drawings for the Handlon Grinder Building HVAC upgrades, managed by the Michigan Department of Technology, Management and Budget's State of Michigan Design and Construction Division. The drawings provide general HVAC notes, a symbols legend, and floor plans detailing the installation of new exhaust fans, unit heaters, louvers, and thermostats. Key elements include a Class 1, Division 1 hazardous environment in the screen room, and the requirement for all work and materials to conform to the Michigan Mechanical Code. Bid documents are due on April 27, 2023.

The drawings also include electrical plans and details, specifying a new 200A 480/277V 3-phase electrical service, fiber optic connectivity, and various Class 1, Division 1 explosion-proof equipment and wiring requirements for the hazardous area. The project will be funded through the State of Michigan and requires compliance with all relevant electrical and safety codes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL HVAC NOTES

1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS,

COMBUSTION EQUIPMENT STACKS, & PLUMBING VENTS AT

LEAST 10 FEET FROM OUTDOOR AIR INTAKES.

2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER

MANUFACTURERS WRITTEN INSTRUCTIONS.

3. COORDINATE LOUVER SIZES WITH ARCHITECTURAL TRADES

PRIOR TO CONSTRUCTION.

4. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER

DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

5. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,

ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT

MAY AFFECT THE WORK.

6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"

CONDITION DURING CONSTRUCTION.

7. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.

8. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,

LATEST APPLICABLE EDITION.

9. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT

FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED

OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED

SHEET METAL, MIN. 26 GA.

10. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE

FLEXIBLE DUCT CONNECTORS.

11. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR

SPECIFICATIONS THE MORE STRINGENT AND GREATER COST

ITEM SHALL BE USED.

12. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.

IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

DO NOT SCALE FROM DRAWINGS.

MECHANICAL SYMBOLS LEGEND

HVAC PIPING SYMBOLS

F/S

F/S s s

TEMPERATURE CONTROL SYMBOLS

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

GATE VALVE

GAS COCK

CHECK VALVE

BALANCE COCK

CIRCUIT SETTER

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

BALL VALVE

SOLENOID VALVE

EXPANSION VALVE WITH

THERMOSTATIC BULB

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

HOSE & DRAIN END VALVE

PRESSURE RELIEF VALVE

PRESSURE REDUCING VALVE

TRIPLE DUTY VALVE

GAS PRESSURE REGULATOR

STRAINER (BLOW-OFF)

FLOW DIRECTION

PIPING DROP

PIPING RISE

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

THERMOMETER

PUMP

UNION

PIPE ANCHOR

PIPE GUIDE

BACK FLOW PREVENTER

PIPE CAP

PIPE BREAK

THERMOMETER WELL

EXPANSION LOOP

EXPANSION COMPENSATOR

FLOAT & THERMOSTATIC STEAM TRAP

INVERTED BUCKET STEAM TRAP

THERMOSTAT

PROGRAMMABLE THERMOSTAT

THERMOSTAT (W/ NIGHT SETBACK)

ROOM SENSOR

HUMIDISTAT

PRESSURE GAUGE

DAMPER (ELECTRIC OPERATION)

DAMPER (PNEUMATIC OPERATION)

DAMPER BLADES

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

TURNING VANES

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

90° TEE W/45° APPROACH

CONICAL TAKE-OFF

CONICAL TAKE-OFF W/ DAMPER

BALANCE DAMPER

RETURN AIR DUCT BOOT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VERTICAL FIRE DAMPER

EXISTING VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

EXISTING HORIZONTAL FIRE DAMPER

VERTICAL SMOKE DAMPER

HORIZONTAL SMOKE DAMPER

VERTICAL FIRE / SMOKE DAMPER

HORIZONTAL FIRE / SMOKE DAMPER

DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,

PROVIDED & WIRED BY E.T.C.

UNIT HEATER

CEILING EXHAUST FAN

ROOF MOUNTED EXHAUST FAN

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

TAG CFM

NECK REMARKS

SIZE

BT

FT

SD-1 250

8"ø ---

P

H

S

T

T P

T N

M

M

SD

EXHAUST FAN WITH DAMPER DETAIL

SCALE: NTS

1 OUTSIDE AIR LOUVER DETAIL

SCALE: NTS

EXTRUDED ALUMINUM

STATIONARY LOUVER (COLOR TO

BE SELECTED BY ARCHITECT)

BRICK

CONCRETE BLOCK

FACTORY BIRDSCREEN

EXTENDED SILL

SEAL WEATHER TIGHT

DOUBLE-DRAINABLE BLADE

DETAIL NOTE:

SEE PLANS & SCHEDULES FOR

LOUVER DIMENSIONS

EXHAUST FAN

BACKDRAFT

DAMPER/LOUVER

HANGER RODS ASSEMBLY

WITH ELASTOMERIC

ISOLATORS

WALL

WALL SLEEVE WITH GUARD

M

MOTORIZED DAMPER

OA DUCTWORK

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

M-100

LDT

NAS

MECHANICAL SYMBOLS,

ABBREVIATIONS,

+ NOTES

HVAC KEY NOTES

INSTALL ELECTRIC UNIT HEATER AT LOCATION SHOWN.

MOUNT AS HIGH AS POSSIBLE.

INSTALL EXHAUST FAN AT LOCATION SHOWN. MOUNT AS HIGH

AS POSSIBLE.

INSTALL LOUVER AT LOCATION SHOWN WITH BOTTOM OF

LOUVER AT 16" AFF.

INSTALL THERMOSTAT AND ASSOCIATED CONTROL WIRING AT

LOCATION SHOWN.

EF-1

L-1

L-2

T

EUH-2EUH-1

EF-2

M

M

D-1

D-2 1 1

T

GENERAL KEY NOTES

1. ALL WORK AND MATERIALS IN SCREEN ROOM SHALL BE FOR A

CLASS 1, DIVISION 1 HAZARDOUS ENVIRONMENT.

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

M-400

LDT

NAS

FLOOR PLAN - HVAC NEW

N FLOOR PLAN - HVAC NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

FCPS

V

M C

VI

AV

B

C

DC

M

B

KP

SSCP

CR

SS

AS

TS

G

NCC

M P

E

A L B1 B2

S

SRS

X

X

X

CB

EMERGENCY PUSH STATION

CODE BLUE STATION

TVSS

VFD

TRANSIENT VOLTAGE SURGE SUPPRESSION

VARIABLE FREQUENCY DRIVE

GLASS BREAK

DS

DUPLEX RECEPTACLE

TEACHER STATION

ADMINISTRATION STATION

STUDENT STATION

CARD READER

CARBON MONOXIDE DETECTOR

H

DOCK LIGHT FIXTURE

CONTROL MODULE

S

TELEPHONE / DATA OUTLET

DUTY STATION

STAFF STATION

STAFF REGISTER STATION

DOME LIGHT

DUAL BED STATION

SINGLE BED STATION

BED / LIGHT INTERFACE

PENDENT INTERFACE

EMERGENCY PULL STATION

MASTER STATION

NURSE CALL CONTROLLER

NURSE CALL

ADDENDUM NOTE

PLAN NOTE

DEMOLITION NOTE

THREE PHASE MOTOR

BELL

AUDIO / VIDEO INPUT

VIDEO INPUT

WALL MOUNTED SPEAKER / CLOCK COMBO

WALL MOUNTED SPEAKERS

DUAL FACE CLOCK

CCTV CONTROL PANELCCTV

SECURITY SYSTEM CONTROL PANEL

KEY PAD

BEAM DETECTOR

MOTION DETECTOR

DOOR CONTACT

CAMERA

MONITOR MODULE

FIRE CONTROL POWER SUPPLY

VISUAL ONLY UNIT

ELECTRICAL SYMBOLS LEGEND

DH

V

S

C

M

I

J

SINGLE RECEPTACLE (120 VOLT)

EMERGENCY RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SINGLE FACE CLOCK

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

OUTLETS

LIGHT FIXTURE

STRIP FIXTURE

IN-GRADE LIGHT FIXTURE

SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)

WALL MOUNT LIGHT FIXTURE

CEILING LIGHT FIXTURE

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED LIGHT FIXTURE

EXTERIOR WALL MOUNT LIGHT FIXTURE

WALLPACK LIGHT FIXTURE

SPECIAL PURPOSE LIGHT FIXTURE

HIGH BAY LIGHT FIXTURE

EMERGENCY EGRESS LIGHT FIXTURE

(number of heads shown)

EMERGENCY LIGHT FIXTURE

FIXTURES

SWITCHES

SINGLE-POLE SWITCH

DIMMER SWITCH

TIME SWITCH

KEY SWITCH

MANUAL MOTOR SWITCH

THERMAL OVERLOAD SWITCH

SWITCH WITH PILOT LIGHT

FOUR-WAY SWITCH

THREE-WAY SWITCH

CIRCUITRY and RACEWAYS

UNDERFLOOR DUCT

BUS DUCT

PLUGMOLD AS SPECIFIED

WIREMOLD AS SPECIFIED

FLEXIBLE PIGTAILS/CONNECTIONS

"CONDUIT RUN CONTINUES" INDICATION

END OF CONDUIT RUN, CAP AND STAKE

END OF CONDUIT RUN

HOME RUN (with circuit numbers)

CONDUIT STUB DOWN

CONDUIT STUB UP

CONDUIT INSTALLED

CONDUIT INSTALLED

MECHANICAL

ELECTRIC WATER HEATER

ELECTRIC UNIT HEATER

PIPE TRACE HEATER

RESISTANCE HEATER, KW SHOWN

SINGLE PHASE MOTOR

SOUND and SIGNAL

INTERCOM OUTLET

MICROPHONE OUTLET

TELEVISION OUTLET

CHIME

BUZZER

VOLUME CONTROL

SPEAKER

SERVICE and EQUIPMENT

THERMOSTAT

CAPACITOR

ENCLOSED CIRCUIT BREAKER

TRANSFER SWITCH

WIREWAY

GROUND CONNECTION PER N.E.C.

TELEPHONE TERMINAL BOARD

GENERATOR, KW SHOWN

CURRENT TRANSFORMERS

UTILITY METER, AS REQUIRED

WEATHERHEAD

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

COMB. STARTER

MAGNETIC STARTER

DISCONNECT SWITCH

TRANSFORMER

CONTROL

xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt

LIGHTING CONTACTOR

CONTROL TRANSFORMER

buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)

PHOTOCELL (voltage as required)

HUMIDISTAT

FIRE ALARM

TAMPER SWITCH (furnished by FP/C) FLOW SWITCH (furnished by FP/C)

FIREFIGHTER COMMUNICATION JACK

MAGNETIC DOOR HOLDER

REMOTE INDICATING LIGHT, CLG. MTD.

REMOTE INDICATING LIGHT, WALL MTD.

END OF LINE DEVICE

ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

PULL STATION

SPEAKER & LIGHT

SPEAKER

HORN

DUCT SMOKE DETECTOR

HEAT DETECTOR

SMOKE DETECTOR

HORN & LIGHT

DESIGNATIONS

(by E.C.)

(by others)

TT

FACP

ANN

EOL

G

WW

PC

CT

TS

T

H

TC

IC

F

FC

F

T

1,3

OR

PM

WM

BD

UFD

B

F S

J

J

D

WH

PP

J

SWITCH STYLE OCCUPANCY SENSOROC

DIGITAL TIME SWITCH

POWER PACK

DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT

DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT

ULTRASONIC SENSOR - 360° - 2 CIRCUIT

OCCUPANCY SENSOR / PHOTOCELL

WALL MOUNT DUAL TECHNOLOGY SENSOR

OS5

OS4

T

OS2

OS3

OS1

PP

DUCT SMOKE DETECTORF/S

CEILING MOUNTED WIFI

DIGITAL EQUIPMENT METER, AS REQUIRED

POLE

PUMP

PANEL

P

PNL

PVC

PRV-

P-

PB

POLY VINYL CLORIDE

POWER ROOF VENTILATOR

PULL BOX

GENERAL CONTRACTOR

GROUND

HUMIDIFIERH-

GND

GFI

GC

GROUND FAULT INTERUPTER

ABBREVIATIONS LEGEND

POWER

SWITCH

RECEPT

SF-

SWBD

TCC

SPEC

SW

RGC

RTU-

PWR

VOLTS

WATTS

UF

V

W

UL

VL

UNO

UH-

TS

TYP

TR

ROOF TOP UNIT

RECEPTACLE

SWITCHBOARD

UNDER FLOOR

SPECIFICATIONS

RIGID GALVANIZED STEEL CONDUIT

UNLESS NOTED OTHERWISE

UNDERWRITERS' LABORATORIES, INC.

TAMPER PROOF RECEPTACLE

TAMPER PROOF SWITCH

TEMPERATURE CONTROL CONTRACTOR

VERIFY LOCATION WITH OWNER

TYPICAL

UNIT HEATER

SUPPLY FAN

WITH

WITHOUT

W/

XFMR

W/O

WP

TRANSFORMER

WEATHER PROOF

HOUR

LIGHT

JUNCTION BOX

LIGHT CONTROL

ISOLATED GROUND

HORSEPOWER

MINIMUM

MOUNT

MAKE-UP AIR UNIT

MOTOR CONTROL CENTER

MAIN LUG ONLY

MOUNTED

MOUNTING

MAXIMUM

LIGHTING

LT FLEX

MTD

MUAU-

MTG

MLO

MIN

MT

MC

MAX

MCC

LTG

IG

LC

LT

IMC

JB

HR

HVAC

HOA

HP

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

NIGHT LIGHTNL

NTS

NO

NIC

NC

HAND-OFF-AUTO SELECTOR SWITCH

HEATING/VENTILATING/AIR CONDITIONING

INTERMEDIATE METAL CONDUIT

LIQUID TIGHT FLEXIBLE METAL CONDUIT

MECHANICAL CONTRACTOR

HID HIGH INTENSITY DISCHARGE

A

AC

AFF

ACU-

AHJ

AHU-

AS

B-

BC

AIC

ATS

BLDG

CHLR-

CND (C)

CKT BKR

CKT

CUH-

CU-

DISC

DFU-

EF-

EC

DWH-

EBB-

DWG

CT-

EXIST (E)

EWC

FLEX

FLA

FLR

FSES

FLUOR

EMT

ABOVE FINISHED FLOOR

AIR CONDITIONING UNIT

AMPS

ABOVE COUNTER

AIR HANDLING UNIT

AUTOMATIC TRANSFER SWITCH

AMPS INTERUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

ABOVE SHELF

BOILER

BUILDING

BELOW COUNTER

CHILLER

DOMESTIC WATER HEATER

CABINET UNIT HEATER

CIRCUIT

CIRCUIT BREAKER

CONDUIT

CONDENSING UNIT

COOLING TOWER

DUCT FURNACE

DRAWING

DISCONNECT

FOOD SERVICE EQUIP. SUPPLIER

ELECTRIC WATER COOLER

ELECTRICAL CONTRACTOR

ELECTRIC BASEBOARD

ELECTRICAL METALLIC TUBING

EXISTING

EXHAUST FAN

FLOOR

FLUORESCENT

FLEXIBLE CONDUIT

FULL LOAD AMPS

EM EMERGENCY

F/S FIRE/SMOKE

FU- FURNACE

LED - 4' EXPLOSION PROOF FIXTURE. FIXTURE IS RATED FOR CLASS 1, DIVISION 1, CLASS D.

FIXTURE

MOUNTING

HEIGHT

LAMPSDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.

LIGHTING FIXTURE SCHEDULE

LE551-L3-V1-4-D-E-PB

WDGE3-LED-P2-50K-70CRI-R4-MVOLT-DDBXDLITHONIA LIGHTING OR

EQUAL

LBEM

LB

LAEM

LA

LED - EXPLOSION PROOF LIGHT FIXTURE WITH EMERGENCY BATTERY PACK.

LED - EXTERIOR WALL PACK.

LED - EXTERIOR WALL PACK WITH EMERGENCY BATTERY PACK.

CEILING SURFACE

MOUNT

5070 LUMENS

4000K , 43W

LED

12'-0" ABOVE FINISH

GRADE

12'-0" ABOVE FINISH

GRADE

BALLAST INFO

0-10V

GENERAL ELECTRICAL NOTES

1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL RATING.

2. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL STEEL.

3. CONTRACTORS SHALL VISIT THE PROJECT SITE AND DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED

BEFORE BIDDING THE PROJECT.

4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT WHERE WORK IS BEING DONE EXCEPT

ITEMS NOTED OTHERWISE.

5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK, SURFACES SHALL BE PATCHED TO MATCH

ADJACENT.

6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND

THEN PATCHED TO MATCH, OR AS NOTED.

7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED.

PROVIDE ALL REQUIRED CUTTING AND PATCHING.

8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL

SURFACE MOUNTED EQUIPMENT.

9. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING SERVICE TO EQUIPMENT.

10. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO

ENGINEER FOR CLARIFICATION.

11. CONDUITS AND BOXES:

11.1. 3/4" MINIMUM TRADE SIZE.

11.2. EMT TYPE CONDUIT IS APPROVED.

11.3. NO PVC ALLOWED INSIDE OF BUILDINGS.

11.4. CONDUITS SHALL BE ATTACHED WITH TWO-HOLE STRAPS. SINGLE HOLE STRAPS ARE NOT PERMITTED.

11.5. NO SET SCREWS ARE ALLOWED.

11.6. TAMPER-PROOF SCREWS REQUIRED FOR EXPOSED CONDUIT AND BOXES MOUNTED BELOW TEN FEET.

11.7. DRIVE PIN ANCHORS USED ON MASONRY OR CONCRETE WALLS/ CEILINGS.

12. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

12.1. STRAP DISTANCE: 5 FEET.

12.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.

12.3. FITTINGS: COMPRESSION.

12.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.

13. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

13.1. STRAP DISTANCE: 3 FEET.

13.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.

13.4. FITTINGS: COMPRESSION.

13.5. BELL BOXES: FS TYPE.

13.6. NO KNOCKOUTS.

13.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES

14. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE CEILINGS IS ACCEPTABLE. REFER TO TC

DRAWINGS FOR SUPPORT DETAILS.

15. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.

16. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.

17. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED CONDUIT FOLLOWING NOTES 11 AND 12

ABOVE.

18. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.

19. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE EPC-40-PVC

20. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER PORTABLE GENERATORS SHALL BE USED TO

REPLACE ANY ELECTRICAL SERVICE EXCEEDING THIS TIME PERIOD.

CEILING SURFACE

MOUNT

WDGE3-LED-P2-50K-70CRI-R4-MVOLT-E20WC-DDBXD

9,504 LUMENS

4000K, 60W

LED

8,077 LUMENS

5000K, 59W

LED

HZCAS700-SA-R-HO-120/277VBEGHELLI OR EQUALXA LED - EXIT SIGN. -- LED

8,077 LUMENS

5000K, 59W

LED

HZ-CAS300-SA-VLO-WT50-120-277V-HZ-STN90; BSL310HAZLDPI OR EQUAL

LDPI OR EQUAL

CSL4-LSCSKIM LIGHTING OR

EQUAL

LCEM

LC LED - 4' INDUSTRIAL STRIP FIXTURE.

LED - 4' INDUSTRIAL STRIP FIXTURE WITH EMERGENCY BATTERY PACK.KIM LIGHTING OR

EQUAL UR20-96L-50-4K8-3-BLT-TPL; COMPASS-CPL25

5,191 LUMENS

4000K, 38W

LED

5,191 LUMENS

4000K, 38W

LED

CEILING SURFACE

MOUNT

CEILING SURFACE

MOUNT

0-10V

0-10V

0-10V

0-10V

0-10V

LITHONIA LIGHTING OR

EQUAL

M file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

E-100

MMG

JFS

ELECTRICAL

SYMBOLS,

ABBREVIATIONS,

+ NOTES

Service Road

Bluewater Hwy

Bluewater Hwy

PANE LP-PB

480/277V-3PH, 200A

FROM EXISTING

MAINTENANCE

BUILDING

1 2

A B

FIBER PANEL

ELECTRICAL KEY NOTES

CONTRACTOR SHALL PROVIDE AND INSTALL NEW 200A/3P BREAKER IN

EXISTING MAIN DISTRIBUTION PANEL. CONTRACTOR SHALL FIELD VERIFY

AND MATCH EXISTING BREAKER MANUFACTURER.

CONTRACTOR SHALL INSTALL NEW FIBER FROM EXISTING MAINTENANCE

BUILDING NETWORK SWITCH TO NEW FIBER SWITCH IN THE BAR SCREEN

BUILDING.

CONDUIT & WIRE SCHEDULE

-(4) 250 KCMIL 3" #2 THHN/THWN75

TAG KCMIL

AWG °C TEMP.

SIZE

CONDUIT GND RATED TYPE REMARKS

A

FIBER. REFER TO E-800.- (1) 2" - --B

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

E-200

MMG

JFS

ELECTRICAL

SITE PLAN

N ELECTRICAL - SITE PLAN

SCALE: 1" = 40'-0"

100 5 20 40 80 100

ELECTRICAL KEY NOTES

ALL DEVICES IN NOTED ROOM ARE REQUIRED TO BE CLASS 1, DIVISION 1,

EXPLOSION PROOF.

LC

LCEM

GENERAL ELECTRICAL NOTES

1. CONTRACTOR SHALL PROVIDE ALL COMPONENTS FOR A COMPLETE

WORKING SYSTEM.

2. ALL ELECTRICAL GEAR PLACED OUTSIDE SHALL BE NEMA 3R RATED.

3. TYPICAL SEQUENCE FOR GAS DETECTION SYSTEM IS AS FOLLOWS:

· HYDROGEN SULPHIDE (H2S)-RANGE 0-25PPM. 1ST LEVEL ALARM

10PPM. (FAN ACTIVATION) 2ND ALARM AT 15 PPM. REMOTE AUDIO

VISUAL AND SHUT DOWN SOURCE ACTIVATION.

· OXYGEN (O2) - RANGE 0-25%/VOL-1ST ALARM 19.5% (FAN

ACTIVATION). 2ND ALARM 17%-SHUT DOWN SOURCE OF O2

DEPLETING GAS , REMOTE AUDIO VISUAL ACTIVATED AND

EVACUATE THE SPACE IN QUESTION.

· METHANE (CH4) - RANGE 0-100% LEL-1ST ALARM 20%/VOL (FAN

ACTIVATION) AND 2ND ALARM AT 40% LEL - REMOTE AUDIO VISUAL,

SHUT DOWN COMBUSTIBLE GAS SOURCE, SEND NOTICE OUT TO

FIRE PANEL OR SECURITY NOTICE AND EVACUATE.

2017 NATIONAL ELECTRIC CODE -

· CHAPTER 5 - SPECIFY ANY CLASSIFIED AREAS AS DEFINED IN

APPLICABLE ARTICLES OF CHAPTER 5 OF THE NEC. THE BUILDING

COMES PRE-WIRED AND IS UL LISTED AS AN ASSEMBLY.

CONTRACTOR SHALL COMPLY WITH THE NEC.

· SECTION 110.2 - APPROVAL. MEDIUM VOLTAGE EQUIPMENT IS

REQUIRED TO BE LISTED BY AN INDEPENDENT NATIONALLY

RECOGNIZED TESTING LABORATORY.

· ARTICLE 250, PART X - PROPER GROUNDING OF HIGH VOLTAGE

SYSTEMS AND CIRCUITS IS REQUIRED. (OVER 1000V)

· SECTION 225.56 - ELECTRICAL SYSTEMS OVER 1000 VOLTS SHALL

BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON-SITE.

LA

LAEM

LA

LBEM LB

LBEM

LAEM

LA

PC

XA

LP-PB-17

LP-PB-17

LP-PB-17

PANEL RP-PB

208/120V-3PH, 80A

PANE LP-PB

480/277V-3PH, 200A

EF-1

120V-1PH, 5.8A

EF-2

120V-1PH, 4.4A

EUH-1

480V-3PH, 12.7A

GENERAL ELECTRICAL NOTES

1. CONTRACTOR SHALL PROVIDE ALL COMPONENTS FOR A COMPLETE

WORKING SYSTEM.

2. ALL ELECTRICAL GEAR PLACED OUTSIDE SHALL BE NEMA 3R RATED.

3. TYPICAL SEQUENCE FOR GAS DETECTION SYSTEM IS AS FOLLOWS:

· HYDROGEN SULPHIDE (H2S)-RANGE 0-25PPM. 1ST LEVEL ALARM

10PPM. (FAN ACTIVATION) 2ND ALARM AT 15 PPM. REMOTE AUDIO

VISUAL AND SHUT DOWN SOURCE ACTIVATION.

· OXYGEN (O2) - RANGE 0-25%/VOL-1ST ALARM 19.5% (FAN

ACTIVATION). 2ND ALARM 17%-SHUT DOWN SOURCE OF O2

DEPLETING GAS , REMOTE AUDIO VISUAL ACTIVATED AND

EVACUATE THE SPACE IN QUESTION.

· METHANE (CH4) - RANGE 0-100% LEL-1ST ALARM 20%/VOL (FAN

ACTIVATION) AND 2ND ALARM AT 40% LEL - REMOTE AUDIO VISUAL,

SHUT DOWN COMBUSTIBLE GAS SOURCE, SEND NOTICE OUT TO

FIRE PANEL OR SECURITY NOTICE AND EVACUATE.

2017 NATIONAL ELECTRIC CODE -

· CHAPTER 5 - SPECIFY ANY CLASSIFIED AREAS AS DEFINED IN

APPLICABLE ARTICLES OF CHAPTER 5 OF THE NEC. THE BUILDING

COMES PRE-WIRED AND IS UL LISTED AS AN ASSEMBLY.

CONTRACTOR SHALL COMPLY WITH THE NEC.

· SECTION 110.2 - APPROVAL. MEDIUM VOLTAGE EQUIPMENT IS

REQUIRED TO BE LISTED BY AN INDEPENDENT NATIONALLY

RECOGNIZED TESTING LABORATORY.

· ARTICLE 250, PART X - PROPER GROUNDING OF HIGH VOLTAGE

SYSTEMS AND CIRCUITS IS REQUIRED. (OVER 1000V)

· SECTION 225.56 - ELECTRICAL SYSTEMS OVER 1000 VOLTS SHALL

BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON-SITE.

ELECTRICAL KEY NOTES

CONTRACTOR SHALL TIE NEW LIFT STATION PUMP(S) ALARM CONTROLS

INTO EXISTING STARNET SYSTEM.

DISCONNECT BY MANUFACTURER.

CONTRACTOR SHALL PROVIDE AND INSTALL AMC-270-D SERIES

ELECTROCHEMICAL OXYGEN (02) SENSOR / TRANSMITTER.

CONTRACTOR SHALL PROVIDE AND INSTALL AMC-282-A SERIES

ELECTROCHEMICAL HYDROGEN SULPHIDE (H2S) SENSOR / TRANSMITTER.

CONTRACTOR SHALL PROVIDE AND INSTALL AMC-CSA-CAT CATALYTIC

COMBUSTIBLE SENSOR / TRANSMITTER.

CONTRACTOR SHALL PROVIDE AND INSTALL AMC-RAM-3 REMOTE ALARM

MODULE.

CONTRACTOR SHALL PROVIDE AND INSTALL WEATHER PROOF AMC-1400

FOUR CHANNEL GAS MONITOR CONTROL PANEL. CONTRACTOR SHALL TIE

THE NEW GAS MONITORING SYSTEM INTO THE EXISTING STARNET SYSTEM.

CONTRACTOR SHALL PROVIDE AND INSTALL MANUALLY OPERATED

INTERVAL TIMER, 0-60 MINUTES WITHOUT HOLD. INTERLOCK WITH SUPPLY

FAN. TIMER SHALL BE ADJUSTABLE FOR OWNERS OPERATION SCHEDULE.

CONTRACTOR SHALL MOUNT 45KVA TRANSFORMER ABOVE PANEL C.

CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM NEW CONTROL

PANEL TO NEW PUMPS.

CLASS 1, DIVISION 1, EXPLOSION PROOF EQUIPMENT. INTER LOCK D-1 WITH

EF-1. D-1 SHALL OPEN WHEN EF-1 OPENS.

CLASS 1, DIVISION 1, EXPLOSION PROOF EQUIPMENT. INTERLOCK D-2 WITH

EF-2. D-2 SHALL OPEN WHEN EF-2 OPERATES.

CONTRACTOR SHALL PROVIDE AND INSTALL CLASS 1, DIVISION 1,

EXPLOSION PROOF EQUIPMENT.

ALL WIRING AND DEVICES IN THE NOTED ROOM SHALL BE CLASS 1 DIVISION

1 RATED.

NEW SECOR FIBER PANEL. CONTRACTOR SHALL PROVIDE ALL

COMPONENTS AND ACCESSORIES TO TIE SYSTEM INTO STARNET 2 SYSTEM.

REFER TO E800 FOR MORE INFORMATION.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW TELECOMMUNICATIONS

GROUND BAR. REFER TO SHEET E800 DETAIL 3 FOR MORE INFORMATION.

OXYGEN SENSOR

HYDROGEN SULPHIDE SENSOR

CATALYTIC COMBUSTIBLE SENSOR

J J J

J

TIMER

WP

J

REMOTE ALARM MODULE

WP

SANITARY SCREEN

480V-3Ø, 2.1A

TPB

AMC-1400

FOUR CHANNEL GAS MONITOR

PANEL RP-PB

208/120V-3PH, 80A

30KVA TRANSFORMER

PANE LP-PB

480/277V-3PH, 200A

LIFT STATION CONTROL PANEL

WASHER

480V-3Ø, 1.6A

GARAGE DOOR

208V-1PH, 5A

WP

GFI

WP

GFI

48"AFF

EUH-2

480V-3PH, 12.7A

L-1

L-2

D-1

D-2

RP-PB-1

RP-PB-3

RP-PB-2

RP-PB-2

13 13

LP-PB-1,3,5

LP-PB-2,4,6

LP-PB-7,9,11

LP-PB-8,10,12

RP-PB-5,7

WP GFI

48"AFFRP-PB-2

FIBER PANEL

NEW FIBER

GROUND BAR

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

E-500

MMG

JFS

ELECTRICAL

FLOOR PLAN

NEW

N ELECTRICAL - FLOOR PLAN - LIGHTING

SCALE: 1/4" = 1'-0"

0 1 5 10

N ELECTRICAL - FLOOR PLAN - POWER

SCALE: 1/4" = 1'-0"

0 1 5 10

TC101

CONNECTIVITY CODE3

TC101

COMMUNICATIONS GROUNDING DETAIL

TC101

MONITORING OF SYSTEMS CONNECTED TO

STARNET SYSTEM

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

E-800

MMG

JFS

ELECTRICAL

DETAILS

file no.

checked by drawn by consultant issue date contract order no.

472MTUMAINTPROJ

consultant job no.

22484.00

M a t r ix

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

R O

B E

R T

C H

A L

L R

A N

C A

R B

D

IR

E

C T

O R

F A

C

IL

IT

IE

S A

N D

B U

S

IN

E S

S S

E R

V

IC

E S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

472/20205.SMD

90% CD 04.25.23

BID DOCUMENTS 04.27.23

funding code sheet description

Y23004

E-900

MMG

JFS

ELECTRICAL

PANEL SCHEDULE(S)

Sheets and Views
A000-2248400-A-000
P100-2248400-30x42
P400-2248400-Layout1
M100-2248400-30x42
M400-2248400-30x42
E100-2248400-30x42
E200-2248400-30x42
E500-2248400-30x42
E800-2248400-30x42
E900-2248400-30x42

File details come from the government source that posted it. Updated .