Drawings_Part_3.pdf

PDF 8 MB Posted

Attached to
NOAA Office Relocation, 13th Floor Federal contract opportunity
Solicitation number
GS-05P-16-FB-C-7003
Issued by
General Services Administration Public Buildings Service

About this file

Drawings Part 3

View the file

Other files for this federal contract opportunity

Other files attached to NOAA Office Relocation, 13th Floor, newest first.
File Type Posted
SF_30_002.pdf PDF
SF_30.pdf PDF
Drawings_A3-01.zip ZIP file
Drawings_A2-02.zip ZIP file
Drawings_A3-02.zip ZIP file
Drawings_Part_1.pdf PDF
Drawings_Part_2.zip ZIP file
RFP_Vol_III.pdf PDF
RFP_Vol_II.pdf PDF
RFP_Vol_I.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DD

EE

FF

GG

HH

F A

C P

FAPB

Future Tenant

1300X

Ops. Forcaster Stations

13-22 Ops. Stations

13-20 Collaboration

Area 13-11

MIC

Office 13-12

SOO

Office

13-14

WCM

Office 13-13

ESA

Office

13-15

Elec./ Tech.

13-16B

Training

13-09

Elec.

13-08

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

13-01

Hall 13-04

Equip.

13-07

Multipurpose Rm.

13-02

Vest 13-00

Bldg. Corr 13-18

Copy/ Stor

RMS

Office

13-17

Elec./ Tech.

13-16A

Hall 13-10

Storage 13-19

PPB

PPC PPA

DP

ATS

TR-PPB

EGB

X

X

R13B

R13C

PP13

X

X

X

X

DP13

T-13

EL13

EP13

X

L13ET-13

CLG.

HEAT

B.D.R.

EMER.

B.D.R.

XNORM.

B.D.R.

EMER.

B.D.R.

X

X

X

X

PPC2

4 5

R13A

TGB

HP13

LCP13

X

X

X

X

X

TDW

R

AW

IP

S

BAT.

AW

IP

S

AW

IP

S

AW

IP

S

AW

IP

S

CRS

CRS

RPG

RPG

LIN

UX

W

IN

D

NET

VIP

LAN

FTI COM

SEC

DIS

P

UPS

MB

PPM

BAT.

HP13B

NEW

Rm. #13-016 Telephone

P A

T H

W A

Y P

A T

H W

A Y

PATHWAYPATHWAY

DISC.

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEV

ATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR ELECTRICAL AND TECHNOLOGY KEY PLAN

CODED NOTES:

1 NEW GENERATOR'S FEEDER AND CONTROL WIRING CONDUITS ROUTED UP FROM 12TH FLOOR

INTO 13TH FLOOR MECHANICAL ROOM #017. ROUTE CONDUITS UP NEAR CEILING, THRU WEST

WALL OF MECHANICAL ROOM AND INTO NEW CONSTRUCTION AREA. CONTINUE ROUTING

CONDUITS OVER TO NEW WALL MOUNTED AUTOMATIC TRANSFER SWITCH IN NEW ELECTRICAL

ROOM #13-08. ROUTE POWER FEEDER THRU "SERVICE ENTRANCE" DISCONNECT SWITCH TO

EMERGENCY LUGS OF ATS. TERMINATE GENERATOR'S POWER FEEDER AND CONTROL WIRING

ON EMERGENCY LUGS AND CONTROL CIRCUITS OF ATS, RESPECTIVELY. REFER TO "PARTIAL

ONE-LINE DIAGRAM" FOR GENERATOR POWER FEEDER, CONTROL WIRING AND CONDUIT SIZES.

E.C. SHALL PROVIDE NEW 600V-400A-3P FUSED BUS PLUG WITH (3) 400A RK1 FUSES. INSTALL

BUS PLUG ON EXISTING "NORMAL POWER" BUS DUCT RISER. PROVIDE NEW FEEDER FROM

LOAD SIDE OF NEW BUS PLUG AND ROUTE THRU WALLS OF ELECTRICAL ROOM, CORRIDOR

AND MECHANICAL ROOM AND INTO NEW STORAGE RM #13-19. CONTINUE ROUTING FEEDER

CONDUIT TO NORMAL LUGS OF NEW WALL MOUNTED AUTOMATIC TRANSFER SWITCH IN

ELECTRICAL ROOM #13-08 AND CONNECT COMPLETE. PROVIDE ACCESS PANEL IN CEILING

OUTSIDE OF EXISTING ELECTRICAL ROOM. REFER TO "PARTIAL ONE-LINE DIAGRAM" FOR

NORMAL POWER CONDUIT AND FEEDER SIZES.

E.C. SHALL PROVIDE CONDUIT AND FEEDER FROM 100A-3P (FULLY RATED) BREAKER IN NEW

EQUIPMENT ROOM PANEL "PPB" AND ROUTE THRU WALLS OVER TO TELEPHONE #016. PROVIDE

CORE DRILLS THRU CEILINGS/FLOORS OF STACKED TELEPHONE ROOMS BETWEEN 13TH

FLOOR AND 21ST FLOOR. CONTINUE ROUTING CONDUIT UP THRU STACKED TELEPHONE

ROOMS AND ABOVE FINISHED CEILING OF 21ST FLOOR. REFER TO "PARTIAL 21ST FLOOR

ELECTRICAL AND TECHNOLOGY KEYPLAN" FOR CONTINUATION OF CONDUIT ROUTE AND

ADDITIONAL WORK REQUIREMENTS.

E.C. SHALL PROVIDE CONDUIT RISER (STRAIN RELIEF) CABLE GRIPS FOR PERMANENT

SUPPORT OF GENERATOR'S VERTICALLY SUSPENDED POWER FEEDER AND CONTROL WIRING

DUE TO CABLES' WEIGHT. PROVIDE CABLE GRIPS AT EQUAL INTERVALS ALONG ENTIRE LENGTH

OF EACH VERTICAL ROUTE PER MANUFACTURER'S REQUIREMENTS.

E.C. SHALL PROVIDE CODE-COMPLYING PULLBOXES IN ACCESSIBLE LOCATIONS NEAR CEILING

OF STACKED TELEPHONE ROOMS ON 14TH FLOOR, 18TH FLOOR AND 21ST FLOOR. CONDUIT

PATH MAY NEED TO OFFSET WITHIN TELEPHONE ROOM BETWEEN FLOORS - ( DO NOT ASSUME

A STRAIGHT VERTICAL PATH THRU TELEPHONE ROOMS - FIELD VERIFY). ADJUST CONDUIT

ROUTE THRU TELEPHONE ROOMS AS REQUIRED TO AVOID INTERFERENCE WITH EXISTING

LIGHTING FIXTURES, ELECTRICAL EQUIPMENT, CONDUITS, DUCTWORK AND PIPING. LABEL

CONDUIT AS "N.O.A.A. ROOFTOP PANEL "PPB2" AT EACH FLOOR. SEAL ALL CONDUIT

PENETRATIONS THRU FLOORS, CEILINGS AND WALLS TO MAINTAIN FIRE RATING.

T.C. SHALL ROUTE TELECOM BACKBONE CABLES UP FROM CONDUIT SLEEVE AT 13TH FLOOR

AND THRU WALL OF EXISTING MECHANICAL ROOM #017 AT HEIGHT OF LADDER RACKS IN

EQUIPMENT ROOM #13-07 VIA FIRE-RATED PATHWAYS. CONTINUE ROUTE OF CABLES INTO

EQUIPMENT ROOM #13-07. SEAL WALL PENETRATIONS TO MAINTAIN FIRE RATINGS.

PROVIDE 50'-0" SERVICE LOOPS OF "T1-LINES" AND "POTS" ANALOG LINES AT "COMM" TELECOM

RACK. CROSS-CONNECT CABLES AT 66 PUNCHDOWN BLOCKS.

PROVIDE 50'-0" SERVICE LOOP OF OPTICAL FIBERS AT "NOAANET" TELECOM RACK. TERMINATE

IN LIUs WITH "LC" CONNECTORS.

T.C. SHALL PROVIDE CORE DRILLS AND (4) 4" CONDUIT SLEEVES THRU CEILING/FLOORS OF

STACKED TELECOM ROOMS BETWEEN 13TH FLOOR AND 21ST FLOOR. T.C. SHALL ROUTE

LOW-VOLTAGE CABLES PROVIDED BY N.O.A.A. FROM EQUIPMENT ROOM #13-07 UP TO

"ANTENNA FARM" ON ROOF AT 22ND FLOOR. SEAL CEILING AND FLOOR PENETRATIONS TO

MAINTAIN FIRE RATINGS. REFER TO "PARTIAL 21ST FLOOR ELECTRICAL AND TECHNOLOGY

KEYPLAN" FOR CONTINUATION OF CABLE ROUTE AND ADDITIONAL WORK REQUIREMENTS.

PROVIDE NEW 600V-400A-3P FUSED BUS PLUG WITH (3) 400A RK1 FUSES. INSTALL BUS PLUG ON

EXISTING HEATING POWER BUS DUCT RISER. PROVIDE NEW FEEDER FROM LOAD SIDE OF NEW

BUS PLUG AND ROUTE THROUGH WALL OF ELECTRICAL ROOM, CORRIDOR AND MECHANICAL

ROOM. CONTINUE ROUTE OF FEEDER TO MAIN LUGS ON NEW PANEL "HP13B" AND CONNECT

COMPLETE. REFER TO ONE LINE DIAGRAM FOR CONDUIT AND FEEDER SIZES.

PROVIDE 3/4"C - 4 #12 AND 2 #12 EG, RESPECTIVELY, FROM AVAILABLE SPARE CIRCUITS IN

EXISTING 208/120V-3Ø-4W "LIFE SAFETY" PANEL "EP13-14,16" TO FEED NEW ACCESS CONTROL

SYSTEM EQUIPMENT LOCATED IN EXISTING TELEPHONE ROOM #13-016. PROVIDE ACCESS

PANELS IN DRYWALL CEILINGS AS REQUIRED TO ACCOMMODATE CONDUIT ROUTING.

PROVIDE FIRE-RATED PATHWAYS (STI #EZ PATH-SERIES 44 OR APPROVED EQUAL) THRU

MULTI-PURPOSE ROOM WALLS TO ACCOMMODATE ROUTING LOW-VOLTAGE CABLES FROM

EQUIPMENT ROOM TO EXISTING TELEPHONE ROOM #13-016.

E1-04

ECW

Partial 13th Floor Electrical and Tech. Key Plan

OUTLINE OF EXISTING

ANTENNA FARM AT

ROOF

PATHWAY

PATHWAY

PATHWAY

5 10

PPB2

OUTLINE OF NEW

DRY COOLER UNIT

AT ROOF

OUTLINE OF DISC.

SWITCH AT ROOF

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

PROJECT

SCOPE

N O

R T

H

Roof Key Plan - Stokes Roof Plan not to scale

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 21ST FLOOR ELECTRICAL AND TECHNOLOGY KEY PLAN

E1-05

ECW

Partial 21st Floor Electrical / Technology Key Plan

CODED NOTES:

1 E.C. SHALL ROUTE CONDUIT AND FEEDER FOR ROOFTOP PANEL "PPB2" UP AND THRU WALL OF TELEPHONE #016

AND ABOVE CEILING OF VOID SPACE #163. CONTINUE ROUTE THRU WALL OF VOID SPACE, CORRIDOR #162 AND

FILE ROOM #157 TO BELOW LOCATION OF ROOFTOP PANEL "PPB2". FIELD VERIFY EXACT CONDUIT ROUTE.

E.C. SHALL PROVIDE CORE DRILL AND STUB POWER PANEL CONDUIT THRU CEILING DECK OF 21ST FLOOR AND

ONTO ROOF (22ND FLOOR) VIA PIPE CURB. COORDINATE EXACT LOCATION OF PANEL "PPB2" PRIOR TO CORE

DRILLING. SEAL CONDUIT PENETRATIONS THRU WALLS AND CEILING DECK/ROOF WATER-TIGHT AND TO

MAINTAIN FIRE RATING.

PROVIDE CODE-COMPLYING PULLBOXES ON 100' FT CENTERS ALONG CONDUIT ROUTE.

E.C. SHALL PROVIDE 4" SQ. FIRE-RATED PATHWAYS THRU WALL OF TELEPHONE ROOM, CORRIDOR AND FILE

ROOM . T.C. SHALL ROUTE ANTENNA'S LOW-VOLTAGE CABLING THRU PATHWAYS AND OVER TO CONDUIT

SLEEVES IN CEILING OF FILE ROOM #157. SEAL ALL WALL PENETRATIONS TO MAINTAIN FIRE-RATING.

PROVIDE CORE DRILLS AND (4) 4" CONDUITS SLEEVES THRU CEILING/ROOF VIA PIPE CURB. ROUTE ANTENNA'S

LOW-VOLTAGE CABLING THRU CONDUIT SLEEVE AND ONTO ROOF.

E.C. SHALL PROVIDE CORE DRILL AND DRY COOLER UNIT'S BRANCH CIRCUIT CONDUIT DOWN THRU ROOF VIA

PIPE CURB TO CEILING HEIGHT OF 21ST FLOOR. CONTINUE ROUTE OF CONDUIT NEAR CEILING OVER TO

LOCATION INDICATED BELOW MECHANICAL ROOM #103.

STUB CONDUIT UP THRU FLOOR AND INTO MECHANICAL ROOM #103 NEAR EXTERIOR WALL. FIELD VERIFY EXACT

CONDUIT ROUTE. SEAL CONDUIT PENETRATIONS THRU CEILING FLOOR TO MAINTAIN FIRE RATING.

GENERAL NOTES:

ALL WORK AT 21ST FLOOR SHALL BE STRICTLY COORDINATED WITH

GSA AND TENANT.

CODED NOTES CONT.:

PROVIDE 3/4"C - 2 #12 AND 1 #12 EG FROM 20A-1P BREAKER IN PANEL "PPB2-6" FOR ROOF MOUNTED LIGHT AND

RECEPTACLE. ROUTE CONDUIT ADJACENT TO DRY COOLER'S POWER CIRCUIT CONDUIT. ROUTE THRU ROOF VIA

PIPE CURB.

STUB CONDUIT UP THRU FLOOR AND INTO MECHANICAL ROOM #103 NEAR EXTERIOR WALL. FIELD VERIFY EXACT

CONDUIT ROUTE. SEAL CONDUIT PENETRATIONS THRU FLOOR TO MAINTAIN FIRE RATING.

REFER TO "PARTIAL 22ND FLOOR ELECTRICAL AND TECHNOLOGY PLAN" FOR ADDITIONAL ELECTRICAL AND

TECHNOLOGY WORK REQUIREMENTS.

J K

EE

FF

GG

HH

J K

DD

EE

FF

GG

HH

J K

DD

EE

FF

GG

HH

J K

DD

EE

FF

GG

HH

SD

SD

F

EL

EL

J

F

R13A-1

R13A- 1,2,4,6,13

R13A-1

R13A-1

R13A-1

JR13A-

2,4,6

R13A-2

R13A-2

R13A-4

F

R13A-4

F UH

UH

UH

R13A-11

X

XX

XRR

J

XRR

F

XRR

F

XRR

F

XRR

J

J J J

FLR.

FAPB

X

11'-0"AFF

J

XRR

XRR

X

XRR

XRR

XRR

XRR XRR

XRR

X

X

XRR

XN

XN

XN

XRR

XX

X X X

X X

X X X X

X

XX

FXRR

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

E

LE

V A

TO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR ELECTRICAL DEMOLITION PLAN

D1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC.

THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE

NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT

DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT

MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL

INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS

COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE

CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION WORK AND SHALL

INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

D2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE

OWNER SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

D3. DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.

D4. REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO

SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE THESE COMPONENTS AS REQUIRED.

D5. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT

BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS

NECESSARY TO ACHIEVE SAME.

D6. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK

WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED

CIRCUITS IN A TIMELY MANNER.

D7. CONTACT THE ENGINEER IF A QUESTION SHOULD ARISE CONCERNING THE STATUS OF ANY OUTLET, DEVICE, LIGHTING FIXTURE, ETC.

ELECTRICAL DEMOLITION NOTES

E2-01

ECW

Partial 13th Floor Electrical Demolition Plan

CODED NOTES:

REMOVE EXISTING SHELL SPACE LIGHTING FIXTURES, SWITCH CONTROL AND REINSTALL AT NEW LOCATIONS

IN SHELL SPACE AS INDICATED ON NEW LIGHTING PLAN. EXTEND EXISTING LIGHTING CIRCUITS TO FIXTURE'S NEW

LOCATIONS AND RECONNECT COMPLETE.

REMOVE EXISTING FIRE ALARM DEVICES AND REINSTALL AT LOCATIONS INDICATED ON NEW FIRE ALARM PLAN.

EXTEND FIRE ALARM CIRCUITS IN SHELL SPACE TO RELOCATED AND NEW FIRE ALARM DEVICES IN RENOVATED

AREA.

REMOVE POWER CIRCUIT FROM EXISTING CEILING MOUNTED UNIT HEATER TO ACCOMMODATE RELOCATION OF

HEATER TO NEW LOCATION IN SHELL SPACE BY M.C. E.C. SHALL EXTEND UNIT HEATER'S POWER CIRCUIT AND

CONTROL WIRING TO NEW LOCATION AND RECONNECT COMPLETE.

REMOVE EXISTING RECEPTACLE AND REINSTALL AT NEW LOCATION IN SHELL SPACE. EXTEND RECEPTACLE

CIRCUITS TO NEW LOCATIONS AND RECONNECT COMPLETE. REMOVE REMAINING RECEPTACLES AND ASSOCIATED

CONDUIT AND WIRING BACK TO POWER SOURCE.

REMOVE EXISTING ELEVATOR RECALL FIRE ALARM SMOKE DETECTOR COMPLETE AND ASSOCIATED CONDUITS

AND WIRING BACK TO NEAREST REMAINING ADDRESSABLE DEVICE.

REPLACE EXISTING 2' x 2' LIGHTING FIXTURES AND LIGHT SWITCH WITH NEW AT SAME LOCATION. PROVIDE

ADDITIONAL WIRING AS REQUIRED.

FF

GG

HH

F A

C P

FAPB

L

L

L

L

L

P

P

D

B

B

A A

A

PPB

PPC2

PPA

DP

ATS

PPC

L

L

L

L

L

L

L

H

H

H

H

H

H

L

L

L

L

L

L

L

L

L

L

L

L

L

L

B

L

L L

L

E

E

L L

H

H

H

H

H

C

C

F

J

C

K

-K

Db Da

D c d

3d

Dg D g

D f

D e

D d

D c

D b h a

D m

Dh

D n

Df

Dm u

U

N

N

N

Future Tenant

1300X

Ops. Forcaster Stations

13-22

Ops. Stations

13-20 Collaboration Area 13-11

MIC

13-12

SOO

13-13

WCM Office

13-14

ESA Office

13-15

Elec./ Tech.

13-16A

Training

13-09

Equip.

13-07

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

130-01

Hall 13-04

Elec.

13-08

Multipurpose Rm.

13-02Vest 13-00

RMS Office 13-17

Copy/Stor

Storage

13-19

Elec./ Tech.

13-16B

Bldg. Corr.

13-16B

NL

NL

NL

NL

D p

M M

M M

M

M

M

M

M

M

R

R

R

R

R

M

M

M

M

M

M

R

R

OS

P

P

P

R

R

R

P

XN

D

D r

X w w w w w w

XL

XL

XL

XL

D t

B4,u

B4,m

B4,m

B2,h

B2,h

B2,hB2,h

B2,h

B2,g

B2,g

B2,f

B2,e

B2,d

B2,c

B2,b

B2,b

B2,b

B2,b

B2,b

B3,u

B3,u

B3,c

B1,d

B1,d

B1,d

B1,g

B1,g

B1,g

B1,h B1,h

B1,h

B1,m

B1,m

B1,m

B1,a

B1,a

B1,a

B3, f

B3, g

B3, f

B3,e

3q

3q

B3,q

B3,q

B3,q

B3,w

NL B3,v

B3,v

PPM

R13A

XX

X

B3,e

B3,e

B3,e

B3,w

B3,w

B3,w

B3,a

B3,a

B3,a

B3,a

B3,a

B3,a B3,a

B3,a

B3,a

B3,a

B3,b

B3,b

B3,b B3,b

B3,b

B3,b

B3,b

B3,b B3,b

K5

K5

K5

K5

K5

K5

K5

K5

K1

K1

K1

B4,n

B4,r

B4,t

B4,p

B4,pB4,p

B4,n

B4,r

B4,t B4,t

K5

K5

TYP

3Dy

3D y

B3,y B3,y

B3,y

B3,y B3,y

B3,y

B3,y

XL

Dv w

TYP

B3,b

B3,b

B3,b

B3,b

B3,b

TYP

TYP

B3,c

TYP

TYP

TYP

TYP

TYP

G

G

G

G

B3, f

B3, f

LCP13

HP13

X

X

HP13B

NEW

R

R

B1,d

B1,d

B1,d

R

R

R

B1,d

B1,d

R

R

RB1,d

B1,d

R

R

R

R

R

B1,d

B1,d

B1,d

K1

GTD

K5

GTD

K5

GTD

K5

K1

GTD

K5

XN

N

XN

N

XN

N

N

K1

X X

X X

X

XX

B3,b PS remote

Dg

De

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEV

ATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR LIGHTING PLAN

E3-01

ECW

Partial 13th Floor Lighting Plan

CODED NOTES:

REINSTALL LIGHTING FIXTURE AT NEW LOCATIONS INDICATED. CONNECT COMPLETE TO EXISTING SHELL

SPACE LIGHTING CIRCUIT AND NEW SWITCH CONDUITS VIA 3/4" - 2 #12 AND 1 #12 EG.

LIGHTING FIXTURE AND ELECTRICAL DEVICE CIRCUIT ASSIGNMENTS ARE INDICATED WITH PANEL'S

ABBREVIATED LETTER DESIGNATION AND PANEL CIRCUIT NUMBER (i.e. "B2" = "PPA-2"). ENGRAVE ALL SWITCH

AND RECEPTACLE COVER PLATES WITH ACTUAL PANEL NAME AND CIRCUIT NUMBER.

CONNECT NEW LIGHTING FIXTURES TO 277V LIGHTING CIRCUITS AND SWITCH CONTROLS INDICATED VIA

3/4"C - 2 #12 AND #12 EG

CONNECT NEW EXIT SIGNS AND EGRESS (SHADED) LIGHTING FIXTURES TO EXISTING "LIFE SAFETY" CIRCUITS

IN THIS AREA VIA 3/4"C - 2#12 AND 1#12 EG AHEAD OF LOCAL SWITCHING.

INSTALL TYPE "R" LIGHTING FIXTURES, IN EQUIPMENT ROOM #13-07, SUSPENDED FROM CEILING AT 10'-0"AFF

OR AT SAME HEIGHT AS BOTTOM OF DUCTWORK SO THAT THE LIGHT OUTPUT IS NOT BLOCKED BY THE

DUCTWORK. COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHT WITH M.C. SUBMIT COORDINATION

DRAWINGS WITH LOCATION OF LIGHTING FIXTURES, DUCTWORK AND PIPING SHOWN IN EQUIPMENT ROOM

#13-07 FOR REVIEW PRIOR TO INSTALLATION OF LIGHTING FIXTURES.

PROVIDE BODINE #GTD GENERATOR TRANSFER DEVICE (GTD) TO CONTROL OPERATION OF LIGHTING

FIXTURES INDICATED. INSTALL GTD WALL MOUNTED IN ACCESSIBLE LOCATION ABOVE FINISHED CEILING.

CONNECT EMERGENCY "CRITCAL" AND EMERGENCY "LIFE SAFETY" CIRCUITS TO RESPECTIVE INPUTS ON

"GTD". CONNECT OUTPUT OF "GTD" TO INPUT ON LIGHTING FIXTURE'S DRIVER. PROVIDE ADDITIONAL

EMERGENCY "CRITICAL" UNSWITCHED HOT CONDUCTOR TO "GTD" VOLTAGE SENSING INPUTS SO THAT LOSS

OF EMEGENCY "CRITICAL" POWER TO "GTD" WILL SWITCH TO THE EMERGENCY "LIFE SAFETY" SOURCE TO

SUPPLY POWER TO INDICATED LIGHTING FIXTURE AHEAD OF SWITCH CONTROL FOR EGRESS LIGHTING. SEE

ATTACHED DETAIL ON THIS DRAWINGS.

REFER TO ARCHITECTURAL ELEVATIONS DRAWING "A3-01" FOR LAYOUT AND DIMENSIONS OF THIS EXIT SIGN.

PROVIDE BROWN LIGHT SWITCH WITH STAINLESS STEEL WALL PLATE FOR WALL MOUNTED LIGHT SWITCHES

LOCATED AT THE READY ROOM #13-06.

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND ELEVATIONS FOR FINAL LOCATION OF ALL

CEILING AND WALL MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE THE LOCATION OF LIGHTING

FIXTURES AND SMOKE DETECTORS WITH HVAC DUCT, DIFFUSERS, PLUMBING, SPRINKLERS, ETC. ADJUST

LOCATION OF SELECTED ELECTRICAL DEVICES IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

2. CLOSELY COORDINATE EXACT LOCATION OF ALL SMOKE DETECTORS WITH HVAC DUCT, DIFFUSERS, PLUMBING, SPRINKERS, LIGHTING FIXTURES, ETC. ADJUST LOCATIONS OF SELECTED ELECTRICAL DEVICES

IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

3. FOR EXISTING CIRCUITS TO BE RECONNECTED TO NEW DEVICES OR EXISTING DEVICES BEING

RECONNECTED TO NEW CIRCUITS, PROVIDE ALL NECESSARY CONDUIT AND CONDUCTOR EXTENSIONS TO

ACCOMMODATE NEW DEVICE LOCATIONS. CONTRACTOR SHALL VERIFY THAT ALL EXISTING CIRCUITS

BEING RE-USED ARE NOT LOADED TO GREATER THAN 16A PER 20A CIRCUIT AFTER CONNECTION OF NEW

LOADS.

LIGHTING GENERAL NOTES:

ELECTRICAL PANELBOARDELECTRICAL PANEL

NAME-AMPERAGE-VOLTAGE

A

LETTER DESIGNATION

B

C

D

E

F

G

H

"PPB2" - 100A-208/120V-3Ø-4W PANEL

"PPC" - 225A-208/120V-3Ø-4W PANEL

"DP" - 400A-480/277V-3Ø-4W PANEL

SYSTEM

SOURCE

"PPB" - 175A-208/120V-3Ø-4W PANEL

EMERG.

"PPA" - 100A-480/277V-3Ø-4W PANEL

"PPM" - 150A-480/277V-3Ø-4W PANEL

K

"R13A" - 225A-208/120V-3Ø-4W PANEL NORMAL

"PPC2" - 100A-208/120V-3Ø-4W PANEL

"EL13" - 60A-480/277V-3Ø-4W PANEL LIFE SAFETY

EXIST OR NEW

NEW

EMERG.

EMERG.

EMERG.

EMERG.

UPS

UPS

NEW

NEW

NEW

NEW

NEW

NEW

EXISTING

EXISTING

L "HP13" - 400A-480/277V-3Ø-4W PANEL NORMAL EXISTING

M "HP13B" - 400A-480/277V-3Ø-4W PANEL NORMAL NEW

VOLTAGE

SENSING

AC

BALLAST

OR

DRIVER

EMERGENCY "LIFE SAFETY" NEUTRAL

EMERGENCY "CRITICAL" NEUTRAL

UNSWITCHED HOT

EMERGENCY "CRITICAL"

WALL SWITCH

SWITCHED HOT

EMERGENCY "LIFE SAFETY"

NOT TO SCALE

BODINE GENERATOR TRANSFER DEVICE (GTD) WIRING DIAGRAM

GTD

FF

GG

HH

F A

C P

FAPB

Future Tenant

1300X

Ops. Forcaster Stations 13-22

Ops. Stations

13-20

Collaboration Area 13-11

MIC

13-12

SOO

13-13

WCM Office

13-14

ESA Office 13-15

Elec./ Tech.

13-16A

Training 13-09

Equip.

13-07

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

130-01

Hall 13-04

Elec.

13-08

Multipurpose Rm.

13-02

Vest 13-00

RMS Office 13-17

Copy/Stor

REF

AC

COPY/FAX

AC

AC

MICRO.

COFF.

AC

AC

PROJ.

BC

BC

AC

TV

TV

48"

F1

PPB

PPC PPA

DP

ATS

TR-PPB

UPS

GEN-ATS

EGB

IG IG

IG

IG

IG

IG

IG

IG

IG

IG

TV

IG

TV

IG

TV

IG

TV

IG

IG

IG

TV

TV

TV

TV

IG

IG

IG

COPY/FAX

Storage 13-19

Elec./ Tech.

13-16B

Bldg. Corr.

13-16B

F1

F1

PPC2

TDW

R

AW

IP

S

MB

AW

IP

S

AW

IP

S

AW

IP

S

AW

IP

S

CRS

CRS

RPG

RPG

LIN

UX

W

IN

D

NET

VIP

LAN

FTI COM

SEC DISP

TGB

UPS

FB

IG FB

IG FB

IG

FB

FB

FB

IG

FB

IG

FB

IG

FB

IG

FB

IG

FB

IG

FB

IG

FB

IG

BAT.

TV

TV

R13A

XX

X

PPM

FB

IG

FB

IG

IG

IG

IG

IG

TV IG

TV

FB

IG

FB

IG

IG

BAT.

IG

IG

IG

IG

IG IG

IG

IG

TV

IG

TVIG

TVIG

IG

TV

IG

TV

IG

TV J

BC

DISPOSAL

X

XL

X

XL

XL

H32

H32

H30

H32

H32

D8

H32

G29

H32 G29

G31

H30 D8

G32

H30

D6

D6

G15

G15

G15

D6

D6 H30

H28 G27

H28

H30

H23

D8

H28

H26

D5

D9

H28

H24

F30

H27

F30

F32

F30

F30

H25

F32 F30

F32

F28

H27

H25 F26

F32

F28 F26

H27

F22

F24

F26 H25 F24

F22

D2

F22

H22

F24

F20

F22

D4

F20

D4

F18

H20

F18

D4

D4

F18

H20

H20

H20

F20

H22

H22

H29

H31

G19

H31D10

G19

H29

G19

H29 D10

G19

H27

G17

LCP13

HP13

X

X

HP13B

NEW

G21 G21

G21

G23

G23

G23

G25

G25

G25

G26

G26

G28

IG

G28

G28

G30

IG

G30

G30

TYP.

TYP.

TYP.

G27

F25

J

EP13-14,16

Rm. #016 Telephone

J

EP13-20

AD

AC

JH35

DRYER

HAND

FB

FB

FB

FB

FB

H34

H34

H34 H36

H36

IG

IG

IG

IG

IG

FB

H37

FB

H37

DISC.

XX

X

X X X X

TV

IG

TV

IG

TV

IG

G32

G32

G32

FB

IG

FB

IG

F25

F25

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

F25

F27

F27

F27

F27

F25

F25

F25

G33

G33

G33

G33

TYP.

TYP.

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEVATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR POWER PLAN 1

GENERAL_NOTES

1. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING

MOUNTED DEVICES WITH ARCHITECTURAL ELEVATIONS.

2. COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FIVE

WORKING DAYS IN ADVANCE.

3. ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED ON WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS.

INCLUDE ALL PREMIUM TIME CHARGES IN BID.

4. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.

5. ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. [EXISTING WALLS IN CATH LAB ARE LEAD LINED AND THE INTEGRITY OF THE LEAD LINING SHALL BE MAINTAINED]. THE COST TO CUT AND PATCH WALLS

SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.

6. ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE, SURFACE MOUNTED, STEMS, ETC.) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT

ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING TYPES.

8. INCLUDE AN ELECTRICAL CONTINGENCY ALLOWANCE OF $ IN THE BID SUBMITTAL TO BE CHARGED AGAINST SPECIAL ADDITIONAL DEMOLITION WORK AND NEW WORK AS AUTHORIZED BY THE OWNER. DO

NOT CHARGE ANY COST AGAINST THIS ALLOWANCE, UNLESS AUTHORIZED BY THE OWNER.

E4-01

ECW

Partial 13th Floor Power Plan

CODED NOTES:

REINSTALL EXISTING RECEPTACLE AT NEW LOCATIONS INDICATED. SPLICE AND EXTEND CONDUIT AND WIRING AS REQUIRED

AND RECONNECT COMPLETE.

CONNECT ALL NEW RECEPTACLES AND ELECTRICAL DEVICES SHOWN TO CIRCUITS INDICATED VIA 3/4"C - 2 #12 AND 1 #12 EG.

ELECTRICAL DEVICES LOCATED MORE THAN 100'FT FROM POWER SOURCE SHALL BE CONNECTED VIA #10AWG

CONDUCTORS.

ELECTRICAL DEVICE CIRCUIT ASSIGNMENTS ARE INDICATED WITH PANEL'S ABBREVIATED LETTER DESIGNATION AND PANEL CIRCUIT NUMBER (i.e. "F23" = "PPC-23"). ENGRAVE ALL SWITCH AND RECEPTACLE COVER PLATES WITH ACTUAL PANEL NAME

AND CIRCUIT NUMBER.

REFER TO "PARTIAL 13TH FLOOR EQUIPMENT ROOM POWER PLAN" FOR RECEPTACLE LOCATIONS AND CIRCUIT ASSIGNMENTS IN EQUIPMENT ROOM #13-07 AND ELECTRICAL ROOM #13-08 AS INDICATED BY DASHED OUTLINE..

GARBAGE DISPOSAL - 120V-1Ø-20AMOCP, FURNISHED AND INSTALLED BY M.C. E.C. SHALL PROVIDE JUNCTION BOX BELOW COUNTER AND TOGGLE SWITCH ABOVE COUNTER. ROUTE CIRCUIT THRU TOGGLE SWITCH AND CONNECT COMPLETE TO

GARBAGE DISPOSAL.

PROVIDE 6" CORE DRILLS THRU LEVEL THIRTEEN'S FLOOR FOR NEW FIRE-RATED POKE-THRUS IN CONFERENCE ROOM.

ROUTE POWER CIRCUIT CONDUITS ABOVE LEVEL TWELVE'S FINISHED CEILING OVER TO NEAREST LEVEL THIRTEEN'S STUD WALL PARTITION. CONTINUE ROUTING UP IN WALL TO ABOVE LEVEL THIRTEEN'S FINISHED CEILING TO CIRCUIT INDICATED.

REMOVE AND REINSTALL LEVEL TWELVE'S CEILING MOUNTED ELECTRICAL DEVICES TO ACCOMMODATE THIS WORK. SEAL FLOOR PENETRATIONS TO MAINTAIN FIRE RATING. COORDINATE EXACT LOCATION OF POKE-THRU WITH OWNER PRIOR TO

CORE DRILL.

PROVIDE NEW FREE-AXEZ FLOOR SYSTEM POWER-VOICE-DATA FLOOR BOXES AT LOCATIONS INDICATED. ROUTE RECEPTACLE CIRCUITS ABOVE FINISHED CEILING FROM POWER PANEL OVER TO AND CONCEALED DOWN THRU SOUTH WALL OF OPS. STATION ROOM #13-20. TRANSITION EMT CONDUITS AND CONDUCTORS AT BASE OF WALL AND FLOOR SYSTEM'S ACCESS PANELS TO FLEXIBLE METAL CONDUITS WITH #12AWG CONDUCTORS. ROUTE FLEXIBLE METAL CONDUITS THRU FLOOR SYSTEM WIRING CHANNELS TO FLOOR BOX RECEPTACLES AND CONNECT COMPLETE. COORDINATE EXACT LOCATION

OF FLOOR BOXES PRIOR TO ROUTING CIRCUITS.

POWER PLAN GENERAL NOTES:

1. CLOSELY COORDINATE EXACT LOCATION OF ALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AN/OR MOUNTING HEIGHTS WHERE NECESSARY TO AVOID INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGED PRIOR TO ROUGH-IN.

2. EXISTING CIRCUIT ASSIGNMENTS INDICATED ARE ACCORDING TO RECORD DRAWINGS. VERIFY CIRCUIT

ASSIGNMENTS ARE ACCURATE PRIOR TO CONNECTION OF NEW LOADS.

3. CONTRACTOR IS RESPONSIBLE FOR ADDITIONAL CONDUITS, CONDUCTORS, PULLBOXES, ETC. THAT ARE REQUIRED BUT NOT PROVIDED BY THE EQUIPMENT VENDOR AND ARE NOT INDICATED ON THIS PLAN.

4. FOR EXISTING CIRCUITS TO BE RECONNECTED TO NEW DEVICES OR EXISTING DEVICES BEING RECONNECTED TO NEW CIRCUITS, PROVIDE ALL NECESSARY CONDUIT AND CONDUCTOR EXTENSIONS TO ACCOMMODATE NEW DEVICE LOCATIONS. CONTRACTOR SHALL VERIFY THAT ALL EXISTING CIRCUITS BEING RE-USED ARE NOT LOADED TO GREATER THAN 16A PER 20A CIRCUIT AFTER CONNECTION OF NEW

LOADS.

DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH

CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.

ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.

CODED NOTES:

PROVIDE NEW 250A-480/277V-3Ø-3P AUTOMATIC TRANSFER SWITCH "ATS-N.O.A.A" - CUMMINS #CHPC SERIES - WALL MOUNTED IN ELECTRICAL ROOM. CONNECT POWER FEEDERS FROM "NORMAL POWER" RISER AND "EMERGENCY STANDBY" GENERATOR TO THEIR RESPECTIVE LUGS ON "ATS-N.O.A.A". CONNECT POWER FEEDER FROM LOAD SIDE LUGS OF "ATS-N.O.A.A." TO LINE SIDE OF MAIN BREAKER IN DISTRIBUTION PANEL "DP". REFER TO ONE-LINE DIAGRAM FOR CONDUIT

AND FEEDER SIZES.

PROVIDE NEW POWER-COMMAND ANNUNCIATOR FOR REMOTE REPORTING OF GENERATOR AND AUTOMATIC TRANSFER SWITCH STATUS AND ALARM POINTS - CUMMINS #0300-5929-002. INSTALL REMOTE ANNUNCIATOR FLUSH MOUNTED IN WALL OF OPERATIONS FORECASTER STATIONS #13-22. REFER TO "REMOTE ANNUNCIATOR TYPICAL WIRING DIAGRAM" FOR

CONNECTION REQUIREMENTS.

PROVIDE NEW REMOTE ALARM STATUS PANEL - APC #UNC5-10470043-ME SERIES - COMPATIBLE WITH SYMMETRA PX100KW, MODULAR, SCALABLE UNINTERRUPTIBLE POWER SUPPLY SYSTEM. INSTALL REMOTE STATUS PANEL FLUSH MOUNTED IN WALL OF OPERATIONS FORECASTER STATIONS #13-22. CONNECT POWER INPUT OF REMOTE STATUS PANEL TO 120V CIRCUIT "F25" VIA 3/4"C - 2 #12 AND 1 #12 EG. REFER TO "UPS REMOTE STATUS PANEL TYPICAL WIRING DIAGRAM FOR CONNECTION

REQUIREMENTS."

PROVIDE WALL MOUNTED JUNCTION BOX WITH (2) 120V CIRCUITS FROM EXISTING PANEL "EP13-14,16" VIA 3/4"C - 4 #12 AND 2 #12 EG. CONNECT CIRCUITS COMPLETE TO NEW "HIRSCH ELECTRONICS" ACCESS CONTROL SYSTEM CONTROLLER PER

MANUFACTURER'S WIRING DIAGRAMS.

AUTOMATIC DOOR OPERATOR - 120V-1Ø-20AMOCP, FURNISHED AND INSTALLED BY G.C. E.C. SHALL PROVIDE JUNCTION BOX ABOVE CEILING WITH 120V "LIFE SAFETY CIRCUIT INDICATED. CONNECT AUTODOOR OPERATOR COMPLETE VIA 3/4"C - 2 #10 AND 1 #10 EG . INSTALL AUTODOOR PUSHPLATEs ABOVE WORK COUNTER AT RECEPTION DESK AND WALL MOUNTED ADJACENT TO DOUBLE DOORS AS INDICATED . CONNECT PUSHPLATE COMPLETE TO AUTODOOR OPERATOR VIA 3/4"C - 2 #12

AND1 #12 EG.

PROVIDE DUPLEX RECEPTACLE MOUNTED TO UNISTRUT SUPPORTS FOR CEILING MOUNTED TELEVISIONS. CONNECT RECEPTACLES COMPLETE TO CIRCUITS INDICATED VIA 3/4"C - 2 #12 AND 1 #12 EG. FIELD VERIFY EXACT LOCATIONS PRIOR TO

ROUGH-IN.

PROVIDE BROWN RECEPTACLES WITH STAINLESS STEEL WALL PLATES FOR WALL AND MILLWORK MOUNTED RECEPTACLES

LOCATED AT THE RECEPTION #13-01, COPY/STORAGE #13-03 AND READY ROOM #13-06.

ELECTRICAL PANELBOARDELECTRICAL PANEL

NAME-AMPERAGE-VOLTAGE

A

LETTER DESIGNATION

B

C

D

E

F

G

H

"PPB2" - 100A-208/120V-3Ø-4W PANEL

"PPC" - 225A-208/120V-3Ø-4W PANEL

"DP" - 400A-480/277V-3Ø-4W PANEL

SYSTEM

SOURCE

"PPB" - 175A-208/120V-3Ø-4W PANEL

EMERG.

"PPA" - 100A-480/277V-3Ø-4W PANEL

"PPM" - 150A-480/277V-3Ø-4W PANEL

K

"R13A" - 225A-208/120V-3Ø-4W PANEL NORMAL

"PPC2" - 100A-208/120V-3Ø-4W PANEL

"EL13" - 60A-480/277V-3Ø-4W PANEL LIFE SAFETY

EXIST OR NEW

NEW

EMERG.

EMERG.

EMERG.

EMERG.

UPS

UPS

NEW

NEW

NEW

NEW

NEW

NEW

EXISTING

EXISTING

L "HP13" - 400A-480/277V-3Ø-4W PANEL NORMAL EXISTING

M "HP13B" - 400A-480/277V-3Ø-4W PANEL NORMAL NEW

F A C

P

FAPB

SOO Office 13-14

ESA Office 13-15

Elec./ Tech.

13-16A

Training 13-09

Equip.

13-07

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

130-01

Hall 13-04

Elec.

13-08

RMS Office 13-17

Copy/Stor

PPB

PPC PPA

DP

ATS

TR-PPB

EGB

IG

PPC2

TDW

R

AW

IP

S

MB

AW

IP

S

AW

IP

S

AW

IP

S

AW

IP

S

CRS

CRS

RPG

RPG

LIN

UX

W

IN

D

NET

VIP

LAN

FTI

COM

SEC

DISP

TGB

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

UPS

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

EPOBAT.

IG

IG

IG

IG

IG

IG

IG

IG

IG

IG

R13A

XX

X

PPM

BAT.

IG

IG

G24

F23

G18,20,22

F17,19,21

F15

G16

G14

F12

H23

F16

F16

F1

F3

F5

F7

F9

F11

G12

G10

G8

G1

G6

F2

G4

G2

F4

G3

G5

G7

F6

F8

F10

F12

F14 F11

G13

G11

G9

H23

H23

D1

1 2

(30A-3P)

(30A-1P)

HP13

HP13B

LCP13

X

NEW

X

(30A-3P)

EPO

DISC.

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEVATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/4" = 1'0"

2' 4' 8' 16'

PARTIAL 13TH FLOOR EQUIPMENT ROOM POWER PLAN

GENERAL_NOTES

1. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING

MOUNTED DEVICES WITH ARCHITECTURAL ELEVATIONS.

2. COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FIVE

WORKING DAYS IN ADVANCE.

3. ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED ON WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS.

INCLUDE ALL PREMIUM TIME CHARGES IN BID.

4. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.

5. ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. [EXISTING WALLS IN CATH LAB ARE LEAD LINED AND THE INTEGRITY OF THE LEAD LINING SHALL BE MAINTAINED]. THE COST TO CUT AND PATCH WALLS

SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.

6. ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE, SURFACE MOUNTED, STEMS, ETC.) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT

ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING TYPES.

8. INCLUDE AN ELECTRICAL CONTINGENCY ALLOWANCE OF $ IN THE BID SUBMITTAL TO BE CHARGED AGAINST SPECIAL ADDITIONAL DEMOLITION WORK AND NEW WORK AS AUTHORIZED BY THE OWNER. DO

NOT CHARGE ANY COST AGAINST THIS ALLOWANCE, UNLESS AUTHORIZED BY THE OWNER.

NOT TO SCALE

TELECOM EQUIPMENT RACK

OUTLET MOUNTING DETAIL

1. ALL TELECOM EQUIPMENT RACK RECEPTACLES SHALL BE INSTALL ON

BACKSIDE (WALL SIDE) OF RACKS. RECEPTACLES WHERE SHOWN ON

BOTH SIDES OF RACKS ARE FOR CLARITY ONLY.

2. ATTACH CONDUITS TO UNISTRUTS SUPPORTING THE LADDER RACK

PATHWAY.

3. SECURE RECEPTACLE OUTLET BOX TO STRUT MOUNTED PARALLEL TO

THE LADDER RACK PATHWAY AND POSITION AS SHOWN, TYPICAL.

Sheet-# Sheet-Total

CODED NOTES:

CONNECT ALL NEW RECEPTACLES AND ELECTRICAL DEVICES SHOWN TO CIRCUITS INDICATED VIA 3/4"C - 2 #12 AND 1 #12 EG. ELECTRICAL DEVICES LOCATED MORE THAN 100'FT FROM POWER

SOURCE SHALL BE CONNECTED VIA #10AWG CONDUCTORS.

ELECTRICAL DEVICE CIRCUIT ASSIGNMENTS ARE INDICATED WITH PANEL'S ABBREVIATED LETTER DESIGNATION AND PANEL CIRCUIT NUMBER (i.e. "F23" = "PPC-23"). ENGRAVE ALL SWITCH AND

RECEPTACLE COVER PLATES WITH ACTUAL PANEL NAME AND CIRCUIT NUMBER.

PROVIDE NEW THREE-PHASE, 50KVA UNINTERRUPTIBLE POWER SUPPLY SYSTEM - APC #SYMMETRA PX SERIES WITH 480V-3Ø-3W INPUT, 208/120V-3Ø-4W OUTPUT, SCALEABLE FROM 10KVA TO 100KVA IN 10KVA INCREMENTS, EXTERNAL "MAKE BEFORE BREAK" BYPASS SWITCH, IGBT RECTIFIER/PWM INVERTER , HIGH INPUT/OUTPUT POWER FACTORS, "K-13" STEP-DOWN TRANSFORMER, PRECISION

VOLTAGE REGULATION, MODULAR POWER ASSEMBLIES, GRAPHICAL INTERFACE, WEB BASED

MONITORING OPTIONS, INTERCONNECTION BRACKETS, SEISMIC ANCHORS, CASTERS/LEVELERS

AND ADVANCED BATTERY MANAGEMENT SYSTEM, REMOTE STATUS PANEL, UL LISTED FOR 30

MINUTES OF FULL LOAD BATTERY OPERATION. INSTALL UPS SYSTEM ON 4" HIGH CONCRETE PAD.

REFER TO ONE-LINE DIAGRAM FOR CONNECTION REQUIREMENTS

PROVIDE EMERGENCY OFF PUSHBUTTONS (EPO) - APC #EPW9 EPO SYSTEM - WALL MOUNTED IN

EQUIPMENT ROOM AT LOCATIONS INDICATED. CONNECT COMPLETE TO "NORMALLY OPEN"

CONTACTS IN UNINTERRUPTIBLE POWER SUPPLY'S (UPS) AUXILIARY CABINET CONTACTS OF

SHUNT TRIP OUTPUT BREAKER VIA 3/4"C - 2 #12 AND 1 #12 EG. COORDINATE EXACT LOCATION

PRIOR TO ROUGH-IN.

CONNECT 30A-3P TWIST-LOCK TYPE RECEPTACLE VIA 3/4"C - 3 #10 AND 1 #10 EG (EACH).VERIFY

NEMA CONFIGURATION REQUIRED FOR RECEPTACLE PRIOR TO ORDERING.

CONNECT 30A-1P TWIST-LOCK TYPE RECEPTACLE VIA 3/4"C - 2 #10 AND 1 #10 EG. VERIFY NEMA

CONFIGURATION REQUIRED FOR RECEPTACLE PRIOR TO ORDERING.

ELECTRICAL PANELBOARDELECTRICAL PANEL

NAME-AMPERAGE-VOLTAGE

A

LETTER DESIGNATION

B

C

D

E

F

G

H

"PPB2" - 100A-208/120V-3Ø-4W PANEL

"PPC" - 225A-208/120V-3Ø-4W PANEL

"DP" - 400A-480/277V-3Ø-4W PANEL

SYSTEM

SOURCE

"PPB" - 175A-208/120V-3Ø-4W PANEL

EMERG.

"PPA" - 100A-480/277V-3Ø-4W PANEL

"PPM" - 150A-480/277V-3Ø-4W PANEL

K

"R13A" - 225A-208/120V-3Ø-4W PANEL NORMAL

"PPC2" - 100A-208/120V-3Ø-4W PANEL

"EL13" - 60A-480/277V-3Ø-4W PANEL LIFE SAFETY

EXIST OR NEW

NEW

EMERG.

EMERG.

EMERG.

EMERG.

UPS

UPS

NEW

NEW

NEW

NEW

NEW

NEW

EXISTING

EXISTING

L "HP13" - 400A-480/277V-3Ø-4W PANEL NORMAL EXISTING

M "HP13B" - 400A-480/277V-3Ø-4W PANEL NORMAL NEW

E4-02

ECW

Partial 13th Floor Power Plan

FF

GG

HH

F A

C P

FAPB

F1

PROJ

W

COPY/FAX

D

D

D

D

W

AC

AC

BC

BC

BC

TV

TV

D

WAP

WAP

WAP

WAP

W

TV

TV

TV TV

D

X

TV

TV

TV

TV

TV

TV

TV

WAP

TV

TV

TV

TV

TVTV

TV

TV

TV

TV

COPY/FAX

Future Tenant

1300X

Ops. Forcaster Stations 13-22

Ops. Stations

13-20

Collaboration Area 13-11

MIC

13-12

SOO

13-13

WCM Office

13-14

ESA Office

13-15

Elec./ Tech.

13-16A

Equip.

13-07

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

130-01

Hall 13-04

Multipurpose Rm.

13-02

Vest 13-00

RMS Office 13-17

Copy/Stor

WAP

WAP

WAP

Elec./Tech 13-16B

Storage 13-19

Hall 13-10

F1

F1

W W

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

D

TGB

TGB

TDW

R

AW

IP

S

MB

AW

IP

S

AW

IP

S

AW

IP

S

AW

IP

S

CRS

CRS

RPG

RPG

LIN

UX

W

IN

D

NET

VIP

LAN

FTI COM

SEC DIS

P

UPS

BAT.

PPB

PPC

PPA

DP

ATS

TR-PPB

EGBPPC2

R13A X

TV

TV

TV

PPM

TV TV

FB

FB

FB

FB

TV TV

TV

TV

TV

TV

TV TV TV TVTV TV

BAT.

LCP13

HP13

X

X

HP13B

NEW

XX

VD2

VD1

TYP.

TYP.

TYP.

TYP.

TYP.

CLG.

TYP. Training

13-09

TYP.

TYP.

TYP.

PATHWAYPATHWAY

PATHWAY

PATHWAY

PATHWAY

TYP.

TYP.

TYP.

TYP.

TYP.

X

TYP.

TYP.

TYP.

Rm. #016 Telephone

D

D

D

FB

FB

FB

FB

FB

S

S

S

S

S

S 13

TYP.

TYP.

TYP.

J

FB

S

S

P A

T H

W A

Y P

A T

H W

A Y

DISC.

Elec.

13-08

TV

TV

TV

TV

TV

TV

TV

TV

J

J

J

J

J

J

J J

J J

J

TV

TV

TV

J

TV

TV

TV

TYP.

TYP.

TYP.

FB FB

FB

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

TV

TV TV

TV TV

TV TV

TV TV

TV

TV

TYP.

TYP.

D

D

D

FOR ELECTRIC

METERING

FOR ELECTRIC

METERING

TCP

TCP

TCP

(12TH FLR.)

TCP

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEV

ATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR COMMUNICATION PLAN

E5-01

ECW

Partial 13th Floor Communication Plan

ELECTRICAL PANELBOARDELECTRICAL PANEL

NAME-AMPERAGE-VOLTAGE

A

LETTER DESIGNATION

B

C

D

E

F

G

H

"PPB2" - 100A-208/120V-3Ø-4W PANEL

"PPC" - 225A-208/120V-3Ø-4W PANEL

"DP" - 400A-480/277V-3Ø-4W PANEL

SYSTEM

SOURCE

"PPB" - 175A-208/120V-3Ø-4W PANEL

EMERG.

"PPA" - 100A-480/277V-3Ø-4W PANEL

"PPM" - 150A-480/277V-3Ø-4W PANEL

K

"R13A" - 225A-208/120V-3Ø-4W PANEL NORMAL

"PPC2" - 100A-208/120V-3Ø-4W PANEL

"EL13" - 60A-480/277V-3Ø-4W PANEL LIFE SAFETY

EXIST OR NEW

NEW

EMERG.

EMERG.

EMERG.

EMERG.

UPS

UPS

NEW

NEW

NEW

NEW

NEW

NEW

EXISTING

EXISTING

L "HP13" - 400A-480/277V-3Ø-4W PANEL NORMAL EXISTING

M "HP13B" - 400A-480/277V-3Ø-4W PANEL NORMAL NEW

CODED NOTES:

E.C. SHALL PROVIDE TELECOM OUTLET FLUSH MOUNTED IN WALL AT LOCATIONS INDICATED. PROVIDE 1" CONDUIT WITH PULLWIRE CONCEALED

IN WALL FROM OUTLETS BACKBOX TO ABOVE FINISHED CEILING. ROUTE CONDUITS OVER INTO EQUIPMENT ROOM #13-07 - STUB AND BUSH

CONDUITS. LABEL EACH CONDUIT IN EQUIPMENT ROOM WITH ROOM NAME/NUMBER WHERE TELECOM OUTLET IS LOCATED. T.C. SHALL PROVIDE

DATA JACKS, FACEPLATES AND PLENUM TYPE CAT6 CABLES. ROUTE CAT6 CABLES FROM OUTLETS, THRU CONDUITS TO TELECOM EQUIPMENT

RACKS IN EQUIPMENT ROOM. TERMINATE CABLES AT BOTH ENDS PER BUILDING STANDARDS AND SPECIFICATIONS - TYPICAL FOR ALL TELECOM

OUTLETS.

WIRELESS ACCESS POINT (WAP) - FURNISHED BY OWNER. E.C. SHALL PROVIDE BACKBOX FLUSH MOUNTED IN FINISHED CEILING. PROVIDE 1"

CONDUIT WITH PULLWIRE FROM BACKBOX OVER INTO EQUIPMENT ROOM #13-07 - STUB AND BUSH CONDUITS. LABEL EACH CONDUIT. T.C. SHALL

PROVIDE DATA JACKS, FACEPLATES AND PLENUM TYPE CAT6 CABLES AND ROUTE THRU CONDUITS TO TELECOM EQUIPMENT RACKS IN

EQUIPMENT ROOM. TERMINATE CABLES AT BOTH ENDS. PROVIDE 15'FT OF SLACK ABOVE FINISHED CEILING AT EACH "WAP" FOR FIELD

ADJUSTMENTS.

E.C. SHALL PROVIDE CONDUIT SYSTEM (WITH PULLWIRE) FROM FIRE-RATED POKE-THRU IN CONFERENCE ROOM ABOVE LEVEL TWELVE'S CEILING

OVER TO NEAREST LEVEL THIRTEEN NEW WALL PARTITION. CONTINUE ROUTING UP IN NEW WALL TO ABOVE LEVEL THIRTEEN'S CEILING. T.C.

SHALL PROVIDE TELECOM JACKS AND AUDIO/VISUAL MODULAR DEVICES IN FIRE-RATED POKE-THRU. ROUTE CABLING IN CONDUIT SYSTEM FROM

POKE-THRU TO ABOVE FINISHED CEILING. CONTINUE ROUTING CABLES TO EQUIPMENT ROOM #13-074B VIA 1" CONDUITS AND CONNECT

COMPLETE.

E.C. SHALL PROVIDE BACKBOX FLUSH MOUNTED IN WALL WITH (2) 1" CONDUITS WITH PULLWIRES FROM BACKBOX TO AFC. T.C. SHALL PROVIDE

CATV OUTLET AND "TV" DATA JACK IN COMMON FACEPLATE AT LOCATION OF WALL MOUNTED TELEVISION. ROUTE CAT6 CABLE AND (1) 1"

CONDUIT STUBBED INTO EQUIPMENT ROOM (LABEL CONDUITS). CONTINUE ROUTE OF CAT6 CABLE ALONG LADDER RUNWAY TO TELECOM

EQUIPMENT AND TERMINATE. PROVIDE RG-6 COAX CABLE FROM EXISTING CATV 8-PORT TAP IN EXISTING TELEPHONE ROOM #016. ROUTE COAX

CABLE THRU RENOVATED SPACE WITH ADDITIONAL TAPS, SPLITTERS AND COAX CABLES AND CONNECT COMPLETE TO EACH NEW CATV OUTLET.

TELECOM EQUIPMENT RACK AND CABINET LAYOUT AS INDICATED. RACKS AND CABINETS SHALL BE FURNISHED BY OWNER AND INSTALLED BY T.C.

SECURE RACKS TO CONCRETE FLOOR USING APPROVED HARDWARE. VERIFY EXACT LOCATIONS PRIOR TO DRILLING FLOOR. NETWORK

SWITCHES, PUNCHDOWN BLOCKS, CROSS-CONNECTS AND PATCH PANELS PROVIDED BY OWNER.

T.C. SHALL PROVIDE 19"W x 7'-0"H, 2-POST, TELECOM EQUIPMENT RACK LAYOUT AS INDICATED. RACKS SHALL BE BLACKBOX #RM940A SERIES, CHATSWORTH #55053 SERIES, APC #AR201 SERIES OR APPROVED EQUAL WITH 45RMUs, #10-32 RACK EQUIPMENT MOUNTING HARDWARE, VERITCAL AND HORIZONTAL CABLE MANANGEMENT SYSTEMS. SECURE RACKS TO CONCRETE FLOOR USING APPROVED HARDWARE. VERIFY

EXACT LOCATIONS PRIOR TO DRILLING FLOOR. NETWORK SWITCHES, PUNCHDOWN BLOCKS, CROSS-CONNECTS AND PATCH PANELS PROVIDED

BY OWNER.

CODED NOTES CONT.:

PROVIDE 36"WIDE STEEL CABLE RUNWAY SYSTEM LAYOUT AS INDICATED WITH WATERFALL TRAYS MOUNTED ABOVE EACH TELECOM RACK.

INSTALL LADDER RUNWAYS 8'-0"AFF AND SECURE TO STRUCTURAL SUPPORTS ABOVE AND INDEPENDENT OF CEILING SYSTEM OR OTHER

EQUIPMENT SUPPORTS. COORDINATE EXACT MOUNTING HEIGHT PRIOR TO ROUGH-IN

PROVIDE 20"L x 4"WIDE x 1/4"DEEP COPPER TELECOMMUNICATION GROUNDING BUSBAR (TGB) WALL MOUNTED IN AVAILABLE SPACE IN

EQUIPMENT ROOM #13-07. PROVIDE #1/0, GREEN INSULATED, STRANDED COPPER GROUND CONDUCTOR FROM "TGB" TO BUILDING STEEL

AND CONNECT VIA EXOTHERMIC WELD CONNECTION. PROVIDE 3/4"C WITH #6AWG COPPER GROUNDING CONDUCTOR BETWEEN NEW "TGB"

AND EXISTING "TGB" LOCATED IN EXISTING TELEPHONE ROOM #016 VIA 2-BOLT HOLE, LONG BARREL, COMPRESSION LUG CONNECTORS.

PROVIDE GROUND BUSHINGS ON ENDS OF CONDUIT. BOND ALL TELECOM RACKS, CABINET, ENCLOSURES, LADDER RUNWAYS, CABLE

TRAYS AND PANELBOARDS LOCATED WITHIN EQUIPMENT ROOM TO "TGB" VIA2-BOLT HOLE, LONG BARREL, COMPRESSION LUG

CONNECTORS.

PROVIDE (5) 4" SQ. OPENINGS THRU WALL OF EQUIPMENT ROOM #13-07. PROVIDE STI #EZP544W MULTI-GANG, WALL BRACKET SYSTEM WITH

(5) SERIES 44 FIRE-RATED PATHWAYS THRU WALL OPENINGS TO ACCOMMODATE ROUTING LOW-VOLTAGE CABLES INTO EQUIPMENT ROOM

FROM CABLE TRAY SOFFIT IN CORRIDOR. PROVIDE BLANK COVERPLATES OVER OPENING WHERE PATHWAYS ARE NOT INSTALLED. SEAL

PENETRATIONS TO MAINTAIN FIRE RATING.

PROVIDE (2) 10"W x 3-1/2" DEEP, STEEL, VERTICAL WALL DUCTS WITH FULL LENGTH REMOVABLE COVER FLUSH MOUNTED IN WALLS OF OPS.

STATION #13-20 AT LOCATIONS INDICATED. INSTALL WALL DUCT SYSTEM FROM FLOOR TO ABOVE FINISHED CEILING. CONTRACTOR SHALL

PROVIDE 2-SECTION, CUSTOM, MILLWORK COVERS FOR WALL DUCT SYSTEM. INSTALL ONE COVER SECTION ABOVE FURNITURE'S WORK

SURFACE AND THE OTHER COVER SECTION BELOW WORK SURFACE.

PROVIDE NEW FREE-AXEZ FLOOR SYSTEM POWER-VOICE-DATA FLOOR BOXES AT LOCATIONS INDICATED. INSTALL DATA JACKS AND

AUDIO-VISUAL COMPONENTS IN FLOOR BOX PROVISIONS. ROUTE CAT6 AND OTHER LOW-VOLTAGE CABLING FROM FLOOR BOX TELECOM

OUTLETS THRU FLOOR SYSTEM'S WIRING CHANNELS OVER TO VERITCAL WALL DUCTS. CONTINUE CABLE ROUTE UP TO AND ALONG CABLE

TRAYS INTO EQUIPMENT ROOM #13-07. TERMINATE CABLES AT BOTH ENDS. COORDINATE EXACT LOCATION OF FLOORBOXES PRIOR TO

ROUTING CABLES.

PROVIDE (2) 2-JACK TELECOM OUTLETS WALL MOUNTED ADJACENT TO ACCESS CONTROL SYSTEM CONTROLLER. PROVIDE (2) CAT6

CABLES FROM EACH TELECOM OUTLETS. ROUTE CAT6 CABLES FROM ONE OUTLET TO N.O.A.A'S DATA NETWORK. ROUTE CAT6 CABLES

FROM OTHER OUTLET TO BUILDING'S EXISTING DATA NETWORK. ASSUME 300' FT DISTANCE WITH NEW J-HOOKS TO CONNECT TO

BUILDING'S NEAREST NETWORK. TERMINATE AND LABEL CABLES PER OWNER'S REQUIREMENTS.

PROVIDE CEILING MOUNTED SPEAKER (ATLAS SOUND #SD72 OR APPROVED EQUAL) IN AVAILABLE SPACE FINISHED CEILING. PROVIDE

#18AWG, 2-CONDUCTOR CABLE DAISY-CHAINED BETWEEN SPEAKERS AND ROUTED OVER TO STUD WALL BEHIND RECEPTION DESK.

PROVIDE 2-GANG JUNCTION BOX FLUSH MOUNTED IN WALL WITH 1" CONDUIT WITH PULLWIRE STUBBED AND BUSHED ABOVE FINISHED

CEILING. ROUTE SPEAKER CIRCUIT THRU CONDUIT AND JUNCTION BOX AND CONNECT COMPLETE TO OWNER PROVIDE MUSIC EQUIPMENT.

COORDINATE EXACT LOCATION OF JUNCTION BOX WITH OWNER PRIOR TO ROUGH-IN.

PROVIDE JUNCTION BOX FLUSH MOUNTED IN WALL AT HEIGHT OF TELEVISIONS AND ADJACENT TO CATV /DATA OUTLET WITH 1" CONDUIT

WITH PULLWIRE CONCEALED IN WALL AND STUBBED ABOVE CEILING. PROVIDE ADDITIONAL JUNCTION BOX FLUSH MOUNTED IN WALL AT

STANDARD RECEPTACLE HEIGHT WITH 1" CONDUIT WITH PULLWIRE CONCEALED IN WALL AND STUBBED ABOVE CEILING. AUDIO-VISUAL

SYSTEM COMPONENTS AND CABLING BETWEEN JUNCTION BOXES SHALL BE FURNISHED AND INSTALLED BY OWNER.

PROVIDE CATV JACK AND DATA JACK INSTALL IN COMMON FACEPLATE AND MOUNTED TO UNISTRUT SUPPORTS FOR CEILING MOUNTED

TELEVISIONS. CONNECT CATV JACK CATV SYSTEM VIA NEW J-HOOKS AND COAX CABLES. CONNECT DATA JACK TO NETWORK VIA NEW

J-HOOKS AND CAT6 CABLES. FIELD VERIFY EXACT LOCATIONS PRIOR TO ROUGH-IN.

PROVIDE (2)-JACK DATA OUTLET AT EACH TEMPERATURE CONTROL PANEL AND CONNECT COMPLETE VIA (2) CAT6 CABLES.

NOT TO SCALE

AUDIO-VISUAL ROUGH-IN DETAIL

TV

TV J TV

J

CEILING

FLOOR

DESK WALL TELEVISION WALL

VERIFY LOCATION &

MOUNTING HEIGHT

VERIFY LOCATION &

MOUNTING HEIGHT

YY

EE

FF

GG

F A

C P

FAPB

ES

CR

F

SD

F

SD

SD

X

EL

F

F

F X

XL

XL

FXL

XL

F

F

F

PPB

PPC PPA

DP

"TR-PPB"

Future Tenant

1300X

Ops. Forcaster Stations 13-22

Ops. Stations

13-20

Collaboration Area 13-11

MIC

13-12

SOO

13-13

WCM Office

13-14

ESA Office

13-15

Elec./ Tech.

13-16A

Training

13-09

Equip.

13-07

Conference Rm.

13-05

Ready Rm

13-06

13-03

Reception

130-01

Hall 13-04

Elec.

13-08

Multipurpose Rm.

13-02

Vest 13-00

RMS Office 13-17

Copy/Stor

Elec./Tech 13-16B

Storage 13-19

Hall 13-10

PPC2

TGB

PPM

ATS

F

SD

MM

CM

SD

F

XL

F

F

F

TDW

R

AW

IP

S

BAT.

AW

IP

S

AW

IP

S

AW

IP

S

AW

IP

S

CRS

CRS

RPG

RPG

LIN

UX

W

IN

D

NET

VIP

LAN

FTI COM

SEC

DIS

P

UPS

MB

IC3

IC

P

S

BAT.

IC2

R13A

XX

X

LCP13

HP13

X

X

HP13B

NEW

Rm. #016 Telephone

CM

TYP.

TYP.

TYP.

SD

TYP.

IC

EP13-18

ES

CR

ES

CR

CM

AD 6

DC

DC

DC

DC

DCCM

SCP

ES

CR

DC

F

F

F

F

F

F

F-2

F-1

F-4

F-5

F-7

F-6

F-3

SB-HP-2

SB-HP-3

SB-HP-1

F-8

CM

CM

CM

CM

CM

CM

CM

CM

CM

CM

CM

CM

MM

MM

MM MM

TS FS

CM

FS

DISC.

EP13-22

EP13-22

EP13-22

EP13-22

F

F

XL

Corridor 13-18

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATE

DESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O

N T

R A

C T

O R

S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Carl B. Stokes US Court House

801 West Superior Avenue

Cleveland

11/18/2015Final Design Submittal

GS-05P-11-SLD-0057

5PSCE-15-0038a

1503A

Fredrick, Fredrick & Heller Engineers

230 South Dearborn St

Chicago, Illinois 60604

OH 44113

NOAA Office Relocation

John Bolovan 24x36

11/18/2015

13 ROH00736

OH0301ZZ

Perspectus Architecture

FUTURE

TENANT

ELEV

ATO

R S

N O

R T

H

Building Key Plan - Stokes 13th Floor not to scale

PROJECT

SCOPE

0'

SCALE: 1/8" = 1'0"

4' 8' 16' 32'

PARTIAL 13TH FLOOR FIRE ALARM PLAN AND SECURITY PLAN

F1. ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE MAIN FIRE ALARM SYSTEM

CONTROL PANEL IN ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWING

WIRING DIAGRAMS AND DETAILS.

F2. ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE CONDUIT SYSTEM.

F3. IN GENERAL ALL MANUAL PULL STATIONS SHALL BE INSTALLED AT 48" ABOVE FINISHED FLOOR. MANUAL

PULL STATIONS SHALL BE INSTALLED WITHIN 5'-0" OF ALL EXIT DOORWAY OPENINGS AT EACH EXIT ON

EACH FLOOR. ADDITIONAL MANUAL PULL STATIONS SHALL BE PROVIDED SO THAT THE TRAVEL

DISTANCE TO THE NEAREST PULL STATION WILL NOT EXCEED 200' MEASURED HORIZONTALLY ON THE

SAME FLOOR.

F4. ALL AUDIO/VISUAL AND VISUAL ONLY FIRE ALARM SYSTEM DEVICES SHALL BE ADA TYPE. IN ALL CASES

VISUAL DEVICES SHALL BE WALL MOUNTED AT 80" ABOVE FINISHED FLOOR. VISUAL DEVICES SHALL BE

LOCATED NOT MORE THAN 15' FROM THE END OF ALL CORRIDORS WITH A SEPARATION NOT GREATER

THAN 100' BETWEEN DEVICES. AUDIO DEVICES SHALL BE INSTALLED THROUGHOUT THE BUILDING TO

ATTAIN MINIMUM DECIBEL LEVELS REQUIRED BY CODE. COMBINATION AUDIO/VISUAL DEVICES AND

ADDITIONAL VISUAL ONLY DEVICES SHALL BE INSTALLED AT LOCATIONS AS INDICATED ON FLOOR

PLANS.

F5. IN GENERAL SMOKE DETECTORS SHALL BE INSTALLED ON CEILINGS WITH SPACING NOT TO EXCEED

MANUFACTURER'S RECOMMENDATION.

F6. SPRINKLER SYSTEM WATERFLOW ALARM INITIATING DEVICES SHALL BE CONNECTED COMPLETE TO THE

FIRE ALARM SYSTEM.

F7. DUCT TYPE SMOKE DETECTORS SHALL BE PROVIDED FOR ALL HVAC RETURN AIR SYSTEMS WITH

DESIGN CAPACITY GREATER THAN 2,000 CFM. WHERE RETURN AIR RISERS SERVE TWO OR MORE

STORIES, AND ARE PART OF A RETURN AIR SYSTEM HAVING A DESIGN CAPACITY GREATER THAN 15,000

CFM, DUCT DETECTORS SHALL BE PROVIDED AT EACH STORY. COORDINATE EXACT DETECTOR

LOCATIONS AND PROVISION OF ADEQUATE DUCT LENGTHS WITH THE MECHANICAL CONTRACTOR PRIOR

TO ROUGH-IN.

F8. PROVIDE ALL FIRE ALARM SYSTEM COMPONENTS NECESSARY FOR SHUT DOWN OF HVAC EQUIPMENT

BY THE FIRE ALARM SYSTEM WHERE SAME IS REQUIRED.

F9. PROVIDE ALL FIRE ALARM SYSTEM COMPONENTS NECESSARY FOR ELEVATOR CAPTURE BY THE FIRE

ALARM SYSTEM WHERE SAME IS REQUIRED.

F10. SMOKE DETECTORS SHALL BE INSTALLED WITHIN 5'-0" OF CENTERLINE OF SMOKE DOORS ON

HOLD-OPEN.

F11. SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER THAN 3'-0" FROM AN AIR SUPPLY DIFFUSER.

F12. AUTOMATIC DOORS LOCATED ON A 2-HOUR FIRE RATED WALL SHALL HAVE A FIRE ALARM INTERFACE

THAT INTERRUPTS 120V POWER FOR THE AUTOMATIC DOOR OPENER UNDER A FIRE ALARM CONDITION.

PROVIDE (1) CONTROL MODULE FROM EACH BUILDING FIRE ALARM SYSTEM IF LOCATED ALONG ALONG

THE BORDER OF TWO BUILDINGS.

GENERAL FIRE ALARM SYSTEM NOTES

CODED NOTES:

1 REINSTALL EXISTING PROVIDE NEW FIRE ALARM DEVICES AT LOCATIONS INDICATED AND CONNECT COMPLETE TO EXISTING BUILDING'S FIRE ALARM

SYSTEM VIA 3/4"C AND WIRING AS INDICATED ON FIRE ALARM SHOP DRAWING SUBMITTALS.

PROVIDE FIRE ALARM MONITOR MODULE AT LOCATION OF EQUIPMENT ROOM'S AC UNITS. CONNECT COMPLETE THRU AUXILIARY CONTACTS IN AC UNIT'S

INTEGRAL SMOKE DETECTOR TO NOTIFY BUILDING'S FIRE ALARM SYSTEM WHEN INTEGRAL SMOKE DETECTOR IS ACTIVATED.

ACCESS CONTROL SYSTEM - 120V-1Ø-20AMOCP - HIRSCH ELECTRONICS #MX8 SERIES WITH POWER SUPPLIES, SOFTWARE, PROGRAMMING, ENROLLMENT

AND CARD ACCESS FOR UP TO (35) PERSONNEL. E.C. SHALL RETAIN INSOLVES INNOVATIVE SOLUTIONS UNLIMITED, LLC (BRIAN WILSON - 740-289-3282, EXT.