90__GSA_Maint_Guides_DRAFT_Enovity.pdf
PDF 5 MB Posted
- Solicitation number
- GS-01P-12-BW-D-0062
About this file
Preventive Maintenance Guide
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_0012_Post.pdf | ||
| Final_Question_and_Answers_9.20.12_For_Amend_11.pdf | ||
| AppendixI_UST_Guide.pdf | ||
| Amendment_0011_Post.pdf | ||
| Revised_L M_9.20_for_Amend_11.pdf | ||
| 1449_9.20_for_Amend_11.pdf | ||
| AppendixG_UW_Guide.pdf | ||
| AppendixH_RefrigMng_Guide_(1).pdf | ||
| Amendment_0010_Post.pdf | ||
| Amendment_0009_Post.pdf | ||
| Amendment 0007 post.pdf | ||
| Amendment 0008 Post.pdf | ||
| Amendment 0006 Post.pdf | ||
| CPAR FORM 7-11 | — | |
| Amendment 0005 Post.pdf | ||
| Updated Wage Determination.txt | TXT text file | |
| Amendment 0004 Post.pdf | ||
| Amendment 0003 post.pdf | ||
| Amendment 0002.pdf | ||
| Amendment 0001.pdf | ||
| FormSF1449 1 .pdf |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
General Services Administration Public Buildings Service
Office of Real Property Management and Safety - PM
PUBLIC BUILDINGS
MAINTENANCE GUIDES
90% DRAFT
March 2012
Contents
This Maintenance Guide is divided into the following Sections:
Section 1: Introduction and Maintenance Guide List
Section 2: Maintenance Guides
Appendix A: NETA Qualifications, Responsibilities and Safety
Appendix B: NETA Electrical Test Frequencies
Appendix C: Maintenance Guide Number Key
Appendix D: Equipment Attributes Lists
Appendix E: RFID Tag Procedure
Appendix F: Point Naming Procedure
Appendix G: Universal Waste Guide
Appendix H: Refrigerant Management Guide
Appendix I: Underground Storage Tank Regulatory Requirements
Appendix J: Predictive Maintenance and Toolsets
General Services Administration Preventive Maintenance Guide Effective Date: April, 2012
Section 1
General Services Administration Public Buildings Service
Maintenance Practices and General Information for Federal Buildings
1. General Overview. The objective of these maintenance guides is to provide helpful instruction in the performance of preventive and predictive maintenance techniques, in order to maximize the efficiency of operation and the useful life of equipment, systems, and structures, and to provide reliable and suitable conditions for the building tenants. They are generic in nature and not intended to substitute for manufacturer's instructions or to apply uniformly across all types and configurations of equipment and systems installed in Federal buildings. Therefore, maintenance staffs and contractors must exercise a measure of caution in the application of these guides. Abide by the following standards during the performance of these maintenance procedures.
2. Maintenance Guide Numbers. The GSA Maintenance Guide, Region 9 Supplement is arranged by sections according to building equipment groups or building components. A four (4) tier system is used to easily identify the type of building group, equipment type and frequency for performing maintenance on these systems. The format is as follows:
a) Tier 1 identifies the building component system or type of building equipment group, i.e. Electrical (ELEC), Heating Ventilation, Air Conditioning (HVAC)
b) Tier 2 identifies the type of equipment, i.e. Transformer (TRN), Chiller
(CLR)
c) Tier 3 further defines the equipment by number when there is more than one type, i.e. Centrifugal Chiller (04), Absorption Chiller (05)
d) Tier 4 defines the frequency for the specific maintenance task to be performed, i.e. Monthly (01M), Quarterly (03M) Semi-annually (06M), Annually (01Y)
The Guide number appears in the format of: HVAC-CLR-04-01Y which identifies the guide as: a HVAC System chiller of type 4 (centrifugal) to be performed annually.
3. GEMnet. Most buildings in Region 9 are part of the GSA Energy and Maintenance Network (GEMnet). This network facilitates a Computerized
Maintenance Management System (CMMS) which O&M Contractors will utilize for scheduling and tracking of maintenance in each facility. The CMMS will generate the Preventative Maintenance Guide on the prescribed schedule frequency. The CMMS can also be used to store information on a particular piece of equipment.
4. Equipment Attributes. Appendix D contains Equipment Attributes lists that the Operations and Maintenance Contractor is required to collect data from each piece of equipment. This task is part of the maintenance requirements for each building in order for GSA to have an accurate and up to date database of each building’s equipment. Equipment is listed with the values and the type of data that shall be collected. Attribute fields have been created in the CMMS for each equipment type. Once the data has been collected it shall be input into the CMMS by the contractor.
5. Good Maintenance Practices. The following is a list of good practices to observe when performing maintenance.
a) Machinery and equipment shall be cleaned and touch up painted as necessary to restore surface condition and inhibit corrosion.
b) Install replacement parts that are appropriate to the equipment, its operating conditions, and the required performance levels. Substandard components shall not be used in government equipment. All parts, materials, components, and replaceable inserts used in the maintenance and repair of equipment and systems in Federally controlled space shall be new, suitable for the type and severity of service, and meet safety performance codes and standards. Refurbished parts are not to be used unless approved by proper authority. Normal rework of machinery casings, tube sheets, shafts, and other similar types of work, where repair to a major structural item is accepted industry practice, is permitted unless safety and performance are adversely affected.
c) Proper documentation through a system of record keeping is required. The types of records authorized may be preprinted government forms or locally produced forms of an appropriate format. It is paramount to maintain equipment history records to facilitate decision making throughout the life of the equipment. Predictive maintenance frequently entails trending analysis, so a history of the test data on the equipment is required.
d) The intent of language such as "check", "inspect", etc., is to determine the status of the check point item and to take appropriate corrective action to eliminate any deficiencies found. If additional calibration, adjustment, replacement of parts and fluids, and other work are necessary, that work shall be accomplished or scheduled for future action.
e) Maintenance work shall be scheduled so as to minimize the disruption to building occupants and operations. Proper notification and coordination shall be made when maintenance work necessitates shutting down equipment or otherwise terminating services to the building occupants.
f) Equipment under warranty shall be maintained in accordance with warranty instructions and conditions. Warranty provisions will be stringently complied with during the periods that they apply.
g) When fixed fire protection systems are temporarily removed or disconnected from service, they must be reconnected and/or placed back into service at the end of each work day unless otherwise authorized. Fixed fire protection systems include equipment and devices whose function is to prevent, detect, or control fires, or transmit signals related to fire emergencies. The status of major equipment or systems not operating or that become non operational during the workday, or any system or equipment item, including elevators, not operational by the official working hours start time, shall be reported to the proper authority (buildings manager or contracting officer's representative.) Security and fire alarm system malfunctions must be reported immediately to the GSA control center. All fire related equipment operation and maintenance shall follow the appropriate National Fire Protection Association (NFPA) code or standard, such as NFPA 72 the National Fire Alarm Code.
h) When performing maintenance in space that may be occupied or accessible during the performance of the work, provide adequate steps for the protection of the public and employees.
i) Trash, debris, and wastes from contract work inside buildings shall be removed daily. Exceptions shall be approved in advance. Premises shall be left neat and clean after each work shift so that the Government business can proceed without interruption the next regular workday. All waste material shall be properly disposed of in accordance with applicable Federal, state, and local regulations.
j) All equipment and systems shall be maintained at a level, fair wear and tear excepted, to assure that the building(s) are operated in an efficient and economical manner.
k) All work, including contact with and handling of hazardous materials and wastes, the disturbance or dismantling of structures or equipment containing hazardous materials and/or the disposal of ordinary and hazardous materials and wastes shall comply with applicable Federal requirements including 29 CFR 1910/1926, 40 CFR 260-265, 40 CFR 61, 49 CFR 171-179, and applicable state and municipal safety and environmental requirements. Submit copies of permits, certificates, and manifests that indicate hazardous waste has been disposed of in compliance with the regulations. Where there is a conflict between applicable regulations, the most stringent shall apply.
6. Occupational Safety and Health.
Several preventive maintenance guides identify specific Standard Operating Procedures (SOP's) that must be complied with. They are listed below and are for the safety and health of the workers performing maintenance tasks. Personnel must be properly trained in either these SOP's or the regional Safety and Environmental Management Office approved SOP's. Copies are contained in the GSA publication "A Compendium of Occupational Safety and Health Procedures and Training Materials for GSA Managers and Supervisors," which is available in the buildings manager's office.
• Confined Space Entry.
• Controlling Hazardous Energy Sources.
• Selection, Care, and Use of Respiratory Protection Parts I and II.
• Emergency Eyewash and Shower Equipment
• Powered Industrial Trucks (Forklifts)
7. Certification.
a) Licenses, Permits and Bonding. All personnel engaged in the maintenance activities shall possess certificates of training, licenses, permits, and bonding as required by the state, county, parish, city, other local jurisdictions and as specified for each activity they will be directly engaged in or supervise. All certificates of training, licenses, permits and bonds shall be current and valid.
b) Mechanics. All persons engaged in maintenance activities must be licensed by the appropriate state and local authorities in those trades, crafts or professions which require licensing by such jurisdictions. The license must be of a grade or other level consistent with the requirement of the work being performed as established by these jurisdictions. Effective November 14, 1994, persons who maintain, service, or repair appliances that contain Class I or Class II refrigerants shall be certified by an Environmental Protection Agency approved certifying program in accordance with 40 CFR Part 82.
8. Uniforms. All employees, including supervisors, shall present a clean, neat appearance and wear appropriate uniforms at all times while on duty.
9. Protection to the Public and Property.
a) Take all necessary precautions to prevent injury to the public, building occupants, or damage to the property of others.
b) Storing, positioning, or use of equipment, tools, scraps, trash, and furniture in a manner likely to present a hazard to the public or building occupants by its accidental shifting, ignition, or other hazardous qualities is prohibited.
c) No corridor, aisle, stairway, door, or exit shall be obstructed or used in such a manner as to encroach upon routes of ingress or egress utilized by the public or building occupants, or to present unsafe or unhealthy conditions to the public or building occupants.
d) Work shall not be performed in any area occupied by the public or building occupants unless specifically permitted by the proper authorities and unless adequate steps are taken for the protection of the public or employees.
e) Wherever practicable, the work area shall be fenced, barricaded, or otherwise blocked off from the public or building occupants to prevent unauthorized entry into the work area.
f) When the nature of the work prevents isolation of the work area and the public or building occupants may be in or pass through, under, or over the work area, alternate precautions such as the posting of signs, the use of signal persons, the erection of barricades or similar protection around particularly hazardous operations shall be used as appropriate.
g) When work is to be performed over a public thoroughfare such as a sidewalk, lobby, or corridor, the thoroughfare shall be closed, if possible, or other precautions taken such as the installation of screens or barricades.
When the exposure to heavy falling objects exists, as during the erection of building walls or during demolition, special protection of the type detailed in 29 CFR 1910/1926 shall be provided.
h) Fences and barricades shall be removed upon completion of the project, in accordance with local ordinances.
10. Forms and Devices: The facilities maintenance management system uses the forms and devices listed below. Suitable substitutes may be used, as appropriate:
a) Forms.
i) GSA Form 10, Keep Out Tag.
ii) GSA Form 55, Certificate of Elevator Inspection. This form is used to record the results of an elevator inspection.
iii) GSA Form 283, Notice of Work Required. This form is for use by any employee who observes the need for work that he/she cannot do or which is not assigned or responsible for. It serves as a notice of a deficiency or work requirement for later scheduling, assignment and accomplishment as required.
iv) GSA Form 349, Inspection Report of Boiler. This is prepared for each boiler when it is inspected.
v) GSA Form 350, Inspection Report of Unfired Vessels. This is used to report the inspection of unfired pressure vessels.
vi) GSA Form 1003, Storage Battery Monthly Record. This form is used to record the specific gravity for batteries as prescribed by the preventive maintenance guides.
vii) GSA Form 1034, Certificate of Inspection, Pressure Vessels. This is issued when the boiler and pressure vessels have been approved for operation.
viii)GSA Form 1128, Danger Tag.
ix) GSA Form 1231, Elevator Data Card. This form serves a dual purpose.
The front serves as an inventory card and contains a complete description of all components of the elevator. The reverse side contains rope information and space to record repairs or alterations. It is used for elevators, escalators, dumbwaiters, and sidewalk elevators.
x) GSA Form 1736, Equipment Inventory List. This form is used to record all building equipment that requires maintenance.
xi) GSA Form 1737, Operator Assignment. This form is used to record and document the principal work requirements of an operator. it also prescribes a route to be followed for expeditious fulfillment of the work.
xii) GSA Form 1738, Preventive Maintenance Control. This form is used to initiate programmed preventive maintenance work and as a control on the work that is scheduled. the card is issued to the crafts supervisor when the work prescribed for the item shown on the card is due and is returned to the office when the work is completed showing the date the work was finished, the time used, and the initials of the mechanic(s).
xiii)GSA Form 1739, Equipment History. This form is used to record the repair work or modifications that are performed on selected items of equipment. the form provides for information describing the item and its appurtenances in detail with space to enter the record of repair modifications.
xiv) GSA Form 1897, Maintenance Authorization. This form is used to record and authorize requests for service, trouble calls, and emergency work. this form is also used to authorized all maintenance, repair, replacement, and modification work.
xv) GSA Forms 2103, 2103a, and 2103b, Annual Man-hour Requirements.
These forms are used to determine and document the annual man-hours for operating tours of building equipment established on a basis of review and need. Deviation from established frequencies of inspection may be made where separately justified.
xvi) GSA Forms 2104 and 2104A, Annual Man-hour Watch Requirements. These forms are used to record and document the man-hours required for watch assignment in accordance with provisions of the Procedures Governing Boiler and Compressor Room Operation.
xvii) GSA Form 2105, Annual Man-hour Preventive Maintenance Requirements. This form is used to identify the items of equipment that are to receive periodic maintenance; to determine and document the annual man-hours required for the preventive maintenance program;
and to schedule a balanced workload for planned accomplishment.
xviii) GSA Form 2106, Annual Man-hour Service Call Requirements. This form is used to develop and document the man-hours required for service calls computed from a standard allowable time and an estimate of the anticipated number of service calls on the basis of past experience at the individual location.
xix) GSA Form 2107, Annual Building Operation and Maintenance - Craft Requirements. This form is used to summarized all operation and maintenance productive man-hours on an individual basis that have been computed and documented on the above annual man-hours.
xx) GSA Form 2109, Annual Field Office Crafts Requirements. This is a summation sheet of all of the data collected from all the GSA forms listed on GSA form 2107, In addition, all reimbursable, incidental repair, etc., and supervisory requirements for the field office are entered on this form. Thus, this form reflects total field office craft man-hour requirements and may be used as a staffing guide.
xxi) GSA Form 2523, Lampist Daily Call Record. This form is used to record and authorize spot lamp replacement. It is used in lieu of GSA Form 1897 for this special service. When completed, it contains a record of the number of lamps replaced and time expended.
xxii) GSA Form 2543, Low Voltage Circuit Breaker Test Record. This form is used to record the test results of low voltage circuit breakers.
File this form by circuit designation.
xxiii) GSA Form 2543A, Network Protector Test Record. This form is used to record the test results of network protectors. File this form by unit designation.
xxiv) GSA Form 2543B, Protective Relay Test Record. This form is used to record the test results of protective relays. File this form by circuit designation.
xxv) GSA Form 3532, Asbestos Records. This form is used to label folders and file drawers containing asbestos related information.
b) Devices
i) Operating schedule. This is a written procedure for a building specifying the hours of operation for the heating and air-conditioning equipment based on the seasons and in accordance with the outside temperature conditions.
ii) Preventive maintenance guides. The guides outline the minimum preventive maintenance work that is required and authorized for building equipment. The guides also recommend that equipment manufacturer's recommendations are followed when applicable. If these guides are not considered adequate for specific equipment, submit a new or revised guide card and justification for approval. Recommendations of standard man-hour requirements are also welcome.
iii) Predictive Maintenance Guides. The predictive guides allow the use of predictive maintenance practices. These tasks and can be used as an alternative to the purely preventive maintenance guide. If the facility elects to use this guide as a substitute for the preventive maintenance guide, then it is not necessary to follow the relevant preventive guide(s).
iv) NETA Electrical Testing Requirements. The 2011 International Electrical Testing Association (NETA) and American National Standards Institute (ANSI) Maintenance Testing Specifications has been used as the guide for all electrical testing procedures. The ANSI/NETA requirements for Qualifications, Responsibilities and Safety for test procedures have been included in Appendix A for reference. Appendix B also contains the ANSI/NETA schedule for the Frequency of Maintenance test as a reference. All tests shall conform to the appropriate ANSI/NETA test procedure and the values used as standards shall conform to the manufacturer's, NETA, and ANSI Standards specifications. For NETA Testing, note that Low Voltage is 1,000 Volts or less and Medium Voltage is 1,000 to 100,000 Volts.
11. Electrical test equipment. All electrical test equipment shall conform to the following requirements, outlined in ANSI/NETA MTS-2011.
a) Suitability of Test Equipment
i) All test equipment shall meet the requirements in paragraph b) Test Instrument Calibration and be in good mechanical and electrical condition.
ii) Field test metering used to check power system meter calibration must be more accurate than the instrument being tested.
iii) Accuracy of metering in test equipment shall be appropriate for the test being performed.
iv) Wave shape and frequency of test equipment output waveforms shall be appropriate for the test to be performed and the equipment to be tested.
b) Test Equipment calibration
i) The testing organization shall have a calibration program which assures that all applicable test instruments are maintained within rated accuracy for each test instrument calibrated.
ii) The firm providing calibration service shall maintain up-to-date instrument calibration instructions and procedures for each test instrument calibrated.
iii) The accuracy shall be directly traceable to the National Institute of Standards and Technology (NIST).
iv) Instruments shall be calibrated in accordance with the following frequency schedule:
Field instruments: analog and digital, 12 month maximum.
Laboratory instruments: 12 month maximum.
Leased specialty equipment: 12 month maximum.
v) Dated calibration labels shall be visible on all test equipment.
vi) Records which show date and results of instruments calibrated or tested must be kept up to date.
vii) Calibrating standard shall be of better accuracy than that of the instrument tested.
12. Standard tools. The following lists serve as guides for supplying maintenance personnel with tools. Basic and trade tools required will vary depending on equipment served and on individual preferences. Special recommended tools, materials, and equipment are listed in the individual guides as required.
STANDARD TOOLS - BASIC
(All Trades)
1. Standard and Phillips head screw drivers-various sizes.
2. Pliers-vise grip (2), slip-joint, needle-nose, diagonal,
3. cutting pliers, side cutters.
4. Ball peen hammer.
5. Hack saw and spare blades.
6. 3/8' drive socket set and ratchet.
7. Small set of Allen wrenches.
8. Assorted center punches, drift punches, and steel chisel.
9. 12' measuring tape.
10. Crescent wrenches 4" to 8".
11. Open and box end wrenches ¼" to ¾".
12. File.
13. Pipe wrenches to 14".
14. Small level and square.
15. Pocket knife.
16. Flashlights.
17. Grease guns and oilers
18. Wire brush.
19. Extension cord and inspection lights.
20. Various cleaning tools - brushes, scrapers, etc.
21. Emery cloth.
TOOL GROUP A
1. Standard tools - basic
2. Refrigeration - gauges
3. Leak detector-electronic or halogen
4. Pocket thermometer
5. Clamp on meter (volt - ohm - amp meter)
6. Flaring tool
7. Tubing cutters
8. Packing kit and packing
9. Crescent wrenches to 14"
TOOL GROUP B
2. Insulated pliers and screwdrivers
3. Wire strippers
4. Wire crimpers
5. Voltmeter - Ohmmeter - Milliammeter
6. Clamp on meter(volt - ohm - amp meter)
7. Soldering kit
8. 1/8" 25' fish tape
9. Burnishing tool
TOOL GROUP C
2. Pipe wrenches to 24"
3. Tubing cutters
4. Flaring tool
5. Small acetylene outfit
6. Packing tool kit and packing
7. ¾" socket set
8. Crescent wrenches to 14"
Maintenance Guide Listing
General Services Administration
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
ARCHITECTURAL AND STRUCTURAL
ARCS-BAR-01-06M Security Bollards and Barricades Apr-12 Semi-annually
ARCS-DAV-01-01Y Davits Apr-12 Annually
ARCS-DOR-01-06M Door, Power Operated Apr-12 Semi-annually
ARCS-DOR-02-03M Door, Hydraulic, Electric or Pneumatic Operated Apr-12 Quarterly
ARCS-DOR-03-06M Door, Manual, Overhead Apr-12 Semi-annually
ARCS-DOR-04-06M Door, Main Entrance Apr-12 Semi-annually
ARCS-FPL-01-01M Fireplace Apr-12 Monthly
ARCS-FPL-01-01Y Fireplace Apr-12 Annually
ARCS-FPL-02-01Y Incinerator Apr-12 Annually
ARCS-LND-01-06M Fountain, Memorial or Decorative Apr-12 Semi-annually
ARCS-LND-02-06M Gates and Fences, Security and Access Apr-12 Semi-annually
ARCS-LND-03-01Y Lawn Sprinklers (per nozzle) Apr-12 Annually
ARCS-LND-04-03M Flag Pole, Electric Apr-12 Quarterly
ARCS-LND-05-06M Lawn Mower and Edger Apr-12 Semi-annually
ARCS-MHL-01-01Y Manhole, Electrical Apr-12 Annual
ARCS-MHL-02-03M Manhole, Sewer Apr-12 Quarterly
ARCS-MHL-03-06M
Manhole, Water/Steam/Fuel Oil (also includes hot water, chilled water, and condenser water) Apr-12 Semi-annually
ARCS-RFS-01-06M Roof Inspection - Built-up type (per square, or 100 sq. ft.) Apr-12 Semi-annually
ARCS-RFS-02-06M Roof Inspection - Shingle Type (per 100 sq. ft.) Apr-12 Semi-annually
ARCS-RFS-03-03M Extensive and Intensive Vegetative Roof Apr-12 Quarterly
ARCS-SCT-01-03M Key Card System Apr-12 Quarterly
ARCS-SCT-02-01Y Parking Arm Gates Apr-12 Annually
ARCS-STR-01-01Y Lightning Protection (per down conductor) Apr-12 Annually
ARCS-SWM-01-01M Storm Water Management: Ponds (Dry and Wet) Apr-12 Monthly
ARCS-SWM-01-01Y Storm Water Management: Ponds (Dry and Wet) Apr-12 Annually
ARCS-SWM-02-01M Storm Water Management: Basins Apr-12 Monthly
ARCS-SWM-02-01Y Storm Water Management: Basins Apr-12 Annually
ARCS-SWM-03-01M Storm Water Management: Trenches Apr-12 Monthly
ARCS-SWM-03-01Y Storm Water Management: Trenches Apr-12 Annually
ARCS-SWM-04-01M Storm Water Management: Dry Wells Apr-12 Monthly
ARCS-SWM-04-01Y Storm Water Management: Dry Wells Apr-12 Annually
ARCS-SWM-05-01M Storm Water Management: Permeable Pavers Apr-12 Monthly
ARCS-SWM-05-01Y Storm Water Management: Permeable Pavers Apr-12 Annually
ARCS-SWM-06-01M
Storm Water Management: Hydrodynamic Structures (i.e.
swales) Apr-12 Monthly
Administration
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
ARCS-SWM-06-01Y
Storm Water Management: Hydrodynamic Structures (i.e.
swales) Apr-12 Annually
ARCS-SWM-07-01M Storm Water Management: Biofiltration Apr-12 Monthly
ARCS-SWM-07-01Y Storm Water Management: Biofiltration Apr-12 Annually
ARCS-WIN-01-01Y Window Washing Scaffold, Power Operated Apr-12 Annually
CHILD CARE
CHLD-EQP-01-01M Child Care Equipment Apr-12 Monthly
CHLD-SEC-01-01M Child Care Secured Perimeter Systems Apr-12 Monthly
CHLD-SPC-01-01M Child Care Areas Apr-12 Monthly
CLEANING
CLNG-SCB-01-03M Scrubbing Machine, Battery or Propane Powered Apr-12 Quarterly
CLNG-SNO-01-01Y Snow Blower Apr-12 Annually
CLNG-SWP-01-06M Sweeper Apr-12 Semi-annually
CLNG-TCP-01-01Y Trash Compactor Apr-12 Annually
CLNG-VAC-01-06M Vacuum Cleaner, Heavy Duty, Tank Type Apr-12 Semi-annually
CLNG-VAC-02-01Y Vacuum System, Centralized Apr-12 Annually
CONTROLS
CTRL-DDC-01-01W BAS Server Apr-12 Weekly
CTRL-DDC-01-01M BAS Server Apr-12 Monthly
CTRL-DDC-01-03M BAS Server Apr-12 Quarterly
CTRL-DDC-01-01Y BAS Server Apr-12 Annually
CTRL-DDC-02-01W BAS Server Client Workstation Apr-12 Weekly
CTRL-DDC-02-01M BAS Server Client Workstation Apr-12 Monthly
CTRL-DDC-02-03M BAS Server Client Workstation Apr-12 Quarterly
CTRL-DDC-02-01Y BAS Server Client Workstation Apr-12 Annually
CTRL-DDC-03-03M Network, Management Level Apr-12 Quarterly
CTRL-DDC-03-01Y Network, Management Level Apr-12 Annually
CTRL-DDC-04-03M Network, Building Level Apr-12 Quarterly
CTRL-DDC-04-01Y Network, Building Level Apr-12 Annually
CTRL-DDC-05-01Y Field Panel Apr-12 Annually
CTRL-DDC-06-01Y Controller Apr-12 Annually
CTRL-DDC-07-01Y Controls, Sensors Electronic Apr-12 Annually
CTRL-DDC-08-01M Alarm Maintenance Apr-12 Monthly
CTRL-DDC-09-06M
BAS Wireless Electronic/Pneumatic End Devices
(Thermostats) Apr-12 Semi-annually
CTRL-DDC-09-01Y
BAS Wireless Electronic/Pneumatic End Devices
(Thermostats) Apr-12 Annually
CTRL-END-01-01Y End Devices Apr-12 Annually
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
CTRL-PNU-01-06M Control Air System Apr-12 Semi-annually
CTRL-PNU-02-06M Receiver Controller Apr-12 Semi-annually
CTRL-PNU-03-03M Filter, Control Air Apr-12 Quarterly
ELECTRICAL
ELEC-ATS-01-03M Automatic Transfer Switch, per NFPA 110 Apr-12 Quarterly
ELEC-ATS-01-01Y Automatic Transfer Switch Apr-12 Annually
ELEC-BDT-01-01Y Metal-Enclosed Busways, Thermographic Survey Apr-12 Annually
ELEC-BDT-01-03Y Metal-Enclosed Busways Apr-12 3-Year
ELEC-CAP-01-01Y Capacitors, Thermographic Survey Apr-12 Annually
ELEC-CAP-01-03Y Capacitors Apr-12 3-Year
ELEC-CAP-02-01Y Reactors-Dry-Type, Thermographic Survey Apr-12 Annually
ELEC-CAP-02-03Y Reactors – Dry-Type Apr-12 3-Year
ELEC-CAP-03-01M Reactors – Liquid-Filled, Oil Leakage Apr-12 Monthly
ELEC-CAP-03-01Y Reactors – Liquid-Filled, Oil Sampling Apr-12 Annually
ELEC-CAP-03-03Y Reactors – Liquid-Filled Apr-12 3-Year
ELEC-CBL-01-01Y Cables, Low-Voltage, Thermographic Survey Apr-12 Annually
ELEC-CBL-01-03Y Cables, Low-Voltage Apr-12 3-Year
ELEC-CBL-02-01Y
Medium- and High-Voltage Cables, Thermographic
Survey Apr-12 Annually
ELEC-CBL-02-03Y Medium- and High-Voltage Cables Apr-12 3-Year
ELEC-CKB-01-01Y Circuit Breakers, Air, Insulated-Case/Molded-Case Apr-12 Annual
ELEC-CKB-01-03Y Circuit Breakers, Air, Insulated-Case/Molded-Case Apr-12 3-Year
ELEC-CKB-02-01Y Circuit Breakers, Air, Low-Voltage Power Apr-12 Annually
ELEC-CKB-02-03Y Circuit Breakers, Air, Low-Voltage Power Apr-12 3-Year
ELEC-CKB-03-01Y Circuit Breakers, Air, Medium-Voltage Apr-12 Annually
ELEC-CKB-03-03Y Circuit Breakers, Air, Medium-Voltage Apr-12 3-Year
ELEC-CKB-04-01M Circuit Breakers, Oil, Medium- and High-Voltage Apr-12 Monthly
ELEC-CKB-04-01Y Circuit Breakers, Oil, Medium- and High-Voltage Apr-12 Annually
ELEC-CKB-04-03Y Circuit Breakers, Oil, Medium- and High-Voltage Apr-12 3-Year
ELEC-CKB-05-01Y Circuit Breakers, Vacuum, Medium-Voltage Apr-12 Annually
ELEC-CKB-05-03Y Circuit Breakers, Vacuum, Medium-Voltage Apr-12 3-Year
ELEC-CLK-01-06M Clocks, Central System Apr-12 Semi-annually
ELEC-DCS-01-01M DC Batteries, Lead Acid Apr-12 Monthly
ELEC-DCS-01-01Y DC, Batteries, Lead-Acid Apr-12 Annually
ELEC-DCS-02-01M Dry Cell Battery Apr-12 Monthly
ELEC-DCS-02-01Y Dry Cell Battery Apr-12 Annually
ELEC-DCS-03-03M Nickel Cadmium Batteries Apr-12 Quarterly
ELEC-DCS-04-01M Direct-Current Systems, Chargers Apr-12 Monthly
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
ELEC-DCS-04-01Y Direct-Current Systems, Chargers Apr-12 Annually
ELEC-EMG-01-01M Emergency Generator, Electric Tests Apr-12 Monthly
ELEC-EMG-01-01Y Emergency Generator, Electric Tests Apr-12 Annually
ELEC-GRD-01-01Y Grounding Systems Apr-12 Annually
ELEC-GRD-01-03Y Grounding Systems Apr-12 3-Year
ELEC-ITR-01-01Y Instrument Transformers Apr-12 Annually
ELEC-ITR-01-03Y Instrument Transformers Apr-12 3-Year
ELEC-LTG-01-03M Dimmer and Control, Stage and General Lighting Apr-12 Quarterly
ELEC-LTG-02-02Y Fluorescent Lighting Fixture, Washing and Relamping Apr-12 2-Year
ELEC-LTG-02-05Y Fluorescent Light Fixture, Relamping Only Apr-12 5-Year
ELEC-LTG-03-01Y Lighting, Special Feature Apr-12 Annually
ELEC-LTG-04-06M
Lighting, Outside Incandescent Fluorescent, Mercury
Vapor or High Pressure Sodium Apr-12 Semi-annually
ELEC-LTG-04-05Y
Lighting, Outside Incandescent Fluorescent, Mercury
Vapor or High Pressure Sodium Apr-12 5-Year
ELEC-LTG-05-01M Spotlights, Fixed and Portable Apr-12 Monthly
ELEC-LTG-06-03M Emergency Lights, Closed System Apr-12 Quarterly
ELEC-LTG-07-03M Emergency Lighting, Wet Cell Apr-12 Quarterly
ELEC-MCC-01-01Y Low-Voltage Motor Starters Apr-12 Annually
ELEC-MCC-01-03Y Low-Voltage Motor Starters Apr-12 3-Year
ELEC-MCC-02-01Y Medium-Voltage Motor Starters Apr-12 Annually
ELEC-MCC-02-03Y Medium-Voltage Motor Starters Apr-12 3-Year
ELEC-MCC-03-01Y Low-Voltage Motor Control Centers Apr-12 Annually
ELEC-MCC-03-03Y Low-Voltage Motor Control Centers Apr-12 3-Year
ELEC-MCC-04-01Y Medium-Voltage Motor Control Centers Apr-12 Annually
ELEC-MCC-04-03Y Medium-Voltage Motor Control Centers Apr-12 3-Year
ELEC-MOT-01-01M Rotating Machinery, AC Induction Motors and Generators Apr-12 Monthly
ELEC-MOT-01-01Y Rotating Machinery, AC Induction Motors and Generators Apr-12 Annually
ELEC-MOT-01-02Y Rotating Machinery, AC Induction Motors and Generators Apr-12 2-Year
ELEC-MTR-01-01Y Metering Devices Apr-12 Annually
ELEC-MTR-01-03Y Metering Devices Apr-12 3-Year
ELEC-MTR-02-01Y Advanced Metering Apr-12 Annually
ELEC-NWP-01-01Y Network Protectors, 600 V Class Apr-12 Annually
ELEC-PVS-01-06M Photovoltaic Systems Apr-12 Annually
ELEC-REG-01-01M Step-Voltage Regulators Apr-12 Monthly
ELEC-REG-01-01Y Step-Voltage Regulators Apr-12 Annually
ELEC-REG-01-02Y Step-Voltage Regulators Apr-12 2-Year
ELEC-REG-02-01M Induction Regulators Apr-12 Monthly
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
ELEC-REG-02-01Y Induction Regulators Apr-12 Annually
ELEC-REG-02-03Y Induction Regulators Apr-12 3-Year
ELEC-REG-03-01M Load-Tap-changers Apr-12 Monthly
ELEC-REG-03-01Y Load-Tap-changers Apr-12 Monthly
ELEC-REG-03-03Y Load-Tap-changers Apr-12 3-Year
ELEC-RLY-01-01Y Protective Relays, Microprocessor-Based Apr-12 Annually
ELEC-SRG-01-01Y Surge Arresters, Low-Voltage Surge Protection Devices Apr-12 Annually
ELEC-SRG-01-03Y Surge Arresters, Low-Voltage Surge Protection Devices Apr-12 3-Year
ELEC-SRG-02-01Y Medium Voltage Surge Arresters Apr-12 Annually
ELEC-SRG-02-03Y Medium Voltage Surge Arresters Apr-12 3-Year
ELEC-SWB-01-01Y Switchgear and Switchboard Assemblies Apr-12 Annually
ELEC-SWB-01-03Y Switchgear and Switchboard Assemblies Apr-12 3-Year
ELEC-SWT-01-01Y Low-Voltage Air Switches Apr-12 Annually
ELEC-SWT-01-03Y Low-Voltage Air Switches Apr-12 3-Year
ELEC-SWT-02-01Y Switches, Air, Medium-Voltage, Metal-Enclosed Apr-12 Annually
ELEC-SWT-02-03Y Switches, Air, Medium-Voltage, Metal-Enclosed Apr-12 3-Year
ELEC-SWT-03-01Y Medium- and High-Voltage Open Switches Apr-12 Annually
ELEC-SWT-03-03Y Medium- and High-Voltage Open Switches Apr-12 3-Year
ELEC-SWT-04-01M Medium-Voltage Oil Switches Apr-12 Monthly
ELEC-SWT-04-01Y Medium-Voltage Oil Switches Apr-12 Annually
ELEC-SWT-04-03Y Medium-Voltage Oil Switches Apr-12 3-Year
ELEC-SWT-05-01Y Medium-Voltage Vacuum Switches Apr-12 Annually
ELEC-SWT-05-03Y Medium-Voltage Vacuum Switches Apr-12 3-Year
ELEC-SWT-06-01Y Medium-Voltage SF6 Switches Apr-12 Annually
ELEC-SWT-06-03Y Medium-Voltage SF6 Switches Apr-12 3-Year
ELEC-SWT-07-01Y Cutouts Apr-12 Annually
ELEC-SWT-07-03Y Cutouts Apr-12 3-Year
ELEC-TRN-01-01Y Transformers, Dry-Type, Air-Cooled, Low-Voltage, Small Apr-12 Annually
ELEC-TRN-01-03Y Transformers, Dry-Type, Air-Cooled, Low-Voltage, Small Apr-12 3-Year
ELEC-TRN-02-01Y Transformers, Dry-Type, Air-Cooled, Large Apr-12 Annually
ELEC-TRN-02-03Y Transformers, Dry-Type, Air-Cooled, Large Apr-12 3-Year
ELEC-TRN-03-01M Transformers, Liquid-Filled Apr-12 Monthly
ELEC-TRN-03-01Y Transformers, Liquid-Filled Apr-12 Annually
ELEC-TRN-03-02Y Transformers, Liquid-Filled Apr-12 3-Year
ELEC-UPS-01-01M Uninterruptible Power System Apr-12 Monthly
ELEC-UPS-01-01Y Uninterruptible Power System Apr-12 Annually
ELEC-VFD-01-01Y Adjustable Speed Drive Systems Apr-12 Annually
ELEC-VFD-01-03Y Adjustable Speed Drive Systems Apr-12 3-Year
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
FIRE LIFE SAFETY
FLSF-ALM-01-01M Alarm Check Valves and Accessories Apr-12 Monthly
FLSF-ALM-01-05Y Alarm Check Valves and Accessories Apr-12 5-Year
FLSF-ALM-02-03M Fire Supervisory Signals, Testing Apr-12 Quarterly
FLSF-ALM-02-06M Fire Supervisory Signals, Testing Apr-12 Semi-annually
FLSF-ALM-03-01Y Automatic Fire Detection, Smoke Detectors Apr-12 Annually
FLSF-ALM-04-03M Automatic Fire Detection, Waterflow Alarms Apr-12 Quarterly
FLSF-ALM-05-01Y Automatic Fire Detection, Heat Detectors Apr-12 Annually
FLSF-ALM-06-06M Automatic Fire Detection, Operational Testing (per zone) Apr-12 Semi-annually
FLSF-ALM-07-01Y Fire Alarm Control Panel and Remote Annunciators Apr-12 Annually
FLSF-ALM-08-01Y Fire Alarm Control Panel, Special Systems (Halon, etc) Apr-12 Annually
FLSF-ALM-09-01Y Central Station, Transmitters Apr-12 Annually
FLSF-ALM-10-01D
Central Station, Receiver and Re-transmission
Equipment Apr-12 Daily
FLSF-ALM-11-01W Fire Alarm System, Recorder Apr-12 Weekly
FLSF-ALM-12-03M Fire Alarm System. Event Printer Apr-12 Quarterly
FLSF-ALM-13-01Y Fire Alarm System, Audio Control Panel Apr-12 Annually
FLSF-ALM-14-01Y Fire Alarm System, Remote Controller Apr-12 Annually
FLSF-ALM-15-01Y Fire Alarm System, Remote Amplifier Apr-12 Annually
FLSF-ALM-16-01Y Manual Fire Alarm Stations - Coded and Uncoded Apr-12 Annually
FLSF-ALM-17-01Y Fire Life Safety Fire Alarm Apr-12 Annually
FLSF-ALM-17-05Y Fire Life Safety Fire Alarm Apr-12 5-Year
FLSF-DOR-01-03M Fire Doors, Stairwells and Exitways, Swinging Apr-12 Quarterly
FLSF-DOR-02-03M Fire Doors, Sliding and Vertical Rolling Apr-12 Quarterly
FLSF-EPR-01-01Y Emergency Generator; Gasoline, or Natural Gas Engine Apr-12 Annually
FLSF-EPR-02-03M Emergency Generator, Diesel Engines Apr-12 Quarterly
FLSF-EPR-02-01Y Emergency Generator, Diesel Engines Apr-12 Annually
FLSF-EPR-03-01W Emergency Generator Apr-12 Weekly
FLSF-EPR-03-01M Emergency Generator Apr-12 Monthly
FLSF-EPR-03-03M Emergency Generator Apr-12 Quarterly
FLSF-EPR-03-06M Emergency Generator Apr-12 Semi-annually
FLSF-EPR-04-03M Emergency Pumps and Ventilators Apr-12 Quarterly
FLSF-EPR-04-01Y Emergency Pumps and Ventilators Apr-12 Annually
FLSF-EPR-05-06M Fuel Oil Filter/Strainer Apr-12 Semi-annually
FLSF-EPR-06-01Y Heater, Fuel Oil, Unit Apr-12 Annually
FLSF-EPR-07-01M Emergency Generator, Steam Driven Apr-12 Monthly
FLSF-EPR-07-01Y Emergency Generator, Steam Driven Apr-12 Annually
FLSF-EPR-08-01Y Load Bank Testing Apr-12 Annually
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
FLSF-EPR-08-03Y Load Bank Testing Apr-12 3-Year
FLSF-FEX-01-01M Fire Extinguisher, Inspection Apr-12 Monthly
FLSF-FEX-01-01Y Fire Extinguisher, Inspection Apr-12 Annually
FLSF-FEX-01-05Y Fire Extinguisher, Hydrostatic Testing Apr-12 5-Year
FLSF-FEX-01-12Y Fire Extinguisher, Hydrostatic Testing Apr-12 12-Year
FLSF-FEX-02-01Y Fire Extinguisher, Stored Pressure with Gauge Apr-12 Annually
FLSF-FEX-02-06Y
Fire Extinguisher, Stored Pressure with Gauge (Non
Stainless Steel Shell) Apr-12 6-Year
FLSF-FEX-03-01Y Fire Extinguishers - Non rechargeable Apr-12 Annually
FLSF-FEX-04-01Y Fire Extinguisher, Gas Cartridge or Cylinder (No Gauge) Apr-12 Annually
FLSF-FEX-05-01M Water Spray Extinguishing Systems Apr-12 Monthly
FLSF-FEX-05-01Y Water Spray Extinguishing Systems Apr-12 Annually
FLSF-FEX-06-01M
Fire Extinguisher System, Carbon Dioxide (High
Pressure), Halon, Dry Chemical - Inspection Apr-12 Monthly
FLSF-FEX-06-06M
Fire Extinguisher System, Carbon Dioxide (High
Pressure), Halon, Dry Chemical Apr-12 Semi-annually
FLSF-FSD-01-02Y Fire and Smoke Dampers Apr-12 2-Year
FLSF-FSP-01-01Y Sprinkler Head, Sprinklered Areas (per 1,000 sq. ft.) Apr-12 Annually
FLSF-FSP-02-01Y Antifreeze Solution in Sprinkler Systems Apr-12 Annually
FLSF-HSE-01-01M Fire Hose - 1.5 in., Racked in Buildings Apr-12 Monthly
FLSF-HSE-01-01Y Fire Hose - 1.5 in., Racked in Buildings Apr-12 Annually
FLSF-HSE-02-03M Fire Department Hose Connections (Standpipe Outlets) Apr-12 Quarterly
FLSF-HSE-02-05Y Fire Department Hose Connections (Standpipe Outlets) Apr-12 5-Year
FLSF-HSE-03-01M
Fire Department Pumper Connections, Standpipe or
Sprinkler Apr-12 Monthly
FLSF-HYD-01-05Y Fire Hydrant Flow Test - Dry Barrel and Wet Barrel Apr-12 5-Year
FLSF-PMP-01-01W Fire Pump, Diesel Engine Driven Apr-12 Weekly
FLSF-PMP-01-01M Fire Pump, Diesel Engine Driven Apr-12 Monthly
FLSF-PMP-01-03M Fire Pump, Diesel Engine Driven Apr-12 Quarterly
FLSF-PMP-01-01Y Fire Pump - Diesel Engine Driven Apr-12 Annually
FLSF-PMP-02-01W Fire Pump - Electric Motor Driven Apr-12 Weekly
FLSF-PMP-02-01M Fire Pump - Electric Motor Driven Apr-12 Monthly
FLSF-PMP-02-01Y Fire Pump - Electric Motor Driven Apr-12 Annually
FLSF-VLV-01-01W Dry Pipe, Deluge and Preaction Valves Apr-12 Weekly
FLSF-VLV-01-01M Dry Pipe, Deluge and Preaction Valves Apr-12 Monthly
FLSF-VLV-01-01Y Dry Pipe, Deluge and Preaction Valves Apr-12 Annually
FLSF-VLV-01-05Y
Dry Pipe, Deluge and Preaction Valves: Strainers, Filters and Orifices Apr-12 5-Year
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
FLSF-VLV-02-01M Post Indicator Valves Apr-12 Annually
FLSF-VLV-03-01W Fire Control Valves Apr-12 Weekly
FLSF-VLV-03-01M Fire Control Valves Apr-12 Monthly
FLSF-VLV-03-01Y Fire Control Valves Apr-12 Annually
FLSF-VLV-04-01Y Valves, Fire System - Pressure Regulating Type Apr-12 Annually
FLSF-VLV-04-05Y Valves, Fire System - Pressure Regulating Type Apr-12 5-Year
HEATING VENTILATION AND AIR CONDITIONING
HVAC-ACR-01-01M Air Conditioning Unit, Special Purpose Apr-12 Monthly
HVAC-ACR-02-01Y Heat Pumps, Water Cooled Apr-12 Annually
HVAC-ACR-03-01Y Air Conditioning Unit or Heat Pump, Split System Apr-12 Annually
HVAC-ACR-04-01Y Air Conditioning Unit, Ceiling/Wall Mounted Apr-12 Annually
HVAC-ACR-05-01Y Air-cooled Condenser Apr-12 Annually
HVAC-ACR-06-01Y Evaporative Condenser Apr-12 Annually
HVAC-AHU-01-01Y Built-Up AHU >5000 CFM Apr-12 Annually
HVAC-AHU-02-01Y Built-Up AHU <5000 CFM Apr-12 Annually
HVAC-AHU-03-01Y Built-Up AHU >5000 CFM Predictive Apr-12 Annually
HVAC-AHU-04-01Y Package AHU (includes DX, Heat Pumps, Gas Heat) Apr-12 Annually
HVAC-AHU-05-01Y Package AHU Predictive Apr-12 Annually
HVAC-AHU-06-01Y Air Washer or Wet Coil System Apr-12 Annually
HVAC-AHU-07-01Y Hot Air Furnace Apr-12 Annually
HVAC-AHU-08-01Y AHU UV Treatment System Apr-12 Annually
HVAC-AIR-01-06M Air Dryer, Refrigerated or Regenerative Desiccant Type Apr-12 Annually
HVAC-AIR-02-06M Air Compressor Apr-12 Semi-annually
HVAC-AIR-03-06M Glycol Dry Cooler, Special Purpose Apr-12 Semi-annually
HVAC-AIR-03-01Y Glycol Dry Cooler Apr-12 Annually
HVAC-AIR-04-06M After-Cooler/Separator Apr-12 Semi-annually
HVAC-BLR-01-01Y Boiler (Natural Gas and Oil Fired) Apr-12 Annually
HVAC-BLR-02-01Y Boiler, Electric Apr-12 Annually
HVAC-BLR-03-01Y Burner, Gas Apr-12 Annually
HVAC-BLR-04-01Y Burner, Oil Apr-12 Annually
HVAC-BLR-05-01Y Boiler, Instruments/Controls Apr-12 Annually
HVAC-BSB-01-02Y
Radiant Baseboards/Convectors (steam, hot water, or electric - per linear foot) Apr-12 2-Year
HVAC-CLR-01-03M Central Chilled Water Package Unit, Special Purpose Apr-12 Quarterly
HVAC-CLR-01-01Y Central Chilled Water Package Unit Apr-12 Annually
HVAC-CLR-02-01Y Refrigeration Machine, Screw and Scroll Apr-12 Annually
HVAC-CLR-03-01Y Refrigeration Machine, Centrifugal Apr-12 Annually
HVAC-CLR-04-01Y Refrigeration Machine, Absorption Unit Apr-12 Annually
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
HVAC-CLR-05-01Y Control Panel - Central Refrigeration Unit Apr-12 Annually
HVAC-CLR-06-01M Refrigerant Monitor Apr-12 Monthly
HVAC-CLR-07-01Y High Efficiency Purge Units Apr-12 Annually
HVAC-CLR-08-02Y Vibration Analysis, Chillers Apr-12 2-Year
HVAC-CLR-09-03Y Non-Destructive Tube Analysis (Eddy Current Analysis) Apr-12 3-Year
HVAC-CLS-01-01Y Coils, Preheat, Reheat, Etc. (Remote Locations) Apr-12 Annually
HVAC-CND-01-01M Condensing Unit, Refrigeration Apr-12 Monthly
HVAC-CND-01-01Y Condensing Unit, Refrigeration Apr-12 Annually
HVAC-DMP-01-01Y Motorized Dampers, Pneumatic or Electric Apr-12 Annually
HVAC-EVP-01-03M Indirect Evaporative Cooling Apr-12 Quarterly
HVAC-EVP-02-03M Direct Evaporative Cooling Apr-12 Quarterly
HVAC-EVP-03-03M Humidification Systems Apr-12 Quarterly
HVAC-FAN-01-01Y Fan, Centrifugal Apr-12 Annually
HVAC-FAN-02-01Y Fan, Propeller, 24 in. Diameter or Larger Apr-12 Annually
HVAC-FCU-01-03M Fan Coil Unit, Under Window Type Apr-12 Quarterly
HVAC-FLT-01-03M Filter, Throw Away Apr-12 Quarterly
HVAC-FLT-02-03M Filter, Roll Type, Disposable Media Apr-12 Quarterly
HVAC-FLT-02-01Y
Filter, Roll Type, Disposable Media, Manual or Motor
Driven Apr-12 Annually
HVAC-FLT-03-03M Filter, Electrostatic Apr-12 Quarterly
HVAC-FLT-04-03M Filters, Viscous Type (Wire Mesh) Apr-12 Quarterly
HVAC-FLT-05-03M Filter, Charcoal Apr-12 Quarterly
HVAC-HXR-01-01Y Plate and Frame Heat Exchanger Apr-12 Annually
HVAC-PMP-01-01Y Pump, Centrifugal Apr-12 Annually
HVAC-PMP-02-01Y Pump, Vacuum Apr-12 Annually
HVAC-STM-01-01Y Condensate or Vacuum Pump Apr-12 Annually
HVAC-TAB-01-01Y Test and Balance Apr-12 Annually
HVAC-TMU-01-01Y Terminal Units, Pneumatic or Electric Apr-12 Annually
HVAC-TMU-02-03M Terminal Units, DDC Only, Predictive Apr-12 Quarterly
HVAC-TWR-01-03M Cooling Tower, Cleaning Apr-12 Quarterly
HVAC-TWR-01-01Y Cooling Tower, Maintenance Apr-12 Annually
HVAC-UHT-01-01Y Unit Heater (Steam and Hot Water) Apr-12 Annually
HVAC-UHT-02-01Y Unit Heater (Gas and Oil Fired) Apr-12 Annually
HVAC-VLV-01-01Y Valve, Motor Operated (DDC) Apr-12 Annually
HVAC-WTM-01-01M Water Treatment Guide Apr-12 Monthly
HVAC-WTM-03-06M Chemical Feeder Apr-12 Semi-annually
HVAC-WTM-04-03M Water Treatment, Chemical Free Apr-12 Quarterly
HVAC-WTM-04-01Y Water Treatment, Chemical Free Apr-12 Annually
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
KITCHEN
KTCH-DSH-01-03M Dishwashing Machine Apr-12 Quarterly
KTCH-FRY-01-03M Fryer Apr-12 Quarterly
KTCH-GRL-01-3M Grill Apr-12 Quarterly
KTCH-ICM-01-03M Ice Cream & Shake Maker Apr-12 Quarterly
KTCH-ICE-01-06M Ice Maker Apr-12 Semi-annually
KTCH-KTL-01-06M Kettle Apr-12 Semi-annually
KTCH-OVN-01-03M Oven Apr-12 Quarterly
KTCH-OVN-01-06M Oven Apr-12 Semi-annually
KTCH-RNG-01-03M Range Apr-12 Quarterly
KTCH-RNG-01-06M Range Apr-12 Semi-annually
MATERIAL
HANDLING
MHDL-CRN-01-03M Crane, Electric Apr-12 Quarterly
MHDL-DMW-01-03M Dumbwaiter Apr-12 Quarterly
MHDL-HST-01-01Y Chain Hoist and Trolley Apr-12 Annually
MHDL-HST-02-01Y Hoist, Electric Apr-12 Annually
MHDL-HST-03-01Y Hoist, Lighting Apr-12 Annually
MHDL-LFT-01-06M Lift, Electric, Stage Screen Apr-12 Semi-annually
MHDL-LFT-02-01M Material Handling Equipment Electric Lift Trucks Apr-12 Monthly
MHDL-LFT-02-01Y Material Handling Equipment Electric Lift Trucks Apr-12 Annually
MHDL-LFT-03-03M Loading Ramp, Adjustable Apr-12 Quarterly
MHDL-PPB-01-01Y Paper Baler Apr-12 Annually
MHDL-VHL-01-06M Material Handling Equipment, Engine Driven Vehicles Apr-12 Semi-annually
MHDL-VHL-02-01Y Carts and Scooters, Engine or Battery Powered Apr-12 Annually
PLUMBING
PLMB-DRN-01-01Y Roof Drains, Downspout, and Gutter Inspection Apr-12 Annually
PLMB-DRN-02-01Y Drains, Areaway, Driveway, Storm Apr-12 Annually
PLMB-DWS-01-01Y Hot Water Heater, Gas Apr-12 Annually
PLMB-DWS-02-01Y Hot Water Heater, Electric Apr-12 Annually
PLMB-DWS-03-01Y Hot Water Heater, Steam Coil Apr-12 Annually
PLMB-DWS-04-06M Water Softener Apr-12 Semi-annually
PLMB-DWS-05-06M Water Filter Apr-12 Semi-annually
PLMB-DWV-01-01Y Sewage Ejector (Pneumatic Tank Type Ejectors) Apr-12 Annually
PLMB-DWV-02-01Y Sewage ejector, Sump Type Apr-12 Annually
PLMB-DWV-03-01Y Sump Pump Apr-12 Annually
PLMB-DWV-04-01W Emergency Wash Apr-12 Weekly
PLMB-DWV-05-01Y Emergency Shower Apr-12 Annually
MAINTENANCE TIME STANDARDS
Office of Real Property
Management and Safety
Guide # Equipment Item Effective
Date Frequency
PLMB-DWV-06-01Y Septic Tank and Drain Field Apr-12 Annually
PLMB-HWS-01-01Y Hot Water Converter, Steam Apr-12 Annually
PLMB-HWS-02-06M Solar Heating System Apr-12 Semi-annually
PLMB-HWS-02-01Y Solar Heating System Apr-12 Annually
PLMB-PLB-01-01Y Expansion Joints in Piping Apr-12 Annually
PLMB-PLB-02-01Y Strainer, Y-Type Apr-12 Annually
PLMB-PLB-03-01Y Strainer, Bolted Flange (water and steam) Apr-12 Annually
PLMB-PLB-04-01Y Dual Strainer Apr-12 Annually
PLMB-PLB-05-01Y Backwash Strainer Apr-12 Annually
PLMB-PLB-06-01Y Steam Traps, All Types high pressure Apr-12 Annually
PLMB-PLB-06-05Y Steam Traps, All Types low pressure Apr-12 5-Year
PLMB-PLB-07-01Y Distiller, Water, Laboratory use only Apr-12 Annually
PLMB-VLV-01-01M Valve, Safety Relief Apr-12 Monthly
PLMB-VLV-02-01Y Valve Regulating Apr-12 Annually
PLMB-VLV-03-01Y Valve, Manually Operated Apr-12 Annually
PLMB-VLV-04-01Y Valve, Critical Check Apr-12 Annually
PLMB-VLV-05-01Y Backflow Preventer Apr-12 Annually
TANKS
TANK-AGS-01-01Y Tank, Air/Refrigerant/LP Gas Apr-12 Annually
TANK-CHM-01-01Y Tank, Chemical Apr-12 Annually
TANK-FOL-01-04Y Tank, Fuel Oil Storage Apr-12 4-Year
TANK-UST-01-01M Underground Storage Tank (UST) Apr-12 Anually
TANK-WTR-01-03Y Tank, Water (All Types) Apr-12 3-Year
VERTICAL TRANSPORTATION
VTRN-ELV-01-06M Elevator, Hydraulic, Inspection 4 floors or less. Apr-12 Semi-annually
VTRN-ELV-01-01Y Elevator, Hydraulic, Inspection 4 floors or less. Apr-12 Annually
VTRN-ELV-02-01Y Elevator, Electric, Inspection 4 floors or less. Apr-12 Annually
VTRN-ELV-02-05Y Elevator, Electric, Inspection 4 floors or less. Apr-12 5-Year
VTRN-ELV-03-01W Elevator, Electric or Hydraulic 4 floors or less. Apr-12 Weekly
VTRN-ELV-03-01M Elevator, Electric or Hydraulic 4 floors or less. Apr-12 Monthly
VTRN-ELV-03-03M Elevator, Electric or Hydraulic Apr-12 Quarterly
VTRN-ESC-01-01W Escalator Apr-12 Weekly
VTRN-ESC-01-01Y Escalator (and Moving Walkway) Apr-12 Annually
VTRN-WLF-01-01M Wheelchair Lift Apr-12 Monthly
Section 2
Preventative Maintenance Guides
ARCS-BAR-01-06M Frequency: Semi-annually Security Bollards/Barricade
Application:
This guide card applies to automatic hydraulic security Bollards/Barricades found at driveway entrances, and other areas where vehicular traffic must be controlled.
Special Instructions:
1. Preventive maintenance services should be performed by a qualified manufacturer's service representative.
2. Review manufacturer's instructions.
3. Review the Standard Operating Procedure for "Controlling Hazardous
Energy Sources".
4. De-energize, lock out, and tag electrical circuits.
5. This work should be scheduled at non-peak hours.
6. Notify affected personnel before performing PM (alarmed or security entrances).
7. Post "out of service" signs and/or barricades, as appropriate.
Check points:
1. Check that Bollards/Barricade extend to full height.
1. Check that Bollards/Barricade retract to full depth.
2. Check Bollards/Barricade for exterior damage.
3. Check and clean sump pits and pump.
4. Check that Bollards/Barricade fasteners are tight.
5. Check Bollard/Barricade safeties (proximity, Photo, infra red, pressure etc)
6. Check Bollard/Barricade activation devices for proper operation
(auto/manual/emergency)
7. Check Bollard operation under no power.
8. Inspect electrical power panel.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .