Q A 5.pdf

PDF 11 KB Posted

Attached to
Solicitation Re-issue NO CHANGE FROM PREVIOUS Federal contract opportunity
Solicitation number
GS01P12BWD0050
Issued by
General Services Administration Public Buildings Service Region 1

About this file

Final Q A

View the file

Other files for this federal contract opportunity

Other files attached to Solicitation Re-issue NO CHANGE FROM PREVIOUS, newest first.
File Type Posted
FormSF30.pdf PDF
Q A 4.pdf PDF
Q A 3.pdf PDF
Amendment 0004.pdf PDF
Questions 2.pdf PDF
FormSF30.pdf PDF
FormSF30.pdf PDF
FormSF30.pdf PDF
Call in Number.docx DOCX document
Per-Proposal Conf Notice.pdf PDF
SOLICITATION COMP .pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GSA New England Region

U.S. General Services Administration Thomas P. O'Neill, Jr. Federal Building 10 Causeway Street Boston, MA 02222 www.gsa.gov

7 June 2012

Solicitation GS-01P-12-BW-D-0050

JANITORIAL AND MECHANICAL MAINTENANCE SERVICES AT 9 LAND PORTS OF ENTRY

(LPOE) THROUGHOUT NORTHERN MAINE

Question and Answer 07 June 2012

Q 27: During the site visit, it was put out that all fire and life safety systems and equipment inspections must be performed by NICET II certified technicians. As a result, the nationally recognized subcontractor we have contacted are interpreting what was put out during the site visit to mean that this extended all the way down to weekly visual inspection of sprinkler components and backflows, monthly inspections of fire extinguishers, monthly emergency light inspection, monthly fire pump procedures, etc.

This results in an exorbitant cost to GSA.

Please clarify that the expectation for NICET II Technician is for Quarterly, Semiannual, Annual, 3 and 5 year services, and that the weekly and monthly services such as exercising the fire pump, visual inspection of sprinkler heads, fire doors, dampers, and fire extinguisher monthly inspection can be performed by onsite mechanics who do not need to be NICET II level certified.

A: The NICET Level II standard essentially just ensures that the person performing work has a minimum of 2 years experience these systems as well as having passed tests to prove knowledge of applicable NFPA codes pertaining to fire sprinklers and or fire alarm systems. We do want the technician performing this maintenance to have this certification since it is essentially requiring the technician to have achieved a "journeyman" type level in the field.

Fire doors, dampers, and extinguishers are neither fire alarm system equipment, nor fire sprinkler system equipment and would therefore not be subject to the NICET II requirement. The fire pump and fire sprinkler would be, as they are part of the fire alarm and fire sprinkler systems.