This document is an Asbestos NESHAP (National Emissions Standards for Hazardous Air Pollutants) Inspection Report prepared by Asbestos Abatement Incorporated (AAI) for the Michigan State Police, focused on the Grass Lake East Bound Scale facility located at 12500 I-94 in Grass Lake, Michigan. The inspection was conducted on February 13, 2018, to comply with Michigan Occupational Safety and Health Administration (MIOSHA) Asbestos and Lead Standards. The report provides a comprehensive assessment of potential asbestos-containing materials (ACM) and lead-containing paints throughout the facility, including a detailed inventory of 32 distinct suspect materials across various building areas such as the first floor, addition, basement, attic, restrooms, and exterior.

The laboratory analysis by QuanTEM Laboratories revealed that no sampled materials contained asbestos, though certain materials like 6" x 6" ceramic floor tile, grout, bedding compound, roofing materials, and mirror adhesive were assumed to contain asbestos and require careful handling. Lead testing by GPI Laboratories found two paint samples with lead content: gray floor paint at 0.20% and black paint on structural steel at 0.083%. The report recommends a comprehensive Asbestos NESHAP and lead-paint inspection prior to any demolition or renovation, with specific guidance on regulatory compliance, hazard communication, and employee training. The document emphasizes that while a good faith effort was made to identify potential hazardous materials, hidden or concealed materials may exist and should be treated with caution.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2420 N. Grand River Ave.

Lansing, Michigan 48906 www.asbestosabatementinc.com Ph. 517-323-0050 Fax 517-323-7382

April 8, 2018

Michigan State Police Attn: Mr. Paul Akeo PO Box 30634 Lansing MI 48909

Re: Asbestos and Lead Paint Inspection Report Grass Lake East Bound Scale, 12500 I-94, Grass Lake, MI

Dear Mr. Paul Akeo:

Asbestos Abatement Incorporated, (AAI) was retained by the Michigan State Police to conduct an asbestos and lead paint inspection at the Grass Lake East Bound Scale, 12500 I-94, Grass Lake, MI. The asbestos inspection was requested to comply with the Michigan Occupational Safety and Health Administration (MIOSHA) Asbestos for General Industry Standard and the Asbestos Standards for Construction. Additionally, paint samples were collected and analyzed for lead to comply with the MIOSHA Lead in General Industry and Lead Exposure in Construction Standards.

This report includes the procedures and methodologies, analytical laboratory results and any applicable conclusions and recommendations made during the course of this inspection. This report must be provided to the following persons who work within this weigh station: 1) State of Michigan employees, 2) Employers of employees who perform housekeeping activities, 3) Prospective employers who are applying or bidding for work, 4) On multi-employer worksites, all employers of employees, and 5) Tenants who will occupy the building.

While a good faith effort was made to identify all ACM and PACM during this inspection, as the building was not scheduled for demolition or renovation, hidden, concealed or missed materials may exist within the building. If any materials not sampled as part of this survey are discovered, the material should be assumed to contain asbestos and, if necessary, immediately stop work and notify AAI so that additional testing and/or necessary clean-up can be performed. Additionally, prior to demolition or renovation, a comprehensive inspection in accordance with the Asbestos National Emissions Standards for Hazardous Air Pollutants (NESHAP) Standard is required. An Asbestos NESHAP inspection includes destructive testing to find hidden or concealed materials, such as those present in pipe chases and wall cavities.

Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition

2420 N. Grand River Ave.

Lansing, Michigan 48906 www.asbestosabatementinc.com Ph. 517-323-0050 Fax 517-323-7382 to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.

AAI appreciates the opportunity to perform these services for you and look forward to working with you in the future. In the meantime, if you have questions or comments regarding the information in this report or if we can be of further assistance please do not hesitate to contact AAI at 517-323-0050.

Sincerely, Asbestos Abatement Inc.

Mr. Jeff Suty Asbestos Inspector Accreditation #A32393

ASBESTOS AND LEAD PAINT INSPECTION REPORT

Conducted at:

Grass Lake East Bound Scale, 12500 I-94

Grass Lake, MI

AAI Project Number: 1019

Date of Inspection:

February 13, 2018

Report prepared for:

Michigan State Police Mr. Paul Akeo PO Box 30634 Lansing MI 48909

Inspection conducted by:

Mr. Jeff Suty, Accreditation #A32393 Asbestos Abatement Inc.

2420 N. Grand River Ave.

Lansing, Michigan 48906 Phone: 517-323-0052 Fax: 517-323-7382

ASBESTOS NESHAP INSPECTION REPORT

AAI Project Number: 1019

TABLE OF CONTENTS

1.0 Introduction

2.0 Certification

3.0 Inspection Procedures

4.0 Analytical Results

5.0 Pertinent Observations

6.0 Regulatory Guidance

7.0 Recommendations

8.0 APPENDICES

APPENDIX A – DEFINITIONS & CLASSIFICATIONS

APPENDIX B – INSPECTOR(S) CREDENTIALS

APPENDIX C – LABORATORY CERTIFICATION

APPENDIX D – INSPECTION DATA

APPENDIX E – ANALYTICAL DATA

Asbestos NESHAP Inspection Report

P a g e | 1

1.0 Introduction

Asbestos Abatement Incorporated, (AAI) was retained by the Michigan State Police to conduct an asbestos and lead paint inspection at Grass Lake East Bound Scale, 12500 I-94, Grass Lake, MI.

The asbestos inspection was requested to comply with the Michigan Occupational Safety and Health Administration (MIOSHA) Asbestos for General Industry Standard and the Asbestos Standards for Construction. Additionally, paint samples were collected and analyzed for lead to comply with the MIOSHA Lead in General Industry and Lead Exposure in Construction Standards. The on-site portion of asbestos and lead paint building inspection took place on February 13, 2018. Definitions and Classification explanations for select terms can be found in Appendix A.

Asbestos

During the inspection, good faith effort was made to identify the presence, location and quantity of all accessible ACM and PACM. However, as the building was not scheduled for demolition or renovation, AAI was not retained to conduct destructive testing. A such, hidden, concealed or missed materials may exist within the building. Destructive testing (i.e., and Asbestos NESHAP inspection) must be conducted prior to demolition or renovation to find all hidden, concealed or missed materials.

Lead

Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.

2.0 Certification

Asbestos

The asbestos inspection was conducted by Mr. Jeff Suty, a State of Michigan Accredited Asbestos Inspector. A copy of his inspector credentials appears in Appendix B.

All of the collected asbestos bulk samples were submitted to QuanTEM Laboratories for analysis.

Bulk samples of suspect asbestos-containing materials were analyzed by polarized-light microscopy (PLM) using the EPA Method 600/R-93/116. QuanTEM Laboratories is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP). A copy of their NVLAP Accreditation can be found in Appendix C.

P a g e | 2

Lead

Paint chip samples were also collected by Mr. Suty and were submitted to GPI Laboratories, Inc.

for total lead analysis. GPI Laboratories, Inc. is accredited by the National Lead Laboratory Accreditation Program (NLLAP). A copy of their NLLAP Accreditation can be found in Appendix C.

3.0 Inspection Procedures

Asbestos

This asbestos inspection was conducted to determine the presence, location and quantity of all accessible ACM and PACM in accordance with the requirements of the MIOSHA Asbestos for General Industry Standard and the MIOSHA Asbestos Standards for Construction. The inspection consisted of a thorough visual inspection of all functional spaces within the building and all exterior areas on the building for suspect ACM. Additionally, representative bulk sampling was conducted of most materials to determine whether the material is proven ACM or non-ACM.

Materials visibly identified as non-asbestos (metal, glass, wood, etc.) by the accredited inspector were not sampled.

Prior to collecting any samples, suspect ACMs were identified as homogenous areas (HAs) to develop a sampling strategy. A homogenous area is defined as an area of surfacing material, thermal system insulation, or miscellaneous material that is uniform in color and texture (e.g., exterior white window caulk).

The actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and the professional judgment of the inspector. A minimum of two samples of each HA were collected and submitted to an accredited laboratory for analysis by PLM. The number of samples collected for each material identified was determined according to the following table:

Guidelines for Determining the Number of Samples Collected HA Category HA Size Samples Required

Miscellaneous Materials No Stipulation 2

Thermal Systems Insulation No Stipulation 3

Surfacing Material

< 1,000 SQ. FT 3

1,000 – 5,000 SQ. FT 5

> 5,000 SQ. FT 7

P a g e | 3

Determined by the visual inspection, a total of 32 distinct suspect ACMs were identified during this inspection. A complete list of all suspect ACMs identified, including analytical results, friability, location, and estimated quantities can be found in Appendix D.

Lead

Identification and testing of suspect lead-containing paint was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Paint samples were collected in a manner to minimize substrate dilution. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted. A complete list of all sampled paints, including analytical results, can be found in Appendix D.

4.0 Analytical Results

Asbestos

A material is considered to be ACM when it contains greater than 1% asbestos. Such materials must be handled according to Federal, State and local regulations. For homogenous areas with multiple samples collected, only one sample with greater than 1% asbestos is required for the entire homogenous area to be considered ACM.

For friable materials, when the amount of asbestos in the sample material is reported as “None- Detected” by routine PLM analysis, no further verification of the sample results by Point Counting Methodology is recommended.

For friable materials, when the amount of asbestos in the sample material is reported at less than 10% by PLM analysis, the client may either assume the amount to be greater than 1% and treat the material as ACM or request further verification of the asbestos content by Point Counting Methods.

If the result obtained by Point Counting is different from the result obtained by routine PLM analysis, the Point Count Method result should be used.

For non-friable materials, when the amount of asbestos in the sample material is reported at greater than 1% by PLM analysis, no further verification of the sample results by alternative methods of identification is required.

The QuanTEM Laboratories PLM analytical report, including detailed information on individual sample layers, can be found in Appendix E.

P a g e | 4

No sampled suspect materials were determined to contain asbestos.

The following identified suspect ACMs were not sampled and are assumed to contain asbestos:

6” x 6” gray with white specks ceramic floor tile Grout with 6” x 6” gray with white specks ceramic floor tile Bedding compound under 6” x 6” gray with white specks ceramic floor tile Roofing materials (e.g., caulks) Mirror adhesive

The following identified materials were determined to not contain asbestos:

Cinderblock Cinderblock mortar Concrete floor 4" gray cove molding and mastic Glazed wall brick, yellow Mortar with glazed wall brick, yellow Drywall Drywall joint compound 1' x 1' ceiling tile with gouges and holes and glue pods Drywall above 1' x 1' ceiling tile with gouges and holes and glue pods Interior window caulk, gray, pliable Interior door caulk, cream, pliable Yellow carpet mastic 12" floor tile under carpet and brown tile mastic Wall brick Wall brick mortar Office window and door glazing, gray Old roof tar paper/debris Tan adhesive residue Building caulk, white, pliable White sink undercoating 1' x 1' white ceiling tile with large and small holes and glue pods Stair tread and mastic Duct mastic, yellow Building caulk, white (basement) Exterior gray window caulk Exterior black window glazing

P a g e | 5

A paint is considered lead-containing if any amount of lead is detected in the submitted sample.

The GPI Laboratories, Inc. analytical report can be found in Appendix E.

The following paints were determined to contain lead:

Gray paint on floor Black paint on structural steel

5.0 Pertinent Observations

During the visual inspection, select observations were made and documented. With the inspection procedures and analytical results taken into consideration, the pertinent observations are as follows:

All quantities listed in the Building Inventory Data form (Appendix D) are estimates and its accuracy is not guaranteed.

6.0 Regulatory Guidance

This section offers regulatory guidance for ACM and lead-containing paint identified during this inspection and does not guarantee compliance with all regulatory requirements. Please refer to the applicable asbestos and/or lead regulation(s) or contact AAI for project-specific regulatory requirements.

Asbestos

This report must be maintained throughout the life of this building, and to comply with the MIOSHA asbestos hazard communication requirements, this report must be provided to the following persons who work within this weigh station:

State of Michigan employees, Employers of employees who perform housekeeping activities, Prospective employers who are applying or bidding for work, On multi-employer worksites, all employers of employees, and Tenants who will occupy the building.

Mechanical rooms/areas in which ACM is present must have signs at the entrance which identify the ACM materials which are present, its location, and appropriate work practices which, if followed, will ensure that ACM and/or PACM will not be disturbed.

Asbestos awareness training (or Class IV training) is required for the following employees:

P a g e | 6

Employees who are likely to be exposed to airborne concentrations of asbestos at or above the permissible exposure limit and/or excursion limit.

Employees who perform Class I and II work (e.g., asbestos removal).

Employees who perform Class III work (e.g., repair and maintenance operations, where

"ACM", including TSI and surfacing ACM and PACM, is likely to be disturbed).

Employees who perform Class IV work (maintenance and custodial activities during which employees contact but do not disturb ACM or PACM and activities to clean up dust, waste and debris resulting from Class I, II, and III activities).

Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.

Known lead hazards should be communicated as required by the MIOSHA Hazard Communication standard and any real estate transaction laws. Additionally, State of Michigan employees shall be informed of the contents of Appendices A and B to 29 C.F.R. §1910.1025 ‘Lead.’

Lead awareness training is required for the following employees who are subject to exposure to lead at or above the action level, or for whom the possibility of skin or eye irritation exists.

This report shall not be used as a compliance tool. It is the responsibility of all employers of employees working within this to comply with all applicable laws and regulations.

This guidance is based on the visual inspection, analytical results, pertinent observations and AAI’s understanding of the project. This guidance may require modification should there be a change in building ownership, use and/or during demolition or renovation.

7.0 Recommendations

Based on the visual inspection (including pertinent observations), and the bulk sample analytical data, the following recommendations are offered:

Prior to establishing a project budget (including contractors submitting bids), verify quantities listed in the Building Inventory Data form (Appendix D) as they are estimates and accuracy is not guaranteed.

Utilize Section 6.0 as a guide for regulatory compliance including, but not limited to:

hazard communication and training. Refer to the appropriate regulation(s) for additional requirements and/or contact AAI for assistance.

P a g e | 2

Prior to demolition or renovation, conduct a comprehensive Asbestos NESHAP and lead-paint inspection to identify any hidden, concealed or missed suspect asbestos materials and suspect lead-containing paints.

APPENDIX A

DEFINITIONS & CLASSIFICATIONS

Asbestos Definitions and Classifications ACM (Asbestos Containing Material) – Commercial asbestos product containing more than 1% asbestos.

ACM must be disposed as regulated waste. Note: Federal OSHA and Cal-OSHA control materials containing any amount of asbestos.

ACBM (Asbestos Containing Building Material) – AHERA/ASHARA term for material containing more than 1% asbestos in or on interior structural members or other structural components. Includes covered walkways, porticos and exterior HVAC TSI.

ACCM (Asbestos Containing Construction Material) – California term for a manufactured construction material containing greater than .1% (one tenth of one percent) asbestos.

PACM (Presumed Asbestos Containing Material) OSHA considers all TSI and surfacing materials installed prior to1980 to be ACM unless proven otherwise.

Friable Asbestos Containing Material that can be crumbled pulverized or reduced to powder by hand pressure when dry.

NOA Naturally Occurring Asbestos. CARB defines as having >.25% by point counting.

ACM CARB term for naturally occurring asbestos >.25% by point counting DACM Designated Asbestos Containing Material: Floor tile installed before 1981

Categories of Asbestos Used BY EPA AHERA/ASHARA and OSHA/Cal-OSHA TSI (Thermal System Insulation) - “Thermal system insulation (TSI)” means ACM applied to pipes, fittings, boilers, breeching, tanks, ducts or other structural components to prevent heat loss or gain. “Thermal system insulation ACM” is thermal system insulation which contains more than 1% asbestos.

SURFACING

(usually mixed on site at time of application)

“Surfacing material” means material that is sprayed, troweled-on or otherwise applied to surfaces (such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, and other purposes).

“Surfacing ACM” means surfacing material which contains more than 1% asbestos. NOTE:

OSHA/Cal-OSHA do not classify skim coat, taping mud, floor tile mastic, stucco, leveling compound, and hard wall plasters or wall texturing as surfacing.

MISC. All other ACM, including classify taping mud, floor tile mastic, stucco, leveling compound, and hard wall plasters or wall texturing as surfacing.

NESHAPS Categories for Asbestos (Used by Air Quality Management Districts for Renovation and Demolition)

Category I Cat I Non-friable Asbestos Containing Material(ACM) refers to asbestos containing packing, gaskets, resilient floor covering, Galbestos, and asphalt roofing products containing more than 1% asbestos.

Category II Cat II Non-friable Asbestos-Containing Material (ACM) is any material that is not Cat I that contains greater than 1% asbestos.

RACM “Regulated Asbestos-Containing Material.” – Friable manufactured asbestos material (ACM) or a Category I non-friable ACM that has become friable OR a Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting or abrading OR Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations. RACM should be removed prior to renovation or demolition.

APPENDIX B

INSPECTOR(S) CREDENTIALS

APPENDIX C

LABORATORY CERTIFICATION

APPENDIX D

INSPECTION DATA

Asbestos Inspection Data Grass Lake East Bound Scale, 12500 I-94, Grass Lake, MI

HA # HA Description Friable ACM Quantity/Location

1 Cinderblock No No

1,650 SF

Throughout

2 Cinderblock mortar No No

825 SF

Throughout

6” x 6” gray with white specks ceramic floor tile No No

350 SF

1st Floor

Grout with 6” x 6” gray with white specks ceramic floor tile

No Assumed

175 SF

1st Floor

Bedding compound under

6” x 6” gray with white specks ceramic floor tile

No Assumed

350 SF

1st Floor

6 Concrete floor Yes Assumed

1,519 SF

Throughout

4" gray cove molding and mastic No No

45 SF

1st Floor

8 Glazed wall brick, yellow No No

750 SF

1st Floor

Mortar associated with glazed wall brick, yellow No No

375 SF

1st Floor

10 Drywall No No

88 SF

1st Floor

11 Drywall joint compound No No

44 SF

1st Floor 12 Reserved N/A N/A N/A

1' x 1' ceiling tile with gouges and holes and glue pods

Yes No 1,000 LF 1st Floor

Drywall above 1' x 1' ceiling tile with gouges and holes and glue pods

No No

1,000 SF

1st Floor

15 Mirror adhesive No Assumed

8 SF

Restrooms

Interior window caulk, gray, pliable No No

12 SF

Throughout

Interior door caulk, cream, pliable No No

16 SF

Throughout

18 Yellow carpet mastic No No

500 SF

Addition

12" floor tile under carpet and brown tile mastic No No

500 SF

Addition

20 Wall brick No No

200 SF

1st Floor

21 Wall brick mortar No No

100 SF

1st Floor

Office window and door glazing, gray No No

2 SF

Addition

23 Old roof tar paper/debris Yes No

10 SF

Attic

24 Tan adhesive residue No No

1 SF

Restroom

Roofing materials (e.g., caulks) No Assumed

1,600 SF

Exterior

Building caulk, white, pliable No No

4 SF

Restrooms/Kitchen

27 White sink undercoating No No

1SF

Kitchen

1' x 1' white ceiling tile with large and small holes and glue pods

Yes No

60 SF

Stairs

29 Stair tread and mastic No No

10 SF

Stairs

30 Duct mastic, yellow No No

20 SF

Basement

Building caulk, white

(basement) No No

20 SF

Basement

32 Reserved N/A N/A N/A

33 Exterior gray window caulk No No

10 SF

Exterior

Exterior black window glazing No No

10 SF

Exterior

Lead Paint Chip Sample Log Grass Lake East Bound Scale, 12500 I-94, Grass Lake, MI

HA # HA Description Lead Content 1 Gray floor paint 0.2%

1 Black on steel 0.083%

APPENDIX E

ANALYTICAL DATA

Date Received: 03/19/2018

Project: Grass Lake Scale - East Bound

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

001 1-1 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Cement

Gray

002 1-2 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Cement

Gray

003 2-1 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

004 2-2 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

005 6-1 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Concrete

Gray

006 6-2 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Concrete

Gray

007 7-1 Layered CaCO3

Vinyl

Asbestos Not Present NA

Cove Base

Gray

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

007a Layered GlueAsbestos Not Present NA

Mastic

Yellow

008 7-2 Layered CaCO3

Vinyl

Asbestos Not Present NA

Cove Base

Gray

008a Layered GlueAsbestos Not Present NA

Mastic

White

009 8-1 Homogeneous Clay

Sand

Asbestos Not Present NA

Brick

Yellow

010 8-2 Homogeneous Clay

Sand

Asbestos Not Present NA

Brick

Yellow

011 9-1 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

012 9-2 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

013 10-1 Homogeneous GypsumAsbestos Not Present 15Cellulose

Sheetrock

White

014 10-2 Homogeneous GypsumAsbestos Not Present 15Cellulose

Sheetrock

White

015 11-1 Homogeneous CaCO3Asbestos Not Present NA

Joint Compound

White

016 11-2 Homogeneous CaCO3Asbestos Not Present NA

Joint Compound

White

017 13-1 Homogeneous Perlite

Paint

Asbestos Not Present 50

Cellulose

Glass FiberCeiling Tile

White

018 13-2 Homogeneous Perlite

Paint

Asbestos Not Present 50

Cellulose

Glass FiberCeiling Tile

White

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

019 14-1 Homogeneous GypsumAsbestos Not Present 15Cellulose

Sheetrock

White

020 14-2 Homogeneous GypsumAsbestos Not Present 15Cellulose

Sheetrock

White

021 16-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Gray

022 16-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Gray

023 17-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Cream

024 17-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Cream

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

025 18-1 Homogeneous Glue

CaCO3

Asbestos Not Present NA

Carpet Mastic

Yellow

026 18-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Carpet Mastic

Yellow

027 19-1 Layered CaCO3

Vinyl

Asbestos Not Present NA

Floor Tile

Tan

027a Layered GlueAsbestos Not Present NA

Mastic

Brown

028 19-2 Layered CaCO3

Vinyl

Asbestos Not Present NA

Floor Tile

Tan

028a Layered GlueAsbestos Not Present NA

Mastic

Brown

029 20-1 Homogeneous Clay

Sand

Asbestos Not Present NA

Brick

Red

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

030 20-2 Homogeneous Clay

Sand

Asbestos Not Present NA

Brick

Gray

031 21-1 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

032 21-2 Homogeneous CaCO3

Sand

Asbestos Not Present NA

Mortar

Gray

033 22-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Window Glazing

Gray

034 22-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Window Glazing

Gray

035 23-1 Homogeneous TarAsbestos Not Present 70Cellulose

Tar Paper

Black

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

036 23-2 Homogeneous TarAsbestos Not Present 70Cellulose

Tar Paper

Black

037 24-1 Homogeneous CaCO3

Glue

Asbestos Not Present NA

Adhesive

Tan

038 24-2 Homogeneous CaCO3

Glue

Asbestos Not Present NA

Adhesive

Tan

039 26-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

White

040 26-2 ** ** Not Analyzed

No Sample in Container

041 27-1 Homogeneous CaCO3

Gypsum

Asbestos Not Present 15Cellulose

Sink Undercoat

White

042 27-2 Homogeneous CaCO3

Gypsum

Asbestos Not Present 15Cellulose

Sink Undercoat

White

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

043 28-1 Homogeneous PaintAsbestos Not Present 90Cellulose

Ceiling Tile

White

044 28-2 Homogeneous PaintAsbestos Not Present 90Cellulose

Ceiling Tile

White

045 29-1 Layered VinylAsbestos Not Present NA

Stair Tread

Black

045a Layered Glue

CaCO3

Asbestos Not Present NA

Mastic

White

046 29-2 Layered VinylAsbestos Not Present NA

Stair Tread

Black

046a Layered Glue

CaCO3

Asbestos Not Present NA

Mastic

White

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

047 30-1 Homogeneous Glue

CaCO3

Asbestos Not Present NA

Mastic

Yellow

048 30-2 Layered Asbestos Not Present 100Glass Fiber

Insulation

Pink

048a Layered Glue

CaCO3

Asbestos Not Present NA

Mastic

Yellow

049 31-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

White

050 31-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

White

051 33-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Gray

052 33-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Caulk

Gray

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

QuanTEM Lab No. 292095

Analyzed By: Dee Ammerman

Methodology: EPA/600/R-93/116

Polarized Light Microscopy Asbestos Analysis Report

Project Location: NA

Project Number: NA

Account Number: C008

Received By: Amber Bassett

Date Analyzed: 03/30/2018

QuanTEM

Sample ID

Client

Sample ID Composition

Color /

Description Asbestos (%)

Non-Asbestos

Fiber (%)

Client: Asbestos Abatement, Inc.

2420 N. Grand River

Lansing, MI 48906

Non Fibrous

053 34-1 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Window Glazing

Black

054 34-2 Homogeneous CaCO3

Binder

Asbestos Not Present NA

Window Glazing

Black

Date of Report

3/30/2018

Dee Ammerman, Analyst

QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.

ANALYTICAL LABORATORY REPORT Friday, March 23, 2018 Page 1 of 2

CUSTOMER: Asbestos Abatement, Inc

2420 N Grand River

Lansing, MI 48906

DATE RECEIVED: Tuesday, March 20, 2018

PO/PROJECT #:

SUBMITTAL #: 2018-03-20-008

LAB NUMBER: AC51170

Sampled By: Jeff Suty

Job Location: Grass Lake Scale

Sample Identification: P-1: Gray

Date Sampled: February 13, 2018

Sample Description: Paint Chips

Preparation Method: EPA 3050B-P-M (Acid Digestion for Paints)

Analysis Method: EPA 6010C-M (ICP-AES Method for Determination of Metals)

Date Analyzed: Thursday, March 22, 2018

ELEMENT RESULT (by dry weight)

REPORTING

LIMIT (RL)

Lead 0.20 % 0.0025 %

LAB NUMBER: AC51171

Sampled By: Jeff Suty

Job Location: Grass Lake Scale

Sample Identification: P-2: Black

Date Sampled: February 13, 2018

Sample Description: Paint Chips

Preparation Method: EPA 3050B-P-M (Acid Digestion for Paints)

Analysis Method: EPA 6010C-M (ICP-AES Method for Determination of Metals)

Date Analyzed: Thursday, March 22, 2018

ELEMENT RESULT (by dry weight)

REPORTING

LIMIT (RL)

Lead 0.083 % 0.0036 %

GPI Laboratories, Inc. has obtained accreditation under the programs detailed on the final page of the laboratory report. The accreditations pertain only to the testing performed for the elements, and in accordance with the test methods, listed in the scope of accreditation table. Testing which is performed by GPI

Laboratories, Inc. according to other test methods, or for elements which are not included in the table fall outside of the current scope of laboratory accreditation.

This report shall not be reproduced except in full, without written approval of GPI Laboratories, Inc..

4403 Donker CT SE · Grand Rapids, MI 49512-4054 · (616) 940-3112 · www.gpinet.com

ANALYTICAL LABORATORY REPORT Friday, March 23, 2018 Page 2 of 2

CUSTOMER: Asbestos Abatement, Inc

2420 N Grand River

Lansing, MI 48906

DATE RECEIVED: Tuesday, March 20, 2018

PO/PROJECT #:

SUBMITTAL #: 2018-03-20-008

Tests Reviewed By: Michael J. Swiech, Technical Manager

Unless otherwise noted, the condition of each sample was acceptable upon receipt, all laboratory quality control requirements were met, and sample results have not been adjusted based on field blank or other analytical blank results. Individual sample results relate only to the sample as received by the laboratory.

Reporting Limit (RL): The lowest concentration of analyte in a sample that can be reported with a defined, reproducible level of certainty. This value is based on the lowest standard used for instrument calibration and must be at least twice the MDL.

GPI Laboratories, Inc. has obtained accreditation under the following programs:

· National Lead Laboratory Accreditation Program (NLLAP)

AIHA-LAP: Environmental Lead Laboratory Accreditation Program (ELLAP), Laboratory ID#101030 ( www.aihaaccreditedlabs.org)

· OH: Ohio Department of Health Lead Poisoning Prevention Program, Approval #E10013 ( www.odh.ohio.gov)

· AIHA-LAP: Industrial Hygiene Laboratory Accreditation Program (IHLAP) , Laboratory ID#101030 (www.aihaaccreditedlabs.org)

· National Environmental Laboratory Accreditation Program (NELAP)

NY: State of New York Department of Health, Laboratory ID#11609 (Serial # 56089, 56973-56975, & 57314) (518-485-5570)

LA: State of Louisiana Department of Environmental Quality, Laboratory ID#180321 (Certificate 05036) ( www.deq.louisiana.gov)

OK: Oklahoma Department of Environmental Quality, Laboratory ID#9993 (Certificate 2017-067) ( www.deq.state.ok.us)

Testing which is performed by GPI Laboratories, Inc. according to test methods, or for elements which are not included in the table below fall outside of the current scope of laboratory accreditation. Customers are encouraged to verify the current accreditation status with the individual accreditation programs by calling or visiting the appropriate website for the applicable program.

SCOPE OF ACCREDITATION

Air and Emissions

Element/Test Method Accreditation(s)

Suspended Particulates: PM10 / TSP 40 CFR 50 Appendix J / 40 CFR 50 Appendix B NY, LA

Lead in Airborne Dust 40 CFR 50 Appendix G ELLAP, IHLAP, LA

Lead in Airborne Dust NIOSH 7300 ELLAP, OH, NY, LA

Lead in Airborne Dust EPA 600/R-93/200/ EPA 6010C ELLAP, OH

Metals in Airborne Dust EPA 600/R-93/200/ NIOSH 7300/ EPA 6010C IHLAP

Solid Chemical Materials

Element/Test Method Accreditation(s)

TCLP EPA 1311(Sample Preparation Method) NY, LA, OK

Lead in Soil EPA 3050B/ EPA 6010C ELLAP, OH, NY, LA, OK

Lead in Paint EPA 3050B/ EPA 6010C ELLAP, OH, NY, LA

Lead in Paint ASTM D 3335-85A/ EPA 6010C NY

Lead in Dust Wipes EPA 3050B/ EPA 6010C NY, LA

Lead in Dust Wipes EPA 600/R-93/200/ EPA 6010C ELLAP, OH

Ignitability EPA 1010A NY

Non-Potable Water / Analysis by ICP Solid Chemical Materials

Element/Test Method Accreditation(s) Method Accreditation(s)

Arsenic EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Barium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Cadmium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Chromium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Copper EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Lead EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Mercury EPA 245.1 Rev.3/ EPA 7470A NY, LA, OK EPA 7471B NY, LA, OK

Nickel EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Selenium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Silver EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Zinc EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK

Cobalt ---- ---- EPA 6010C NY, LA, OK

Manganese ---- ---- EPA 6010C NY, LA, OK

Acid Digestion EPA 3010A NY, LA EPA 3050B NY, LA

This report shall not be reproduced except in full, without written approval of GPI Laboratories, Inc..

4403 Donker CT SE · Grand Rapids, MI 49512-4054 · (616) 940-3112 · www.gpinet.com

Grass Lake - East Bound word.pdf
292095_C008_PLM_With_COC.pdf
2018-03-20-008.pdf
2018-03-20-008.pdf
2018-03-20-008c
2018-03-23T15:17:38-0400
Michael Swiech

File details come from the government source that posted it. Updated .