GenCom project drawings.pdf

PDF 3 MB Posted

Attached to
Radio Communications Cabinet Installation
Solicitation number
23-BM34
Issued by
Dane County, Wisconsin

About this file

GenCom Project Drawings Summary

This is a set of project drawings for an equipment cabinet installation project for Sun Prairie Police Department at a site located at 991 N Bird Street in Sun Prairie, Wisconsin. The project involves the installation of an outdoor radio equipment cabinet (81" H x 30" W x 34" D, NEMA 4 rated, 5G-LTE capable) on a concrete pad at the existing water tower compound. The cabinet will house a 26 RU radio compartment, battery compartment, 8-space 100A load center, 4000 BTU HVAC unit, and weatherproof aluminum construction with a 15-year warranty and 550 lbs weight capacity. The project includes associated site preparation, utility infrastructure installation, electrical service upgrades to 100A 120/240V single-phase service, grounding system installation, underground conduit runs, and concrete pad foundation work. The site is located on a parcel under Sun Prairie Utilities ownership (Parcel ID: 081105287006) in a Neighborhood Commercial (NC) zoning classification at ground elevation 1014' NAVD 88.

The drawings were prepared by Edge Consulting Engineers, Inc. (624 Water Street, Prairie du Sac, WI 53578) under the direction of Professional Engineer Arlen Ostreng and submitted on November 8, 2022. The project drawings include comprehensive details for site preparation with 4,000 PSI concrete foundations meeting ACI standards, grounding system design with copper conductors and exothermic connections meeting Harris manual guidelines with a 3 ohm or less resistance requirement, electrical utility plans with underground SCH 80 PVC conduits, and transmission line grounding throughout the facility. General Communications, Inc. serves as the technology consultant, Sun Prairie Utilities is the owner, and Rick Wicklund (Utility Manager) and Gary Pelletier serve as primary project contacts. The contractor is responsible for field verification of existing underground utilities, soil conditions, precise anchor spacing, bearing capacity confirmation, and coordination with electrical service providers prior to excavation.

View the file

Other files

File Type Posted
23-BM34_Notice of Intent to Award Letter.pdf PDF
23-BM34 QA.pdf PDF
Bid Opening Log_Typed.pdf PDF
RFB 23-BM34 Radio Communications Cabinet.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ G

-0 .d g n

35241

G-001

T

IT

L E

S H

E E

T

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

SITE LOCATION

NORTH

ENGINEER SEAL:

EQUIPMENT CABINET INSTALLATION

SUN PRAIRIE, WISCONSIN

SUN PRAIRIE POLICE (BIRD STREET WT)

NORTH

SITE LOCATION

COMMERCIAL

ZONING CLASSIFICATION: (NC) NEIGHBORHOOD

PARCEL ID: 081105287006

ASR NUMBER: N/A

GROUND ELEVATION (NAVD 88): 1014'

LONG (NAD83/2011): 89°-13'-31.1" W (-89.225306)

LAT (NAD83/2011): 43°-11'-36.0" N (43.193333)

TOWER COORDINATES (PER PREVIOUS DRAWINGS:

SUN PRAIRIE, WI 53590

125 W. MAIN STREET

SUN PRAIRIE UTILITIES

PROPERTY OWNER:

SUN PRAIRIE, WI 53590

991 N BIRD ST

SITE ADDRESS:

PROJECT INFO

PHONE: (608) 960-4047 EXT. 231

CONTACT: RICK WICKLUND, UTILITY MANAGER

SUN PRAIRIE, WI 53590

125 W. MAIN STREET

SUN PRAIRIE UTILITIES

ELECTRICAL SERVICE PROVIDER:

PHONE: (608) 310-7122

CONTACT: GARY PELLETIER

MADISON, WI 53719

2880 COMMERCE PARK DR

GENERAL COMMUNICATIONS, INC.

TECHNOLOGY CONSULTANT:

PHONE: (608) 960-4047 EXT. 231

CONTACT: RICK WICKLUND, UTILITY MANAGER

SUN PRAIRIE, WI 53590

125 W. MAIN STREET

SUN PRAIRIE UTILITIES

OWNER:

PHONE: (608) 644-1449

CONTACT: ARLEN OSTRENG, PE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

EDGE CONSULTING ENGINEERS, INC.

ENGINEER:

PROJECT DIRECTORY

AJO

UTILITY RACK DETAILSE-505

UTILITY DETAILSE-504

GROUNDING DETAILSE-502

GROUNDING DETAILSE-501

UTILITY PLANE-102

GROUNDING PLANE-101

OUTDOOR EQUIPMENT CABINET DETAILSA-101

SITE DETAILSC-501

COMPOUND PLANC-102

OVERALL SITE PLANC-101

TITLE SHEETG-001

SHEET TITLENO.:

SHEET INDEX

UNDER THE LAWS OF THE STATE OF WISCONSIN.

A DULY LICENSED PROFESSIONAL ENGINEER

NOTED IN THE SHEET INDEX, AND THAT I AM

SUPERVISION OTHER THAN THE EXCEPTIONS

PREPARED BY ME OR UNDER MY DIRECT

I HEREBY CERTIFY THAT THIS PLAN SET WAS

DATE:

SIGNATURE:

LLAC ENO

L A

N

OI

T

ANRETNI

S M

E T

S Y

S

3 WORK DAYS NOTICE BEFORE YOU EXCAVATE

WI STATUTE 182.0175 (1974) REQUIRES MIN. OF

FAX A LOCATE: 1-800-242-5811

TOLL FREE: 1-800-242-8511

WISCONSIN, CALL DIGGERS HOTLINE

UNDERGROUND FACILITIES BEFORE YOU DIG IN

TO OBTAIN LOCATION OF PARTICIPANTS'

© 2022 Microsoft Corporation © 2022 Maxar ©CNES (2022) Distribution Airbus DS

C-101

NORTH

O V

E R

A L

L S

IT

E

P L

A N

PROJECT. ALL PROPERTY LINES SHOWN ARE APPROXIMATE.

NO PROPERTY SURVEY WAS PERFORMED AS PART OF THIS 3.

AERIAL IMAGERY PER BING MAPS.2.

NORTH ARROW SHOWN AS APPROXIMATE.1.

GENERAL NOTES: (THIS SHEET)

CABINET ON CONCRETE PAD

OUTDOOR RADIO EQUIPMENTA.

KEYNOTES: (THIS SHEET)

010' 10'

10'22" x 34" - 1" =

20'11" x 17" - 1" = SCALE:

20'

ATHLETIC WAY

N B

IR

D S

T

OWNER: WATER & LIGHT COMM

PARCEL #: 081105287006

APPROX. PROPERTY LINE

APPROX. PROPERTY LINE

A

SWING ACCESS GATE

EXISTING 16' WIDE DOUBLE-

EQUIPMENT SHELTER

EXISTING VERIZON

EQUIPMENT SHELTER

EXISTING U.S. CELLULAR

EXISTING WATER TOWER

TOWER LADDER

(NOT PART OF THIS PROJECT)

TO BE REMOVED

EXISTING EQUIPMENT SHELTER

1351063

WISCONSIN GAS CO.

EXISTING GAS METER;

EXISTING GENERATOR

SERIAL #: 29540669

SUN PRAIRIE UTILITIES

EXISTING SINGLE ELECTRIC METER

EXISTING POWER POLE

EXISTING POWER POLE

(TYP.)

TRANSFORMER

EXISTING

FIBER VAULT

EXISTING

SUBSTATION

ELECTRIC

UTILITY PROVIDER TO VERIFY SOURCE

PROPOSED ELECTRIC SERVICE;

#3034

EXISTING TRANSFORMER

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ C

-1

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

BUILDING

EXISTINGBUILDING

EXISTING

SHELTER

EQUIPMENT

EXISTING

GENERATOR

EXISTING

SHELTER

EQUIPMENT

EXISTING

C-102

C O

M P

O U

N D

P L

A N

NORTH

AT NEW CABINET LOCATION.

CONDUIT AND INSTALL NEW FITTINGS TO CREATE STUB-UP

CONTRACTOR TO LOCATE EXISTING UNDERGROUND PVC C.

SEE E-505 FOR DETAILS

SINGLE METER UTILITY RACK;B.

SEE C-501 & A-101 FOR DETAILS

CABINET ON CONCRETE PAD;

OUTDOOR RADIO EQUIPMENTA.

NORTH ARROW SHOWN AS APPROXIMATE.1.

GENERAL NOTES: (THIS SHEET)

KEYNOTES: (THIS SHEET)

02.5' 2.5'

22" x 34" - 1" = 2.5'

11" x 17" - 1" = 5'SCALE:

5'

TOWER LEG

TOWER LADDER

ROUTING UNDERGROUND

EXISTING PVC CABLE CONDUIT

EXISTING OVERFLOW PIPE

GRASS

ASPHALT

EXISTING WATER TOWER

UNDERGROUND COAX ROUTE

EXISTING VERIZON

CONTRACTOR TO VERIFY

COAX CONDUIT;

EXISTING UNDERGROUND

APPROXIMATE ROUTE OF

A PROPOSED EQUIPMENT LOCATION

A

B

A

PROPOSED ELECTRIC SERVICE

UNDERGROUND COAX CONDUIT

APPROXIMATE ROUTE OF EXISTING

CABINET ON CONCRETE PAD

OUTDOOR RADIO EQUIPMENT

C

UTILITY VAULT

EXISTING

EXISTING FIBER VAULT

'-6

'-6

5'-0"3'-2"

'-0

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ C

-1

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

M

IN

M

IN

MIN.

D O

O R

S

ID

E

D O

O R

S

ID

E

SECTION

PLAN VIEW

CONTRACTOR TO FIELD VERIFY ANCHOR HOLE SPACING WITH CABINET DIMENSIONS6.

USE 2” FENDER WASHER, LOCK WASHER AND SECURE WITH 3”X ½”LAG BOLTS5.

PLACE ENCLOSURE ON PAD WITH ALIGNMENT OF HOLES4.

USING A HAMMER, LIGHTLY TAP 3” LAG SLEEVE INTO HOLE UNTIL FLUSH WITH PAD SURFACE3.

CLEAN HOLES OF DEBRIS2.

DRILL (4) HOLES 3”DEEP, DIA 0.875”(7/8) PER DRILL PATTERN IN CONCRETE PAD1.

RECOMMENDED PROCEDURE FOR PAD MOUNTING (PER MFG SPECS):

C-501

LIVE LOAD, ETC.). CONTRACTOR TO VERIFY EXACT SHELTER SIZE AND TYPE.

FOUNDATION DESIGN BASED ON INFORMATION PROVIDED BY SHELTER MFG. (WEIGHT, 9.

CONTRACTOR TO ENSURE POSITIVE DRAINAGE FROM ALL FOUNDATIONS.8.

UNDERCUT DEPTH.

FOOTING FOR EVERY FOOT IN DEPTH. CONSULT WITH ENGINEER FOR REQUIRED

REPLACED WITH 3-INCH BREAKER STONE. UNDERCUT ONE FOOT ON EACH SIDE OF THE

SOILS NOT MEETING THE DESIGN BEARING STRENGTH SHALL BE UNDERCUT AND 7.

THESE CONDITIONS BEFORE INSTALLATION.

AND MAX. PLASTICITY INDEX OF 20, CONTRACTOR TO CONFIRM BEARING SOILS MEET

FOUNDATION DESIGN BASED ON A PRESUMPTIVE SOIL BEARING CAPACITY OF 2000 PSF 6.

AND CONSTRUCTION CONSIDERATIONS.

CONSULT GEOTECHNICAL INVESTIGATION REPORT FOR ANTICIPATED SOIL CONDITIONS 5.

FOOTPRINT. DO NOT UTILIZE THESE SOILS FOR BACKFILL.

REMOVE ALL ORGANIC MATERIAL, SOFT AND/OR UNSUITABLE SOILS WITHIN FOUNDATION 4.

ACCORDANCE WITH ACI STANDARDS

ALL CONCRETE REINFORCING SHALL BE ASTM A615 GRADE 60 AND PLACED IN 3.

ADDED AFTER SLUMP HAS BEEN MEASURED.

CONTRACTOR TO PERFORM CONCRETE SLUMP TEST (4" MAX SLUMP). NO WATER TO BE

EXTERIOR CONCRETE TO BE AIR ENTRAINED WITH 6% +/- 1% AIR CONTENT.

SHALL ACHIEVE A 28-DAY COMPRESSIVE STRENGTH (f’c) OF 4,000 PSI. EXPOSED

ALL CONCRETE UNLESS SPECIFICALLY NOTED SHALL BE NORMAL WEIGHT(145 PCF) AND 2.

REQUIREMENTS AND MOST CURRENT VERSION OF ACI STANDARDS.

ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH LOCAL BUILDING CODE 1.

CONCRETE AND REINFORCING NOTES:

A

CONCRETE PAD - OUTDOOR CABINET PAD MOUNT DETAIL

3/4" CHAMFER

GEOTEXTILE WEED BARRIER

COMPACTED SUBGRADE

COMPOUND FINISH AGGREGATE

COMPACT TO 90% MODIFIED PROCTOR

6" OF 3/4" CRUSHED AGGREGATE

A .G

.L

#4 VERT. HOOPS @ 18" O.C.

3" 3"

3"

(MAINTAIN 3" OF COVER IN ALL DIRECTIONS)

(3) AT TOP & (3) AT BOTTOM

(6) - #4 HORIZ. BARS FULL LENGTH

UTILITY STUB-UP BOX

ALL REBAR SHALL MAINTAIN 3" OF COVER IN ALL DIRECTIONS3.

FINISH: MEDIUM BROOM.2.

CONCRETE MIX TO BE 4,000 PSI @ 28 DAYS.1.

NOTES:

3'-6"

DRILLED ANCHOR HOLES

/4

(V E

R

IF

Y

"4

36" (VERIFY)2

12'-4"4

S

IT

E D

E T

A

IL

S

T H

IS

S

PA

C E I N T E N T

IO

N A

LL

Y L

E

FT

B

LA

N

K

T H

IS

S

PA

C E I N T E N T

IO

N A

LL

Y L

E

FT

B

LA

N

K

T H

IS

S

PA

C E I N T E N T

IO

N A

LL

Y L

E

FT

B

LA

N

K

4"

4"

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ C

-5 .d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

SEE SITE PLAN FOR SIZE REQUIREMENTS

B

E L

O W

G R

A D

E

A-101

KEYNOTES: (THIS SHEET)

GENERAL NOTES: (THIS SHEET)

B

BATTERY COMPARTMENT

(26) RU RAILS

HVAC UNIT

UNLIMITED

AND REQUIREMENTS. ORDER CABLE ENTRY FROM DDB

ENTRY OPENING INTO CABINET WALL. VERIFY PORT SIZING

CONTRACTOR TO FIELD CUT TRANSMISSION LINE CABLE A.

A

T

A L

L

30"

RADIO COMPARTMENT

O U

T D

O O

R E

Q U

IP

M

E N

T C

A B

IN

E

T D

E T

A

IL

S

C

43.0"

.6

UTILITY STUB-UP BOX

GENERATOR PLUG

8 SPACE

100A LOAD CENTER

4000 BTU HVAC

INTERIOR ELECTRICAL OUTLET

WEATHERPROOF ALUMINUM CABINET

15 YEARWARRANTY:

550 LBS (BARE CABINET)WEIGHT:

81”H x 30”W x 34”D (26 RU)DIMENSIONS:

5G-LTE (NEMA 4)MODEL:

DDB UNLIMITED

CABINET DRAWINGS PROVIDED BY:1.

C

C D

D

SECTION C - C SECTION D - D

OUTDOOR CABINET - PLAN VIEW

A

OUTDOOR CABINET - ISOMETRIC VIEW

OUTDOOR CABINET - ELEVATION VIEWS

A

A

B

B

SECTION A - A SECTION B - B

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ A

-1 .d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

E-101

G R

O U

N D

IN

G

P L

A N

KEYNOTES: (THIS SHEET)

RADIO CABINET ENCLOSURE GROUND, (1) LEADH.

GROUND TEST WELL; SEE DETAIL C/E-502 FOR DETAILSG.

(2) LEADS

EQUIPMENT GROUND RING TO TOWER STEEL,F.

A/C METER BOX GROUND E.

UTILITY POST GROUND; SEE E-501 FOR DETAILSD.

SEE DETAIL F/E-502

(1) LEAD TO EQUIPMENT GROUND RING;

INTERIOR CABINET GROUND BAR (MGB),C.

(1) TO TOWER STEEL; SEE DETAIL D/E-501

(2) LEADS TO EQUIPMENT GROUND RING &

LOWER TOWER GROUND RF BAR,B.

FROM PAD FOUNDATION

EQUIPMENT GROUND RING, MAINTAIN 2' SEPARATIONA.

NORTH

GROUNDING LEGEND: (THIS SHEET)

SPRAYED WITH COLD GALVANIZING COMPOUND TO PREVENT CORROSION.

ALL ABOVE GRADE CADWELD CONNECTIONS (TO GALVANIZED ITEMS) SHALL BE 7.

CONNECTIONS. SELF-TAPPING SCREWS ARE NOT ALLOWED.

LUG & CONNECTION POINT. USE COPPER ANTI-OXIDANT FOR COPPER-TO-COPPER

STAINLESS-STEEL HARDWARE. PROVIDE ANTI-OXIDANT COMPOUND BETWEEN

ALL MECHANICAL GROUND CONNECTIONS TO UTILIZE 2-HOLE LUGS AND 6.

REFER TO GEOTECH REPORT FOR SOIL CONDITIONS.

OVER TOWER FOUNDATION OR WHERE DRIVING GROUND RODS IS NOT FEASIBLE.

INSTALL 18"X18" COPPER PLATES IN LIEU OF GROUND RODS WHEN INSTALLING 5.

GRADE. (SEE DETAIL A/E-501)

GROUND RINGS & TOP OF RODS SHALL BE INSTALLED AT 30" BELOW FINISHED 4.

ENCASED IN 1/2" PVC & SEALED WITH SILICONE.

ALL NON-INSULATED GROUND LEADS EXTENDING ABOVE GROUND LEVEL SHALL BE 3.

UPON COMPLETION.

PRIOR TO BACKFILLING. SYSTEM SHALL PROVIDE 3 OHM OR LESS RESISTANCE

RS SHALL BE TESTED BY CONTRACTOR THE GROUNDING SYSTEM & CONDUCTO2.

MANUAL AE/LZT 123 4618/1 REV F (JUNE 2017).

GROUNDING AND LIGHTNING PROTECTION GUIDELINES. REFER TO INSTALLATION

ALL EXTERIOR GROUNDING SHALL MEET OR EXCEED THE CURRENT HARRIS SITE . 1

GENERAL NOTES: (THIS SHEET)

01' 1'

1'22" x 34" - 1" =

2'11" x 17" - 1" = SCALE:

2'

A

B

C

D

D

E

F

F

G

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-1

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

IN ENHANCED GROUND TRENCH, SEE E-502 FOR DETAILS

#2 AWG BARE SOLID TINNED COPPER CONDUCTOR

IN STANDARD GROUND TRENCH, SEE E-502 FOR DETAILS

#2 AWG BARE SOLID TINNED COPPER CONDUCTOR

(BURNDY 2-HOLE LUG OR APPROVED EQUAL)

MECHANICAL CONNECTION

(CADWELD OR HYGROUND)

EXOTHERMIC OR UL RATED IRREVERSIBLE CONNECTION

SPACE @ 2X GOUND ROD LENGTH (20' O.C. MAX., 6' MIN.)

COPPER PLATE, (18" x 18" x 0.032" THK)

SPACE @ 2X GOUND ROD LENGTH (20' O.C. MAX., 6' MIN.)

COPPER CLAD GROUND ROD, (5/8" DIA. x 10' LONG)

GROUND TEST WELL, SEE E-502 FOR DETAILS

E-102

U T

IL

IT

Y P

L A

N

KEYNOTES: (THIS SHEET)

COORDINATE INSTALLATION WITH UTILITY PROVIDER

SEE C-101 FOR APPROXIMATE ROUTE;

(1) 1.25" CODUIT (RNMC);

SINGLE ELECTRIC METER UTILITY RACK.

100A 120/240V 1P SECONDARY ELECTRIC SERVICE TO F.

SEE E-505 FOR DETAILS

CONTRACTOR;

SINGLE ELECTRIC METER UTILITY RACK INSTALLED BY E.

COORDINATE INSTALLATION WITH UTILITY PROVIDER

INSTALLED BY CONTRACTOR;

EQUIPMENT RADIO CABINET. (1) 1.25" CONDUIT (RNMC)

100A 120/240V 1P ELECTRIC SERVICE TO OUTDOOR D.

THROUGH "UTILITY STUB-UP BOX"

UTILITY CONDUIT STUB-UP(S) TO ENTER CABINETC.

8 SLOT 100A LOAD CENTER BUILT INTO RADIO CABINETB.

OUTDOOR RADIO EQUIPMENT CABINETA.

NORTH

SEE E-503 FOR CONDUIT INSTALLATION REQUIREMENTS.13.

CONDUITS.

RGS). COMPRESSION FITTINGS ARE REQUIRED FOR EMT

ALL INDOOR EXPOSED CONDUIT TO BE METALLIC (EMT OR 12.

PROVIDE PULL STRINGS IN ALL CONDUITS.11.

IDENTIFIED AND LABELED.

ALL CONDUIT STUBS IN BUILDINGS & PULL BOXES TO BE 10.

DISTRIBUTION PANEL WITHIN EQUIPMENT BUILDING.

CONDUITS FROM EXTERIOR ELECTRICAL ITEMS TO

PROVIDE AND INSTALL ALL NECESSARY WIRING AND 9.

MEET OR EXCEED THE SPEC.

MFR. BY OTHERS ARE EQUALLY ACCEPTABLE PROVIDED THEY

USED FOR QUALITY AND PERFORMANCE ONLY. EQUIPMENT

REFERENCE MANUFACTURER AND CATALOG NUMBERS ARE 8.

JOINT.

GRADE CONDUIT STUB UPS TO BE SCH 80 PVC WITH SLIP

RUNS TO BE RIGID GALVANIZED STEEL (RGS). ALL BELOW

ALL OUTDOOR ABOVE GRADE EXPOSED ELECTRICAL CONDUIT 7.

PROVIDER.

SCH. 80 PVC UNLESS OTHERWISE REQUIRED BY THE UTILITY

ALL UNDERGROUND ELECTRICAL & TELCO CONDUITS TO BE 6.

ALL CONDUCTORS TO BE COPPER.5.

COMPACTION AND AGGREGATE INSTALLATION.

NSTALLATION TO BE COMPLETED PRIOR TO FINAL SUBGRADE I

ALL UNDERGROUND TRENCHING, PIPE AND CONDUIT4.

AND LOCAL CODES.

ALL ELECTRICAL WORK SHALL CONFORM TO NATIONAL, STATE, 3.

LOCAL REQUIREMENTS.

ALL UTILITIES SHALL BE INSTALLED ACCORDING TO STATE AND 2.

SIZES OF ALL EXISTING UTILITIES.

CONTRACTOR SHALL FIELD VERIFY DEPTHS, LOCATIONS, & 1.

GENERAL NOTES: (THIS SHEET)

01' 1'

1'22" x 34" - 1" =

2'11" x 17" - 1" = SCALE:

2'

A B

C

D

E

F

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-1

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

CABINET

EQUIPMENT

E-501

G R

O U

N D

IN

G

D E

T A

IL

S

KEYNOTES: (THIS SHEET)

RADIO CABINET ENCLOSURE GROUND, (1) LEADN.

(2) LEADS

EQUIPMENT GROUND RING TO TOWER STEEL;M.

A/C METER BOX GROUNDL.

SEE E-502 FOR DETAILS

TO 24" BELOW GRADE;

#2 BARE SOLID TINNED ENCASE IN CARFLEX CONDUIT

UTILITY RACK POST GROUND;K.

(1) LEAD TO EQUIPMENT GROUND RING

INTERIOR RADIO CABINET GROUND BAR (MGB);J.

STEEL.

HANGERS OR ANGLE ADAPTERS CONNECTED TO TOWER

GRADE. SUPPORT ALONG TOWER LEG WITH COAX SNAP-IN

CONDUIT TO BE SUPPORTED EVERY +/- 30-INCHES TO

AND FROM LOWER TGB TO TOWER STEEL (1) REQ'D;

FROM LOWER TGB TO EQUIPMENT GROUND RING (2) REQ'D

#2 BARE SOLID TINNED ENCASED IN CARFLEX CONDUIT

LOWER TGB GROUNDS;I.

ICE BRIDGE)

LEADS INSTALL ON TOWER WITH INSULATORS AT 12" (ABOVE

DIAGONALLY FOR EASIER HOOK-UP OF GROUNDING KIT

- SIZED FOR (30) 2 HOLE GROUND LUGS MOUNT "4

4" x 18" x

LOWER TOWER GROUND RF BAR (TGB) (TINNED);H.

#2 BARE SOLID TINNED

MAINTAIN 2' SEPARATION FROM PAD FOUNDATION;

EQUIPMENT GROUND RING;G.

- PAINT WITH COLD GALV. COMPOUND AFTER BONDING.

- USE EXTERNAL ANTI-OXIDATION COMPOUND.

BONDING PLATE

- HARGER #223T HEAVY DUTY TINNED FLANGE

OR

1-1/4" TO 2" DIA. ROUND MEMBERS

- HARGER BGC41.25-2 PIPE CLAMPS FOR

UL LISTED BONDING CLAMP;F.

TOWER STEEL WITH UL LISTED BONDING CLAMP

GROUND BAR CONNECT GROUND KIT JUMPER DIRECTLY TO

FOR SINGLE ANTENNAS AT ONE LEVEL OMIT ANTENNA E.

STEEL

INSTALL #2 STRANDED LEAD FROM GROUND BAR TO TOWER

LEVEL MOUNT TO TOWER STEEL;

FOR CONNECTION OF MULTIPLE GROUND KITS AT ONE

ANTENNA GROUND BAR (TINNED);D.

CONNECT TO GROUND BAR WITH 2 HOLE LONG BARREL LUG

GROUND KIT JUMPER;C.

SEE DETAIL THIS SHEET

COAX / WAVEGUIDE TRANSMISSION LINE GROUND KIT;B.

PIPE TO BE MECHANICALLY CONNECTED TO TOWER STEEL

MECHANICALLY FASTEN AIR TERMINAL TO MAST PIPE MAST

EXTEND 2' ABOVE HIGHEST ANTENNA MIN. ON MAST PIPE

AIR TERMINAL;A.

MEMBERS

FOR FLANGE

#223T

MAST PIPE

AIR TERMINAL

MOUNT

ANTENNA

ANTENNA

COAX OR WAVEGUIDE

A

B

C

ED

F

A

ANTENNA LEVEL GROUNDING

MEMBERS

FOR ROUND

#BGC41.25-2

TOWER STEEL

GROUND KIT ASSEMBLY

FROM GROUND BAR TO TOWER STEEL

#2 STRANDED INSULATED LEAD

BETWEEN LUGS AND GROUND BAR

INSTALL ANTI-OXIDANT COMPOUND

HOLE COMPRESSION LUGS;

CONNECT TO GROUND BAR W/ 2

#6 STRANDED INSULATED JUMPER

(HARGER #213T, #223T OR EQUIV.)

BONDING CLAMP CONNECTOR

UL LISTED CABLE TO FLAT METAL

SEE NOTE #2

AT REQUIRED MOUNTING ELEVATION

MOUNT DIAGONALLY BELOW GROUND KITS

TINNED COPPER GROUND BAR

CONNECT GROUND KIT DIRECTLY TO TOWER STEEL WITH UL LISTED BONDING CLAMP.

MULTIPLE ANTENNAS AT EACH LEVEL. WHEN ONLY ONE ANTENNA IS INSTALLED AT A LEVEL,

INSTALL ANTENNA GROUND BARS AT EACH ANTENNA TIER LEVEL FOR CONNECTION OF 2.

D. EQUIPMENT BUILDING ENTRY

C. TOWER BASE

B. AT 75 FOOT MAX INTERVALS FROM ANTENNA LEVEL TO BASE OF TOWER

A. ANTENNA / DISH LEVEL

INSTALL GROUND KITS ON EACH TRANSMISSION LINE IN THE FOLLOWING LOCATIONS:1.

NOTES:

COAX/WAVEGUIDE TRANSMISSION LINE

C

TRANSMISSION LINE GROUNDING

FINISHED GRADE

REQUIREMENTS UP THE TOWER

TRANSMISSION LINE GROUNDING

SEE DETAIL THIS SHEET FOR

LEG

TOWER

EXISTING

B

SITE LEVEL GROUNDING

K

B C

I

I

H

D

LOWER TOWER GROUNDING

H

I

I

G

J

L

M

M

N

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-5

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

T H

IS

D

E T A

IL

N

O T A

P P L

IC

A B L E

T H

IS

D

E

TA

IL

N

O T A

P P L

IC

A B L

E-502

G R

O U

N D

IN

G

D E

T A

IL

S

D

FENCE GATE GROUNDING

SWINGING GATE FRAME

FIXED GATE FRAME

SILICONE ON BOTH ENDS

BELOW GRADE; SEAL WITH

NON-METALLIC CONDUIT TO 24"

ENCASED IN LIQUID-TIGHT FLEXIBLE

#2 SOLID TINNED COPPER LEAD

SITE GROUND SYSTEM

EXOTHERMIC CONNECTION

HARGER # GJX2S24 OR APPROVED EQUAL

TYPICAL AT EACH GATE;

#2 SOLID FLEXIBLE GATE JUMPER

COMPACT BACK FILL TO 95% MODIFIED PROCTOR.2.

GROUNDING TRENCHES TO BE BACK FILLED WITH NATIVE SOIL.1.

NOTES:

A

GROUNDING TRENCH

12"

6" MIN.

12" 2 M

IN

(1" ABOVE & BELOW CONDUCTOR x 6" WIDE)

2" ULTRAFILL BACKFILL

EXISTING SUBGRADE

COMPACTED BACKFILL

STANDARD GROUND TRENCH ENHANCED GROUND TRENCH

SEE E-101 FOR CONDUCTOR SIZE

SITE GROUND CONDUCTORS;

B

STEEL POST GROUNDING

FENCE, ICE BRIDGE, UTILITY RACK, ETC.

STEEL POST (TYP.);

EXOTHERMIC CONNECTION

SILICONE ON BOTH ENDS

BELOW GRADE; SEAL WITH

NON-METALLIC CONDUIT TO 24"

ENCASED IN LIQUID-TIGHT FLEXIBLE

#2 SOLID TINNED COPPER LEAD

EXOTHERMIC CONNECTION

GROUND RING

CONCRETE PIER

(TOP OF GRAVEL)

FINISHED GRADE

FLUSH WITH FINISH GRADE

FLUSH MOUNT ACCESS COVER ASSEMBLY

C

INSPECTION WELL

10" DIA. x 24" DEEP

SYSTEM

SITE GROUND

GROUND LOOP WIRE

FILL TEST WELL TO WITHIN 6" OF TOP OF

3/4" CLEAR CRUSHED STONE.

GROUND IMPEDANCE TESTING

30" LONG LOOP USED FOR

GROUND TEST WELL

E

FENCE FABRIC AND DETERRENT WIRING BONDING

CONNECTIONS

EXOTHERMIC

(1 OF 3)

FENCE FABRIC GROUNDING CLAMP

GATE JUMPER

#2 SOLID TINNED

TOP RAIL JUMPER

GATE POST JUMPER

TO SITE GROUND SYSTEM

CONNECT FENCE BONDING CONDUCTOR

GROUND CONNECTION

UNIVERSAL PIPE CLAMP MECHANICAL

COMPOUND

UL LISTEDCONDUCTIVE ANTI-OXIDANT

CONNECTOR LIBERALLY COAT WITH

UL LISTED BIMETALIC TRANSITION

TYP. INSTALLED ON EACH WIRE

DETERRENT WIRE GROUNDING CLAMP

SYSTEM

FENCE FABRIC TO SITE GROUND

COPPER CONDUCTOR BONDING

#2 SOFT DRAWN TINNED SOLID

SYSTEM

SITE GROUND

F

INTERIOR / EXTERIOR SHELTER GROUND BARS

LOCATION

SIZE WILL VARY AT EACH

TRANSMISSION LINE NUMBER &

COAX / WAVEGUIDE

COAX ENTRY PANEL ASSEMBLY

UNUSED HOLES IN CUSHIONS

WAVEGUIDE INCLUDE PLUGS FOR

QUANTITY AND SIZE OF COAX /

APPROPRIATELY SIZE CUSHIONS FOR

BOOT ASSEMBLIES (INSIDE AND OUT)

BETWEEN LUG AND GROUND BAR (TYP.)

APPLY ANTI-OXIDANT COMPOUND

LONG BARREL COMPRESSION LUGS

ATTACH TO GROUND BAR W/ 2 HOLE

GROUND KIT LEAD;

GROUND LUGS MIN.)

(SIZED FOR 44 - 2 HOLE

4"x24"x1/4"

(TINNED ON EXTERIOR)

COPPER GOUND BAR

MASTER GROUND BAR. SEE SHEET E-503.

CONNECTION OF GROUND LEADS TO INTERIOR

FOLLOW PANI ORGANIZATION SYSTEM FOR

AND ROUTE TO SHELTER GROUND RING;

EXOTHERMIC CONNECTION TO GROUND BAR

#2 BARE SOLID TINNED

(2) FROM INTERIOR GROUND BAR

(2) FROM EXTERIOR GROUND BAR &

GROUND LEADS;

LUGS AT BOTH ENDS

LONG BARREL COMPRESSION

JUMPER CONNECT WITH 2 HOLE

(1) #6 STRANDED INSULATED

ENTRY PANEL GROUND;

SEALING CAPS

COVERED W/

OPENINGS SHALL BE

UNOCCUPIED PANEL

WALL OPENING

OUTLINE OF SHELTER

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-5

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

T H

IS

D

E T A

IL

N

O T A

P P L

IC

A B L E

T H

IS

D

E T A

IL

N

O T A

P P L

IC

A B L E

T H

IS

D

E T A

IL

N

O T A

P P L

IC

A B L

FINISHED GRADE

FINISHED GRADE

FINISHED GRADE

UTILITY WARNING TAPE

SUBGRADE

(CLEAN SAND OR EQUIV.)

SELECT GRANULAR BACKFILL

COMPACTED BACKFILL

SECURED TO TOP OF CONDUITS TYP.

INSTALLED BY ELEC. CONTRACTOR

TRACER WIRE

SEE SITE PLAN FOR SIZE & MATERIAL

INSTALLED BY ELEC.CONTRACTOR

CONDUIT TYP.

E-504

U T

IL

IT

Y D

E T

A

IL

S

D

TOWER LIGHTING INSTALLATION

PHOTOCELL

ACROSS ICE BRIDGE

CONDUIT SLEEVE

CABLE WITHIN

ROUTE FLASHER

ICE BRIDGE;

CABLE ACROSS " 2

FLASHER CABLE

ICE BRIDGE

THROUGH SHELTER WALL

1" RMC CONDUIT SLEEVE

BOX SECURED TO EXTERIOR WALL

6" x 6" x 4" NEMA 3R METALLIC JUNCTION

SEE NOTE #1

INTERIOR WALL;

SECURED TO

" SQUARE (5S) BOX16

PHOTO CELL WIRES

FLASHER CABLE AND

CONTROLLER FOR

1" CONDUIT TO LIGHTING

SEE NOTE #1

SPECIFICATIONS;

PER MANUFACTURER

SECURED TO INTERIOR WALL

LIGHTING CONTROLLER

" RMC FOR PHOTO CELL2

" NPT FEMALE THREADS2

OTHER APPROVED METHOD

WITH BUTTERFLY CLAMP OR

SECURE RMC TO SHELTER

1.

NOTES:

INTERIOR JUNCTION BOX TO INTERIOR GROUND HALO SYSTEM.

PROVIDE GROUND BOND FROM LIGHTING CONTROLLER BOX AND

THI

S

SPACE

IN

TENTI

ONALLY

LEFT

BLANK

B

CONDUIT STUB-UP

SECURED TO TOP OF CONDUIT

TRACER WIRE

SEE UTILITY PLAN FOR SIZE AND MATERIAL TYPE

BURIED CONDUIT;

TO CONDUIT

SECURE TRACER WIRE

CONDUIT END

CAP EXPOSED

A

UTILITY TRENCH

5. VERIFY CONDUIT DEPTH REQUIREMENTS WITH LOCAL UTILITY PROVIDER.

4. CONTRACTOR TO CHECK CONTINUITY OF TRACER WIRE BEFORE AND AFTER BURIAL.

EXTEND TO GRADE AT BOTH ENDS - LOOP AND WRAP AROUND APPROPRIATE CONDUIT.

SECURE TO TOP OF CONDUIT AND RUN CONTINUOUSLY ALONG THE ENTIRE LENGTH.

3. TRACER WIRE TO BE 14 GA. SOLID COPPER WIRE WITH CORROSION PROTECTIVE COATING.

INSTALL TAPE 12” ABOVE THE TOP OF THE CONDUITS.

2. WARNING TAPE TO RUN CONTINUOUSLY ALONG THE ENTIRE CONDUIT LENGTH.

NO DUCT TAPE CAPS ALLOWED

1. ALL CONDUITS TO BE EQUIPPED W/ PULL CORDS & CAPPED FOR FUTURE LINE PULLS.

NOTES:

WIDTH

M

IN

C

O V

E R

4" MIN.

AS REQ'D.

A L

L S

ID

E

S T

Y P

ALL SIDES TYP.

3" MIN.

M

IN

(S E

E N

O T

E

C

CONDUIT STUB-UP AT SHELTER

SEE UTILITY PLAN FOR SIZE AND MATERIAL TYPE

BURIED CONDUIT;

SECURED TO TOP OF CONDUIT

TRACER WIRE

TO CONDUIT

SECURE TRACER WIRE

FOUNDATION

SHELTER

LB

SHELTER EXTERIOR

(AS REQUIRED)

CONDUIT SUPPORT

SLIP JOINT

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-5 .d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

AJO

T H

IS

D

E

TA

IL

N

O T A

P P

LI

C A B

LE

T H

IS

D

E

TA

IL

N

O T A

P P

LI

C A B

LE

E-505

U T

IL

IT

Y R

A C

K D

E T

A

IL

S

A

SINGLE METER UTILITY RACK

22" x 34" - 1" = 1'-0"

SCALE: 11" x 17" - 1/2" = 1'-0"

ELEVATION VIEW

14" (TYP.)

(TYP.)

18" O.C.

(3) #3 TIES AT

SPACED (TYP.)

(6) #4 REBAR EQUALLY

S E

E N

O T

E

4'-0"

FINISH GRADE

PIER FOUNDATION DEPTH TO BE A MINIMUM OF 48"; DEPTH TO EXCEED LOCAL FROST DEPTH.3.

MAINTAIN 3" MINIMUM REBAR COVER IN ALL DIRECTIONS.2.

CONCRETE FOR PIER TO BE A MINIMUM OF 4,000 PSI AT 28 DAYS.1.

NOTES:

PLAN VIEW

POST FOUNDATION (TYP.)

METER SOCKET

UNISTRUT

STEEL POSTS W/ CAPS

3" SCH. 40 (3-1/2" O.D.) GALVANIZED

TOUCH UP W/ COLD GALVANIZED SPRAY

GRIND AND ROUND ALL CUT ENDS

GALVANIZED UNISTRUT (TYP.);

(1) 200A, SINGLE PHASE METER SOCKET

VERIFY SIZE W/ UTILITY PROVIDER

(1) 1.25" CONDUIT TO ELEC. TRANSFORMER

3/4" GROUNDING CONDUIT

TO EQUIPMENT CABINET

(1) 1.25" ELECTRIC SERVICE CONDUIT

SLIP JOINT (TYP.)

CONDUIT SUPPORT (TYP.)

DATE: DESCRIPTION:

SUBMITTAL:

INT.

SHEET

NUMBER

11/8/2022

I:

\3

\3

\D e s ig n \C

A D

\F R

\P lo t\ E

-5

.d g n

35241

BY

CHECKED

DATE

PLOT

NUMBER

PROJECT

TYPE

SET

CONSULTANT:

CLIENT:

www.edgeconsult.com

608.644.1549 FAX

608.644.1449 VOICE

PRAIRIE DU SAC, WI 53578

624 WATER STREET

S U

N P

R A

IR

IE

W

IS

C

O N

S

IN

S U

N P

R A

IR

IE

P O

L

IC

E

B

IR

D S

T R

E E

T W

T

FR

G-001
C-101
C-102
C-501
A-101
E-101
E-102
E-501
E-502
E-504
E-505