Garner MW building 90 Percent PLANS v1.pdf
PDF 9 MB Posted
- Solicitation number
- 645-RFP-2133-2026
- Issued by
- Carroll County, Iowa
About this file
This is a 90% complete architectural and engineering drawing set prepared by the Iowa Department of Transportation (Iowa DOT) Resources & Acquisitions Bureau for a new Mechanical and Wash Bay (MW) Building located at 280 Highway 18E in Garner, Iowa 50438, in Hancock County. The project involves the construction of a new 5,120-square-foot facility (64 feet by 80 feet) designed to serve as a maintenance and wash facility, featuring multiple functional areas including a 1,716-square-foot wash bay, 2,270-square-foot mechanics bay, 270-square-foot welding station, 153-square-foot office and parts area, utility and mechanical rooms, restrooms, and a 3,068-square-foot equipment platform. The building will be constructed adjacent to an existing Maintenance Garage (MG) structure, separated by approximately 10 feet 8 inches, with the new facility featuring insulated precast concrete exterior wall panels, steel roof trusses with metal decking, a fully adhered 60-mil EPDM membrane roof system, and concrete floor slabs designed for heavy equipment and vehicle use. The drawings include comprehensive architectural, structural, mechanical, plumbing, electrical, and technology system plans, with detailed specifications for wall types, fire-rated separations, door and window schedules, interior elevations, building sections, roof plans, and equipment layouts.
The project incorporates multiple design considerations including 2015 International Building Code compliance as adopted by Iowa, with specific provisions for Group S-1 moderate-hazard storage occupancy classification, 3-hour fire barrier separation between the new and existing buildings, and ADA accessibility standards throughout the facility. Mechanical systems include HVAC coverage with exhaust fans, a welding exhaust system with a 13-foot swivel arm, booster pump and monitoring controls, water heater, and air dryer units. Plumbing provisions include service sinks, restroom fixtures, drinking fountains, eye wash stations, and hose bibs. Electrical infrastructure incorporates underground utility feeds, equipment platforms, lighting fixtures, power distribution, and communications equipment. The floor slab design includes perforated poly drain tile with filter sock at the exterior footing elevation for subgrade drainage, multiple concrete control joints, and provisions for various penetrations and mechanical equipment mounting. The drawing set was dated January 28, 2025, and is designated as project number BG-1G32 (000)--80-41, prepared at 90% completion with provisions for future revisions and field verification by the contractor.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION:
SITE LOCATION:
GARNER MG
MW BUILDING
4 5
HANCOCK
OSCEOLALYON
DICKENSON
CRAWFORD
OBRIEN
CHEROKEE
SIOUX
EMMET
KOSSUTH
WINNEBAGO WORTH MITCHELL HOWARD
CLAY
MONONA
PLYMOUTH
BUENA VISTA POCAHONTAS
PALO ALTO
HUMBOLT WRIGHT FRANKLIN
FLOYD CHICKASAW
WINNESHIEK ALLAMAKEE
FAYETTE CLAYTON
BREMER
BUTLER
BLACK HAWK
CARROL
WOODBURY IDA SAC CALHOUN
HANCOCK CERRO GORDO
GREENE BOONE STORY MARSHALL
TAMA
GRUNDYHARDINHAMILTONWEBSTER
POWESHIEKJASPERPOLK
SCOTT
CLINTON
JACKSON
DUBUQUEDELAWAREBUCHANAN
JONES
CEDAR
LINN
BENTON
IOWA
JOHNSONHARRISON
POTTAWATTAMIE
MILLS
FREMONT
MADISON
DALLAS
GUTHRIEAUDUBON
SHELBY
CASS
ADAIR
UNIONADAMSMONTGOMERY
PAGE TAYLOR RINGGOLD
WAREN MARION
LUCASCLARKE
DECATUR WAYNE
LEE
DES MOINES
LOUISA
MUSCATINE
WASHINGTONKEOKUKMAHASKA
HENRY
JEFFERSONWAPELLOMONROE
APPANOOSE DAVIS VAN BUREN
IOWA COUNTY AND DISTRICT KEY
PROJECT:
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
SHEET
DATE:
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :5
A
M
GARNER MW FACILITY
BG-1G32 (000)--80-41
280 Hwy 18E Garner, IA 50438
G A
R N
E R
M W
F A
C
IL
IT
Y
T
IT
L E
S H
E E
T
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
0A_001
ARCHITECTURE
NO. SHEET NAME
0A_001 TITLE SHEET
0A_002 ARCHITECTURAL SITE PLAN
1A_000 GENERAL NOTES, LEGENDS & ABBREVIATIONS
1A_001 CODE PLAN
1A_002 WALL TYPES, SIGNAGE, & ADA
1A_100 FLOOR SLAB AND SUBGRADE DRAINAGE PLAN
1A_110 FLOOR PLAN
1A_111 ENLARGED CORE AREA
1A_200 DOOR / FRAME ELEVATIONS, DETAILS, SCHEDULES
1A_201 DOOR DETAILS
1A_300 EXTERIOR ELEVATIONS
1A_400 BUILDING SECTIONS
1A_401 WALL SECTIONS
1A_500 INTERIOR ELEVATIONS
1A_610 REFLECTED CEILING PLAN
1A_700 ROOF PLAN
1A_810 FIRST FLOOR EQUIPMENT
CIVIL
NO. SHEET NAME
C_101 NOTES AND LEGEND
C_110 EXISTING CONDITIONS AND DEMOLITION
C_200 SITE PLAN
C_400 SANITARY PLAN AND PROFILE
C_401 WATER PLAN AND PROFILE
C_402 WATER PLAN AND PROFILE
C_500 CIVIL DETAILS
TECHNOLOGY
NO. SHEET NAME
1T_000 TECHNOLOGY COVERSHEET
1T_010 SITE PLAN - TECHNOLOGY
1T_201 FIRST FLOOR PLAN - TECHNOLOGY
1T_202 EQUIPMENT PLATFORM PLAN - TECHNOLOGY
1T_300 TECHNOLOGY ENLARGED PLANS
1T_400 TECHNOLOGY DETAILS
1T_500 TECHNOLOGY DIAGRAMS
1T_600 TECHNOLOGY SCHEDULES
STRUCTURAL
NO. SHEET NAME
S_01 GENERAL NOTES
S_02 TESTING, INSPECTIONS AND OBSERVATIONS
S_101 FOUNDATION PLAN
S_102 SECOND FLOOR FRAMING PLAN
S_103 ROOF FRAMING PLAN
S_201 FOUNDATION DETAILS
S_202 STRUCTURAL FRAMING DETAILS
MECHANICAL
NO. SHEET NAME
1M_000 VENTILATION COVERSHEET
1M_201 FIRST FLOOR PLAN - VENTILATION
1M_203 ROOF PLAN - VENTILATION
1M_400 HVAC DETAILS
1M_500 HVAC DIAGRAMS
1M_600 HVAC SCHEDULES
PLUMBING
NO. SHEET NAME
1P_000 PLUMBING COVERSHEET
1P_200 UNDERFLOOR PLAN - PLUMBING
1P_201 FIRST FLOOR PLAN - PLUMBING
1P_203 ROOF PLAN - PLUMBING
1P_300 PLUMBING ENLARGED PLANS
1P_400 PLUMBING DETAILS
1P_401 PLUMBING DETAILS
1P_600 PLUMBING SCHEDULES
ELECTRICAL
NO. SHEET NAME
1E_000 ELECTRICAL COVERSHEET
1E_010 SITE PLAN - ELECTRICAL
1E_201 FIRST FLOOR PLAN - LIGHTING
1E_202 EQUIPMENT PLATFORM PLAN - LIGHTING
1E_211 FIRST FLOOR PLAN - POWER
1E_212 EQUIPMENT PLATFORM PLAN - POWER
1E_213 ROOF PLAN - POWER
1E_400 ELECTRICAL DETAILS
1E_401 ELECTRICAL DETAILS
1E_500 ELECTRICAL DIAGRAMS
1E_600 ELECTRICAL SCHEDULES
1E_700 ELECTRICAL PANEL SCHEDULES
N O
D
A T
E
C om ple te
EXISTING MG
VERIFY W/ CIVIL EXISTING
FINISHED FLOOR 0'-0"
ELEVATION
15' - 0" 80' - 0" 15' - 0"
V
E R
IF
Y
137' - 7"
57' - 7" 80' - 0"
64 X 80 MW BUILDING
FINISHED FLOOR 0' - 0" ELEVATION
TO MATCH EXISTING MG, VERIFY
W/ CIVIL
FROST STOOP
CONCRETE
APPROACH
FROST STOOP
FROST STOOP
CONCRETE
APPROACH
GRAVEL COVER
BETWEEN BUILDINGS
CONCRETE PAVING
BETWEEN BUILDINGS
V E
R
IF
Y
EXISTING SALT STORAGE
E L E
C F
E E
D
UNDER GROUND ELEC.
FEED, VERIFY
W A
T E
R
WATER
WATER
W A
T E
R
W A
T E
R
WATER
WATER
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :5
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
A R
C H
IT
E
C T
U R
A L S
IT
E
P L A
N
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
0A_002
SITE GENERAL NOTES:
1. SEE CIVIL ENGINEERING DRAWINGS FOR ALL SITEWORK,
PAVING, DRIVES, GRADING, UTILITIES, ETC.
2. SEE CIVIL ENGINEERING DRAWINGS FOR ALTERNATE BID
PRICING
3. SEE ELECTRICAL DRAWINGS FOR UNDERGROUND
ELECTRICAL UTILITY LOCATIONS. UNDERGROUND PRIMARY
SERVICE WIRE AND CONDUIT BY UTILITY COMPANY.
ELECTRICAL CONTRACTOR NEEDS TO PROVIDE TRENCHING
AND BACKFILLING.
4. SEE ELECTRICAL DRAWINGS FOR CONCRETE PADS DETAILS
FOR GENERATOR AND TRANSFORMER. CONCRETE PADS
FURNISHED AND INSTALLED BY GENERAL CONTRACTOR.
5. SEE CIVIL PLANS FOR REPLACED AND NEW PAVING AND
ALTERNATES.
1" = 20'-0"0A_002
1 ARCHITECTURAL SITE PLAN
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
ABBREVIATIONS:
A
A ASTRAGAL
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
& AND
APPROX APPROXIMATE
ARCH ARCHITECT
B
B BASE
BLDG BUILDING
BLKG BLOCKING
BO BY OTHERS
BOT BOTTOM
BRD BOARD
BRK BRICK
BSMT BASEMENT
BUR BUILT-UP ROOFING
C
C CARPET, CORNICE
CB CATCH BASIN
CFMF COLD FORMED METAL FRAMING
CH CEILING HEIGHT
CI CAST IRON
CJ CONTROL JOINT
CL CENTER LINE, CLOSET
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CP CEILING PAINT
CT CERAMIC TILE
CVB COVED VINYL BASE
D
D DOOR, DRYER
DBL DOUBLE
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DIAG DIAGONOL
DIAM DIAMETER
DIM DIMENSION
DISP DISPOSAL
DTL DETAIL
DW DISHWASHER
DWG DRAWING
E
EA EACH
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATOIN
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FF FINISHED FLOOR, FACTORY FINISH
FIN FINISH
FL FLOOR
FOW FACE OF WALL
FT FOOT
FTG FOOTING
G
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS/GLAZING
GWB GYPSUM WALL BOARD
GYP GYPSUM
GYP BD GYPSUM BOARD
H
HB HOSE BIB
HDW HARDWARE
HDWD HARDWOOD
HDPE HIGH DENSITY POLYETHYLENE
HM HOLLOW METAL
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATION, AIR CONDITIONING
I
ID INSIDE DIAMETER
INS INSULATE (D)
INT INTERIOR
IJ ISOLATION JOINT
J
JAN JANITOR
JT JOINT
K
KIT KITCHEN
L
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LT LIGHT
LT GA LIGHT GAUGE
LVR LOUVER
M
M MIRROR
MANUF MANUFACTURER FINISH
MAX MAXIMUM
MB MARBLE
MC MECHANICAL CONTRACTOR
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MOLDING
MTD MOUNTED
MTL METAL
N
NATF NATURAL FINISH
NIC NOT IN CONTRACT
NOM NOMINAL
NS NO SILL
NSF NET SQUARE FOOTAGE
NTS NOT TO SCALE
NUM NUMBER
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OH OPPOSITE HAND
OHD OVERHEAD DOOR
OPG OPENING
OPP OPPOSITE
P
P PAINT, PANEL MOLDING
PL PLASTIC LAMINATE
PLC POLYCARBONATE
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PT POINT
PTD PAINTED
PTN PARTITION
PVC POLYVINYL CHLORIDE
Q
QT QUARRY TILE
R
R RISER, CHAIR RAIL, RADIUS
RD ROOF DRAIN
RE REFER TO
REF REFERENCE, REFRIDGERATOR
REINF REINFORCED
RESIL RESILIENT
RO ROUGH OPENING
REQ REQUIRED
REV REVISION
RM ROOM
S
SC SOLID CORE, SKIM COAT
SECT SECTION
SF SQUARE FEET
SH SHELVES
SHR SHOWER
SIM SIMILAR
SLR SEALER
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL, SERVICE SINK
ST STONE
STL STEEL
STN STAINED
STOR STORAGE
STRUC STRUCTURAL
T
T TREAD, DOOR OPENING, OR WINDOW TRIM
TEL TELEPHONE
TEMP TEMPERED
TF TRANSPARENT FINISH
THK THICKNESS
TOC TOP OF CONCRETE
TOW TOP OF WALL
-X TYPE X
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
VCT VINYL COMPOSITE TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VT VINYL TILE
VTR VENT THROUGH ROOF
W
W WASHER
W/ WITH
WC WATER CLOSET, WALL COVERING
WD WOOD
WF WOOD FLOORING
W/O WITHOUT
WP WATERPROOF
WR WATER RESISTANT
WT WEIGHT
MATERIALS LEGEND:
ASPHALT
SOIL
GRAVEL
SAND GRAVEL
BRICK
CONCRETE
CMU
WOOD STUD
METAL STUD
BATT INSULATION
RIGID
PLYWOOD
GYPSUM
SYMBOLS LEGEND:
NORTH ARROW
A101
SIM
SECTION
SHEET NUMBER
A101
1Ref
1 R e f
1 R e f
1Ref
EXTERIOR ELEVATION
ELEVATION
SHEET NUMBER
A101
1 Ref
1 Ref
R e f
INTERIOR ELEVATION
ELEVATION
SHEET NUMBER
A101
SIM
DETAIL
SHEET NUMBER
Name Elevation
SPOT ELEVATION
1i WALL PARTITION TYPE
101 DOOR OPENING NUMBER
1t WINDOW TYPE
WINDOW OPENING NUMBER
Room name
ROOM NAME
ROOM NUMBER
R e f
GENERAL NOTES:
1. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION (AIA DOCUMENT
A201 LATEST EDITION) WILL APPLY TO THIS CONTRACT.
2. DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONAL INFORMATION.
3. THE CONTRACTOR SHALL PREVIEW PLANS AND THE AREA OF CONSTRUCTION
CAREFULLY TO ENSURE FULL UNDERSTANDING OF EXACT SCOPE OF WORK.
4. THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS IN THE FIELD AND NOTIFY THE D.O.T. PROJECT MANAGER OF ANY
DISCREPANCIES BEFORE PROCEEDING WITH ANY WORK. NO CHANGES SHALL BE
MADE TO ANY PLAN WITHOUT PRIOR COMMENT OF THE D.O.T. PROJECT MANAGER.
5. THE CONTRACTOR SHALL FURNISH A SYSTEM OF TEMPORARY LIGHTS, HEAT, AND
WATER THROUGHOUT THE SPACE UNDER CONSTRUCTION, IF REQUIRED.
6. THE CONTRACTORS SHALL REMOVE FROM THE BUILDING ALL RUBBISH AND WASTE
MATERIALS FROM THE CONSTRUCTION OF THE BUILDING.
7. ALL DRAWINGS AND CONSTRUCTION NOTES ARE COMPLEMENTARY AND WHAT IS
CALLED FOR BY ONE WILL BE AS BINDING AS IF CALLED BY ALL.
8. THE CONTRACTOR SHALL OBTAIN FULL KNOWLEDGE BY PERSONNEL AND CAREFUL
EXAMINATION OF ALL EXISTING CONDITIONS AT THE SITE AND OF ALL
REQUIREMENTS OF THE SPECIFICATIONS AND DRAWINGS. THE CONTRACTOR
HEREBY ACCEPTS ALL SUCH CONDITIONS AND REQUIREMENTS AND HEREBY
ASSUMES ALL RESPONSIBILITY AND COSTS RESULTING FROM THE CONTRACTOR'S
FAILURE TO OBTAIN KNOWLEDGE OF THEM.
9. WHERE THE TERM "OR EQUAL" IS USED IN SPECIFICATIONS, IT SHALL BE
UNDERSTOOD THAT THE REFERENCE IS MADE TO THE RULING JUDGEMENT OF THE
OWNER AND SHALL BE SUBMITTED TO THE PROJECT MANAGER.
10. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING ALL DIMENSIONS. IF THERE
ARE DISCREPENCIES, CONTACT THE PROJECT MANAGER BEFORE PROCEEDING.
APPLIES TO ALL SHEETS
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :5
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
G E
N E
R A
L N
O T
E S
L E
G E
N D
S
A B
B R
E V
IA
T
IO
N
S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_000
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed ARCHITECT under the laws of the state of Iowa.
Printed or typed name
Signature Date
License expires
Pages or sheets covered by this seal:
Date issued
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed MECHANICALN ENGINEER under the laws of the state of Iowa.
Printed or typed name
Signature Date
License expires
Pages or sheets covered by this seal:
Date issued
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed ELECTRICAL ENGINEER under the laws of the state of Iowa.
Printed or typed name
Signature Date
License expires
Pages or sheets covered by this seal:
Date issued
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed CIVIL ENGINEER under the laws of the state of Iowa.
Printed or typed name
Signature Date
License expires
Pages or sheets covered by this seal:
Date issued
Steve Trost
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed STRUCTURAL ENGINEER under the laws of the state of Iowa.
Printed or typed name
Signature Date
License expires
Pages or sheets covered by this seal:
Date issued
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
1867 SF
WASH BAY
149 SF
UTILITY
284 SF
WELDING STATION 171 SF
OFFICE
69 SF
RR
69 SF
RR
MECHANICS BAY, WELDING STATION, UTL/MECH
& UTL/ELEC, OFFICE & PARTS COMBINED.
OL = 16
16 TOTAL EXITING
EF.E.
EF.E.
EE
F.E.F.E.
OL = 9
9 TOTAL EXITING
(O
V E
R A
L L
B U
IL
D
IN
G
80' - 0" (OVERALL BUILDING)
99' -
/4
BUIL
DIN
G
D
IA
G O
NAL)
2 HR RATED WALL
THERE ARE NO EXISTING OPENINGS OR PENETRATIONS ON THIS WALL
3 HOUR WALL (FIRE BARRIER) , PRECAST
CONCRETE PANEL, (NO INSULATION) PER T707.3.10
EXISTING 1 HOUR WALL,
PRECAST CONCRETE T
CONSTRUCTION
90 MIN RATED DOOR AND FRAME
90 MIN. RATED
DOOR AND FRAME
90 MIN. RATED
DOOR AND FRAME
IMAGINARY PROPERTY LINE
64 SF
UTL.
SERVICE SINK
2435 SF
MECHANICS BAY
CODE REVIEW
APPLICABLE BUILDING CODE:
INTERNATIONAL BUILDING CODES
2015 INTERNATIONAL BUILDING CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULE CHAPTERS 661-201 AND 661-301
2015 INTERNATIONAL FIRE CODE AS ADOPTED BY IOWA ADMINISTRATIVE
RULE CHAPTERS 661-201
2012 INTERNATIONAL ENERGY CONSERVATION CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULE CHAPTERS 661-303
2010 AMERICANS WITH DISABILITIES ACT AS ADOPTED BY IOWA
ADMINISTRATIVE RULE CHAPTER 661-302
SMOKE AND CARBON MONOXIDE DETECTORS
SMOKE ALARMS/DETECTORS AS ADOPTED BY IOWA ADMINISTRATIVE RULE
CHAPTER 661-210 (EFFECTIVE JULY 1, 2021)
CARBON MONOXIDE ALARMS AS ADOPTED BY IOWA ADMINISTRATIVE RULE
CHAPTER 661-211
STATE CODES
STATE MECHANICAL CODE AS ADOPTED BY THE DEPARTMENT OF PUBLIC
HEALTH IOWA ADMINISTRATIVE RULE CHAPTER 641-61
STATE PLUMBING CODE AS ADOPTED BY THE DEPARTMENT OF PUBLIC
HEALTH IOWA ADMINISTRATIVE RULE CHAPTER 641-25
STATE ELECTRICAL CODE AS ADOPTED BY THE STATE ELECTRICAL
LICENSING BOARD IOWA ADMINISTRATIVE RULE CHAPTER 661-504
PLAN LEGEND:
E
FIRE EXTINGUISHERF.E.
3 HR WALL
1/8" = 1'-0"1A_001
2 CODE REVIEW PLAN
2015 IBC
CHAPTER 3 USE AND OCCUPANCY
EXISTING MG, 1980
311.2 MODERATE-HAZARD STORAGE, GROUP S-1
TYPE 2B
EXTERIOR WALLS - PRECAST CONCRETE PANELS
INTERIOR WALLS - PRECAST PANELS, CONCRETE BLOCK
ROOF STRUCTURE - PRECAST DOUBLE T PANELS
NON-SPRINKLED
NEW MW, 2024
311.2 MODERATE-HAZARD STORAGE, GROUP S-1
64 X 80 = 5120 SQ.FT.
EXTERIOR WALLS - INSULATED PRECAST CONCRETE PANELS
INTERIOR WALLS - NON INSULATED PRECAST PANELS, CONCRETE BLOCK
ROOF STRUCTURE - STEEL TRUSSES W/ STEEL DECKING
NON-SPRINKLED
CHAPTER 6 TYPES OF CONSTRUCTION
T 601 FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
(HOURS)
TYPE VB = 0 FOR ALL CATEGORIES
602 CONSTRUCTION CLASSIFICATION
T 602 FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED
ON FIRE SEPARATION DISTANCE
EXISTING MG TO IMAGINARY PROPERTY LINE, = 7' - 8"
10 < X < 30, VB, S-1 = 0
NEW BUILDING TO IMAGINARY PROPERTY LINE = 3' - 0"
X < 5, S-1 = 2
CHAPTER 9 FIRE PROTECTION SYSTEMS
903.2.9 GROUP S-1
903.2.9.1 REPAIR GARAGES
AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
BUILDINGS CONTAINING A GROUP S-1 OCCUPANCY WHEREIN ON OF THE
FOLLOWING EXISTS:
4. A GROUP S-1 FIRE AREA USED FOR THE STORAGE OF COMMERCIAL
MOTOR VEHICLES WHERE THE FIRE AREA EXCEEDS 5000 SQ.FT.
THE S-1 SPACES ARE DIVIDED TO BELOW 5000 SQ.FT. WITH A 3HR SEPARATION.
WASH BAY = 1876 SQ.FT.
MECHANIC'S BAY = 2726 SQ.FT.
SPRINKLERS ARE NOT REQUIRED
908 EMERGENCY ALARM SYSTEMS
908.7 CARBON DIOXIDE SYSTEMS
CO2 ALARM SYSTEMS WILL BE INSTALLED I.A.W. SECTION 5307.5.2 OF THE
INTERNATIONAL FIRE CODE SHALL BE PROVIDED WHERE REQUIRED FOR
COMPLIANCE WITH SECTION 5307.5 IF THE INTERNATIONAL FIRE CODE.
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES CONT.
707 FIRE BARRIERS
T707.3.10 FIRE-RESISTANCE RATING REQUIREMENTS FOR FIRE BARRIER
ASSEMBLIES OR HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS
OCCUPANCY = S1
FIRE-RESISTANCE RATING = 3HRS
722 CALCULATED FIRE RESISTANCE
FIGURE 7.22.2.1.2 FIRE RESISTANCE RATING OF TWO-WYTHE CONCRETE WALLS
T722.2.1.2 (1) VALUES OF RN0.59 FOR USE IN EQUATION 7-4
EQUATION 7-4
R=R10.59 + R20.59 +2.5
SILICEOUS AGGREGATE CONCRETE:
NEW BLDG, INSULATED PRECAST CONCRETE PANELS
3" CONCRETE = 9.5
3" INSULATION, SANDWICHED LAYER = 2.5
6" CONCRETE = 20.7
9.5+2.5+20.7 = 32.7
TABLE 722.2.1.2(2)
32.7, EXCEEDS 240 MIN (4HR)
722.2.1.2.2 FOAM PLASTIC INSULATION
INCH (25.4 MM) OR GREATER, FOR USE IN THE CALCULATION, IS 5 MINUTES;
THEREFORE RN0.59 = 2.5.
OL = XX
AREA BOUNDRY LINE
EXIT
X OCCUPANTS EXITING
OCCUPANT LOAD
CHAPTER 29 PLUMBING SYSTEMS
SECTION 2902 MINIMUM PLUMBING FIXTURES
T2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
(SEE ALSO IPC T 403.1 MINIMUM NUMBER OR REQUIRED PLUMBING
FIXTURES)
CLASSIFICATION = STORAGE
OCCUPANCY = S-1
MALE = 1/100
FEMALE = 1/100
DRINKING FOUNTAINS (SEE ALSO 410 IPC) = 1/1000
OTHER = 1 SERVICE SINK
IPC 403.2 SEPARATE FACILITIES
WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL
BE PROVIDED FOR EACH SEX. (NONE OF THE EXCEPTIONS APPLY HERE)
IPC 410 IPC DRINKING FOUNTAINS
410.3 PROVIDE HIGH AND LOW DRINKING FOUNTAINS
CHAPTER 5 GENERAL BUILDING HEIGHTS AND AREAS
T 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE
S-1, TYPE 2B, NS = 55'
ACTUAL BUILDING HEIGHT = 26' TOP OF PRECAST
T 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
S-1, TYPE 2B, NS = 2
ACTUAL BUILDING STORIES = 1
T506.2 ALLOWABLE AREA FACTOR IN SQFT
S-1, TYPE 2B, NS = 17,500
64 X 80 = 5120 SQ.FT.
CHAPTER 10 GENERAL MEANS OF EGRESS
1004 OCCUPANT LOAD
T 1004.1.2 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
WASH BAY (PARKING GARAGES) - GROSS SQ.FT./200
1876/200=9
MECHANICS BAY/WELDING STATION (PARKING GARAGES) - GROSS SQ.FT./200
2719/200=14
UTL./MECH & UTL. /ELEC. (ACCESSORY STORAGE) - GROSS SQ.FT/300
213/300=1
OFFICE/PARTS (BUSINESS AREA)- GROSS SQ.FT/100
171/100=1
TOTAL OCCUPANT LOAD = 25
T 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
MAX OCCUPANT LOAD OF SPACE, S = 29
MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE (FEET)
W/O A SPRINKLER SYSTEM, OL ≤ 30 = 100'
ALL PATHS OF EGRESS ARE LESS THAN 100'
T 1006.3.1 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY
OCCUPANT LOAD PER STORY 1-500
MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS FROM STORY = 2
T 1017.2 EXIT ACCESS TRAVEL DISTANCE
S-1 W/ SPRINKLER SYSTEM = 250'
IMAGINARY PROPERTY LINE
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :0
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
C O
D E
P L A
N
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_001
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES
704 FIRE RESISTANCE RATING OF STRUCTURAL MEMBERS
ALL STRUCTURAL MEMBERS TO BE PRECAST CONCRETE, RATINGS PER MFG.
1HR MIN.
705.3 BUILDINGS ON THE SAME LOT
BUILDINGS ARE SEPARATED BY 10'-8", I.A.W.
T 602 FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
BASED ON FIRE SEPARATION DISTANCE
705.4 MATERIALS
EXTERIOR WALLS ARE 12" INSULATED PRECAST CONCRETE PANELS
T.705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE
SEPARATION DISTANCE AND DEGREE OF OPENING PROTECTION
FIRE SEPARATION DISTANCE = 10' TO LESS THAN 15', UNPROTECTED NON-
SPRINKLERED, 15% ALLOWABLE AREA
SOUTH WALL: 26' X 80' = 2080 TOTAL SQFT.
312 SQFT. ALLOWED OPENINGS
21 SQFT. ACTUAL OPENINGS
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
1' - 0" 8"
OUTSIDEINSIDE
PRECAST
CONCRETE WITH
RIGID INSULATION
CMU BLOCK INTERIOR PRECAST
CONCRETE
PLUMBING CAVITY
8" CMU
6" 3" 3"
8"
8"8"8"
2' - 0"
1' - 0"
TEXT
RM. NUMBER (1" HIGH)
RM. NAME (5/8" HIGH)
BRAILLE
REMOVEABLE OCCUPANT
NAME SLOT (PRINTING BY
OTHERS)
M
IN
SIGN CENTERED ON
TACTILE CHARACTERS
TEXT 5/8" HIGH
SYMBOLS
18" MIN. CLEAR
DOOR OPENING, LATCH SIDE
TACTILE CHARACTERS
M
IN
T O
M
IR
R O
R E
D S
U R
F A
C E
MIRROR
SD
SOAP
DISPENSER
PAPER TOWEL
DISPENSER
PTD
TOLIET PAPER
DISPENSER
TPD
LAVATORY
(ALL TYPES)
WATER
CLOSET
WATER
COOLER
M
IN
MIRROR
M
IN
36" MIN 6" MAX.
42" MIN.
HORIZONTAL GRAB BAR
1' - 6"
12" MAX 42" MIN
54" MIN
39" - 41"
M
IN
HORIZONTAL & VERTICAL GRAB BAR
NON RECESSED DISPENSER LOCATION -
PROTRUDING DISPENSER BELOW GRAB BAR
F R
O N
T O
F T
O
IL
E T
C .L
O
F D
IS
P
E N
S E
R
M
A X
54" MIN.
M
IN
42" MIN.
7" - 9"
M
IN
/2
M
IN
6" MIN
M
IN
PARTITION
M A
X
13 1/2" MIN
URINAL (WALL HUNG)
X
4" MAX
X
PROTRUDING OBJECTS
ELEVATION PLAN
M
IN
25" MAX
M
IN
M
IN
11" MIN
8" MIN
KNEE CLEARANCE
6" MAX
ELEVATION PLAN
M
IN
17" - 25"
TOE CLEARANCE
CLEAR
18" MIN.
C L E
A R
M
IN
CENTERED ON TACLILE CHARACTERS
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :0
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
W A
L L T
Y P
E S
S
IG
N
A G
E
A D
A
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_002
E1
12" PRECAST INSULATED
8" CMU
8" PRECAST
24" CMU PLUMBING CHASE
1 1/2" = 1' 0 1 1/2" = 1' 0 1 1/2" = 1' 0 1 1/2" = 1' 0
WALL TYPES
ROOM SIGNS:
ROOM SIGN LOCATION:
ADA DETAILS:
PROJECT TO COMPLY WITH:
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
2017 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
DETAILS PROVIDED REFERENCE ONLY
ROOM SIGNAGE NOTES:
1. SIGN LOCATIONS IAW CHAPTER 7
COMMUNICATION ELEMENTS AND
FEATURES
2. SEE PLANS FOR ROOM NAMES AND
NUMBERS
3. COORDINATE W/ OWNER FOR
FINAL APPROVAL
4. SEE ROOM SIGN LOCATION
DIAGRAM BELOW.
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
C .J
C .J
C .J
C .J
C .J
C .J
DRAIN TILE, SEE CIVIL DRAWING
C .J
C .J
C .J
C .J
C .J
C .J
O
V E
R A
L L
A P
P R
O A
C H
O
V E
R A
L L
A P
P R
O A
C H
8' - 0" 8' - 0" 15' - 0"
1716 SF
WASH BAY
2270 SF
MECHANICS BAY
59 SF
R.R.
53 SF
UTL./ELEC.
106B
59 SF
R.R.
153 SF
OFFICE & PARTS
103270 SF
WELDING STATION
127 SF
UTL./MECH.
106A
VALLEY
VALLEY
VALLEY
VALLEY
T Y
P
TYP.
2' - 0"
12' - 0"
S L O
P E
SLOPE
S L O
L O
L O
DRAIN PIT, SEE MECH
S L O
L O
L O
L O
VALLEY VALL
EY
VALLEY VALLEY
VALLEY VALL
EY
VALLEY VALLEY
R
ID
G E
R
ID
G E
4" GRAVEL COVER
CONC. TIE DOWN ANCHORS, 10" SLAB
WITHIN 2' OF INSERTS PER MFG.
DRAIN PITS
CENTERED ON
OVHD. DOORS TYP.
DRAIN PITS
CENTERED ON
OVHD. DOORS TYP.
DRAIN PIT, SEE MECH
DRAIN PIT, SEE MECH DRAIN PIT, SEE MECH
VALLEY
VALLEY
VALLEY
VALLEY
80' - 0" OVERALL BUILDING
40' - 0" 40' - 0"
20' - 6" 19' - 6" 19' - 6" 20' - 6"
4' - 8"
3' - 4"
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :0
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
F L O
O R
S L A
B A
N D
S U
B G
R A
D E
D R
A
IN
A G
E P
L A
N
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_100
3/16" = 1'-0"1A_100
1 FLOOR SLAB AND SUBGRADE DRAINAGE PLAN
1. 4"⌀ PERFORATED POLY DRAIN TILE WITH FILTER SOCK. SET ON EXISTING SUBGRADE @
EXTERIOR FOOTING ELEVATION. COORDINATE TO NEW FOR OTHER PIPING AND PLUMBING
ITEMS BELOW SLAB.COVER WITH 12" FREE DRAINING FILL AT SIDES AND ABOVE.
2. COORDINATE LOCATION OF DRAIN TILE TO AVOID CONFLICT WITH OTHER PLANNED
PLUMBING, ELECTRICAL, GAS AND OTHER APPURTENANCES. PROVIDE SLEEVES,
CONNECTIONS AND ALL FITTINGS.
3. COORDINATE ALL C.J. W/ STRUCTURAL
4. RIDGE AND VALLEY LINES ARE SHOWN FOR PLACEMENT, DO NOT CUT OR FORM JOINTS AT
THESE LOCATIONS
LEGEND:
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
1A_400
1A_400
1A_400
1A_400
1A_401
CONCRETE APPROACH -
SEE CIVIL DRAWINGS
E1
15' - 0" (APPROACH) 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0"
(O
V E
R A
L L
B U
IL
D
IN
G
1716 SF
WASH BAY
2270 SF
MECHANICS BAY
2" FIRE HOSE
E1
E1
59 SF
R.R.
53 SF
UTL./ELEC.
106B
THRU-WALL WEDLING EXHAUST
59 SF
R.R.
103A
105A104A
106A2
1A_700
15' - 0" (APPROACH) 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 15' - 0" (APPROACH)
80' - 0" (OVERALL BUILDING)
102D
W1
101A 101B
102B
1A_400
1A_400
1A_400
1A_400
BOLLARD(S) TYP.
15' - 6"
9' - 9" 9' - 9" 9' - 9" 9' - 9" 9' - 9" 9' - 9" 7' - 10" 3' - 4" 8' - 4"
E1
E1
153 SF
OFFICE & PARTS
COLD HOSE
BIB @ 48"
A.F.F.
COLD HOSE BIB @ 48" A.F.F.
102A
(O
V E
R A
L L
B U
IL
D
IN
G
80' - 0" (OVERALL BUILDING)
1A_111
25' - 4" 52' - 8"
3' - 4" 3' - 4"
CONCRETE APPROACH -
SEE CIVIL DRAWINGS
EXISTING MG
ROOF ACCESS
LADDER
CENTER ON
PANEL SEE
DETAIL
10' - 0" 3' - 4" 3' - 4" 2' - 4"
A
P P
R O
A C
H
(A
P P
R O
A C
H
16' - 8" 16' - 8" 19' - 4"
E1E1E1E1 E1E1 E1
78' - 0"
4' - 8"
6' - 8" 3' - 4"
10' - 0"
270 SF
WELDING STATION
4" GRAVEL COVER
10' - 0"
CONC. TIE DOWN ANCHORS, 10" SLAB
WITHIN 2' OF INSERTS PER MFG.
T Y
P
TYP.
2' - 0"
1' - 0"
1' - 0" 1' - 0"
1A_400
1A_400
1A_400
1A_400
20' - 0" 38' - 0" (CEILING MOUNTED CRANE) 20' - 0"
102E
FROST STOOP,
DETAILS PER
STRUCTURAL
FROST STOOP, DETAILS
PER STRUCTURAL
FROST STOOP, DETAILS
PER STRUCTURAL
FROST STOOP, DETAILS
PER STRUCTURAL
1A_401
101C
102C
127 SF
UTL./MECH.
106A
106A1
1' - 0" 3' - 4" 8' - 4"
8' - 0" 8' - 0"
11' - 8"
(C
E
IL
IN
G
M O
U N
T E
D C
R A
N E
CEILING MOUNTED CRANE
EMG
2' - 4" 3' - 4" 2' - 4"
8' - 0"
FLOOR NOTE:
FLOOR LINES INDICATE A CHANGE IN SLOPE
DIRECTION OR CENTER LINES AND ARE NOT
CONTROL JOINTS. VERIFY CONTROL JOINTS
W/ STRUCTURAL. DO NOT CUT.
1' - 0" 1' - 0"
1' - 0"
1' - 0"
1' - 0"
1' - 0"
1' - 0"
1' - 0" 1' - 0"
1' - 0"
1' - 0"
1' - 0"
1' - 0" 1' - 0"
10' - 0"
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :0
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
F L O
O R
P L A
N
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_110
3/16" = 1'-0"1A_110
1 FLOOR PLAN
GENERAL NOTES:
1. SEE STRUCTURAL DRAWINGS FOR INTERIOR LINTELS @ CMU WALLS AND EXTERIOR STOOPS
2. FOR PLACEMENT OF RESTROOM FIXTURES SEE ADA DETAILS 1A_002.
3. FOR DOOR AND WINDOW SCHEDULES AND ELEVATIONS SEE SHEET 1A_200.
4. ALL EXPOSED/VISIBLE CORNERS AND OPENINGS ON CONCRETE MASONRY WALLS SHALL BE
BULLNOSE.
5. FINISH MASONRY EDGE AGAINST CONCRETE. CAULK 1/2" JOINT TO MATCH MASONRY.
6. FOR ROOM FINISH SCHEDULE SEE SHEET 1A_200.
7. FOR CONCRETE SLAB ISOLATION AND CONTROL JOINTS SEE STRUCTURAL DRAWINGS.
8. SEE CODE REVIEW DRAWING SHEET 1A_001 FOR FIRE EXTINGUISHER LOCATIONS.
9. ALL CMU WALLS AT OFFICE AREA OF BUILDING TO BE CONSTRUCTED TO A HEIGHT OF 9'-4" A.F.F.
10. FOR WALL TYPES SEE SHEET 1A_002.
11. FURNISH AND INSTALL 4'X8'X3/4" THICK A-C FIRE RETARDENT TREATED PLYWOOD ON ONE
WALL IN COMMUNICATION ROOM. FINAL LOCATION AND MOUNTING HEIGHT TO BE VERIFIED
PRIOR TO INSTALL.
12. OUTSIDE & INSIDE BOLLARD TO HAVE PLASTIC BOLLARD SLEEVE PER SPECIFICATIONS.
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
1A_5007
8" 15' - 4" 8" 7' - 4" 8" 8" 8" 7' - 4" 8" 18' - 8"
53 SF
UTL./ELEC.
106B
59 SF
R.R.
59 SF
R.R.
153 SF
OFFICE & PARTS
1716 SF
WASH BAY
2270 SF
MECHANICS BAY
SHELVES DOT
FURNISHED AND
INSTALLED
AIR
COMP.
COMMS.
CABINET
52' - 8"
52' - 8"
3' - 4" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 10' - 0" 3' - 4" 10' - 0" 3' - 4" 6' - 0"
SHELVES DOT
FURNISHED AND
INSTALLED
SHELVES DOT
FURNISHED AND
INSTALLED
S H
E L V
E S
D O
T
F U
R N
IS
H
E D
A N
D
IN
T A
L L E
D
S H
E L V
E S
D O
T
F U
R N
IS
H
E D
A
IN
T A
L L E
D
E1
16' - 8" 16' - 8" 19' - 4"
E1
5' - 4" 2' - 9" 2' - 11" 5' - 8"
EYE WASH STATION
DOUBLE DRINKING FOUNTAIN
2 SIM,OPP
3 SIM,OPP
4 SIM,OPP
1A_111
105A104A
106A2
103AW1
ø 5' - 0"
1A_500
5' - 4" 8" 12' - 8"
9' - 9" 9' - 9"
22 X 23
SERVICE
SINK
127 SF
UTL./MECH.
106A1A_500
3 2
1A_5005 4
1A_500
DESK, N.I.C.
1' - 0" 3' - 4" 8' - 4"
W A
T E
R M
A
IN
A N
D V
A L V
E S
A N
D M
E T
E R
S
GAS POINT OF CONNECTION
ELEC. PANEL
102D
106A1 ø 5' - 0"
S H
E L F
S H
E L F
P.T.D.
T.P.D.
S.D.
P.T.D.
T.P.D.
S.D.
1' - 6" CLR.1' - 6" CLR.
VERIFY CONDUIT
LOCATION W/ ELEC.
E L E
C P
A N
E L
PRESSURE
WASHER
SOAP
BARREL
BOOSTER
PUMP &
MONITOR/
CONTROLS
106B1
CAB. HINGE
CAB. DOOR
CLEAR
1' - 6"
CLEAR
1' - 6"
CLEAR
1' - 6"
CLEAR
1' - 6"
3068 SF
EQUIPMENT
PLATFORM
1716 SF
WASH BAY
2270 SF
MECHANICS BAY
16' - 8" 16' - 8" 19' - 4"
52' - 8"
SAFETY CHAIN
GATE W/ LATCH1.5" DIA. SAFETY PIPE RAILING
4' - 6" 4' - 6"
/4
4' - 11" 4' - 11" 4' - 11" 3' - 0" 1' - 6"COORDINATE ALL DECK PENETRATIONS WITH MECH., ELEC. AND PLUMBING
CMU WALLS BELOW, TYP.
SOUND PANELS, TYP.
AIR
DRYER
WATER
HEATER
28' - 3 3/4" (OVERALL SAFETY RAIL SYSTEM)
CONFIRM LOCATION WITH MEP
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :1
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
E N
L A
R G
E D
C O
R E
A R
E A
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_111
1/2" = 1'-0"1A_111
1 ENLARGED CORE AREA PLAN
1/2" = 1'-0"1A_111
16 EQUIPMENT PLATFORM, PLAN
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
TYPE F1
2" 3' - 0"
2"
WINDOW TYPE NOTES:
TYPE W1
INTERIOR
(SEE SCHEDULE AND PLAN), NON-INSULATED, HM FRAME, 16 GA., TEMPERED GLASS, FACTORY PRIME
AND FIELD PAINT.
FRAME TYPE NOTES:
TYPE F1
INTERIOR
(SEE SCHEDULE AND PLAN), NON-INSULATED, 16 GA., FACTORY PRIME, FIELD PAINT.
TYPE F2
EXTERIOR
(SEE SCHEDULE AND PLAN), INSULATED, THERMALLY BROKEN, INSULATED, HM FRAME, 16 GA.
FACTORY PRIME, FIELD PAINT.
TYPE F3 RATED
INTERIOR
(SEE SCHEDULE AND PLAN), 90 MIN RATED, NON-INSULATED 16 GA. FACTORY PRIME AND FIELD PAINT.
2" 3' - 0"
2"
1A_201
1A_201
1A_201
1A_201
1A_201
TYPE F2
1A_201
2" 3' - 0"
2"
1A_201
TYPE W1
3' - 4"
3' - 4"3' - 4"
TYPE F3
RATED
2" 3' - 0"
2"
3' - 4"
1A_201
1A_201
1A_201
SIM.
TYPE D2
3' - 0"
6"
3' - 0"
6"
TYPE D4
RATED
2' - 0" 6"
TYPE OH1
16' - 0"
1A_201
1A_201
TYPE D3
3' - 0"
DOOR TYPE NOTES:
TYPE D1
INTERIOR
(SEE SCHEDULE AND PLAN), NON-INSULATED, HM DOOR, 16 GA., TEMPERED GLASS,
FACTORY PRIME AND FIELD PAINT. SEE SPEC FOR HARDWARE
TYPE D2
EXTERIOR
(SEE SCHEDULE AND PLAN), INSULATED, HM DOOR, 16 GA., INSULATED, TEMPERED GLASS,
FACTORY PRIME AND FIELD PAINT. SEE SPEC FOR HARDWARE
TYPE D3
INTERIOR
(SEE SCHEDULE AND PLAN), NON-INSULATED, HM DOOR, FACTORY PRIME AND FIELD PAINT.
SEE SPEC FOR HARDWARE
TYPE D4
INTERIOR
(SEE SCHEDULE AND PLAN), 90 MIN. RATED, INSULATED, HM DOOR, 16 GA. 6" X 27" FIRE
GLASS, FACTORY PRIME AND FIELD PAINT. SEE SPEC FOR HARDWARE
TYPE OH1
EXTERIOR
INSULATED SECTIONAL OVERHEAD DOOR W/VIEWING LITES, SEE SPEC.
3' - 0"
6" 6"
TYPE D1
1A_201
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :1
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
D O
O R
F
R A
M E
E L E
V A
T
IO
N S
D
E T
A
IL
S S
C H
E D
U L E
S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_200
DOOR AND FRAME NOTES
SEE SPEC
ABBREVIATIONS
HM - HOLLOW METAL
STL - STEEL
TEMP - TEMPERED GLASS
LOC. - LOCATION
MTL. - MATERIAL
MFG. FIN. - MANUFACTURER FINISH
ROOM FINISH SCHEDULE
NO ROOM NAME FLR BASE
WALLS
CIELING HEIGHT NOTESN S E W
101 WASH BAY F1 N/A W1/SAP1 W1/SAP1 W1/SAP1 W1/SAP1 C2 VARIES SEE SPEC.
102 MECHANICS BAY F1 N/A W1/SAP1 W1/SAP1 W1/SAP1 W1/SAP1 C2 VARIES SEE SPEC.
103 OFFICE & PARTS F2 N/A W1 W1 W1 W1 C1 9'-4" SEE SPEC.
104 R.R. F2 N/A W2 W2 W2 W2 C1 9'-4" SEE SPEC.
105 R.R. F2 N/A W2 W2 W2 W2 C1 9'-4" SEE SPEC.
106A UTL./MECH. F1 N/A W1 W1 W1 W1 C1 9'-4" SEE SPEC.
106B UTL./ELEC. F1 N/A W1 W1 W1 W1 C1 9'-4" SEE SPEC.
107 EQUIPMENT PLATFORM F1 N/A W1/SAP1 N/A W1/SAP1 W1/SAP1 C2 VARIES SEE SPEC.
108 WELDING STATION F1 N/A W1/SAP1 N/A W1 W1/SAP1 C2 VARIES SEE SPEC.
EMG EXIST. MG N/A N/A N/A N/A N/A N/A N/A N/A N/A
ROOM TYPE KEY:
FLOORS:
F1 - SMOOTH STEEL TROWEL FINISH CONCRETE W/ PROTECTIVE COATING/SEALED
F2 - POLISHED CONCRETE, SEALED
WALLS:
W1 - PRIME AND PAINT
W2 - PRIME AND PAINT, EXPOXY PAINT
SOUND ABSORBATION PANELS:
SAP1 - PANELS ABOVE GARAGE DOOR WALLS FROM 15' AFF TO 19' AFF. SEE DWGS.
CEILING:
C1 - PRIME AND PAINT EXPOSED DECK
C2 - STEEL TRUSS AND METAL DECK, SEE SPEC.
DOOR & FRAME SCHEDULE
NO ROOM
DOOR FRAME
NOTESLOC. RTG. W. H. TYPE MATL. / FIN. THK. GLAZ. TYPE RTG. MATL./ FIN. W. H. THK.
101A WASH BAY EXT. N/A 16' - 0" 14' - 0" OH1 STL./MFG. FIN. 2" VIEWING LITES N/A N/A N/A N/A N/A N/A SEE SPEC
101B WASH BAY EXT. N/A 16' - 0" 14' - 0" OH1 STL./MFG. FIN. 2" VIEWING LITES N/A N/A N/A N/A N/A 8 3/4" SEE SPEC
101C WASH BAY EXT. N/A 3' - 0" 7' - 0" D2 HM / PAINT 1 3/4" 30"x30" TEMP. INSUL. F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
102A MECHANICS BAY EXT. N/A 3' - 0" 7' - 0" D2 HM / PAINT 1 3/4" 30"x30" TEMP. INSUL. F1 N/A HM/PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
102B MECHANICS BAY EXT. N/A 16' - 0" 14' - 0" OH1 STL./MFG. FIN. 2" VIEWING LITES N/A N/A N/A N/A N/A N/A SEE SPEC
102C MECHANICS BAY EXT. N/A 16' - 0" 14' - 0" OH1 STL./MFG. FIN. 2" VIEWING LITES N/A N/A N/A N/A N/A N/A SEE SPEC
102D MECHANICS BAY EXT. N/A 3' - 0" 7' - 0" D1 HM / PAINT 1 3/4" 30"x30" TEMP. INSUL. F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
102E MECHANICS BAY EXT. 90 MIN. 3' - 0" 7' - 0" D3 HM / PAINT 1 3/4" 6"x27" FIRE GLASS F2 90 MIN. HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
103A OFFICE & PARTS INT. N/A 3' - 0" 7' - 0" D1 HM / PAINT 1 3/4" 30"x30" TEMP F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
104A R.R. INT. N/A 3' - 0" 7' - 0" D2 HM / PAINT 1 3/4" N/A F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
105A R.R. INT. N/A 3' - 0" 7' - 0" D2 HM / PAINT 1 3/4" N/A F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
106A1 UTL./MECH. INT. N/A 3' - 0" 7' - 0" D1 HM / PAINT 1 3/4" 30"x30" TEMP. F1 N/A HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
106A2 UTL./MECH. INT. 90 MIN. 3' - 0" 7' - 0" D3 HM / PAINT 1 3/4" N/A F2 90 MIN. HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
106B1 UTL./ELEC. INT. N/A 3' - 0" 7' - 0" D3 HM / PAINT 1 3/4" N/A F1 N/A HM/PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
EMG EXISTING MG EXT. 90 MIN. 3' - 0" 7' - 0" D3 HM / PAINT 1 3/4" 6"x27" FIRE GLASS F2 90 MIN. HM / PAINT 3'-4" 7'-4" 8 3/4" SEE SPEC
GENERAL FINISH NOTES:
1. METAL DOOR JAMBS AND WINDOW FRAMES: PAINT FINISH
ENAMEL COLOR TO BE SELECTED FROM MFG. STANDARDS
2. METAL DOORS: ENAMEL COLOR TO BE SELECTED FROM MFG.
STANDARDS
3. EXPOSED METAL FABRICATIONS: ENAMEL COLOR TO BE
SELECTED FROM MFG. STANDARDS
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
INSULATED PRECAST
CONCRETE WALL FACTORY INSTALLED
BLOCKING
SEALANT W/BACKER ROD
CONT. AT PERIMETER
BOTH SIDES, TYP.
DRIP REVEAL
THERMALLY BROKEN HOLLOW
METAL DOOR FRAME. FILL W/
EXTR. POLYSTYRENE RIGID
INSULATION
EXTERIOR INTERIOR
1"
8 3/4"
INSULATED DOOR AS SCHEDULED
1' - 0"
INSULATED PRECAST
CONCRETE WALL
TREATED 2X (TYP.)
DOOR TRACK ASSEMBLY
DOOR ROLLER AND
MOUNTING BRACKET
INSULATED OVERHEAD
DOOR AS SCHEDULED
NEOPRENE DOOR GASKET SEAL
INTERIOR
EXTERIOR
INSULATED PRECAST
CONCRETE WALL
TREATED 2X (TYP.)
PER DOOR MFG.
ROLLER TRACK
INSULATED OVERHEAD DOOR AS SCHEDULED
MOUNTING BRACKET1/2" CHAMFER
NEOPRENE DOOR GASKET SEAL
INTERIOREXTERIOR
DRIP REVEAL
1"
1' - 0"
SEALANT W/BACKER ROD
CONT. AT PERIMETER
BOTH SIDES TYP.
FACTORY INSTALLED BLOCKING
ANCHOR PER MFG.
THERMALLY BROKEN
HOLLOW METAL FILL W/
EXTRUDED POLYSTYRENE
RIGID INSULATION
EXTERIOR
INTERIOR
/4
INSULATED PRECAST
CONCRETE PANEL
THRESHOLD, ANCHOR PER MFG.
EXTERIOR INTERIOR
THERMALLY BROKEN
H.M. FRAME AS SCHEDULED
INSULATED DOOR AS SCHEDULED 1' - 0"
8 3/4"
3"
FOOTING, SEE STRUCTURAL
EXTERIOR SLAB INTERIOR SLAB
INSULATED PRECAST
CONCRETE PANEL
TRACK ASSEMBLY
1/2" EXPANSION JOINT W/ SEALANT CAP
EXTERIOR INTERIOR
FOOTING SEE STRUCTURAL
INSULATED OVERHEAD
DOOR AS SCHEDULED
DOOR WEATHER SEAL
1' - 0"
SLOPED CONCRETE
APPROACH
SEAL AT BOTTOM OF DOOR
GARAGE FLOOR SLAB
SEE STRUCTURAL
SLOPED EDGE SEE STRUCURAL
1' - 0"
GROUTED HM FRAME
8" CMU SEALANT AT PERIMETER
BOTH SIDES, TYP.
GLAZING AS SCHEDULED
/4
INTERIOR
INTERIOR
2"
GROUTED HM FRAME
8" CMU BOND BEAM SEE STRUCTURAL
SEALANT AT PERIMETER
BOTH SIDES, TYP.
GLAZING AS SCHEDULED
8 3/4"
GROUTED HM FRAME
8" CMU
SEALANT AT PERIMETER
BOTH SIDES, TYP.
DOOR AS SCHEDULED
INTERIOR
ANCHOR PER MFG.
/4
INTERIOR
2"
GROUTED HM FRAME
CMU BOND BEAM SEE STRUCT.
SEALANT AT PERIMETER
BOTH SIDES TYP.
DOOR AS SHEDULED
8 3/4"
INTERIOR INTERIOR
8" PRECAST CONCRETE WALL
SEALANT W/BACKER ROD
CONT. AT PERIMETER
BOTH SIDES, TYP.
GROUTED H.M. FRAME
INTERIOR INTERIOR
8 3/4"
DOOR AS SCHEDULED
ANCHOR PER MFG.
8"
8" PRECAST CONCRETE WALL
SEALANT W/BACKER ROD
CONT. AT PERIMETER
BOTH SIDES, TYP.
GROUTED H.M. FRAME
INTERIOR
INTERIOR
/4
2"
DOOR AS SCHEDULED
ANCHOR PER MFG.
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :1
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
D O
O R
D E
T A
IL
S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_201
1 1/2" = 1'-0"1A_201
1 INSUL. DOOR HEAD DETAIL, EXT.
1 1/2" = 1'-0"1A_201
7 DOOR JAMB DETAIL, INSUL. OVERHEAD DOOR, EXT.
1 1/2" = 1'-0"1A_201
2 DOOR HEAD DETAIL INSUL. OVERHEAD DOOR EXT.
1 1/2" = 1'-0"1A_201
6 INSUL. JAMB DETAIL, EXT.
1 1/2" = 1'-0"1A_201
11 INSULATED STOOP/SILL DETAIL, EXT.
1 1/2" = 1'-0"1A_201
12 DOOR SILL DETAIL, INSUL. OVERHEAD DOOR, EXT.
1 1/2" = 1'-0"1A_201
8 WINDOW JAMB DETAIL, INT. CMU
1 1/2" = 1'-0"1A_201
3 WINDOW HEAD AND SILL 2" DETAIL, INT. CMU
1 1/2" = 1'-0"1A_201
9 DOOR JAMB DETAIL, INT. CMU
1 1/2" = 1'-0"1A_201
4 DOOR HEAD DETAIL, INT. CMU
1 1/2" = 1'-0"1A_201
5 DOOR HEAD DETAIL, INT. PRECAST
1 1/2" = 1'-0"1A_201
10 DOOR JAMB DETAIL, INT. PRECAST
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
(R E
V E
A L
(R E
V E
A L
(R E
V E
A L
TOP OF EXIST MG PRECAST
22' - 0"
TOP OF EXIST MG FLOOR
0"
EQ EQEQ EQ
9' - 2"
T Y
P
2' - 0" 26' - 0" 14' - 0" 18' - 0" 4' - 0"
102C 101B 102D
6' - 0" 16' - 0" 8' - 0" 6' - 0" 8' - 0" 16' - 0" 4' - 0"
10' - 8" 64' - 0" (OVERAL BUILDING)
COORDINATE SCUPPER
LOCATION W/ . TYP.
OVHD DOOR
14' - 0"
EXHAUST FANS VERIFY W/ MECH. EXHAUST FANS VERIFY W/ MECH.
2' - 4" 3' - 4" 2' - 4"
12" X 12" X 6" BOX & 2-WAY
ANTENNA COORDINATE LOCATION
W/ IDOT
EQ EQ
EXHAUST, VERIF W/ MECH.
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
15' - 0"
101C
(R E
V E
A L
(R E
V E
A L
10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0"
80' - 0" (OVERAL BUILDING)
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
/2
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
EXHAUST, VERIFY
W/ MECH.
3' - 4" 6' - 8"
EXHAUST, VERIFY W/ MECH.
EXHAUST, VERIFY W/ MECH.
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
TOP OF EXIST MG PRECAST
22' - 0"
TOP OF EXIST MG FLOOR
0"
102A 102B101A
4' - 0" 16' - 0" 8' - 0" 6' - 0" 8' - 0" 16' - 0" 6' - 0" 9' - 2"
(R E
V E
A L
(R E
V E
A L
(R E
V E
A L
64' - 0" (OVERAL BUILDING) 10' - 8"
OVHD DOOR
14' - 0"
EQ EQ EQ EQEQ EQ
2' - 4" 3' - 4" 2' - 4"
EXHAUST, VERIF W/ MECH.
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
(R E
V E
A L
(R E
V E
A L
(R E
V E
A L
V E
R
IF
Y W
S
T R
U C
T U
R A
L
T
Y P
102E
10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0" 10' - 0"
80' - 0" (OVERAL BUILDING)
/2
V E
R
IF
Y W
S
T R
U C
T U
R A
L
3' - 4"3' - 4"3' - 4"
EXHAUST, VERIFY W/ MECH. EXHAUST, VERIFY W/ MECH.
FINISH FLOOR
0"
TOP OF EXIST MG PRECAST
22' - 0"
TOP OF EXIST MG FLOOR
0"
4' - 0" 4' - 0"
8' - 0"
EMG
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :1
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
E X
T E
R
IO
R E
L E
V A
T
IO
N S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_300
1/8" = 1'-0"1A_300
1 EAST ELEVATION
1/8" = 1'-0"1A_300
2 NORTH_ELEVATION
1/8" = 1'-0"1A_300
4 WEST ELEVATION
1/8" = 1'-0"1A_300
3 SOUTH ELEVATION
1/8" = 1'-0"1A_300
5 NEW DOOR AT EXISTNG MG
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
FINISH FLOOR
0"
Knee Wall 2' - 0"
TOP OF PRECAST
26' - 0"
ACCOUSTIC PANELS TYP.
TOP OF EXIST MG PRECAST
22' - 0"
TOP OF EXIST MG FLOOR
0"
2270 SF
MECHANICS BAY
1716 SF
WASH BAY
EXISTING MG
AVAILABLE CRANE LIFT
17' - 0"
102C 102D
101B
53 SF
UTL./ELEC.
106B
ROOF TRUSSES, SEE STRUCTURAL
OVHD DOOR
14' - 0"
SAFTEY RAILING
TROLLEY HOIST BEAM
19' - 6"
30' - 0" (CEILING MOUNTED CRANE)
EXHAUST FANS SEE MECHANICAL EXHAUST FANS SEE MECHANICAL
ACCOUSTIC PANELS TYP.
ACCOUSTIC
PANELS TYP.
106B1
MECHANICAL LEVEL
9' - 10"
MECHANICAL LEVEL
9' - 10"
FINISH FLOOR
0"
FINISH FLOOR
0"
TROLLEY HOIST
TOP OF PRECAST
26' - 0"
TOP OF PRECAST
26' - 0"
ACOUSTIC PANELS TYP.
AVAILABLE CRANE LIFT
17' - 0"
AVAILABLE CRANE LIFT
17' - 0"
2270 SF
MECHANICS BAY
3068 SF
EQUIPMENT
PLATFORM
/2
WELDING STATION
277 SF
105A104A103A
W1
102B 102C
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
ROOF TRUSSES, SEE STRUCTURAL
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
" OVHD DOOR
14' - 0"
OVHD DOOR
14' - 0"
106A1
TROLLEY HOIST BEAM
19' - 6"
TROLLEY HOIST BEAM
19' - 6"
20' - 0"38' - 0" (CEILING MOUNTED CRANE)20' - 0"
BOLLARD(S) TYP.(S
E
E E
L E
C F
O R
H E
IG
H
T T
Y P
ROOF DRAINS SEE ROOF PLAN, COORDINATE
PATH OF TRAVEL THOUGH THE BUILDING
EXHAUST FAN SEE MECHANICAL
SAFTEY RAIL SYSTEM W/GATE
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
ACOUSTIC PANELS TYP.
ACOUSTIC PANELS TYP.
TOP OF EXIST MG PRECAST
22' - 0"
TOP OF EXIST MG FLOOR
0"
EXISTING MG
10' - 8"
9' - 2"
AVAILABLE CRANE LIFT
17' - 0"
1716 SF
WASH BAY
2270 SF
MECHANICS BAY
270 SF
WELDING STATION
10' - 8"
9' - 2"
101A 102A
102B
ACOUSTIC PANELS TYP.
OVHD DOOR
14' - 0"
TROLLEY HOIST BEAM
19' - 6"
30' - 0" (CEILING MOUNTED CRANE)
ROOF TRUSSES, SEE STRUCTURAL
FINISH FLOOR
0"
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
TOP OF PRECAST
26' - 0"
BOLLARD(S) TYP.
1716 SF
WASH BAY
ACOUSTIC PANELS TYP.
101B
101C
101A
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
ROOF TRUSSES, SEE STRUCTURAL
OVHD DOOR
14' - 0"
OVHD DOOR
14' - 0"
(S E
E E
L E
C F
O R
H E
IG
H
T T
Y P
ROOF DRAINS SEE ROOF PLAN, COORDINATE
PATH OF TRAVEL THOUGH THE BUILDING
EXHAUST FAN SEE MECHANICAL
FINISH FLOOR
0"
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
TOP OF PRECAST
26' - 0"
1A_401
1716 SF
WASH BAY
ACOUSTIC PANELS TYP.
106A2
101A101B
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
ROOF TRUSSES, SEE STRUCTURAL
OVHD DOOR
14' - 0"
OVHD DOOR
14' - 0"
BOLLARD(S) TYP.
ROOF DRAINS SEE ROOF PLAN, COORDINATE
PATH OF TRAVEL THOUGH THE BUILDING
EXHAUST FAN SEE MECHANICAL
FINISH FLOOR
0"
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
TOP OF PRECAST
26' - 0"
AVAILABLE CRANE LIFT
17' - 0"
AVAILABLE CRANE LIFT
17' - 0"
/2
ACOUSTIC PANELS TYP.
2270 SF
MECHANICS BAY
102B
102C
ROOF TRUSSES, SEE STRUCTURAL
OVHD DOOR
14' - 0"
OVHD DOOR
14' - 0"
102E
TROLLEY HOIST BEAM
19' - 6"
TROLLEY HOIST BEAM
19' - 6"TROLLEY HOIST
20' - 0" 38' - 0" (CEILING MOUNTED CRANE) 20' - 0"
(V E
R
IF
Y W
S
T R
U C
T U
R A
L
BOLLARD(S) TYP. (S
E
E E
L E
C F
O R
H E
IG
H
T T
Y P
ROOF DRAINS SEE ROOF PLAN, COORDINATE
PATH OF TRAVEL THOUGH THE BUILDING
EXHAUST FAN SEE MECHANICAL
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :2
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
B U
IL
D
IN
G
S E
C T
IO
N
S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_400
1/8" = 1'-0"1A_400
6 SECTION LOOKING EAST AT HIGH SIDE OF ROOF END
1/8" = 1'-0"1A_400
4 MECHANIC'S BAY SECTION 2, LOOKING NORTH
1/8" = 1'-0"1A_400
5 SECTION LOOKING WEST AT LOW SIDE OF ROOF END
1/8" = 1'-0"1A_400
2 WASH BAY SECTION 2, LOOKING NORTH
1/8" = 1'-0"1A_400
1 WASH BAY SECTION 1, LOOKING SOUTH
1/8" = 1'-0"1A_400
3 MECHANIC'S BAY SECTION 1, LOOKING SOUTH
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
R-10 RIGID INSULATION
INTERIOR CONCRETE SLAB
EXPANSION JOINT WITH
SEALANT CAP
FINISH FLOOR
0"
INSULATED PRECAST
CONC. WALL PANEL
PER MFG.
TOP OF PRECAST
26' - 0"
SLOPE
1A_401
E1
EXPANSION JOINT
WITH SEALANT CAP
EXTERIORINTERIOR
APPROVED SUBGRADE SEE SPEC.
RIENFORCED CONCRETE
FOUNDATION SEE STRUCTURAL
(R
E V
E A
L
(R E
V E
A L
1716 SF
WASH BAY
GRANULAR FILL
EXPANSION JOINT
WITH SEALANT CAP
FINISH FLOOR
0"
INSULATED PRECAST
CONC. WALL PANEL PER
MFG.
TOP OF PRECAST
26' - 0"
SLOPE
EXPANSION JOINT
WITH SEALANT CAP
1A_401
CONCRETE SLAB
(SEE STRUCTURE)
DRAINAGE SEE PLAN
EXTERIORINTERIOR
(R
E V
E A
L
(R E
V E
A L
ROOF TRUSS SEE STRUCT.
E1
2270 SF
MECHANICS BAY
R-10 RIGID INSULATION
APPROVED SUBGRADE SEE SPEC.
RIENFORCED CONCRETE FOUNDATION SEE STRUCTURAL
GRANULAR FILL
1x4 TREATED
INSULATED PRE CAST
CONC. PANEL.
STEEL ANGLE AND EMBADED
PLATE, SEE STRUCTURAL
ROOF JOIST, SEE STRUCTURAL
R-30 POLYISOCYANURATE ROOF INSUL.
MECH. ATTACHED
EPDM COUNTERFLASHING
PREFINISHED METAL
FLASHING MATCH HEIGHT
AT ADJACENT COPINGS
1/4" COVER BOARD
VAPOR BARRIER BASE SHEET. FULLY ADHERE
TO DECK AND PANEL PER EPDM MFG.
26'-0"
24'-10"
TOP OF ANGLE
TOP OF PRECAST WALL
SEALANT
FACTORY INSULATED BLOCKING
2X TREATED WOOD TOP PLATE, TYP.
E1
3" METAL DECK
FULLY ADHERED 60 MIL EPDM MEMBRANE
3/4" TRATED PLYWOOD, TYP.
VAPOR BARRIER BASE SHEET. FULLY
ADHERE TO TOP OF PANEL EPDM MFG.
1x4 TREATED BLOCKING
INSULATED PRE CAST
CONC. WALL PANEL.
3" METAL DECK
R-30 POLYISOCYANURATE
ROOF INSUL. MECH. ATTACHED
STEEL ANGLE AND EMBEDDED
PLATE SEE STRUCTURAL
2X TREATED TOP PLATE, TYP.
EPDM COUNTERFLASHING
PREFINISHED METAL FLASHING MATCH
HEIGHT AT ADJACENT COPINGS
1/4" COVER BOARD
FULLY ADHERED 60
MIL EPDM MEMBRANE
26'-0"
23'-2"
TOP OF ANGLE
TOP OF PRECAST WALL
SEALANT
FACTORY INSULATED BLOCKING
3/4" TREATED PLYWOOD
E1
VAPOR BARRIER BASE
SHEET. FULLY ADHERE
PER EPDM MFG.
ROOF JOIST SEE STRUCTURAL
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
1/4" COVER BOARD
1x4 TREATED BLOCKING
INSULATED PRE CAST
CONC. WALL PANEL.
R-30 POLYISOCYANURATE ROOF INSUL.
MECH. ATTACHED
2X TREATED TOP PLATE, TYP.
EPDM COUNTERFLASHING
PREFINISHED METAL FLASHING MATCH
HEIGHT AT ADJACENT COPINGS
1/4" COVER BOARD
FULLY ADHERED VAPOR BARRIER BASE
SHEET PER EPDM MANUF.
26'-0"
VARIES
TOP OF ANGLE
TOP OF PRECAST WALL
SEALANT
FACTORY INSULATED BLOCKING
3/4" TREATED PLYWOOD
FULLY ADHERED 60 MIL EPDM MEMBRANE
E1
3" METAL DECK
STEEL ANGLE AND EMBEDED
PLATE SEE STRUCTURAL
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
1/4" COVER BOARD
1x4 TREATED BLOCKING
INSULATED PRE CAST
CONC. WALL PANEL.
R-30 POLYISOCYANURATE ROOF
INSUL. MECH. ATTACHED
2X TREATED BLOCKING, TYP.
EPDM COUNTERFLASHING
PREFINISHED METAL FLASHING MATCH
HEIGHT AT ADJACENT COPINGS
1/4" COVER BOARD
FULLY ADHERED 60 MIL EPDM MEMBRANE
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
26'-0"
TOP OF PRECAST WALL
SEALANT
FACTORY INSTALLED
BLOCKING
3/4" TREATED PLYWOOD
SEALANT
8"
/2
FULLY ADHERED 60 MIL EPDM MEMBRANE
1/4" COVER BOARD
E1
2X TREATED WOOD BLOCKING, TYP.
3"
2X TREATED BLOCKING
SEALANT
3" METAL DECK
TRUSS TOP CHORD
SEE STRUCTURAL
23'-2"
TOP OF ANGLE
FULLY ADHERED 60 MIL EPDM MEMBRANE
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
FACTORY INSTALLED BLOCKING
METAL FLASHING
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
VAPOR BARRIER BASE SHEET.
FULLY ADHERE PER EPDM MFG.
METAL FLASHING
STEEL ANGLE AND EMBEDED
PLATE SEE STRUCTURAL
FULLY ADHERED 60
MIL EPDM MEMBRANE
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
1A_401
BOLLARD, TYP.
CONCRETE APPROACH
REINFORCED CONCRETE
FOOTING SEE STRUCTURAL
1A_201
1A_201
INTERIOR
R10 RIDGID
E1
1716 SF
WASH BAY
GRANULAR FILL
ROOF TRUSS,
SEE STRUCTURAL
(R E
V E
A L
INSULATED
PRECAST CONC.
WALL PANEL PER
MFG.
OVHD DOOR TRACK
ASSEMBLY
SOUND ATTENUATION
PANELS BEYOND
OVHD DOOR
14' - 0"
EXTERIOR
DRAINAGE SEE PLAN
GRANULAR FILL
101B
APPROVED SUBGRADE SEE SPEC.
/2
/2
/4
/4
1/2" = 1'-0"1A_401
6 WALL SECTION AT SIDE WALL, TYP.
1/2" = 1'-0"1A_401
7 WALL SECTION LOW END
1 1/2" = 1'-0"1A_401
4 PARAPET DETAIL @ HIGH END OF ROOF
1 1/2" = 1'-0"1A_401
3 PARAPET DETAIL AT ROOF LOW END
1 1/2" = 1'-0"1A_401
2 PARAPET AT SIDEWALL
1 1/2" = 1'-0"1A_401
1 OVERFLOW SCUPPER DETAIL
1/2" = 1'-0"1A_401
8 SECTION AT OVHD DOOR, HIGH END
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :2
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
W A
L L S
E C
T
IO
N S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_401
6" = 1'-0"1A_401
5 REVEAL DETAIL
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
UNDER GROUND
CONDUIT, VERIFY
W/ MEP
W A
T E
R M
A
IN
V
A L V
E S
A
M
T E
R S
V E
R F
Y W
M
E P
106A1 AIR
COMP.
BOOSTER
PUMP
ELEC.
PNL.
106B1
2' - 8" 3' - 4" 4' - 0"
COMMS.
CABINET
1' - 4"1' - 4"
1' - 11"
C A
B
C .L
" ELEC.
PNL.
GAS POINT OF
CONNECTION
WATER MAIN AND
VALVES AND
METERS (2). VERIFY
W/ MECH/PLUMB
AIR
COMP.
4' - 0"
106B1
P.T.D.
1' - 6" CLR.
105A
S.D.
1' - 0"
GRAB BARS
T.P.D.
P.T.D.
MIRROR
GRAB BARS
T.P.D.
106A2
PRESSURE
WASHER
W A
T E
R M
A
IN
V
A L V
E S
A
M
T E
R S
V E
R F
Y W
M
E P
1' - 0"
5' - 4" 2' - 9" 2' - 11" 5' - 8"
EYE WASH STATION
DOUBLE
DRINKING
FOUNTIAN
22 X 23
SERVICE
SINK
105A104A
1' - 6" CLEAR 1' - 6" CLEAR
103A
W1
DESK, IDOT
FURNISHED AND
INSTALLED N.I.C.
SHELVES, IDOT
FURNISHED AND
INSTALLED N.I.C.
SHELVES, IDOT
FURNISHED AND
INSTALLED N.I.C.
SHELVES, IDOT
FURNISHED AND
INSTALLED N.I.C.
MECHANICAL LEVEL
9' - 10"
3068 SF
EQUIPMENT
PLATFORM
GATE 1.5" DIA. SAFETY
PIPE RAIL SYSTEM
ACOUSTICAL PANELS, TYP.
3' - 0" 1' - 6"4' - 11"4' - 11"4' - 11"4' - 6"4' - 6"
/4
19' - 4"16' - 8"16' - 8"
52' - 8"
3.5" H TOE KICK
28' - 3 3/4" (OVERALL SAFETY RAIL SYSTEM)
MECHANICAL LEVEL
9' - 10"
3068 SF
EQUIPMENT
PLATFORM
8' - 7 1/4" 2' - 0"
SAFETY CHAIN 1.5" DIA. SAFETY PIPE RAILING
3.5" H TOE KICK
10' - 0"
ACOUSTIC PANELS TYP.
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :3
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
IN
T
E R
IO
R
E L E
V A
T
IO
N S
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_500
1/4" = 1'-0"1A_500
1 UTL. MECH./ELEC. SOUTH
1/4" = 1'-0"1A_500
2 UTL. ELEC. EAST
1/4" = 1'-0"1A_500
3 UTL. ELEC WEST
1/4" = 1'-0"1A_500
4 UTL. MECH. EAST
1/4" = 1'-0"1A_500
5 UTL. MECH. WEST
1/4" = 1'-0"1A_500
6 105 R.R. SOUTH
SEE ADA DETAILS ON 1A_002 FOR
MOUNTING HIEGHTS AND LOCATIONS
1/4" = 1'-0"1A_500
7 105 R.R. WEST
SEE ADA DETAILS ON 1A_002 FOR
MOUNTING HIEGHTS AND LOCATIONS
1/4" = 1'-0"1A_500
8 105 R.R. NORTH
SEE ADA DETAILS ON 1A_002 FOR
MOUNTING HIEGHTS AND LOCATIONS
1/4" = 1'-0"1A_500
9 106A,B, NORTH
1/4" = 1'-0"1A_500
10 MECHANIC'S BAY NORTH
SEE ADA DETAILS ON 1A_002 FOR
MOUNTING HIEGHTS AND LOCATIONS
1/4" = 1'-0"1A_500
11 OFFICE & PARTS SOUTH
1/4" = 1'-0"1A_500
12 OFFICE & PARTS NORTH
1/4" = 1'-0"1A_500
13 OFFICE & PARTS EAST
1/4" = 1'-0"1A_500
14 OFFICE & PARTS ELEVATION WEST
1/4" = 1'-0"1A_500
15 EQUIPMENT PLATFORM, NORTH ELEVATION
1/4" = 1'-0"1A_500
16 EQUIPMENT PLATFORM, EAST ELEVATION
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
20' - 0" 38' - 0" (CEILING MOUNTED CRANE) 20' - 0"
Q
E Q
E Q
E Q
GALVANIZED TRUSS SEE STRUCTURAL
TRUSS SEE STRUCTURAL
TRUSS SEE STRUCTURAL
TRUSS SEE STRUCTURAL
E Q
E Q
(O
V E
R A
L L
B U
IL
D
IN
G
80' - 0" (OVERALL BUILDING)
14' - 0" 16' - 8" 16' - 8" 16' - 8" 14' - 0"
14' - 0" 16' - 8" 16' - 8" 16' - 8" 14' - 0"
EXPOSED METAL DECKING, TYP.
SEE STRUCTURAL
10' - 0" 30' - 0" 30' - 0" 10' - 0"
10' - 0" 30' - 0" 30' - 0" 10' - 0"
78' - 0"
(C
E
IL
IN
G
M O
U N
T E
D C
R A
N E
DOOR CONTROL LOCATION, COORDINATE
W/ ELEC.
DOOR CONTROL LOCATION, COORDINATE
W/ ELEC.
DOOR CONTROL LOCATION, COORDINATE W/
ELEC.
DOOR CONTROL LOCATION, COORDINATE W/ ELEC.
EXPOSED METAL DECKING, TYP.
SEE STRUCTURAL
53 SF
UTL./ELEC.
106B
59 SF
R.R.
59 SF
R.R.
2270 SF
MECHANICS BAY
153 SF
OFFICE & PARTS
127 SF
UTL./MECH.
106A
16' - 8" 16' - 8" 19' - 4"
15' - 4" 7' - 4" 7' - 4" 5' - 4" 12' - 8"
52' - 8"
RCP NOTE:
1. COORDINATE ALL DECK PENETRATIONS WITH MECH., ELEC.
AND PLUMBING
2. NO FINISHED CIELING IN THIS AREA, EXPOSED DECK
1' - 0"
9' - 0" A.F.F 9' - 0" A.F.F
4' - 8" 8' - 0" 8' - 0" 4' - 8"
NO CLNG. OPEN TO ABOVE
12' - 8" 12' - 8"
WELDING EXHAUST SYSTEM
13' SWIVEL ARM RADIUS, MOUNTED
AT 10' - 0" OFF FLOOR
WELDING EXHAUST SYSTEM MAX.
EXTENSION OF FLEXIBLE EXHAUST ARM
A .F
.F
A .F
.F
9' - 0" A.F.F
1' - 8" 4' - 0" 4' - 0" 4' - 0" 1' - 8"
3' - 8" 3' - 8" 3' - 8" 3' - 8" 2' - 8" 2' - 8"
2' - 4" 4' - 0" 4' - 0" 2' - 4"
270 SF
WELDING STATION
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/2
/2
:5 :3
A
M
G A
R N
E R
M W
F A
C
IL
IT
Y
R E
F L E
C T
E D
C E
IL
IN
G P
L A
N
H w y
E
G a rn e r, I A
28 JAN 25
BG-1G32 (000)--80-41
HANCOCK 2
1A_610
CEILING PLAN LEGEND:
2X2 LIGHT FIXTURE
SUPPLY DUCT
(SEE MECHANICAL)
RETURN DUCT
(SEE MECHANICAL)
STRIP LIGHT FIXTURE
GENERAL NOTES:
1. SEE ELECTRICAL DRAWINGS/SPEC. FOR FIXTURE MODEL AND
REQUIREMENTS.
2. LIGHT FIXTURES TO BE SURFACE MOUNTED. SEE ELECTRICAL
AND STRUCTURAL FOR MOUNTING REQUIREMENTS DUCTWORK,
CONDUIT AND PIPING TO BE EXPOSED
3. COORDINATE LIGHTING W/ ELEC.,STRUCT, AND MECH. TO
ENSURE ALL REQUIRED CLEARANCES ARE MET
4. SEE SHEET A103 ENLARGED CORE AREA FOR CORE AREA RCP.
WALL MOUNTED FIXTURE
DOWN LIGHT FIXTURE
3/16" = 1'-0"1A_610
2 FIRST FLOOR RCP
3/16" = 1'-0"1A_610
1 ENLARGED CORE AREA REFLECTED CEILING PLAN
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
C om
1' - 0" 78' - 0" 1' - 0"
15' - 0"
80' - 0" (OVERALL BUILDING)
(O
V E
R A
L L
B U
IL
D
IN
G
RD-1
RD-1
RD-1
EXISTING MG
ROOF SLOPE
ROOF SLOPE
ROOF SLOPE
RIDGE
10' - 0"
MAU, SEE MECH.
RIDGE
RIDGE
RD-1
COORDINATE ROOF DRAINS
W/ STRUCTURAL, TYP.
60 MIL FULLY
ADHERED EPDM,
TYP.
MAU, SEE MECH.
(O
V E
R A
L L
B U
IL
D
IN
G
FINISH FLOOR
0"
TOP OF PRECAST
26' - 0"
1A_700
HEAVY DUTY TUBULAR LADDER, PER MFG.
GRADE
PRECAST WALL
3/16" ALUMINUM BRACKET, PER MFG.
3/16" ALUMINUM BRACKET, PER MFG.
3/16" ALUMINUM BRACKET, PER MFG.
LADDER SAFETY CAPS PER MFG.
1/4" X 3/4" SS HHMB W LOCK NUT AND FLAT WASHER
3/16" ALUMINUM BRACKET AT 10'-0" O.C. MAX
3/8" ANCHOR BOLT EPOXY INTO PRECAST WALL
ALLOY RUNG
EXTRUDED ALUMINUM CHANNEL RAIL
EXTRUDED ALUMINUM COVER PLATE
#12 X 1 1/4" S.S. SELF TAPPING SCREW
PRECAST CONCRETE PANEL
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299