g. Test and Balance-INRC Dispatch Office.pdf

PDF 1 MB Posted

Attached to
Interagency Natural Resource Center (INRC) Heating, Ventilation, Air Conditioning (HVAC) Preventative Maintenance (PM)
Solicitation number
1284LL25Q0012
Issued by

About this file

This document is a National Environmental Balancing Bureau (NEBB) Certified Test and Balance Report for the INRC Warehouse located at 3815 Schrieber Way in Coeur d'Alene, Idaho. The report, prepared by Riley Engineering, Inc. on 3/21/2025, documents the testing, adjusting, and balancing of environmental systems for the facility, specifically focusing on air handling units FN-2, FN-3, and FN-5.

The report includes detailed air apparatus and air outlet test reports for three different units, measuring parameters such as supply air CFM, outside air CFM, return air CFM, motor data, and electrical characteristics. The testing revealed that most air outlets were operating within 73-97% of their design airflow, with some variations noted. The document also includes NEBB certification for Riley Engineering, Inc., instrument calibration certificates for various measurement tools (including flow hoods, thermometers, humidity meters, and electrical meters), and a comprehensive list of abbreviations used in the technical documentation.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-Mail: tim@rileyeng.com

Prepared by:

Riley Engineering, Inc.

P.O. Box 48167

Spokane, Washington 99228

509-325-2576

Coeur d'Alene, Idaho 83815

TEST AND BALANCE REPORT

NEBB Certification No. 3208

INRC Warehouse

Sandy Text Box USFS - CDA Dispatch Office Reorganization

PROJECT: DATE: 3/21/2025

NAME

ADDRESS

ARCHITECT:

NAME

ADDRESS

PHONE

DESIGN ENGINEER:

NAME

ADDRESS

PHONE

MECH. CONTRACTOR:

NAME

ADDRESS

PHONE

NEBB TAB FIRM:

NAME

ADDRESS

PHONE

Riley Engineering, Inc

Hayden, ID 83835

(208) 772-3911

P.O. Box 48167

Spokane, WA 99228

(509) 325-2576

Metalcraft Mechanical LLC

11547 N. Warren

406.542.8880

3011 Palmer St.

Missoula, MT 59808

Morrison-Maierle, inc.

406.721.5643

222 N Higgins

Missoula, MT 59802

A&E Architects

3815 Schrieber Way

Coeur d'Alene, Idaho 83815

CERTIFIED TEST, ADJUST AND BALANCE REPORT

INRC Warehouse ii

PROJECT

National Environmental Balancing Bureau

CERTIFICATION NO. CERTIFICATION EXPIRATION DATE December 31, 2025

REPORT DATE 3/21/2025

NEBB QUALIFIED TAB SUPERVISOR NAME Tim Kenagy

CERTIFICATION

INRC Warehouse

"THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND

FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT

EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND

BALANCING OF ENVIRONMENTAL SYSTEMS . ANY VARIANCES FROM DESIGN QUANTITIES,

WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE

REPORT PROJECT SUMMARY."

SUBMITTED & CERTIFIED BY:

NEBB CERTIFIED TAB FIRM NAME Riley Engineering, Inc.

iii

Project: Kootenai Elementary SchoolINRC Warehouse

NEBB CERTIFICATES PAGE 13

TABLE OF CONTENTS

AIR APPARATUS REPORTS – FN

AIR OUTLET TEST REPORTS – FN

LIST OF ABBREVIATIONS

INSTRUMENT CALIBRATION RECORD

iv

DESIGN ACTUAL

1/2 3/4

RPM NA NA

Rated Volts NA 115 Rated Amps NA 12.9 Phase NA 1 Operation Hz 60 60 Service Factor NA NA

115 120

12.9 6.3

DESIGN ACTUAL

1120 (3) 993 (1) DESIGN ACTUAL

Outside Air CFM 130 140 (2) Return Air CFM 990 915 Number of Pre-Filters NA 2

Pre-Filter Size NA 16x25x1 Number of Final Filters NA 1 Final Filter Size NA 24x24x1 Motor Sheave NA Direct Drive

Discharge S.P. in. NA 0.23 Motor Sheave OD NA NA Suction S.P. in. NA -0.30 Motor Sheave Bore NA NA

Fan Sheave NA NA

0.50 0.53 Fan Sheave Bore NA NA

Fan RPM NA High Sheave Center Distance NA NA Number of Belts NA NA Belt Size NA NA

REMARKS:

UNIT DATA MOTOR DATA

RILEY ENGINEERING, INC.

AIR APPARATUS TEST REPORT

INRC Warehouse SYSTEM/UNIT FN-2

Unit Designation FN-2 HP Manufacturer Carrier Model Number 59TP6A060E17--14 Serial Number 1918A44232

Operating Volts Operating Amps

FAN DATA

Supply Air CFM OTHER DATA

External S.P. in.

National Environmental Balancing Bureau

TEST DATE: 3/21/2025

READINGS BY: J. Lazuhrcatt

OSA Damper position = 12%

(1) Fan on highest speed.

(2) Left as found.

(3) Grill total = 1105

1 1

RPM NA NA

Rated Volts NA 115 Rated Amps NA 14.7 Phase NA 1 Operation Hz 60 60 Service Factor NA NA

115 120

14.7 8.6

DESIGN ACTUAL

1610 1503 (1) DESIGN ACTUAL

Outside Air CFM 320 345 (2) Return Air CFM 1290 1184 Number of Pre-Filters NA 2

Pre-Filter Size NA 20x24x1 Number of Final Filters NA 1 Final Filter Size NA 20x20x1 Motor Sheave NA Direct Drive

Discharge S.P. in. NA 0.17 Motor Sheave OD NA NA Suction S.P. in. NA -0.20 Motor Sheave Bore NA NA

Fan Sheave NA NA

0.50 0.37 Fan Sheave Bore NA NA

Fan RPM NA NA Sheave Center Distance NA NA Number of Belts NA NA Belt Size NA NA

REMARKS: OSA Damper position = 31%

(1) Fan on high speed

(2) Left as is.

UNIT DATA MOTOR DATA

RILEY ENGINEERING, INC.

AIR APPARATUS TEST REPORT

INRC Warehouse SYSTEM/UNIT FN-3

Unit Designation FN-3 HP Manufacturer Carrier Model Number 59TP6A080E21--20 Serial Number 4717A47610

Operating Volts Operating Amps

FAN DATA

Supply Air CFM OTHER DATA

External S.P. in.

National Environmental Balancing Bureau

TEST DATE: 3/21/2025

READINGS BY: J. Lazuhrcatt

3/4 3/4

RPM NA NA

Rated Volts NA 115 Rated Amps NA 10.9 Phase NA 1 Operation Hz 60 60 Service Factor NA NA

115 120

10.9 6.3

DESIGN ACTUAL

1475 844 (1) DESIGN ACTUAL

Outside Air CFM 220 233 (2) Return Air CFM 1250 609 Number of Pre-Filters NA 2

Pre-Filter Size NA 16x24x1 Number of Final Filters NA 1 Final Filter Size NA 16x20x1 Motor Sheave NA Direct Drive

Discharge S.P. in. NA 0.35 Motor Sheave OD NA NA Suction S.P. in. NA -0.10 Motor Sheave Bore NA NA

Fan Sheave NA NA

0.50 0.45 Fan Sheave Bore NA NA

Fan RPM NA NA Sheave Center Distance NA NA Number of Belts NA NA Belt Size NA NA

REMARKS: OSA damper position = 18%

(1) Fan on high speed

(2) Left as is.

UNIT DATA MOTOR DATA

RILEY ENGINEERING, INC.

AIR APPARATUS TEST REPORT

INRC Warehouse SYSTEM/UNIT FN-5

Unit Designation FN-5 HP Manufacturer Carrier Model Number 59TP6A060E17--14 Serial Number 1218A45225

Operating Volts Operating Amps

FAN DATA

Supply Air CFM OTHER DATA

External S.P. in.

National Environmental Balancing Bureau

TEST DATE: 3/21/2025

READINGS BY: J. Lazuhrcatt

AIR OUTLET TEST REPORT

PROJECT SYSTEM

OUTLET MANUFACTURER TEST APPARATUS

NO. TYPE SIZE

1 S-2 8x8 100 116 90 90% 1 S-2 8x8 125 157 121 97% 1 S-2 8x8 100 115 88 88% 1 S-2 8x8 125 145 110 88% 1 S-3 6x6 55 56 (1) 69 125% 1 S-1 8x8 180 125 NW 156 87% 1 S-1 8x8 140 127 N 119 85% 3 S-1 8x8 140 130 C 122 87% 4 S-1 8x8 140 120 S 118 84%

1105 (2) 993 90%

NOTES:

(2) Fan on highest speed.

READINGS BY: J. Lazuhrcatt

National Environmental Balancing Bureau

(1) Existing remote damper not operable.

TEST DATE: 3/21/2025

Womens RR 120 Storage 118 Break 121 Corridor 122A

Women's Shower 114

RILEY ENGINEERING, INC.

INRC Warehouse FN-2

Flow Hood

AREA SERVED

OUTLET

DESIGN

AIRFLOW

CFM

PRELIM.

AIRFLOW

CFM N

O

T E

S AS-FOUND

AIRFLOW

CFM

PERCENT

OF DESIGN

FN-2 Supply Men's Shower 115 Men's RR 119

OUTLET MANUFACTURER TEST APPARATUS

NO. TYPE SIZE

1 S-1 10x10 235 189 NW 191 81% 2 S-1 10x10 235 151 NE 192 82% 3 S-1 10x10 235 154 SW 191 81% 4 S-1 10x10 235 139 SE 179 76% 1 S-2 16x16 670 480 570 85%

1 NA NA NA 153 (1) 180 118%

1610 (2) 1503 93%

NOTES:

(2) Fan on high speed

READINGS BY: J. Lazuhrcatt

National Environmental Balancing Bureau

(1) Grill not on prints. Added for new hallway with windows. Balanced as is.

TEST DATE: 3/21/2025

Waiting 101 Hallway

RILEY ENGINEERING, INC.

INRC Warehouse FN-3

Flow Hood

AREA SERVED

OUTLET

DESIGN

AIRFLOW

CFM

PRELIM.

AIRFLOW

CFM N

O

T E

S AS-FOUND

AIRFLOW

CFM

PERCENT

OF DESIGN

FN-3 Supply Classroom 103

OUTLET MANUFACTURER TEST APPARATUS

NO. TYPE SIZE

1 S-2 8x8 150 92 127 85% 1 S-2 8x8 150 170 NW 130 87% 2 S-1 10x10 275 188 NE 220 80% 3 S-1 10x10 275 260 SW 212 77% 4 S-1 10x10 275 125 SE 200 73% 1 S-1 8x8 180 104 W 141 78% 2 S-1 8x8 180 107 E 145 81%

1485 (1) 1175 79%

NOTES:

READINGS BY: J. Lazuhrcatt

National Environmental Balancing Bureau

(1) Fan on highest speed setting.

TEST DATE: 3/21/2025

Briefing Room 112

RILEY ENGINEERING, INC.

INRC Warehouse FN-5

Flow Hood

AREA SERVED

OUTLET

DESIGN

AIRFLOW

CFM

PRELIM.

AIRFLOW

CFM N

O

T E

S AS-FOUND

AIRFLOW

CFM

PERCENT

OF DESIGN

FN-5 Supply Corridor 113 IA Floor West

RILEY ENGINEERING, INC.

AHU OBD Opposed Blade Damper

AMP OSA Outside Air

CD PD Pressure Differential

CFM PSI Pounds per Square Inch

DD PSID Pounds per Square Inch (differential)

DP RA Return Air

EF RG Return Grille

EG RH Relative Humidity

ERV RPM Revolutions per Minute

EX (E) RTU Rooftop Unit

FA SA Supply Air

FCU SD Slot Diffuser

FG Floor Grille SF Service Factor

FLA Full Load Amperage SG Supply Grille

FPM Feet per Minute SP Static Pressure

GPM Gallons per Minute SW Sidewall Grille

HP Horsepower TB Terminal Box

Hz Hertz TDH Total Dynamic Head

LAT Leaving Air Temperature TU Terminal Unit

MAT Mixed Air Temperature VAV Variable Air Volume

MAU Makeup Air Unit VFD Variable Frequency Drive

NA Not Applicable VP Variable Pitch

NEBB WC Water Column

REMARKS:

Free Air

Fan Coil Unit

National Environmental Balancing Bureau

TEST DATE: 3/21/2025

READINGS BY: J. Lazuhrcatt

National Environmental Balancing Bureau

Differential Pressure

Exhaust Fan

Exhaust Grille

Energy Recovery Ventilator

Existing

Direct Drive

List of Abbreviations

INRC Warehouse LOCATION Coeur d'Alene, Idaho 83815

List of Abbreviations

Air Handling Unit

Ampere

Ceiling Diffuser

Cubic Feet per Minute

TAB Instrument Ownership for Firm: Riley Engineering, Inc.

Calibration Interval:

12 Months

Air Pressure 0 to 10 In. W.G.; 2% of reading +/- .001 In. W.G.; .001 In. W.G. < 1 In. W.G., .01 In. W.G. > 1 In. W.G.

Alnor Model EBT-731, Serial No. EBT731725012 12/10/2024

Air Velocity Instrument 100 FPM to 3500 FPM; +/- 5% of reading, +/- 7 FPM; 1 FPM Alnor Model EBT-731, Serial No. EBT731725012 12/10/2024

Digital Direct Reading Hood 100 CFM to 2000 CFM; +/- 5% of reading +/- 7 CFM; 1 CFM Alnor Model EBT-731, Serial No. EBT731725012 12/10/2024

Air Meter with probe 0 °F to 200 °F; +/- .5% of reading +2.0 °F; .1 °F Meter: Testo Model 720, Serial No. 03206579 Probe: Testo Model 0613.1212, Serial No. MI-9088

9/16/2024

Immersion Meter with probe 0 °F to 200 °F; +/- .5% of reading +2.0 °F; .1 °F Meter: Testo Model 720, Serial No. 03206579 Probe: Testo Model 0613.1712, Serial No. MI-9089

9/16/2024

Humidity Humidity Meter 10% RH to 90% RH; 3% of reading; 1% Oakton Model 35612-00, Serial No. M1-2717 9/17/2024

Amperage Measuurement .1 AC Ampere to 100 AC Amperes; 2% of reading +/- 5 digits; .1 AC Ampere

Fluke Model 365, Serial No. 64010064WS 9/16/2024

Voltage Meter - True RMS 1 VAC to 600 VAC; 2% of reading +/- 5 digits; 1 Volt Fluke Model 365, Serial No. 64010064WS 9/16/2024

Rotation Rotation Measurement 60 RPM to 5000 RPM; 2% of reading +/- 2 RPM; 1 RPM Shimpo Model DT-205L, Serial No. C29B0045 12/9/2024

Pressure Measurement .4 PSI to 200 PSI; 2% of reading +/- 1 PSI; .1 PSI Alnor Model HM 680, Serial No. MI-9693 8/26/2024

Differential Preesure Measurement

.4 PSI to 75 PSI; 2% of reading +/0 .5 PSI; .01 PSI Alnor Model HM 680, Serial No. MI-9693 8/26/2024

Equipment Calibration Certificates

Temperature

Electrical

Hydronic

REQUIRED TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS INSTRUMENTS - Procedural Standard 2019 Ninth Edition

CATEGORY FUNCTION MINIMUM RANGE; ACCURACY; RESOLUTION INSTRUMENT INFORMATION

Air

Flow Hood/Manometer Thermometer

Equipment Calibration Certificates

Humidity Meter Electrical Meter

Equipment Calibration Certificates

Tachometer Water Pressure Meter

File details come from the government source that posted it. Updated .