f. Test and Balance-INRC Main Office.pdf
PDF 525 KB Posted
- Solicitation number
- 1284LL25Q0012
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a Test, Adjust, and Balance (TAB) Report for the INRC Office Building - Phase 3 project in Coeur D Alene, Idaho, dated April 30, 2020. The comprehensive report details airflow measurements and system performance for multiple fan coil units, an energy recovery ventilator (ERV), and a domestic hot water recirculation pump. Key technical findings include that most fan coil units operated within +/- 10% of design airflow, with some units requiring proportional balancing. The domestic hot water circulation pump was found to be operating at approximately 50% of its design flow rate (3.0 GPM out of 6.0 GPM), though hot water remained readily available throughout the building.
The report was prepared by Air Commander Test & Balance, LLC, with Kevin Wold as the primary technician. The testing involved multiple Daikin fan coil units with varying capacities (ranging from 1 to 4.5 tons), an ERV system by RenewAire, and a Taco domestic hot water recirculation pump. Measurements were taken using instruments including a Balometer (TSI Alnor), Electrical Meter (Fluke), and Hydronic Manometer (TSI), with the testing conducted in accordance with NEBB (National Environmental Balancing Bureau) procedural standards. The report provides detailed technical data for each system, including airflow rates, static pressures, motor voltages, and other performance metrics.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| b. PWS_amended.docx | DOCX document | |
| 1284LL25Q0012_0001_SF30.pdf | ||
| b. PWS.docx | DOCX document | |
| d. Mechanical Plans-INRC Dispatch.pdf | ||
| h. Technical Proposal Form.pdf | ||
| i. State of Idaho-Certificate-of-Verification of Workers Compensation Insurance-Form.pdf | ||
| j. WD 2015-5505 Rev 26 Dated 07082025.pdf | ||
| a. 1284LL25Q0012_CSS.docx | DOCX document | |
| c. Mechanical Plans-INRC Main Office.pdf | ||
| e. Mechanical Plans-INRC Warehouse.pdf | ||
| g. Test and Balance-INRC Dispatch Office.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINAL
TEST, ADJUST, AND BALANCE REPORT
April 30, 2020
INRC Office Building - Phase 3 3600 W Nursery Rd
Coeur D Alene, ID 83815
MECHANICAL ENGINEER:
Jody T Waverek Morrison Maierle
1055 Mount Avenue Missoula, MT 59801
MECHANICAL CONTRACTOR:
MetalCraft Mechanical 11547 N Warren St Hayden, ID 83835
TAB CONTRACTOR:
Air Commander Test & Balance, LLC 1521 N Argonne Rd, Suite C254 Spokane Valley, WA 99212
Mike@AirCommanderUSA.com License # AIRCOCT866BW
18-137
Cover Page Table of Contents Certification Instruments Summary - SUMMARY Air Handler - Supply - ERV-1 Air Handler - Ret - ERV-1 Traverse - ERV-1 / SUPPLY Traverse - ERV-1 / EXHAUST Traverse - ERV-1 / OSA BEFORE FC-214 Traverse - ERV-1 / OSA AFTER FC-214 Velocity - ERV-1 / FC OSA VRF SYSTEM 1 Velocity - ERV-1 / FC OSA VRF SYSTEM 2 Velocity - ERV-1 / BASEMENT SUPPLY Flowhood - ERV-1 / EXHAUST Air Handler - Supply - FC-103 Air Handler - Supply - FC-104 Air Handler - Supply - FC-105A Air Handler - Supply - FC-105B Air Handler - Supply - FC-117 Air Handler - Supply - FC-122A Air Handler - Supply - FC-122B Air Handler - Supply - FC-123 Air Handler - Supply - FC-127 Air Handler - Supply - FC-131 Air Handler - Supply - FC-136 Air Handler - Supply - FC-139 Air Handler - Supply - FC-143 Flowhood - SUPPLY / FC-103 Flowhood - SUPPLY / FC-104 Flowhood - SUPPLY / FC-105A Flowhood - SUPPLY / FC-105B Flowhood - SUPPLY / FC-117 Flowhood - SUPPLY / FC-122A Flowhood - SUPPLY / FC-122B Flowhood - SUPPLY / FC-123 Flowhood - SUPPLY / FC-127 Flowhood - SUPPLY / FC-131 Flowhood - SUPPLY / FC-136 Flowhood - SUPPLY / FC-139 Flowhood - SUPPLY / FC-143 Air Handler - Supply - FC-202 Air Handler - Supply - FC-204 Air Handler - Supply - FC-205 Air Handler - Supply - FC-214 Air Handler - Supply - FC-216 Air Handler - Supply - FC-226 Air Handler - Supply - FC-228 Air Handler - Supply - FC-230 Air Handler - Supply - FC-231 Air Handler - Supply - FC-234 Air Handler - Supply - FC-237 Flowhood - SUPPLY / FC-202 Flowhood - SUPPLY / FC-204
INRC Office Building - Phase 3
TABLE OF CONTENTS
Flowhood - SUPPLY / FC-205 Flowhood - SUPPLY / FC-214 Flowhood - SUPPLY / FC-216 Flowhood - SUPPLY / FC-226 Flowhood - SUPPLY / FC-228 Flowhood - SUPPLY / FC-230 Flowhood - SUPPLY / FC-231 Flowhood - SUPPLY / FC-234 Flowhood - SUPPLY / FC-237 Flowhood - EXHAUST / EF-1 Pump - Cartridge - RCP-1 Balance Valve - RCP-1 / DOMESTIC HW RECIRC Abbreviation List
INRC Office Building - Phase 3
TABLE OF CONTENTS
The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standard for Testing, Adjusting and Balancing of Environmental Systems. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed NEBB tolerances, are noted in the TAB report project summary.
SUBMITTED & CERTIFIED BY:
NEBB CERTIFIED TAB FIRM NAME Air Commander Test & Balance, LLC
CERTIFICATION NO. NEBB Certification #
CERTIFICATION EXPIRATION DATE March 31, 2021
REPORT DATE April 30, 2020
NEBB QUALIFIED TAB SUPERVISOR NAME Micheal Maclay, NEBB Certified Professional (CP)
NEBB QUALIFIED TAB SUPERVISOR SIGNATURE
INRC Office Building - Phase 3
CERTIFICATION
Record of Instrument(s) Used on Project INRC Office Building - Phase 3 - CDA, ID
Instrument Model # Manufacturer Serial # Date(s) of Use Calibration Date
Balometer EBT731 TSI Alnor EBT731340014 April 2020 07/02/2019
Electrical Meter 324 Fluke 39840515WS April 2020 01/30/2020
Hydronic Manometer
HM675 TSI 71331118 April 2020 12/26/2019
1521 N Argonne Rd, Suite C254, Spokane Valley, WA 99212 Phone: (509) 619-4348 E-mail: mike@aircommanderusa.com
ERV-1
This RenewAire energy recovery ventilator serves fresh air to the fan coil units and serves as general exhaust for the building. Both supply and exhaust fans total airflow was measured via pitot tube traverse of each fans main branch duct in the penthouse mechanical room. The VFDs were adjusted to the speed that closely delivered design total airflow for each fan. The supply side serving fresh air to the fan coils was then proportionally balanced by using the hot wire to traverse each fresh air duct to each fan coils and then adjusting each fan coils fresh air volume to design. This test data can be seen on the Outlet Velocity sheet test forms for ERV-1.
All exhaust grilles were then proportionally balanced to their design airflow requirements using the flow hood. This system is operating as intended with no discrepancies to report.
Fan Coils
The Daikin fan coils units are equipped with motors that have 4 selectable fan speeds through each units thermostat. There is Fan Only (FO), High, Medium and Low along with a different, and the lowest speed, which is when the unit is placed into Heating Mode. The speed that each fan coil was tested on and reported has been recorded on each units Air Handler test report form under the actual fan speed column. All ducted fan coils have been proportionally balanced using the flow hood. Some fan coils were tested and reported on outside the +/- 10% of the design total airflow as the 4 selectable fan speeds would not provide the design flow requirement for these units.
RCP-1 (Domestic Hot Water Recirc)
The Taco domestic hot water circulation pump was tested for total flow and found to be operating at approximately 50% of design total flow or around 3.0 GPM out of the 6.0 GPM design. This does not appear to pose an issue as the system was functionally tested and hot water was found to be readily available at all fixtures throughout the building.
Kevin Wold
NEBB TAB CT
Member, Air Commander TAB, LLC
509-844-1300
INRC Office Building - Phase 3
SUMMARY
UNIT DESIGNATION: ERV-1
UNIT INFORMATION MOTOR INFORMATION
Unit Location Mechanical Mezz. Manufacturer / Frame Baldor / 184T Area Served FC OSA Horsepower / RPM 5.0 / 1750 Manufacturer RenewAire Volts / Phase / Hertz 208 / 3 / 60 Model Number HE4XIN Full Load Amps / S.F. 13.9 / 1.15 Serial Number H19 4262C Power Factor / Efficiency 0.78 / 0.895 Fan Type / Size Centrifugal / Not labeled Overload Setting VFD
Rotation / Configuration CW / Bottom horizontal Sheave Manufacturer Master Drive Sheave Manufacturer Master Drive Sheave Diameter / Bore (") 1VP68 / 1-1/8
Sheave Diameter / Bore (") AK64 / 1 Sheave Position 4.0 turns open Filter Manufacturer Glassflos Centerline Distance (") 14-1/2
Quantity / Merv Rating 4 / 10 Belt Manufacturer Not labeled Filter Size 20x20x2 Number of Belts / Size 1 / A45
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 3500 3516 Pre Filter DP (in WC) 0.74 (1) Outlet Total Airflow (cfm) 3500 3484 Heating Coil DP (in WC) ---
Fan Speed (rpm) --- 1239 Cooling Coil DP (in WC) --- Motor Voltage 208 150 / Thru / VFD Fan Suction Static Pressure (in WC) -1.22
Corrected Full Load Amps 13.9 8.5 / Thru / VFD Fan Discharge Static Pressure (in WC) 0.18 Brake Horsepower 2.1 Final Filter DP (in WC) ---
External Static (inWC) 1.50 0.43 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- 1.40 VFD Frequency (Hz) 51.0 Outdoor Airflow (cfm) 3500 3516 Outdoor Air Damper Position(%) 100 Return Airflow (cfm) --- --- Return Air Damper Position(%) ---
Notes: (1) Differential pressure as measured across both the heat exchanger and the filter.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
TEST DATE: 04/24/20
READINGS BY: Kevin Wold Page 7 of 49
UNIT DESIGNATION: ERV-1
Unit Location Mechanical Mezz. Manufacturer / Frame Baldor / 184T Area Served General Exhaust Horsepower / RPM 5.0 / 1750 Manufacturer RenewAire Volts / Phase / Hertz 208 / 3 / 60 Model Number HE4XIN Full Load Amps / S.F. 13.9 / 1.15 Serial Number H19 4262C Power Factor / Efficiency 0.78 / 0.895 Fan Type / Size Centrifugal / Not labeled Overload Setting VFD
Rotation / Configuration CW / Bottom horizontal Sheave Manufacturer Master Drive Sheave Manufacturer Master Drive Sheave Diameter / Bore (") 1VP68 / 1-1/8
Sheave Diameter / Bore (") AK64 / 1 Sheave Position 4.0 turns open Filter Manufacturer Glassflos Centerline Distance (") 14-1/2
Quantity / Merv Rating 4 / 10 Belt Manufacturer Not labeled Filter Size 20x20x2 Number of Belts / Size 1 / A45
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 2975 3255 Fan Suction Static Pressure (in WC) -1.30 Outlet Total Airflow (cfm) 2975 2970 Fan Discharge Static Pressure (in WC) 0.15
Fan Speed (rpm) --- 1167 Heat Exchanger/Filter Diff. Pressure (inWC) 0.70 Motor Voltage 208 135 / Thru / VFD
Corrected Full Load Amps 13.9 8.7 / Thru / VFD
Brake Horsepower 1.90 External Static (inWC) 1.50 0.53 Total Static (inWC) --- 1.45 VFD Frequency (Hz) 48.0
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - RETURN FAN
READINGS BY: Kevin Wold Page 8 of 49
SYSTEM: ERV-1
TRAVERSE DESCRIPTION DUCT SIZE
(inches)
AREA
(sq. ft.)
REQUIRED
VELOCITY
(fpm)
REQUIRED
AIRFLOW
(cfm)
ACTUAL
VELOCITY
(fpm)
ACTUAL
AIRFLOW
(cfm)
STATIC
PRESSURE
(inWC)
TEST INSTRUMENT NOTES
SUPPLY 20.0 X 28.0 3.889 900 3500 904 3516 0.19 Pitot tube
EXHAUST 20.0 X 28.0 3.889 765 2975 837 3255 0.14 Pitot tube
OSA BEFORE FC-214 10.0 X 14.0 0.972 - --- 726 706 0.025 Pitot tube
OSA AFTER FC-214 10.0 X 14.0 0.972 - --- 592 576 0.015 Pitot tube
INRC Office Building - Phase 3
TRAVERSE TEST REPORT
READINGS BY: Kevin Wold Page 9 of 49
FC OSA VRF SYSTEM 1
1 FC-103 Duct 8 0.35 400 140 315 110 410 144 103%
2 FC-104 Duct 6 0.20 500 100 385 77 475 95 95%
3 FC-105A Duct 10 0.55 573 315 440 242 550 303 96%
4 FC-105B Duct 10 0.55 573 315 465 256 580 319 101%
5 FC-114 Duct 6 0.20 375 75 270 54 340 68 91%
6 FC-117 Duct 8 0.35 214 75 565 198 230 81 108%
7 FC-127 Duct 6 0.20 350 70 260 52 320 64 91%
8 FC-122A Duct 8 0.35 343 120 325 114 355 124 103%
9 FC-122B Duct 6 0.20 400 80 315 63 400 80 100%
10 FC-123 Duct 6 0.20 400 80 440 88 385 77 96%
11 FC-131 Duct 8 0.35 286 100 420 147 275 96 96%
12 FC-136 Duct 8 0.35 286 100 380 133 285 100 100%
13 FC-137 Duct 6 0.20 250 50 180 36 230 46 92%
14 FC-139 Duct 6 0.20 250 50 555 111 250 50 100%
15 FC-143 Duct 10 0.55 255 140 455 250 265 146 104%
TOTAL 1810 1931 1793 99%
INRC Office Building - Phase 3
VELOCITY TEST REPORT
SYSTEM: ERV-1
NO. AREA
SERVED TYPE SIZE
(inches) Free Area
(sq. ft.)
DESIGN PRELIMINARY FINAL
% of
DESIGN NOTESVELOCITY
(fpm)
AIRFLOW
(cfm)
VELOCITY
(fpm)
AIRFLOW
(cfm)
VELOCITY
(fpm)
AIRFLOW
(cfm)
TEST DATE: 04/24/20
READINGS BY: Kevin Wold
FC OSA VRF SYSTEM 2
16 FC-201 Duct 6 0.20 600 120 375 75 540 108 90%
17 FC-202 Duct 8 0.35 143 50 425 149 155 54 108%
18 FC-204 Duct 8 0.35 143 50 380 133 155 54 108%
19 FC-205 Duct 8 0.35 400 140 365 128 405 142 101%
20 FC-214 Duct 8 1.0 120 120 115 115 130 130 108% (1)
21 FC-216 Duct 6 0.20 500 100 465 93 510 102 102%
22 FC-224 Duct 6 0.20 500 100 305 61 460 92 92%
23 FC-225 Duct 6 0.20 500 100 320 64 465 93 93%
24 FC-226 Duct 8 0.35 400 140 250 88 365 128 91%
25 FC-228 Duct 10x10 0.694 202 140 280 193 210 145 104%
26 FC-230 Duct 8 0.35 400 140 560 196 415 145 104%
27 FC-231 Duct 8 0.35 400 140 490 172 405 142 101%
28 FC-232 Duct 6 0.20 250 50 175 35 240 48 96%
29 FC-234 Duct 6 0.20 300 60 495 99 310 62 103%
30 FC-237 Duct 8 0.35 400 140 430 151 415 145 104%
TOTAL 1590 1752 1590 100%
Notes: (1) Unable to measure directly. See traverse sheets labeled Before & After.
BASEMENT SUPPLY
31 Telecom 002 SW 4x12 0.23 217 50 375 86 215 49 98%
32 Storage 001 SW 4x12 0.23 217 50 445 102 225 52 104%
TOTAL 100 188 101 101%
INRC Office Building - Phase 3
VELOCITY TEST REPORT
SYSTEM: ERV-1
NO. AREA
SERVED TYPE SIZE
(inches) Free Area
(sq. ft.)
DESIGN PRELIMINARY FINAL
% of
DESIGN NOTESVELOCITY
(fpm)
AIRFLOW
(cfm)
VELOCITY
(fpm)
AIRFLOW
(cfm)
VELOCITY
(fpm)
AIRFLOW
(cfm)
TEST DATE: 04/24/20
EXHAUST
1 Print Rm 137 EG 10 250 325 130% 240 96% 250 100%
2 Break Rm 139 EG 8 150 35 23% 145 97% 150 100%
3 Wom. RR 140 EG 10 300 255 85% 270 90% 285 95%
4 Men's RR 141 EG 10 300 285 95% 310 103% 325 108%
5 Men's RR 108 EG 10 300 290 97% 275 92% 290 97%
6 Wom. RR 109 EG 10 300 325 108% 270 90% 285 95%
7 Print Rm 232 EG 10 250 225 90% 235 94% 245 98%
8 Break Rm 234 EG 8 150 200 133% 155 103% 160 107%
9 Wom. RR 235 EG 10 300 325 108% 295 98% 310 103%
10 Men's RR 236 EG 10 300 325 108% 280 93% 295 98%
11 Bsmt. Foyer EG 14x8 125 225 180% 120 96% 125 100%
12 Bsmt. Mech. EG 14x8 125 200 160% 125 100% 130 104%
13 Bsmt. Mech. EG 14x8 125 170 136% 115 92% 120 96%
TOTAL 2975 3185 107% 2835 95% 2970 100%
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: ERV-1
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/24/20
UNIT DESIGNATION: FC-103
Unit Location Lobby Manufacturer / Frame Not labeled / Not labeled Area Served Reception Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ24PBVJU Full Load Amps / S.F. 1.40 / Not labeled Serial Number E017578 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 688 --- Pre Filter DP (in WC) 0.14 Outlet Total Airflow (cfm) 875 880 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/High Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.21
Corrected Full Load Amps 1.4 0.9 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.14 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 140 144 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 735 736 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 13 of 49
UNIT DESIGNATION: FC-104
Unit Location Lobby Manufacturer / Frame Not labeled / Not labeled Area Served Conf 104 Horsepower / RPM 140 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ12PBVJU Full Load Amps / S.F. 1.10 / Not labeled Serial Number E014282 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 1 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-1/4x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 450 --- Pre Filter DP (in WC) 0.06 Outlet Total Airflow (cfm) 225 250 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD Heat/Low Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.11
Corrected Full Load Amps 1.10 0.20 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.07 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 100 95 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 125 155 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
TEST DATE: 04/21/20
READINGS BY: Kevin Wold Page 14 of 49
UNIT DESIGNATION: FC-105A
Unit Location Conf 105 Manufacturer / Frame Not labeled / Not labeled Area Served Conf 105 Horsepower / RPM 380 watts (1) / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ72MVJU Full Load Amps / S.F. 7.60 / Not labeled Serial Number A007700 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 4 / 13 Belt Manufacturer DD Filter Size 18x24x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 2048 --- Pre Filter DP (in WC) 0.05 Outlet Total Airflow (cfm) 1190 1180 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD Heat/Low Cooling Coil DP (in WC) (3) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.11
Corrected Full Load Amps 7.6 3.2 Fan Discharge Static Pressure (in WC) (3) Brake Horsepower (2) Final Filter DP (in WC) ---
External Static (inWC) --- 0.12 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (3) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 315 303 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 875 877 Return Air Damper Position(%)
Notes: (1) Two fan motors at 380 watts each.
(2) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(3) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 15 of 49
UNIT DESIGNATION: FC-105B
Unit Location Conf 105 Manufacturer / Frame Not labeled / Not labeled Area Served Conf 105 Horsepower / RPM 380 watts (1) / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ72MVJU Full Load Amps / S.F. 7.60 / Not labeled Serial Number A007700 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 4 / 13 Belt Manufacturer DD Filter Size 18x24x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 2048 --- Pre Filter DP (in WC) 0.04 Outlet Total Airflow (cfm) 1050 1155 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD Heat/Low Cooling Coil DP (in WC) (3) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.10
Corrected Full Load Amps 7.6 3.2 Fan Discharge Static Pressure (in WC) (3) Brake Horsepower (2) Final Filter DP (in WC) ---
External Static (inWC) --- 0.12 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (3) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 315 319 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 735 836 Return Air Damper Position(%) ---
Notes: (1) Two fan motors at 380 watts each.
(2) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(3) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 16 of 49
UNIT DESIGNATION: FC-117
Unit Location BLM Off. 136 Manufacturer / Frame Not labeled / Not labeled Area Served BLM Offices Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ18PBVJU Full Load Amps / S.F. 1.30 / Not labeled Serial Number E014366 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 635 --- Pre Filter DP (in WC) 0.14 Outlet Total Airflow (cfm) 710 765 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/High Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.24
Corrected Full Load Amps 1.30 0.70 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.22 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 75 81 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 635 684 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 17 of 49
UNIT DESIGNATION: FC-122A
Unit Location BLM Off. 122 Manufacturer / Frame Not labeled / Not labeled Area Served BLM Off. 122 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ30PBVJU Full Load Amps / S.F. 2.20 / Not labeled Serial Number E012212 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1094 --- Pre Filter DP (in WC) 0.09 Outlet Total Airflow (cfm) 800 865 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.16
Corrected Full Load Amps 2.20 0.70 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.20 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 120 124 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 680 741 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 18 of 49
UNIT DESIGNATION: FC-122B
Unit Location BLM Off 122 Manufacturer / Frame Not labeled / Not labeled Area Served BLM Off 122 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ15PBVJU Full Load Amps / S.F. 1.20 / Not labeled Serial Number E007215 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1.25 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Centrifugal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 560 --- Pre Filter DP (in WC) 0.10 Outlet Total Airflow (cfm) 510 595 (1) Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Low Cooling Coil DP (in WC) (3) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.15
Corrected Full Load Amps 1.20 0.50 Fan Discharge Static Pressure (in WC) (3) Brake Horsepower (2) Final Filter DP (in WC) ---
External Static (inWC) --- 0.14 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (3) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 80 80 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 430 515 Return Air Damper Position(%) ----
Notes: (1) Unable to reduce to design total airflow, test on Fan Only Low speed at 117%, Heat/Low is approximately 87%.
(2) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(3) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 19 of 49
UNIT DESIGNATION: FC-123
Unit Location FMO Off 123 Manufacturer / Frame Not labeled / Not labeled Area Served FMO Off 123 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ24PBVJU Full Load Amps / S.F. 1.40 / Not labeled Serial Number E017575 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Centrifugal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 688 --- Pre Filter DP (in WC) 0.08 Outlet Total Airflow (cfm) 600 630 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.14
Corrected Full Load Amps 1.40 0.50 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.14 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 80 77 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 520 553 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 20 of 49
UNIT DESIGNATION: FC-127
Unit Location Hallway Manufacturer / Frame Not labeled / Not labeled Area Served COI Office 127 Horsepower / RPM 90 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ07PBVJU Full Load Amps / S.F. 0.50 / Not labeled Serial Number E010676 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 1 / 13 Belt Manufacturer DD Filter Size 11-3/8x20-3/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 317 --- Pre Filter DP (in WC) 0.05 Outlet Total Airflow (cfm) 238 240 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.10
Corrected Full Load Amps 0.50 0.20 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.18 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 70 64 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 168 176 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 21 of 49
UNIT DESIGNATION: FC-131
Unit Location Open Off. 131 Manufacturer / Frame Not labeled / Not labeled Area Served Open Off. 131 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ48PBVJU Full Load Amps / S.F. 2.70 / Not labeled Serial Number E011643 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 4.0 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1377 --- Pre Filter DP (in WC) 0.14 Outlet Total Airflow (cfm) 1000 1105 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/High Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.28
Corrected Full Load Amps 2.7 1.80 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.34 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 100 96 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 900 1009 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 22 of 49
UNIT DESIGNATION: FC-136
Unit Location BLM Offices 136 Manufacturer / Frame Not labeled / Not labeled Area Served BLM Offices 136 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ30PBVJU Full Load Amps / S.F. 2.20 / Not labeled Serial Number E012211 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1094 --- Pre Filter DP (in WC) 0.06 Outlet Total Airflow (cfm) 800 775 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.20
Corrected Full Load Amps 2.20 0.60 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.24 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 100 100 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 700 675 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 23 of 49
UNIT DESIGNATION: FC-139
Unit Location Hallway Manufacturer / Frame Not labeled / Not labeled Area Served Breakroom 139 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ30PBVJU Full Load Amps / S.F. 2.20 / Not labeled Serial Number E012185 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1094 --- Pre Filter DP (in WC) 0.07 Outlet Total Airflow (cfm) 710 725 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.20
Corrected Full Load Amps 0.60 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.23 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 50 50 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 660 675 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 24 of 49
UNIT DESIGNATION: FC-143
Unit Location Office 144 Manufacturer / Frame Not labeled / Not labeled Area Served Open Off. 143 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ54PBVJU Full Load Amps / S.F. 2.70 / Not labeled Serial Number E005339 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 4.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1624 --- Pre Filter DP (in WC) 0.12 Outlet Total Airflow (cfm) 1200 1150 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/MED Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.22
Corrected Full Load Amps 2.7 1.10 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.20 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 140 146 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 1060 1004 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 25 of 49
FC-103
1 Vestibule CD 6 75 50 67% - 75 100%
2 Mail Rm CD 6 100 105 105% - 100 100%
3 Reception SD 8 175 180 103% - 175 100%
4 Reception SD 8 175 190 109% - 185 106%
5 Reception SD 8 175 185 106% - 180 103%
6 Reception SD 8 175 165 94% - 165 94%
TOTAL 875 875 100% 880 101%
FC-104
1 Conf. 104 SD 8 75 140 187% 105 140% 80 107%
2 Conf. 104 SD 8 75 150 200% 115 153% 85 113% (1)
3 Conf. 104 SD 8 75 150 200% 115 153% 85 113% (1)
TOTAL 225 440 196% 335 149% 250 111%
Notes: (1) Proportionally balanced to +-10% of the overall average. See summary.
FC-105A
1 Meeting 105 CD 8 140 260 186% 275 196% 165 118% (1)
2 Meeting 105 SD 8 150 255 170% 270 180% 165 110%
3 Meeting 105 SD 8 150 240 160% 285 190% 175 117% (1)
4 Meeting 105 SD 8 150 265 177% 270 180% 170 113% (1)
5 Meeting 105 SD 8 150 220 147% 270 180% 165 110%
6 Meeting 105 SD 8 150 305 203% 265 177% 165 110%
7 Meeting 105 SD 8 150 310 207% 290 193% 175 117% (1)
8 Meeting 105 SD 8 150 0 0% 0 0% 0 0% (1)
TOTAL 1190 1855 156% 1925 162% 1180 99%
Notes: (1) Diffuser #8 is not installed, no room is available to install the diffuser in the location shown on the drawings.
Some of the other diffusers are operating slightly above their design due to this. No noise or draft concerns were noticed.
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: SUPPLY
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/21/20
FC-105B
1 Meeting 105 SD 8 150 290 193% 275 183% 170 113% (1)
2 Meeting 105 SD 8 150 250 167% 280 187% 170 113% (1)
3 Meeting 105 SD 8 150 230 153% 275 183% 155 103%
4 Meeting 105 SD 8 150 300 200% 275 183% 170 113% (1)
5 Meeting 105 SD 8 150 270 180% 275 183% 165 110%
6 Meeting 105 SD 8 150 305 203% 275 183% 165 110%
7 Meeting 105 SD 8 150 305 203% 265 177% 160 107%
TOTAL 1050 1950 186% 1920 183% 1155 110%
Notes: (1) Proportionally balanced to +-10% of the overall average. See summary.
FC-117
1 Office 115 CD 6 90 100 111% - 95 106%
2 Office 116 CD 6 90 105 117% - 95 106%
3 Office 117 CD 8 160 185 116% - 175 109%
4 Rm 121A CD 6 50 95 190% - 55 110%
5 Rm 121B CD 6 50 70 140% - 55 110%
6 Office 120 CD 6 90 85 94% - 95 106%
7 Office 119 CD 6 90 95 106% - 100 111% (1)
8 Office 118 CD 6 90 100 111% - 95 106%
TOTAL 710 835 118% 765 108%
Notes: (1) Proportionally balanced to +-10% of the overall average. See summary.
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: SUPPLY
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/21/20
FC-122A
1 Open Off. CD 8 200 250 125% - 215 108%
2 Open Off. CD 8 200 285 142% - 215 108%
3 Open Off. CD 8 200 290 145% - 220 110%
4 Open Off. CD 8 200 255 127% - 215 108%
TOTAL 800 1080 135% 865 108%
FC-122B
1 Open Off. CD 8 170 240 141% 150 88% 200 118% (1)
2 Open Off. CD 8 170 235 138% 145 85% 195 115% (1)
3 Open Off. CD 8 170 240 141% 150 88% 200 118% (1)
TOTAL 510 715 140% 445 87% 595 117% (1)
Notes: (1) Selectable fan speeds do not provide design total airflow. Fan Only Low speed has been reported at 117%.
Heat/Low fan speed is shown in the 2nd prelim airflow column and provides 87% of design total airflow.
FC-123
1 FMO Open Off. CD 8 170 205 121% 185 109% 170 100%
2 FMO Open Off. CD 8 170 235 138% 205 121% 185 109%
3 FMO Open Off. CD 8 170 225 132% 200 118% 185 109%
4 FMO Off. 124 CD 6 90 120 133% 105 117% 90 100%
TOTAL 600 785 131% 695 116% 630 105%
FC-127
1 Office 127 CD 8 188 205 109% 225 120% 185 98%
2 BLM 125 CD 6 50 95 190% 65 130% 55 110%
TOTAL 238 300 126% 290 122% 240 101%
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: SUPPLY
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/21/20
FC-131
1 Office 135 CD 6 80 135 169% - 90 112% (1)
2 Office 134 CD 8 200 250 125% - 220 110%
3 Office 133 CD 8 200 230 115% - 220 110%
4 Office 132 CD 8 200 230 115% - 220 110%
5 Open Off. 131 CD 8 200 215 108% - 220 110%
6 Evidence 130 CD 6 120 115 96% - 135 112% (1)
TOTAL 1000 1175 118% 1105 110%
Notes: (1) Proportionally balanced to +-10% of the overall average. See summary.
FC-136
1 Open Off. 136 CD 8 200 195 98% 220 110% 190 95%
2 Open Off. 136 CD 8 200 225 112% 235 118% 195 98%
3 Open Off. 136 CD 8 200 225 112% 220 110% 200 100%
4 Open Off. 136 CD 8 200 190 95% 215 108% 190 95%
TOTAL 800 835 104% 890 111% 775 97%
FC-139
1 Men's 141 CD 6 50 40 80% 60 120% 50 100%
2 Women's 140 CD 6 50 185 370% 60 120% 50 100%
3 Conf. 138 CD 8 100 170 170% 125 125% 100 100%
4 Break 139 CD 8 170 205 121% 220 129% 175 103%
5 Break 139 CD 8 170 185 109% 220 129% 180 106%
6 Break 139 CD 8 170 165 97% 210 124% 170 100%
TOTAL 710 950 134% 895 126% 725 102%
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: SUPPLY
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/21/20
FC-143
1 Breakout 136 CD 6 100 120 120% - 95 95%
2 Office 144 CD 8 160 230 144% - 155 97%
3 Storage 142 CD 6 100 135 135% - 100 100%
4 Open Off. 143 CD 8 210 230 110% - 200 95%
5 Open Off. 143 CD 8 210 230 110% - 205 98%
6 Open Off. 143 CD 8 210 225 107% - 200 95%
7 Open Off. 143 CD 8 210 225 107% - 195 93%
TOTAL 1200 1395 116% 1150 96%
INRC Office Building - Phase 3
FLOWHOOD TEST REPORT
SYSTEM: SUPPLY
NO. AREA
SERVED TYPE SIZE
DESIGN
AIRFLOW
(cfm)
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
PRELIM
AIRFLOW
(cfm)
% OF
DESIGN
FINAL
AIRFLOW
(cfm)
% OF
DESIGN NOTES
TEST DATE: 04/21/20
UNIT DESIGNATION: FC-202
Unit Location Open Off 202 Manufacturer / Frame Not labeled / Not labeled Area Served Open Off 202 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ24PBVJU Full Load Amps / S.F. 1.40 / Not labeled Serial Number E017657 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.0 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Centrifugal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 688 --- Pre Filter DP (in WC) 0.12 Outlet Total Airflow (cfm) 600 605 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.21
Corrected Full Load Amps 1.40 0.50 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.16 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 50 54 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 550 551 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 31 of 49
UNIT DESIGNATION: FC-204
Unit Location Open Off. 202 Manufacturer / Frame Not labeled / Not labeled Area Served FWS Office Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ15PBVJU Full Load Amps / S.F. 1.20 / Not labeled Serial Number E007219 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1.25 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 560 --- Pre Filter DP (in WC) 0.05 Outlet Total Airflow (cfm) 400 395 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD Heat Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.10
Corrected Full Load Amps 1.20 0.20 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.11 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 50 54 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 350 341 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 32 of 49
UNIT DESIGNATION: FC-205
Unit Location FWS Off 205 Manufacturer / Frame Not labeled / Not labeled Area Served FWS Off 205 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ30PBVJU Full Load Amps / S.F. 2.20 / Not labeled Serial Number E012413 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1094 --- Pre Filter DP (in WC) 0.11 Outlet Total Airflow (cfm) 800 855 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Medium Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.16
Corrected Full Load Amps 2.20 0.60 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.19 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 140 142 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 660 713 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 33 of 49
UNIT DESIGNATION: FC-214
Unit Location Waiting 213 Manufacturer / Frame Not labeled / Not labeled Area Served Executive Offices Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ30PBVJU Full Load Amps / S.F. 2.20 / Not labeled Serial Number E012144 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 2.5 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x26-7/8x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 1094 --- Pre Filter DP (in WC) 0.14 Outlet Total Airflow (cfm) 1000 1040 Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/High Cooling Coil DP (in WC) (2) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.22
Corrected Full Load Amps 2.20 1.0 Fan Discharge Static Pressure (in WC) (2) Brake Horsepower (1) Final Filter DP (in WC) ---
External Static (inWC) --- 0.39 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (2) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 120 130 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 880 910 Return Air Damper Position(%) ---
Notes: (1) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(2) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
TEST DATE: 04/22/20
READINGS BY: Kevin Wold Page 34 of 49
UNIT DESIGNATION: FC-216
Unit Location Conf 224 Manufacturer / Frame Not labeled / Not labeled Area Served Offices Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ15PBVJU Full Load Amps / S.F. 1.20 / Not labeled Serial Number E007218 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1.25 Ton Overload Setting Thermally protected
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD
TEST DATA DESIGN ACTUAL TEST DATA ACTUAL
Fan Total Airflow (cfm) 560 --- Pre Filter DP (in WC) 0.09 Outlet Total Airflow (cfm) 480 560 (1) Heating Coil DP (in WC) ---
Fan Speed (rpm) DD FO/Low Cooling Coil DP (in WC) (3) Motor Voltage 208 213 Fan Suction Static Pressure (in WC) -0.17
Corrected Full Load Amps 1.20 0.50 Fan Discharge Static Pressure (in WC) (3) Brake Horsepower (2) Final Filter DP (in WC) ---
External Static (inWC) --- 0.14 Duct static Pressure Set Point (in WC) --- Total Static (inWC) --- (3) VFD Frequency (Hz) --- Outdoor Airflow (cfm) 100 102 Outdoor Air Damper Position(%) Fixed Return Airflow (cfm) 380 458 Return Air Damper Position(%) ---
Notes: (1) Unable to reduce to design total airflow, test on Fan Only Low speed at 117%, Heat/Low is approximately 87%.
(2) Power factor and efficiency ratings are not listed on the motors nameplate, unable to calculate.
(3) Total discharge static pressure inaccessible, fan discharges directly into coil.
INRC Office Building - Phase 3
AIR HANDLER TEST REPORT - SUPPLY FAN
READINGS BY: Kevin Wold Page 35 of 49
UNIT DESIGNATION: FC-226
Unit Location HRM Off. 226 Manufacturer / Frame Not labeled / Not labeled Area Served HRM Off. 226 Horsepower / RPM 350 watts / Not labeled Manufacturer Daikin Volts / Phase / Hertz 208 / 1 / 60 Model Number FXMQ18PBVJU Full Load Amps / S.F. 1.30 / Not labeled Serial Number E014361 Power Factor / Efficiency Not labeled / Not labeled Fan Type / Size Centrifugal / 1.5 Ton Overload Setting Thermally protected l
Rotation / Configuration Both / Top horizontal Sheave Manufacturer DD Sheave Manufacturer DD Sheave Diameter / Bore (") DD / DD
Sheave Diameter / Bore (") DD / DD Sheave Position DD Filter Manufacturer AAF Centerline Distance (") DD
Quantity / Merv Rating 2 / 13 Belt Manufacturer DD Filter Size 11-3/8x19x4 Number of Belts / Size DD / DD