g. New RELOC OnePass Cables – Cable – OC1 Series (Basis of Design).pdf

PDF 261 KB Posted

Attached to
FBI CJIS Division, Lighting Replacement, Bldg 9
Solicitation number
15F06722Q0000043
Issued by

About this file

This document includes a federal contract opportunity specification for lighting replacement and the related product specification sheet. The FBI CJIS Division is soliciting quotes to purchase LED lighting fixtures to replace existing fixtures at two buildings in Clarksburg, WV. Bidders should complete the attached pricing template by June 30th, 2022 for the fixtures listed on Tab 2 or approved equivalents. The replacement fixtures must meet the energy efficiency and specification requirements and include anticipated delivery dates. Questions are due by June 17th, 2022. The opportunity is set aside for small businesses. The product specification sheet provides details on various cable products for a relocatable wiring system, including conductor sizes, lengths, voltage ratings, and optional features.

View the file

Other files

File Type Posted
FBI_Lutron Driver Allotment Letter_QTY 607.pdf PDF
REVISED 22-0627_Building 9 Lighting PRICING TEMPLATE.xlsx XLSX spreadsheet
20220726 Questions_Answered - LUTRON LETTER.xlsx XLSX spreadsheet
Questions_Answered 220706.xlsx XLSX spreadsheet
UPDATED Questions_Answered 220701.xlsx XLSX spreadsheet
REVISED 22-0627_Building 9 Lighting PRICING TEMPLATE.xlsx XLSX spreadsheet
Questions_Answered 22-0616.xlsx XLSX spreadsheet
OEM Legacy Pricing Letter (FBI BTC L2 SW).pdf PDF
i. New RELOC OnePass Splitter Splice – OSS Series (Basis of Design).pdf PDF
b. RELOC-Ready Luminaire Universal Fixture Connector for Basis of Design Modular Wiring System.pdf PDF
f. New RELOC OnePass Converter - OC Series (Basis of Design).pdf PDF
j. Building 9 BTC Lighting with Basis of Design Modular Wiring.pdf PDF
k. Krueger Ceiling Adapters.pdf PDF
c. BLDG 9’s BTC Photometric w.Basis of Design Light Fixture – Normal LGT.pdf PDF
e. BTC Approx 300 Light Fixtures Drawing PDF - Please Request DWG File.pdf PDF
d. BLDG 9’s BTC Photometric w.Basis of Design Light Fixture – Emergency LGT.pdf PDF
a. New Recessed 2’ x 2’ LED Light Fixture (Basis of Design).pdf PDF
RFQ 15F06722Q0000043 FBI CJIS Lighting Bldg 9.docx DOCX document
h. New RELOC OnePass Cables - Fixture Cable – OFC Series (Basis of Design).pdf PDF
PRICING TEMPLATE Building 9 Lighting 06152022.xlsx XLSX spreadsheet
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OFC_OC1_OC2_OC3

Catalog Number

Notes Type

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 1996-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

FEATURES & SPECIFICATIONS

INTENDED USE

The OnePass Fixture Cable (OFC), Cable 1 port (OC1), Cable 2 port (OC2), and Cable 3 Port (OC3) are male/female cables that provides additional length throughout the RELOC system.

Cables can also provide power to miscellaneous devices such as exits, emergency units, convenience power and access floor systems. The OFC attaches directly into the access plate or through any 1/2” trade-size knockout. The OC2 is a splitter and cable extender in one easy-to-use component. The OC2 All Metal Housings (AMH) provides installers options for how to configure the system based on specification requirements. The OC3 is a splitter and cable extender in one component.

ELECTRICAL

• Rated for use on 20-amp branch circuits.

• Safety-keying prevents accidental mating of components with different voltages.

• C12S option includes three 12 AWG conductors and 18 AWG shielded pair for controls wiring. (-20°C to +90°C).

• The OC2 conductors are 10 AWG or 12 AWG copper conductors with -20°C to +90°C ther-moplastic insulation rated 600V. It includes a fully rated No. 12 AWG & 10 AWG grounding conductor.

• The OC1, OC2 with AMH option, and OC3 are 12 AWG copper with -20°C to +90°C thermo-plastic insulation rated 600V. It includes a fully rated No. 12 AWG grounding conductor.

• The OFC Fixture leads are No. 18 AWG solid copper with prestripped, solid-color leads for easy installation into side, back or push-in-type terminals.

SYSTEM FEATURES

• Pin and socket contacts.

• Color-coded labels for quick voltage identification.

• Available in varying lengths to suit most common fixture spacing requirements.

• Auto-latching springs prevent accidental disengagement.

• Available with green armor standard for easy identification in healthcare facilities (HCF option).

• Dust Cover available for unused ports: RDC3 METAL DUSCT COVER CSA/UL J50 (available job pack of 50 only)

• The OC1, OC2, and OC3 EXT option enables them to be installed in hot and cold applications (-40° to +90°C).

• Type of insulation for EXT option is based on NEC Table 310.104(A).

• Non-plenum rated OC2 plastic housing.

• Plenum rated low voltage cable (LVC option)

OnePass® Cables

OFC, OC1, OC2, OC3

OC1

Cable 1 Port

OC2

Cable 2 Port

OC3

Cable 3 Port

OFC

Fixture Cable

LISTINGS

• C-UL-US Listed (dry location only).

• C12S option meets NEC requirements for separation of Class 2 and Class 3 circuits from Class 1 circuits by a barrier as defined by Article 725.136(B).

• Meets NEC requirements for redundant ground paths for patient care areas in healthcare facilities (HCF option).

• Canadian Patent No. 2,845,603 (Class l, Class ll)

WARRANTY

• 5-year limited warranty. Complete warranty terms located at:

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

Series Voltage Conductors Length Controls Wiring Options Finish9

OC1 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12 AWG conductors, including one 12 AWG ground

12/4G Five 12 AWG conductors, including one 12 AWG ground

1 ft up to 50 ft

(blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires1

CAT5_ Preterminated and tested CAT5 cable attached, specify length2

LVC 3 position connector system for low voltage wiring3

(blank) Not required

2N Two circuit, two neutral4

EXT Extreme temperature rating conductors5

HCF Meets healthcare facility requirements6

IGW Isolated ground wire7

X Cross Over Cable8

(blank) Not required

RD Red

BK Black

WH White

BE Beige

OJ Orange

ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC1 277 12/3G 09

6. HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S, CAT5 and LVC.

7. IGW available only with 120V; 12/3G & 12/4G conductor, and up to 35ft length.

8. X option available with 12/3G conductors only. Hot conductors 1 and 2 alternate internally to the cable.

9. Non-plenum rated color cable available up to 35ft.

NOTES

1. C12S must use 12/2G conductors.

2. See spec sheet RCAT5 for details. CAT5 length must be 2FT longer than OC1. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OC1 and the length of drop for the fixture plus 2FT.

3. See spec sheet LVC for details.

4. 2N option available only in 120V, 277V and 347V; 12/4G conductors only

5. EXT option required for EXTREME hot and cold temperature applications (-40° to 90°C). Available with 12/2G and 12/3G conductors.

OnePass® Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 1996-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

Series Voltage Conductors Length Controls Wiring Options Finish8

OC2 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

10/2G Three 10 AWG conductors, including one 10 AWG ground

10/3G Four 10 AWG conductors, in-cluding one 10 AWG ground

10/4G Five 10 AWG conductors, in-cluding one 10 AWG ground

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12 AWG conductors, including one 12 AWG ground

12/4G Five 12 AWG conductors, including one 12 AWG ground

1 ft up to 50 ft

(blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires1

CAT5_ Preterminated and tested CAT5 cable attached, specify length2

LVC 3 position connector system for low voltage wiring3

(blank) Not required

2N Two circuit, two neutral4

AMH All metal housings5

EXT Extreme temperature rating conductors6

IGW Isolated ground wire7

(blank) Not required

RD Red

BK Black

WH White

BE Beige

OJ Orange

ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC2 277 12/4G 25

6. EXT option required for EXTREME hot and cold temperature applications (-40° to 90°C). Available with

10/2G, 10/3G, 12/2G, and 12/3G conductors.

7. IGW available only with 120V; 12/3G & 12/4G conductor, and up to 35ft length.

8. Non-plenum rated color cable available up to 35ft.

NOTES

1. C12S must use 12/2G conductors.

2. See spec sheet RCAT5 for details. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OC2 and the length of drop for the fixture plus 2FT.

3. See spec sheet LVC for details.

4. 2N option available only in 120V, 277V and 347V; 10/4G and 12/4G conductors only.

5. AMH option available with 12/2G, 12/3G, 12/4G conductors.

Series Voltage Conductors Length Controls Wiring Options Finish8

OC3 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12 AWG conductors, including one 12 AWG ground

12/4G Five 12 AWG conductors, including one 12 AWG ground

1 ft up to 50 ft

(blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires1

CAT5_ Preterminated and tested CAT5 cable attached, specify length2

LVC 3 position connector system for low voltage wiring3

(blank) Not required

2N Two circuit, two neutral4

EXT Extreme temperature rating conductors5

HCF Meets healthcare facility requirements6

IGW Isolated ground wire7

(blank) Not required

RD Red

BK Black

WH White

BE Beige

OJ Orange

ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC3 277 12/3G 15

6. HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S, CAT5 and LVC.

7. IGW available only with 120V; 12/3G & 12/4G conductor, and up to 35ft length.

8. Non-plenum rated color cable available up to 35ft.

NOTES

1. C12S must use 12/2G conductors.

2. See spec sheet RCAT5 for details. When used with OCS, OCU or OD fixture drop, CAT5 length must include the length of the OC3 and the length of drop for the fixture plus 2FT.

3. See spec sheet LVC for details.

4. 2N option available only in 120V, 277V and 347V; 12/4G conductors only

5. EXT option required for EXTREME hot and cold temperature applications (-40° to 90°C). Available with 12/2G, and 12/3G conductors.

OnePass® Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 1996-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

Series Voltage Conductors Length Controls Wiring Options Connector Type

OFC 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12 AWG conductors, including one 12 AWG ground

12/4G Five 12 AWG conductors, including one 12 AWG ground

1 ft up to 50 ft

(blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires1

CAT5_ Preterminated and tested CAT5 cable attached, specify length2

LVC 3 position connector system for low voltage wiring3

(blank) Not required

G Ground wire4

2N Two circuit, two neutral 5

HCF Meets healthcare facility requirements6

X Cross Over Cable7

(blank) Not required

RRL RELOC®

- ready luminaires8

ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OFC 277 12/3G 11

6. HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S, CAT5 and

LVC. G option required with HCF.

7. X option available with 12/3G conductors only. Hot conductors 1 and 2 alternate internally to the cable.

8. If RRL selected, fixture must have RRL and wiring instruction. See fixture spec sheet for details. See RRL spec sheet for connector details. G option required with RRL.

NOTES

1. C12S must use 12/2G conductors. G option required with C12S.

2. See spec sheet RCAT5 for details. CAT5 length must be 2FT longer than OFC.

3. See spec sheet LVC for details. Mating fixture connection shipped with cable.

4. G option required for use in Canada. Required for C12S, HCF and RRL option.

5. 2N option available only in 120V, 277V and 347V; 12/4G conductors only.

OnePass® Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 1996-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

DIMENSIONS

Dimensions are shown in inches (millimeters)

A – Die-cast zinc with zinc-plated CRS cover

B – UL recognized connector body

C – Tin-plated brass contacts

D – MC Cable standard. HCF MC, C12S MC optional, IGW option standard with FMC.

2-1/4 (58)

2-3/16 (55.6)

AB

D C

9/16 (14.3)

7/16 (11.1)

3-1/4 (82.6)

3-3/8 (87.5)

3-1/4 (82.6)

4-1/2 (114.3)

1-1/8 (28.6)A

B 7/16 (11.2)

2-1/4 (57.2)

2-1/4 (57.2)

D

C

OC1 - Cable 1 Port

A – Injection-molded, high-impact polymeric compound enclosure

B – Tin-plated, brass contacts

C – MC Cable standard. C12S MC optional, IGW option standard with FMC.

D – 18-gauge galvanized steel cover, zinc alloyed casting

OC2 - Cable 2 Port

2-1/4 (58)

7/16" (11.1)

5/8" (16)

2 1/4 (58)

3 3/8" (87.5)

4 9/16" (116)

A B

C

D

A – Die-cast zinc with zinc-plated CRS cover

B – UL recognized connector body

C – Tin-plated brass contacts

D – MC Cable standard. HCF MC, C12S MC optional, IGW option standard with FMC.

OC3 - Cable 3 Port

OnePass® Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 1996-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

A – UL-recognized connector body

B – Die-cast zinc with zinc-plated CRS cover

C – Tin-plated, brass contacts

D – Cast snap-in fitting fits 1.2” trade-size K.O. and provides grounding

E – No. 18 AWG solid copper wires rated at 600V, 90°C thermoplastic insulation with stripped leads

F – MC cable standard. HCF MC, C12S MC optional.

NOTES

• One, two or three hot conductors in 120V and 277V as required.

• Rated for 20-amp capacity.

• Prefabricated standard selector cable carrying No. 12 AWG copper conductors. 600V, 90°C thermoplastic insulation and fully rated bare grounding conductor.

• Standard selector cable provides auto-grounding to fixture unless specified otherwise.

B

F

C D

A

2-1/4 (58)

2-3/16 (55.6)

7/16 (11.1)

9/16 (14.3)

1-1/4 (31.8)

3-3/8 (87.5)

3-1/4 (82.6)

E

E

DIMENSIONS

Dimensions are shown in inches (millimeters)

OFC - Fixture Cable

SYSTEM VIEW

System View designs are for illustrative purposes only.

OC1

OFC

OFC

OC

OST

OnePass OFC Wire Color Chart 120V, 277V, 347V Standard Wire Colors

Position 1 2 3 4 5

Conductor Ground Hot #1 Hot #2 Hot #3 Neutral #1

120V & 347V Bare or Green Black Red Blue White

277V Bare or Green Brown Orange Yellow Gray

208V, 240V, 480V Standard Wire Colors

Position 1 2 3 4 5

Conductor Ground Hot #1 Hot #2 Hot #3 Hot #4

208V & 240V Bare or Green Black Red Blue Violet

480V Bare or Green Brown Orange Yellow Violet

120V, 277V, 347V Two Circuit, Two Neutral (2N option)

Position 1 2 3 4 5

Conductor Ground Hot #1 Hot #2 Neutral #2 Neutral #1

120V & 347V Bare or Green Black Red Gray White

277V Bare or Green Brown Orange White Gray

120V, 277V, 347V Class I, Class II (C12S option)

Position 1 2 3 4 5

Conductor Hot #1 Neutral #1 Ground Data #1 Data #2

120V & 347V Black White Bare or Green Violet Gray

277V Brown Gray Bare or Green Violet Gray

208V & 240V Brown Orange Bare or Green Violet Gray

480V Brown Orange Bare or Green Violet Gray

Note: Wire colors are specific for cables with exposed wireleads.

File details come from the government source that posted it. Updated .