f. New RELOC OnePass Converter - OC Series (Basis of Design).pdf

PDF 299 KB Posted

Attached to
FBI CJIS Division, Lighting Replacement, Bldg 9
Solicitation number
15F06722Q0000043
Issued by

About this file

This document includes a federal contract opportunity from the FBI CJIS Division to purchase LED lighting fixtures and replacement components. The FBI seeks to award a single purchase order on a best value basis for delivery to Clarksburg, WV by the anticipated dates. Bids are due by June 30, 2022 and shall utilize the attached pricing template, which includes the specifications and existing fixtures. The replacement light fixtures must meet the energy efficiency and specification requirements provided in the second tab. Questions are due by June 17, 2022 and shall be submitted to the specified contracting officer and acquisition support personnel via email. This is an open market, brand name or equal, simplified acquisition that has been set aside 100% for small business concerns.

View the file

Other files

File Type Posted
FBI_Lutron Driver Allotment Letter_QTY 607.pdf PDF
REVISED 22-0627_Building 9 Lighting PRICING TEMPLATE.xlsx XLSX spreadsheet
20220726 Questions_Answered - LUTRON LETTER.xlsx XLSX spreadsheet
Questions_Answered 220706.xlsx XLSX spreadsheet
UPDATED Questions_Answered 220701.xlsx XLSX spreadsheet
REVISED 22-0627_Building 9 Lighting PRICING TEMPLATE.xlsx XLSX spreadsheet
Questions_Answered 22-0616.xlsx XLSX spreadsheet
OEM Legacy Pricing Letter (FBI BTC L2 SW).pdf PDF
i. New RELOC OnePass Splitter Splice – OSS Series (Basis of Design).pdf PDF
b. RELOC-Ready Luminaire Universal Fixture Connector for Basis of Design Modular Wiring System.pdf PDF
j. Building 9 BTC Lighting with Basis of Design Modular Wiring.pdf PDF
k. Krueger Ceiling Adapters.pdf PDF
c. BLDG 9’s BTC Photometric w.Basis of Design Light Fixture – Normal LGT.pdf PDF
e. BTC Approx 300 Light Fixtures Drawing PDF - Please Request DWG File.pdf PDF
d. BLDG 9’s BTC Photometric w.Basis of Design Light Fixture – Emergency LGT.pdf PDF
g. New RELOC OnePass Cables – Cable – OC1 Series (Basis of Design).pdf PDF
a. New Recessed 2’ x 2’ LED Light Fixture (Basis of Design).pdf PDF
RFQ 15F06722Q0000043 FBI CJIS Lighting Bldg 9.docx DOCX document
h. New RELOC OnePass Cables - Fixture Cable – OFC Series (Basis of Design).pdf PDF
PRICING TEMPLATE Building 9 Lighting 06152022.xlsx XLSX spreadsheet
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OC_OSFC_OSC2

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

Catalog Number

Notes Type

FEATURES & SPECIFICATIONS

INTENDED USE

The OnePass converters (OC), starter fixture cable (OSFC), and starter cable 2 port (OSC2) provides the interface between hardwiring and RELOC at the homerun location. The OC is a single female port available with 6 inch wire leads standard or with armored cable. The OSFC attaches directly into the access plate or through any 1/2” trade-size knockout. The OSC2 is a splitter and starter extender cable in one easy to-use component.

ELECTRICAL

• Fits a standard 1/2” trade size knockout.

• 6” leads prestripped 5/8” for ease of wiring.

• Available in varying lengths to suit most common fixture spacing requirements.

• Auto-latching springs prevent accidental disengagement.

• The OC with cable length and OSFC available with green armor standard for easy identifica-tion in healthcare facilities (HCF option).

• Non-plenum rated OC2 plastic housing.

• Plenum rated low voltage cable (LVC option).

• The OC, OSS and OSC2 with EXT opiton enables them to be installed in hot and cold applica-tions (-40° to +90°C).

• Type of insulation for EXT option is based on NEC Table 310.104(A)

SYSTEM FEATURES

• Pin and socket contacts.

• Color-coded labels for quick voltage identification.

• Dust Cover available for unused ports: RDC3 METAL DUSCT COVER CSA/UL J50 (available job pack of 50 only)

CONTROLS-ENABLED WIRING OPTIONS

• 0-24V integrated single-circuit or 0-10V low voltage controls applications: select C12S option.

• 0-24V multi-circuit dimming or 0-10V low voltage controls applications: select LVC option.

• Sensor Switch®, nLight®, LC&D XPoint™ fixture level controls applications: select CAT5_ (length) option.

LISTINGS

• C-UL-US Listed (dry location only).

• C12S option meets NEC requirements for separation of Class 2 and Class 3 circuits from Class 1 circuits by a barrier as defined by Article 725.136(B).

• Meets NEC requirements for redundant ground paths for patient care areas in healthcare facilities (HCF option).

• Canadian Patent No. 2,845,603 (Class l, Class ll)

WARRANTY

5-year limited warranty. Complete warranty terms located at:

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Note: Actual performance may differ as a result of end-user environment and application.

Specifications subject to change without notice.

OnePass® Converter/Starter Cables

OC, OSFC, OSC2

OC

Converter

OSFC

Starter Fixture Cable

OSC2

Starter Cable 2 Port

Series Voltage Conductors Length Controls Wiring Options Finish

OC 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12AWG conduc-tors, including one 12 AWG ground

12/4G Five 12 AWG conduc-tors, including one 12 AWG ground

(blank) 6" wire leads (not available with HCF or color finishes)

1 ft up to 50 ft

(blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires 1

LVC 3 position connec-tor system for low voltage wiring 2

(blank) Not required

2N Two circuit, two neutral 3

EXT Extreme temperature rating conductors 4

HCF Meets healthcare facility requirements 5

IGW Isolated ground wire 6

(blank) Not required

RD Red 7

BK Black 7

WH White 7

BE Beige 7

OJ Orange 7

ORDERING INFORMATION For shortest lead times configure product using bolded options. Example: OC 277 12/4G 01 RD

Notes

1. C12S must use 12/2G conductors.

2. See spec sheet LVC for details.

3. 2N option available only in 120V, 277V and 347V and 12/4G conductors only

4. EXT option required for EXTREME hot and cold temperature applications

(-40° to 90°C). Available with 12/2G and 12/3G only.

5. HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S and LVC. Not available with 6” wire leads

6. IGW available only with 120V, 12/3G & 12/4G conductor, and up to 35ft length.

7. Non-plenum rated color cable available up to 35ft. Color finishes not available with 6” wire leads.

OnePass® Converter/Starter Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

Series Voltage Conductors Length Controls Wiring Options Finish6

OSC2 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

10/2G Three 10 AWG conductors, including one 10 AWG ground

10/3G Four 10 AWG conduc-tors, including one 10 AWG ground

10/4G Five 10 AWG conduc-tors, including one 10 AWG ground

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12 AWG conduc-tors, including one 12 AWG ground

12/4G Five 12 AWG conduc-tors, including one 12 AWG ground

1 ft up to 50 ft (blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires 1

CAT5_ Preterminated and tested CAT5 cable attached, specify length 2

LVC 3 position connec-tor system for low voltage wiring 3

(blank) Not required

2N Two circuit, two neutral 4

EXT Extreme temperature rating conductors 5

(blank) Not required

RD Red

BK Black

WH White

BE Beige

OJ Orange

Series Voltage Conductors Length Controls Wiring Options Connector Type

OSFC 120 120V

208 208V

240 240V

277 277V

347 347V

480 480V

12/2G Three 12 AWG conductors, including one 12 AWG ground

12/3G Four 12AWG conduc-tors, including one 12 AWG ground

12/4G Five 12 AWG conduc-tors, including one 12 AWG ground

1 ft up to 50 ft (blank) Not required

C12S Integrated CI,CII rated line voltage and signal wires 1

CAT5_ Preterminated and tested CAT5 cable attached, specify length 2

LVC 3 position connec-tor system for low voltage wiring 3

(blank) Not required

G Ground wire 4

2N Two circuit, two neutral 5

HCF Meets healthcare facility requirements 6

(blank) Not required

RRL RELOC®-ready luminaires 7

ORDERING INFORMATION For shortest lead times configure product using bolded options.

ORDERING INFORMATION For shortest lead times configure product using bolded options.

Example: OSC2 277 10/4G 01

Example: OSFC 277 12/2G 05

Notes

1. C12S must use 12/2G conductors.

2. See spec sheet RCAT5 for details. When used with OCS, OCU or

OD fixture drop, CAT5 length must include the length of the OSC2 and the length of drop for the fixture plus 2FT.

3. See spec sheet LVC for details.

4. 2N option available only in 120V, 277V and 347V; 10/4G and

12/4G conductors only

5. EXT option required for EXTREME hot and cold temperature applications.(-40° to 90°C). Available with 12/2G, 10/2G, 12/3G, and 10/3G only.

6. Non-plenum rated color cable available up to 35ft.

Notes

1. C12S must use 12/2G conductors.

2. See spec sheet RCAT5 for details. CAT5 length must be 2FT longer than OSFC.

3. See spec sheet LVC for details. Mating fixture connection shipped with cable.

4. G option required for use in Canada. Required for C12S, HCF, and

RRL option.

5. 2N option available only in 120V, 277V and 347V; 12/4G conductors only

6. HCF available with 12/4G conductors only. HCF not available with controls wiring options C12S, CAT5_ and LVC.

7. If RRL selected, fixture must have RRL and wiring instruction.

See fixture spec sheet for details. See RRL spec sheet for connector details.

OnePass® Converter/Starter Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

DIMENSIONS

Dimensions are shown in inches (millimeters)

OC – Converter

A – 18-gauge, zinc-plated, CRS cover

B – UL-recognized connector body

C – Tin-plated, brass contacts

D – 6" leads prestripped 5/8"

E – Threaded nipple with locknut for easy installation in 1/2" trade-size K.O.

A – Die-cast zinc with zinc-plated CRS cover

B – UL recognized connector body

C – Tin-plated brass contacts

D – Length option required. MC Cable standard. HCF MC, C12S MC optional. IGW option standard with FMC.

NOTES

• One, two or three hot conductors in 120V and 277V as required.

• Rated for 20-amp capacity.

• Prefabricated circuit distributor carrying No. 12 AWG copper conductors rated at 600V, 90°C thermoplastic insulation and fully rated solid bare grounding conductor.

Standard Construction Armored Cable Construction

2-3/16 (55.6)

2-3/8 (60.3)

9/16 (14.3)

BA

CD

E

2-3/16 (55.6)

9/16 (14.3)

3-3/8 (87.5)

B A

C D

OC2OC

OC2OCS/OCU

OCS/OCU

SYSTEM VIEW

System View designs are for illustrative purposes only.

OnePass® Converter/Starter Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

A – Injection-molded, high-impact polymeric compound enclosure

B – Tin-plated, brass contacts

C – MC Cable standard. C12S MC optional.

DIMENSIONS

Dimensions are shown in inches (millimeters)

4-1/2 (114.3)

1-1/8 (28.7)

2-1/4 (57.2)

B

A

C

SYSTEM VIEW

System View designs are for illustrative purposes only.

OSC2

OC2OCS/OCU

OCS/OCU

OSC2 – Starter Cable 2 Port

OnePass® Converter/Starter Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

OSFC – Starter Fixture Cable

DIMENSIONS

Dimensions are shown in inches (millimeters)

A – UL-recognized connector body

B – Die-cast zinc with zinc-plated CRS cover

C – Tin-plated, brass contacts

D – Cast snap-in fitting fits 1.2” trade-size K.O. and provides grounding

E – No. 18 AWG solid copper wires rated at 600V, 90°C thermoplastic insulation with stripped leads

F – MC Cable standard. FMC, HCF MC, C12S MC optional

NOTES

• One, two or three hot conductors in 120V and 277V as required.

• Rated for 20-amp capacity.

• Prefabricated standard selector cable carrying No. 12 AWG copper conductors. 600V, 90°C thermoplastic insulation and fully rated bare grounding conductor.

• Standard selector cable provides auto-grounding to fixture unless specified otherwise.

B

F

C D

A

2-3/16 (55.6)

9/16 (14.3)

1-1/4 (31.8)

3-3/8 (87.5)

E

E

SYSTEM VIEW

System View designs are for illustrative purposes only.

Connection above the wall

MC CABLE

(BY OTHERS)

MC CABLE

(BY OTHERS)

MC CABLE

(BY OTHERS)

Connection inside the wall

MC CABLE

(BY OTHERS)

MC CABLE

(BY OTHERS)

MC CABLE

(BY OTHERS)

OFSC

OFSCOFSC

OFSC

OFC

OFC

OFC

OFC

OnePass® Converter/Starter Cables

One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupportreloc@acuitybrands.com www.relocwiring.com

© 2017-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/20/19

ONEPASS® CONVERTER/STARTER CABLES WIRE COLOR CHART

120V, 277V, 347V Standard Wire Colors

Position 1 2 3 4 5

Conductor Ground Hot# 1 Hot# 2 Hot# 3 Neutral #1

120V & 347V Bare or Green Black Red Blue White

277V Bare or Green Brown Orange Yellow Gray

208V, 240V, 480V Standard Wire Colors

Position 1 2 3 4 5

Conductor Ground Hot# 1 Hot# 2 Hot# 3 Hot #4

208V & 240V Bare or Green Black Red Blue Violet

480V Bare or Green Brown Orange Yellow Violet

120V, 277V, 347V Two Circuit, Two Neutral (2N option)

Position 1 2 3 4 5

Conductor Ground Hot# 1 Hot# 2 Neutral #2 Neutral #1

120V & 347V Bare or Green Black Red Gray White

277V Bare or Green Brown Orange White Gray

120V, 277V, 347V Class I, Class II (C12S option)

Position 1 2 3 4 5

Conductor Hot #1 Neutral #1 Ground Data #1 Data #2

120V & 347V Black White Bare or Green Violet Gray

277V Brown Gray Bare or Green Violet Gray

208V & 240V Brown Orange Bare or Green Violet Gray

480V Brown Orange Bare or Green Violet Gray

120V Isolated Ground Wire (IGW option)

Position 1 2 3 4 5

Conductor Ground Hot# 1 Hot# 2 IGW Neutral #1

120V Bare or Green Black Red Green w/Yellow stripe White

File details come from the government source that posted it. Updated .