FWRI 3-14-26 Quarterly Report.pdf

PDF 5 MB Posted

Attached to
St Pete Campus Fire Alarm Replacement
Solicitation number
ITB-16820
Issued by
Leon County, Florida

About this file

FWRI 3-14-26 Quarterly Report Summary

This is a quarterly fire alarm system inspection report prepared by Piper Fire for the Florida Fish and Wildlife Conservation Commission's St. Petersburg campus. The report documents inspections conducted on three separate dates in March 2026 across multiple buildings at the 140,000-square-foot campus located at 845 West Peninsula Drive and 100 Eighth Avenue SE, St. Petersburg, Florida. The inspections were performed by certified inspectors Chris Hill (FASA/BASA qualified) and Dwight Overton (FASA/BASA qualified) in accordance with NFPA 72 2019 Edition standards. The work was conducted on behalf of the monitoring entity Simplex, and included comprehensive testing of fire alarm systems, devices, circuits, battery backup systems, and notification procedures across the four-building campus. Testing was performed at the three facilities identified with customer number 8542 and account number 112-1336, with systems restored to normal operation on March 3, 2026 at 3:00 p.m.

The inspections identified multiple fire alarm devices across the campus, including smoke detectors (ion and photo), duct detectors, heat detectors, manual pull stations, horn strobes, and speakers installed throughout various floors and rooms. Three deficiencies were documented during the inspections: a smoke detector in zone I-015 showing no power, a horn strobe in the roof wood shop that failed operation, and a duct detector in zone M2-74 in the electrical room with broken housing that did not activate during testing. All systems utilized Simplex fire alarm control panels with addressable components, sealed lead-acid battery backup (24-hour capacity), and dedicated 120-volt primary power supplies with 20-amp breakers. The inspector noted that the main building experienced panel trouble due to work being performed in the chiller room and recommended that the elevator recall key be available for the next annual inspection. The facility also has a public Halon system in the library that requires attention.

View the file

Other files

File Type Posted
FWC 26.27-22C T&Cs Final.pdf PDF
FWC 26.27-22C ITB Final.pdf PDF
Access System Doors.pdf PDF
FWC 26.27-22C Addendum 2 Q&A.pdf PDF
SW-STP-JU-FP.pdf PDF
FWC 26.27-22C Addendum 1 COE Update.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Combo

Date of Inspection:

03/03/2026

Customer #:

Inspection File #:

I-9341

Inspector Name:

Chris Hill

Inspection Qualification:

FASA/BASA

Property Name:

Florida Fish & Wildlife

Customer Contact:

Dillon Day

Street:

845 West Penninsula Drive

Phone Number:

727-502-4780

City:

St. Petersburg

State:

Florida

Zip Code:

33701

Fax Number:

Building/Location:

Email Address:

dillion.day@myfwc.com

Service Provided:

Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test

Monitoring Entity:

Simplex

Local:

No

Account #:

112-1336

Phone #:

18887467539

FACP Loc.

Lobby

Make:

Simplex

Model #:

Addressable:

Yes

Dialer Make: Model: System Type:

Fire Alarm

Make Notifications

Notications Entity Yes/No Who was notified Time

Monitoring Entity: Jonson controls Yes Matt (maintenance takes systems offline 8:00

Building Occupants:

Other - Specify:

Premises Monitoring

Monitoring Info Yes/No Who/Operator Time

Alarm Signal Yes 9:00

Supervisory Signal Yes 8:45

Supervisory Restore Yes 8:45

Trouble Signal Yes 8:30

Notification That Testing is Complete

Notifications Made Yes/No Who Time

Bldg. Management 3:00

Monitoring Agency Maintenance

Building Occupants

Other - Specify

No of Initiation Circuits Used: No of Initiation Circuits Total:

undefined

Circuit Styles:

B

Last Service Date:

02/03/2025

Equipment Qty Manufacturer Model #

Ion Smoke Detector 9 Simplex 4098-9714

Photo Smoke

Duct Detector 2 Simplex

Heat Detector

Manual Pull Station 8 Simplex

Supervisory Switch

Lic#EF0001219

13075 US HWY 19 N.

CLEARWATER, FL 33764

customersupport@piperfire.com

PINELLAS (727) 581-9339

SARASOTA (941) 377-2100

PINELLAS FAX (727) 581-8332

SARASOTA FAX (941) 377-2001

STATEWIDE (800) 327-7604

Fire Alarm System Test and Inspection Form

Prior to any Testing of Fire Alarm System

Alarm Initiation Devices And Circuit Information

Equipment Qty Manufacturer Model #

Other:

No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:

Y

Circuits Supervised:

Yes

Equipment Qty Manufacturer Model #

Bells

Horns

Horn/Strobes 26 Simplex Red wall mount

Strobes 5 Simplex Red wall mount

Speakers

Speaker/Strobes

Other:

Primary Nominal Voltage:

Is the fire alarm on its own dedicated circuit?

Yes

Breaker/Fuse #:

Panel EM #19

Amps:

Storage Battery - Qty:

Type of Battery:

SEALED / LED ACID

Voltage Per Battery:

Amp Hour:

Date:

4/25

Other:

Calculated capacity to operate system, in hours:

Location of fuel source, if yes:

N/A

Engine driven generator dedicated to fire alarm:

N/A

Location of UPS system:

N/A

Equipment Powered by UPS:

N/A

In Alarm mode (minutes):

Calculated capacity of UPS batteries to drive system in standby (hours):

N/A

Type Functional Visual Comments

Control Panel Yes

Lamps/LEDs Yes

Fuses

Trouble Signals Yes

Disconnect Switches Yes

Ground Fault Monitor Yes

Supervision Yes

Phone Handsets

Phone Jacks

Elevator Recall

Elevator Shunt Trip

Power extender panels

Surge Protection Yes

Primary Power Supply Yes

Battery Condition Yes

Load Voltage Yes

Discharge Voltage: Yes

Charger Test Yes

Engine-driven generator

Fire Pump Yes

Signaling Line Circuits and Circuit Information

Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type

System Tests and Inspections

Type Functional Visual Comments

Door-Releasing Devices

Fan Shutdown

Smoke Control

Smoke Damper

Other - Specify:

Annunciator:

Qty Functional Visual Location

Inspect Test

Location Pass/Fail Device Zone Sensitivity Remarks

FACP Pass

Lobby Pass Manual Pull Station

Pass Horn Strobe

Pass Smoke Detector Visual only no recall key

3rd floor Pass

Lobby Pass Smoke Detector Visual

Pass Manual Pull Station

Pass Horn Strobe

Stairwell 1 Pass Strobe

303 Pass Heat Detector

Pass Horn Strobe

Pass Smoke Detector Normal range

Pass CO Detector

Pass CO Detector

Roof Pass Horn Strobe

Roof wood shop Fail Horn Strobe

I306 Pass Horn Strobe

I 301 N/A

2nd floor lobby

Pass Manual Pull Station

Pass Horn Strobe

Pass Smoke Detector Visual

Men’s room Pass Strobe

Women’s room Pass Smoke Detector Normal range

At restrooms Pass Horn Strobe

I-205 Library/ document N/A HALON SYSTEM

Stair 1 first floor Pass Horn Strobe

1st floor elevator lobby Pass Horn Strobe

Pass Manual Pull Station

N/A Smoke Detector Visual

At electric room Pass Manual Pull Station

Pass Horn Strobe

Men’s room Pass Strobe

Women’s room Pass Strobe

I-117 Pass Horn Strobe

I-105 Pass Horn Strobe

Pass Duct Detector

Pass Remote Test Switch

Pass Duct Detector

Pass Remote Test Switch

Device List

Location Pass/Fail Device Zone Sensitivity Remarks

I-108A Pass Horn Strobe

Hall at I-105A Pass Horn Strobe

I-108 hall Pass Horn Strobe

Pass Manual Pull Station

I-108 Pass Smoke Detector Normal range

I 109A Pass Smoke Detector Normal range

Stair 2 Pass Horn Strobe

Slanted hallway Pass Horn Strobe

Ground floor I-006A Pass Manual Pull Station

Pass Horn Strobe

Storage room on right Pass Horn Strobe

I-205 Pass Horn Strobe

I-026 Pass Strobe

I-009 Pass Horn Strobe

I-010 Pass Horn Strobe

I-024 Pass Horn Strobe

I-015 Fail Smoke Detector Appears to have no power

I-027 Pass Horn Strobe

Pass Duct Detector

Pass Remote Test Switch

Pass Duct Detector

Pass Remote Test Switch

Pass Duct Detector

Pass Remote Test Switch

Pump room Pass

Pass Manual Pull Station

Pass Horn Strobe

EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:

Smoke detector did not operate during inspection

INSPECTOR / TECHNICIAN COMMENTS:

Date the system was restored to normal operation on:

03/03/2026

Time:

3:00

Name of Owner or Representative: Date:

03/03/2026

Owner or Representative Signature:

Technician's Name:

Chris Hill

Date:

03/03/2026

Technician's Signature:

Deficiencies & Comments / Fire Alarm Form

DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.

NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.

CH Chris Hill - 3/3/2026 Public

Halon system in library

CH Chris Hill - 3/3/2026 Resolve

Pass/Fail

Appears to have no power

Linked Field

Row # Location Pass/Fail Device Zone Sensitivity Remarks

57 I-015 Fail Smoke Detector Appears to have no power

CH Chris Hill - 3/14/2026 Public

Panel in trouble upon arrival and departure due to work being preformed in main building chiller room

CH Chris Hill - 3/14/2026 Resolve

Pass/Fail

Horn worked strobe did not

Linked Field

Row # Location Pass/Fail Device Zone Sensitivity Remarks

16 Roof wood shop Fail Horn Strobe

03/03/2026

Customer #:

Inspection File #:

Inspector Name:

Chris Hill

Inspection Qualification:

FASA/BASA

Property Name:

Florida Fish & Wildlife

Customer Contact:

Gavin Hutchinson

Street:

855 West Penninsula Drive

Phone Number:

727-502-4780

City:

St. Petersburg

State:

FL

Zip Code:

33701

Fax Number:

Building/Location: Email Address:

Gavin.Hutchinson@myfwc.com

Service Provided:

Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test

Monitoring Entity:

Simplex

Local:

No

Account #:

112-1336

Phone #:

18887467539

FACP Loc.

Lobby

Make:

Simplex

Model #:

Addressable:

Yes

Dialer Make: Model: System Type:

Fire Alarm

Make Notifications

Notications Entity Yes/No Who was notified Time

Monitoring Entity: Matt ( maintenance takes systems offline 8:00

Building Occupants:

Other - Specify:

Premises Monitoring

Monitoring Info Yes/No Who/Operator Time

Alarm Signal 9:00

Supervisory Signal 8:45

Supervisory Restore 8:45

Trouble Signal 8:30

Notification That Testing is Complete

Notifications Made Yes/No Who Time

Bldg. Management 3:00

Monitoring Agency

Building Occupants

Other - Specify

No of Initiation Circuits Used: No of Initiation Circuits Total:

undefined

Circuit Styles:

B

Last Service Date:

03/03/2026

Equipment Qty Manufacturer Model #

Ion Smoke Detector 1 Simplex

Photo Smoke

Duct Detector 5 Simplex

Heat Detector

Manual Pull Station 10 Simplex B key

Supervisory Switch

Lic#EF0001219

13075 US HWY 19 N.

CLEARWATER, FL 33764

customersupport@piperfire.com

PINELLAS (727) 581-9339

SARASOTA (941) 377-2100

PINELLAS FAX (727) 581-8332

SARASOTA FAX (941) 377-2001

STATEWIDE (800) 327-7604

Fire Alarm System Test and Inspection Form

Prior to any Testing of Fire Alarm System

No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:

Y

Circuits Supervised:

Yes

Equipment Qty Manufacturer Model #

Bells

Horns

Horn/Strobes 16 Simplex Red wall mount

Strobes 5 Simplex

Speakers

Speaker/Strobes

Other:

Primary Nominal Voltage:

Is the fire alarm on its own dedicated circuit?

Yes

Breaker/Fuse #:

Room F010 panel GLP1 #28

Amps:

Storage Battery - Qty:

Type of Battery:

SEALED / LED ACID

Voltage Per Battery:

Amp Hour:

Date:

1/24

Other:

Calculated capacity to operate system, in hours:

Location of fuel source, if yes:

N/A

Engine driven generator dedicated to fire alarm:

N/A

Location of UPS system:

N/A

Equipment Powered by UPS:

N/A

In Alarm mode (minutes):

Calculated capacity of UPS batteries to drive system in standby (hours):

N/A

Type Functional Visual Comments

Control Panel Yes

Lamps/LEDs Yes

Fuses

Trouble Signals Yes

Disconnect Switches Yes

Ground Fault Monitor Yes

Supervision Yes

Phone Handsets

Phone Jacks

Elevator Recall

Elevator Shunt Trip

Power extender panels

Surge Protection Yes

Primary Power Supply Yes

Battery Condition Yes

Load Voltage Yes

Discharge Voltage: Yes

Charger Test Yes

Engine-driven generator

Fire Pump

Signaling Line Circuits and Circuit Information

Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type

Fan Shutdown

Smoke Control

Smoke Damper

Other - Specify:

Annunciator:

Qty Functional Visual Location

Inspect Test

Location Pass/Fail Device Zone Sensitivity Remarks

Lobby Pass Manual Pull Station

Pass Horn Strobe

Pass Smoke Detector Normal range

Stair well F 125 Pass Strobe

F 125A Pass Manual Pull Station

Pass Horn Strobe

At F 113 Pass Manual Pull Station

Pass Horn Strobe

F 109 Pass Horn Strobe

F 107 Pass Horn Strobe

F;106 Pass Duct Detector

Pass Remote Test Switch

Pass Duct Detector

Pass Remote Test Switch

Men’s room Pass Strobe

Women’s room Pass Strobe

F 124 Pass Manual Pull Station

Pass Strobe

Pass Duct Detector

Pass Remote Test Switch

F 123 Pass Horn Strobe

F 121 Pass Manual Pull Station

F 117 Pass Manual Pull Station

Pass Horn Strobe

F 116 Pass Horn Strobe

F 125A Pass Manual Pull Station

Pass Horn Strobe

F 003 Pass Horn Strobe

Specimen room Pass Manual Pull Station

Pass Horn Strobe

Pass Duct Detector

Specimen room near exit at F001 Pass Horn Strobe

Pass Manual Pull Station

F 014 Pass Horn Strobe

F 009 Pass Horn Strobe

At F 011 Pass Horn Strobe

F 010 exit Pass Manual Pull Station

Pass Horn Strobe

F 010A Pass Heat Detector

F 011 Pass Strobe

F 009 Pass Duct Detector

EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:

INSPECTOR / TECHNICIAN COMMENTS:

Date the system was restored to normal operation on:

03/03/2026

Time:

3:00

Name of Owner or Representative: Date:

03/03/2026

Owner or Representative Signature:

Technician's Name:

Chris Hill

Date:

03/03/2026

Technician's Signature:

Deficiencies & Comments / Fire Alarm Form

CH Chris Hill - 3/3/2026 Public

Devices in building

CH Chris Hill - 3/14/2026 Public

Trouble on panel at arrival and departure due to work being performed in main building chiller room.

DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.

NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.

03/02/2026

Customer #:

Inspection File #:

I-9341

Inspector Name:

Dwight Overton

Inspection Qualification:

FASA/BASA

Property Name:

Florida Fish & Wildlife

Customer Contact:

Gavin Hutchinson

Street:

100 8th Ave SE

Phone Number:

7275024780

City:

St.Pete

State:

FL

Zip Code:

33701

Fax Number:

Building/Location: Email Address:

Gavin.Hutchinson@myfwc.com

Service Provided:

Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test

Monitoring Entity:

Simplex

Local:

No

Account #:

112-1336

Phone #:

18887467539

FACP Loc.

In communications room G-107

Make:

Simplex

Model #:

Addressable:

Yes

Dialer Make:

Silent Knight

Model:

System Type:

Fire Alarm

Make Notifications

Notications Entity Yes/No Who was notified Time

Monitoring Entity:

Building Occupants:

Other - Specify:

Premises Monitoring

Monitoring Info Yes/No Who/Operator Time

Alarm Signal

Supervisory Signal

Supervisory Restore

Trouble Signal

Notification That Testing is Complete

Notifications Made Yes/No Who Time

Bldg. Management

Monitoring Agency

Building Occupants

Other - Specify

No of Initiation Circuits Used: No of Initiation Circuits Total:

undefined

Circuit Styles:

B

Last Service Date:

03/02/2026

Equipment Qty Manufacturer Model #

Ion Smoke Detector

Photo Smoke 43

Duct Detector 9

Heat Detector 17

Manual Pull Station 23

Supervisory Switch

Lic#EF0001219

13075 US HWY 19 N.

CLEARWATER, FL 33764

customersupport@piperfire.com

PINELLAS (727) 581-9339

SARASOTA (941) 377-2100

PINELLAS FAX (727) 581-8332

SARASOTA FAX (941) 377-2001

STATEWIDE (800) 327-7604

Fire Alarm System Test and Inspection Form

Prior to any Testing of Fire Alarm System

No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:

Y

Circuits Supervised:

Yes

Equipment Qty Manufacturer Model #

Bells

Horns

Horn/Strobes 98

Strobes 5

Speakers

Speaker/Strobes

Other:

Primary Nominal Voltage:

Is the fire alarm on its own dedicated circuit?

Yes

Breaker/Fuse #:

Main electrical room breaker #15

Amps:

Storage Battery - Qty:

Type of Battery:

SEALED / LED ACID

Voltage Per Battery:

Amp Hour:

Date:

2/24

Other:

Calculated capacity to operate system, in hours:

Location of fuel source, if yes:

N/A

Engine driven generator dedicated to fire alarm:

N/A

Location of UPS system:

N/A

Equipment Powered by UPS:

N/A

In Alarm mode (minutes):

Calculated capacity of UPS batteries to drive system in standby (hours):

Type Functional Visual Comments

Control Panel Yes Yes

Lamps/LEDs Yes Yes

Fuses Yes Yes

Trouble Signals Yes Yes

Disconnect Switches Yes Yes

Ground Fault Monitor Yes Yes

Supervision Yes Yes

Phone Handsets

Phone Jacks

Elevator Recall

Elevator Shunt Trip

Power extender panels Yes Yes

Surge Protection Yes Yes

Primary Power Supply Yes Yes

Battery Condition Yes

Load Voltage

Discharge Voltage:

Charger Test

Engine-driven generator

Fire Pump

Signaling Line Circuits and Circuit Information

Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type

Fan Shutdown

Smoke Control

Smoke Damper

Other - Specify:

Annunciator:

Qty Functional Visual Location

Inspect Test

Location Pass/Fail Device Zone Sensitivity Remarks

Sensitivity range

1.25-3.1%FT

FACP ROOM Pass Dialer Batteries dated 2/24

Pass Smoke Detector Within range

Door JU 4 Pass Speaker

Penthouse/mechanical room 5002 Pass Horn Strobe

Stairwell E/E Pass Manual Pull Station

Pass Horn Strobe

4th fl at stair 2 Pass Manual Pull Station

Pass Horn Strobe

At elevator Pass Smoke Detector Within range

Pass Duct Detector

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

Room 4056 Pass Heat Detector

Electrical room 4057 Pass Smoke Detector Within range

Elevator lobby Pass Horn Strobe

On Terrace fourth floor Pass Horn Strobe

Pass Horn Strobe

Communications room 4005 Pass Smoke Detector Within range

Research labs 4036 Pass

Hallway Pass Horn Strobe

Room 4007 Pass Horn Strobe

Pass Strobe

Across from 4047 Pass Horn Strobe

At room 4042 Pass Horn Strobe

In 4039 Pass Smoke Detector Within range

At room 4010 Pass Horn Strobe

At room 4013 Pass Horn Strobe

In 4037 Pass Smoke Detector Within range

Freight elevator lobby at 4036 N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

Room 4017 Pass Horn Strobe

In section 4023

At room 4028 Pass Horn Strobe

At stairwell Pass Manual Pull Station

In communication closet Pass Smoke Detector Within range

In stairwell between four and three Pass Horn Strobe

Third floor at stairwell Pass Manual Pull Station

Pass Horn Strobe

3RD FL Pass

At 3051 Pass Horn Strobe

In room 3057 Pass Smoke Detector Within range

Elevator lobby N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

In room 3041 Pass Duct Detector

Pass Horn Strobe

At 3061 Pass Horn Strobe

In 3036 Pass Heat Detector

In 3064 Pass Horn Strobe

At 3029 Pass Horn Strobe

In 3069 Pass Strobe

Pass Heat Detector

At 3069 Pass Horn Strobe

In 3025 Pass Heat Detector

In 3023 mechanical Pass Manual Pull Station

Pass Horn Strobe

Pass Duct Detector

Pass Duct Detector

Pass Duct Detector

Fail Duct Detector M2-74

Electrical room 3026 Pass Horn Strobe

Pass Smoke Detector Within range

Systems room 3025 Pass Smoke Detector Within range

Elevator lobby N/A Smoke Detector Within range

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

Hallway at elevator lobby

First Office on left Pass Heat Detector

By room 3001 Pass Horn Strobe

In our office 3003 Pass Horn Strobe

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Horn Strobe

At stairwell #2 Pass Manual Pull Station

Pass Horn Strobe

In room 3020 Pass Horn Strobe

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

In printer room Pass Smoke Detector Within range

3020A Pass Smoke Detector Within range

At 3019 Pass Speaker/Strobe

At stair 1 Pass Manual Pull Station

Pass Horn Strobe

Stairwell between floors three and two Pass Horn Strobe

In 3009 Pass Smoke Detector Within range

3009A Pass Smoke Detector Within range

3009B Pass Smoke Detector Within range

3007 Pass Smoke Detector Within range

Pass Smoke Detector Within range

IT/Computer room Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

Pass Smoke Detector Within range

2ND FL

Elevator lobby N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

At elevator Pass Strobe

Research Labs 2034

At 2035 Pass Horn Strobe

Locker room Pass Horn Strobe

Restroom Pass Horn Strobe

At 2038 Pass Horn Strobe

Closet across from 2075 Pass Heat Detector

At 2073 Pass Horn Strobe

At 2070 Pass Horn Strobe

Freight elevator lobby N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

In 2048 Pass Horn Strobe

At 2057 Pass Horn Strobe

In 2064 Pass Smoke Detector Within range

At stairwell Pass Manual Pull Station

Pass Horn Strobe

At stairwell by 2027A Pass Manual Pull Station

Pass Horn Strobe

Administration room 2004

In 2005 Pass Heat Detector

At 2008 Pass Horn Strobe

At 2012 Pass Horn Strobe

At stairwell Pass Manual Pull Station

At 2017 Pass Horn Strobe

At 2020 Pass Horn Strobe

At 2023 Pass Horn Strobe

First floor elevator lobby N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

At elevator Pass Strobe

Mechanical room1010 Pass Manual Pull Station

Pass Horn Strobe

1010A Pass Smoke Detector Within range

1010B Pass Horn Strobe

Pass Horn Strobe

Mechanical room Pass Duct Detector

Pass Duct Detector

Pass Duct Detector

In 1011 Pass Heat Detector

At 1059 Pass Horn Strobe

At 1057 Pass Horn Strobe

At 1054 Pass Horn Strobe

At 1025 Pass Horn Strobe

In 1026 Pass Smoke Detector Within range

Freight elevator lobby

N/A Smoke Detector Within range

Pass Horn Strobe

Men’s restroom Pass Horn Strobe

Women’s restroom Pass Horn Strobe

Inside 1030 Pass Horn Strobe

In 1049 Pass Heat Detector

At 1042 Pass Horn Strobe

In 1050 Pass Smoke Detector Within range

At stairwell Pass Manual Pull Station

Pass Horn Strobe

In stairwell Pass Horn Strobe

Behind elevator at stairwell Pass Manual Pull Station

Pass Horn Strobe

Seminar room 1007 Pass Horn Strobe

Auditorium

At stairwell Pass Manual Pull Station

Pass Horn Strobe

In auditorium Pass Horn Strobe

Pass Horn Strobe

Behind projector screen in hall Pass Manual Pull Station

Pass Horn Strobe

Projection room Pass Smoke Detector Within range

Ground floor at elevator lobby N/A Smoke Detector Within range

Pass Strobe

Pass Horn Strobe

Reception by G-102 Pass Manual Pull Station

In G-102 Pass Heat Detector

By stairwell Pass Manual Pull Station

Pass Horn Strobe

Ground floor stairwell four Pass Manual Pull Station

Pass Horn Strobe

In MAINE electrical room G108 Pass Manual Pull Station

Pass Heat Detector

Pass Horn Strobe

Mechanical room/chiller room JU7 Pass Manual Pull Station

Pass Horn Strobe

Pass Horn Strobe

Pass Heat Detector

Pass Heat Detector

Pass Heat Detector

JU 8 inside bay doors Pass Manual Pull Station

Pass Horn Strobe

JU 11

At restroom Pass Manual Pull Station

Pass Horn Strobe

Restroom Pass Horn Strobe

Restroom Pass Horn Strobe

Hall by CHRIS Lang Office Pass Horn Strobe

Tiffany Ottoson office Pass Smoke Detector Within range

Ground floor stairwell number three Pass Manual Pull Station

Pass Horn Strobe

At JU 12 Pass

Pass Horn Strobe

In JU 12 Pass Heat Detector

At elevator Pass Heat Detector

In JU 13 Pass Smoke Detector Within range

Pass Heat Detector

EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:

Recommend having the elevator recall key on site for next annual inspection.

INSPECTOR / TECHNICIAN COMMENTS:

This building sets off the other (2) buildings off in general alarm. Our contact is aware and will be reaching out to Simplex to address this issue.

SOUNDING OF THE HORNS MUST TAKE PLACE ON THE WEEKEND!

Date the system was restored to normal operation on:

03/02/2026

Time:

Name of Owner or Representative: Date:

03/02/2026

Owner or Representative Signature:

Technician's Name:

Dwight Overton

Date:

03/02/2026

Technician's Signature:

Deficiencies & Comments / Fire Alarm Form

DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.

NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.

DO Dwight Overton - 3/3/2026 Resolve

Pass/Fail

Duct detector did not activate when testing. Duct detector housing is broken.

Linked Field

Row # Location Pass/Fail Device Zone Sensitivity Remarks

65 Fail Duct Detector M2-74