FWRI 3-14-26 Quarterly Report Summary
This is a quarterly fire alarm system inspection report prepared by Piper Fire for the Florida Fish and Wildlife Conservation Commission's St. Petersburg campus. The report documents inspections conducted on three separate dates in March 2026 across multiple buildings at the 140,000-square-foot campus located at 845 West Peninsula Drive and 100 Eighth Avenue SE, St. Petersburg, Florida. The inspections were performed by certified inspectors Chris Hill (FASA/BASA qualified) and Dwight Overton (FASA/BASA qualified) in accordance with NFPA 72 2019 Edition standards. The work was conducted on behalf of the monitoring entity Simplex, and included comprehensive testing of fire alarm systems, devices, circuits, battery backup systems, and notification procedures across the four-building campus. Testing was performed at the three facilities identified with customer number 8542 and account number 112-1336, with systems restored to normal operation on March 3, 2026 at 3:00 p.m.
The inspections identified multiple fire alarm devices across the campus, including smoke detectors (ion and photo), duct detectors, heat detectors, manual pull stations, horn strobes, and speakers installed throughout various floors and rooms. Three deficiencies were documented during the inspections: a smoke detector in zone I-015 showing no power, a horn strobe in the roof wood shop that failed operation, and a duct detector in zone M2-74 in the electrical room with broken housing that did not activate during testing. All systems utilized Simplex fire alarm control panels with addressable components, sealed lead-acid battery backup (24-hour capacity), and dedicated 120-volt primary power supplies with 20-amp breakers. The inspector noted that the main building experienced panel trouble due to work being performed in the chiller room and recommended that the elevator recall key be available for the next annual inspection. The facility also has a public Halon system in the library that requires attention.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FWC 26.27-22C T&Cs Final.pdf | ||
| FWC 26.27-22C ITB Final.pdf | ||
| Access System Doors.pdf | ||
| FWC 26.27-22C Addendum 2 Q&A.pdf | ||
| SW-STP-JU-FP.pdf | ||
| FWC 26.27-22C Addendum 1 COE Update.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Combo
Date of Inspection:
03/03/2026
Customer #:
Inspection File #:
I-9341
Inspector Name:
Chris Hill
Inspection Qualification:
FASA/BASA
Property Name:
Florida Fish & Wildlife
Customer Contact:
Dillon Day
Street:
845 West Penninsula Drive
Phone Number:
727-502-4780
City:
St. Petersburg
State:
Florida
Zip Code:
33701
Fax Number:
Building/Location:
Email Address:
dillion.day@myfwc.com
Service Provided:
Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test
Monitoring Entity:
Simplex
Local:
No
Account #:
112-1336
Phone #:
18887467539
FACP Loc.
Lobby
Make:
Simplex
Model #:
Addressable:
Yes
Dialer Make: Model: System Type:
Fire Alarm
Make Notifications
Notications Entity Yes/No Who was notified Time
Monitoring Entity: Jonson controls Yes Matt (maintenance takes systems offline 8:00
Building Occupants:
Other - Specify:
Premises Monitoring
Monitoring Info Yes/No Who/Operator Time
Alarm Signal Yes 9:00
Supervisory Signal Yes 8:45
Supervisory Restore Yes 8:45
Trouble Signal Yes 8:30
Notification That Testing is Complete
Notifications Made Yes/No Who Time
Bldg. Management 3:00
Monitoring Agency Maintenance
Building Occupants
Other - Specify
No of Initiation Circuits Used: No of Initiation Circuits Total:
undefined
Circuit Styles:
B
Last Service Date:
02/03/2025
Equipment Qty Manufacturer Model #
Ion Smoke Detector 9 Simplex 4098-9714
Photo Smoke
Duct Detector 2 Simplex
Heat Detector
Manual Pull Station 8 Simplex
Supervisory Switch
Lic#EF0001219
13075 US HWY 19 N.
CLEARWATER, FL 33764
customersupport@piperfire.com
PINELLAS (727) 581-9339
SARASOTA (941) 377-2100
PINELLAS FAX (727) 581-8332
SARASOTA FAX (941) 377-2001
STATEWIDE (800) 327-7604
Fire Alarm System Test and Inspection Form
Prior to any Testing of Fire Alarm System
Alarm Initiation Devices And Circuit Information
Equipment Qty Manufacturer Model #
Other:
No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:
Y
Circuits Supervised:
Yes
Equipment Qty Manufacturer Model #
Bells
Horns
Horn/Strobes 26 Simplex Red wall mount
Strobes 5 Simplex Red wall mount
Speakers
Speaker/Strobes
Other:
Primary Nominal Voltage:
Is the fire alarm on its own dedicated circuit?
Yes
Breaker/Fuse #:
Panel EM #19
Amps:
Storage Battery - Qty:
Type of Battery:
SEALED / LED ACID
Voltage Per Battery:
Amp Hour:
Date:
4/25
Other:
Calculated capacity to operate system, in hours:
Location of fuel source, if yes:
N/A
Engine driven generator dedicated to fire alarm:
N/A
Location of UPS system:
N/A
Equipment Powered by UPS:
N/A
In Alarm mode (minutes):
Calculated capacity of UPS batteries to drive system in standby (hours):
N/A
Type Functional Visual Comments
Control Panel Yes
Lamps/LEDs Yes
Fuses
Trouble Signals Yes
Disconnect Switches Yes
Ground Fault Monitor Yes
Supervision Yes
Phone Handsets
Phone Jacks
Elevator Recall
Elevator Shunt Trip
Power extender panels
Surge Protection Yes
Primary Power Supply Yes
Battery Condition Yes
Load Voltage Yes
Discharge Voltage: Yes
Charger Test Yes
Engine-driven generator
Fire Pump Yes
Signaling Line Circuits and Circuit Information
Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type
System Tests and Inspections
Type Functional Visual Comments
Door-Releasing Devices
Fan Shutdown
Smoke Control
Smoke Damper
Other - Specify:
Annunciator:
Qty Functional Visual Location
Inspect Test
Location Pass/Fail Device Zone Sensitivity Remarks
FACP Pass
Lobby Pass Manual Pull Station
Pass Horn Strobe
Pass Smoke Detector Visual only no recall key
3rd floor Pass
Lobby Pass Smoke Detector Visual
Pass Manual Pull Station
Pass Horn Strobe
Stairwell 1 Pass Strobe
303 Pass Heat Detector
Pass Horn Strobe
Pass Smoke Detector Normal range
Pass CO Detector
Pass CO Detector
Roof Pass Horn Strobe
Roof wood shop Fail Horn Strobe
I306 Pass Horn Strobe
I 301 N/A
2nd floor lobby
Pass Manual Pull Station
Pass Horn Strobe
Pass Smoke Detector Visual
Men’s room Pass Strobe
Women’s room Pass Smoke Detector Normal range
At restrooms Pass Horn Strobe
I-205 Library/ document N/A HALON SYSTEM
Stair 1 first floor Pass Horn Strobe
1st floor elevator lobby Pass Horn Strobe
Pass Manual Pull Station
N/A Smoke Detector Visual
At electric room Pass Manual Pull Station
Pass Horn Strobe
Men’s room Pass Strobe
Women’s room Pass Strobe
I-117 Pass Horn Strobe
I-105 Pass Horn Strobe
Pass Duct Detector
Pass Remote Test Switch
Pass Duct Detector
Pass Remote Test Switch
Device List
Location Pass/Fail Device Zone Sensitivity Remarks
I-108A Pass Horn Strobe
Hall at I-105A Pass Horn Strobe
I-108 hall Pass Horn Strobe
Pass Manual Pull Station
I-108 Pass Smoke Detector Normal range
I 109A Pass Smoke Detector Normal range
Stair 2 Pass Horn Strobe
Slanted hallway Pass Horn Strobe
Ground floor I-006A Pass Manual Pull Station
Pass Horn Strobe
Storage room on right Pass Horn Strobe
I-205 Pass Horn Strobe
I-026 Pass Strobe
I-009 Pass Horn Strobe
I-010 Pass Horn Strobe
I-024 Pass Horn Strobe
I-015 Fail Smoke Detector Appears to have no power
I-027 Pass Horn Strobe
Pass Duct Detector
Pass Remote Test Switch
Pass Duct Detector
Pass Remote Test Switch
Pass Duct Detector
Pass Remote Test Switch
Pump room Pass
Pass Manual Pull Station
Pass Horn Strobe
EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:
Smoke detector did not operate during inspection
INSPECTOR / TECHNICIAN COMMENTS:
Date the system was restored to normal operation on:
03/03/2026
Time:
3:00
Name of Owner or Representative: Date:
03/03/2026
Owner or Representative Signature:
Technician's Name:
Chris Hill
Date:
03/03/2026
Technician's Signature:
Deficiencies & Comments / Fire Alarm Form
DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.
NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.
CH Chris Hill - 3/3/2026 Public
Halon system in library
CH Chris Hill - 3/3/2026 Resolve
Pass/Fail
Appears to have no power
Linked Field
Row # Location Pass/Fail Device Zone Sensitivity Remarks
57 I-015 Fail Smoke Detector Appears to have no power
CH Chris Hill - 3/14/2026 Public
Panel in trouble upon arrival and departure due to work being preformed in main building chiller room
CH Chris Hill - 3/14/2026 Resolve
Pass/Fail
Horn worked strobe did not
Linked Field
Row # Location Pass/Fail Device Zone Sensitivity Remarks
16 Roof wood shop Fail Horn Strobe
03/03/2026
Customer #:
Inspection File #:
Inspector Name:
Chris Hill
Inspection Qualification:
FASA/BASA
Property Name:
Florida Fish & Wildlife
Customer Contact:
Gavin Hutchinson
Street:
855 West Penninsula Drive
Phone Number:
727-502-4780
City:
St. Petersburg
State:
FL
Zip Code:
33701
Fax Number:
Building/Location: Email Address:
Gavin.Hutchinson@myfwc.com
Service Provided:
Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test
Monitoring Entity:
Simplex
Local:
No
Account #:
112-1336
Phone #:
18887467539
FACP Loc.
Lobby
Make:
Simplex
Model #:
Addressable:
Yes
Dialer Make: Model: System Type:
Fire Alarm
Make Notifications
Notications Entity Yes/No Who was notified Time
Monitoring Entity: Matt ( maintenance takes systems offline 8:00
Building Occupants:
Other - Specify:
Premises Monitoring
Monitoring Info Yes/No Who/Operator Time
Alarm Signal 9:00
Supervisory Signal 8:45
Supervisory Restore 8:45
Trouble Signal 8:30
Notification That Testing is Complete
Notifications Made Yes/No Who Time
Bldg. Management 3:00
Monitoring Agency
Building Occupants
Other - Specify
No of Initiation Circuits Used: No of Initiation Circuits Total:
undefined
Circuit Styles:
B
Last Service Date:
03/03/2026
Equipment Qty Manufacturer Model #
Ion Smoke Detector 1 Simplex
Photo Smoke
Duct Detector 5 Simplex
Heat Detector
Manual Pull Station 10 Simplex B key
Supervisory Switch
Lic#EF0001219
13075 US HWY 19 N.
CLEARWATER, FL 33764
customersupport@piperfire.com
PINELLAS (727) 581-9339
SARASOTA (941) 377-2100
PINELLAS FAX (727) 581-8332
SARASOTA FAX (941) 377-2001
STATEWIDE (800) 327-7604
Fire Alarm System Test and Inspection Form
Prior to any Testing of Fire Alarm System
No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:
Y
Circuits Supervised:
Yes
Equipment Qty Manufacturer Model #
Bells
Horns
Horn/Strobes 16 Simplex Red wall mount
Strobes 5 Simplex
Speakers
Speaker/Strobes
Other:
Primary Nominal Voltage:
Is the fire alarm on its own dedicated circuit?
Yes
Breaker/Fuse #:
Room F010 panel GLP1 #28
Amps:
Storage Battery - Qty:
Type of Battery:
SEALED / LED ACID
Voltage Per Battery:
Amp Hour:
Date:
1/24
Other:
Calculated capacity to operate system, in hours:
Location of fuel source, if yes:
N/A
Engine driven generator dedicated to fire alarm:
N/A
Location of UPS system:
N/A
Equipment Powered by UPS:
N/A
In Alarm mode (minutes):
Calculated capacity of UPS batteries to drive system in standby (hours):
N/A
Type Functional Visual Comments
Control Panel Yes
Lamps/LEDs Yes
Fuses
Trouble Signals Yes
Disconnect Switches Yes
Ground Fault Monitor Yes
Supervision Yes
Phone Handsets
Phone Jacks
Elevator Recall
Elevator Shunt Trip
Power extender panels
Surge Protection Yes
Primary Power Supply Yes
Battery Condition Yes
Load Voltage Yes
Discharge Voltage: Yes
Charger Test Yes
Engine-driven generator
Fire Pump
Signaling Line Circuits and Circuit Information
Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type
Fan Shutdown
Smoke Control
Smoke Damper
Other - Specify:
Annunciator:
Qty Functional Visual Location
Inspect Test
Location Pass/Fail Device Zone Sensitivity Remarks
Lobby Pass Manual Pull Station
Pass Horn Strobe
Pass Smoke Detector Normal range
Stair well F 125 Pass Strobe
F 125A Pass Manual Pull Station
Pass Horn Strobe
At F 113 Pass Manual Pull Station
Pass Horn Strobe
F 109 Pass Horn Strobe
F 107 Pass Horn Strobe
F;106 Pass Duct Detector
Pass Remote Test Switch
Pass Duct Detector
Pass Remote Test Switch
Men’s room Pass Strobe
Women’s room Pass Strobe
F 124 Pass Manual Pull Station
Pass Strobe
Pass Duct Detector
Pass Remote Test Switch
F 123 Pass Horn Strobe
F 121 Pass Manual Pull Station
F 117 Pass Manual Pull Station
Pass Horn Strobe
F 116 Pass Horn Strobe
F 125A Pass Manual Pull Station
Pass Horn Strobe
F 003 Pass Horn Strobe
Specimen room Pass Manual Pull Station
Pass Horn Strobe
Pass Duct Detector
Specimen room near exit at F001 Pass Horn Strobe
Pass Manual Pull Station
F 014 Pass Horn Strobe
F 009 Pass Horn Strobe
At F 011 Pass Horn Strobe
F 010 exit Pass Manual Pull Station
Pass Horn Strobe
F 010A Pass Heat Detector
F 011 Pass Strobe
F 009 Pass Duct Detector
EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:
INSPECTOR / TECHNICIAN COMMENTS:
Date the system was restored to normal operation on:
03/03/2026
Time:
3:00
Name of Owner or Representative: Date:
03/03/2026
Owner or Representative Signature:
Technician's Name:
Chris Hill
Date:
03/03/2026
Technician's Signature:
Deficiencies & Comments / Fire Alarm Form
CH Chris Hill - 3/3/2026 Public
Devices in building
CH Chris Hill - 3/14/2026 Public
Trouble on panel at arrival and departure due to work being performed in main building chiller room.
DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.
NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.
03/02/2026
Customer #:
Inspection File #:
I-9341
Inspector Name:
Dwight Overton
Inspection Qualification:
FASA/BASA
Property Name:
Florida Fish & Wildlife
Customer Contact:
Gavin Hutchinson
Street:
100 8th Ave SE
Phone Number:
7275024780
City:
St.Pete
State:
FL
Zip Code:
33701
Fax Number:
Building/Location: Email Address:
Gavin.Hutchinson@myfwc.com
Service Provided:
Quarterly Semi-annual Annual Bi-Annual Sensitivity Walk Test
Monitoring Entity:
Simplex
Local:
No
Account #:
112-1336
Phone #:
18887467539
FACP Loc.
In communications room G-107
Make:
Simplex
Model #:
Addressable:
Yes
Dialer Make:
Silent Knight
Model:
System Type:
Fire Alarm
Make Notifications
Notications Entity Yes/No Who was notified Time
Monitoring Entity:
Building Occupants:
Other - Specify:
Premises Monitoring
Monitoring Info Yes/No Who/Operator Time
Alarm Signal
Supervisory Signal
Supervisory Restore
Trouble Signal
Notification That Testing is Complete
Notifications Made Yes/No Who Time
Bldg. Management
Monitoring Agency
Building Occupants
Other - Specify
No of Initiation Circuits Used: No of Initiation Circuits Total:
undefined
Circuit Styles:
B
Last Service Date:
03/02/2026
Equipment Qty Manufacturer Model #
Ion Smoke Detector
Photo Smoke 43
Duct Detector 9
Heat Detector 17
Manual Pull Station 23
Supervisory Switch
Lic#EF0001219
13075 US HWY 19 N.
CLEARWATER, FL 33764
customersupport@piperfire.com
PINELLAS (727) 581-9339
SARASOTA (941) 377-2100
PINELLAS FAX (727) 581-8332
SARASOTA FAX (941) 377-2001
STATEWIDE (800) 327-7604
Fire Alarm System Test and Inspection Form
Prior to any Testing of Fire Alarm System
No of Indicating Circuits Used: No of Indicating Circuits Total: Circuit Styles:
Y
Circuits Supervised:
Yes
Equipment Qty Manufacturer Model #
Bells
Horns
Horn/Strobes 98
Strobes 5
Speakers
Speaker/Strobes
Other:
Primary Nominal Voltage:
Is the fire alarm on its own dedicated circuit?
Yes
Breaker/Fuse #:
Main electrical room breaker #15
Amps:
Storage Battery - Qty:
Type of Battery:
SEALED / LED ACID
Voltage Per Battery:
Amp Hour:
Date:
2/24
Other:
Calculated capacity to operate system, in hours:
Location of fuel source, if yes:
N/A
Engine driven generator dedicated to fire alarm:
N/A
Location of UPS system:
N/A
Equipment Powered by UPS:
N/A
In Alarm mode (minutes):
Calculated capacity of UPS batteries to drive system in standby (hours):
Type Functional Visual Comments
Control Panel Yes Yes
Lamps/LEDs Yes Yes
Fuses Yes Yes
Trouble Signals Yes Yes
Disconnect Switches Yes Yes
Ground Fault Monitor Yes Yes
Supervision Yes Yes
Phone Handsets
Phone Jacks
Elevator Recall
Elevator Shunt Trip
Power extender panels Yes Yes
Surge Protection Yes Yes
Primary Power Supply Yes Yes
Battery Condition Yes
Load Voltage
Discharge Voltage:
Charger Test
Engine-driven generator
Fire Pump
Signaling Line Circuits and Circuit Information
Primary Power Supply / System Secondary Power Supply Battery Capacities and Battery Type
Fan Shutdown
Smoke Control
Smoke Damper
Other - Specify:
Annunciator:
Qty Functional Visual Location
Inspect Test
Location Pass/Fail Device Zone Sensitivity Remarks
Sensitivity range
1.25-3.1%FT
FACP ROOM Pass Dialer Batteries dated 2/24
Pass Smoke Detector Within range
Door JU 4 Pass Speaker
Penthouse/mechanical room 5002 Pass Horn Strobe
Stairwell E/E Pass Manual Pull Station
Pass Horn Strobe
4th fl at stair 2 Pass Manual Pull Station
Pass Horn Strobe
At elevator Pass Smoke Detector Within range
Pass Duct Detector
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
Room 4056 Pass Heat Detector
Electrical room 4057 Pass Smoke Detector Within range
Elevator lobby Pass Horn Strobe
On Terrace fourth floor Pass Horn Strobe
Pass Horn Strobe
Communications room 4005 Pass Smoke Detector Within range
Research labs 4036 Pass
Hallway Pass Horn Strobe
Room 4007 Pass Horn Strobe
Pass Strobe
Across from 4047 Pass Horn Strobe
At room 4042 Pass Horn Strobe
In 4039 Pass Smoke Detector Within range
At room 4010 Pass Horn Strobe
At room 4013 Pass Horn Strobe
In 4037 Pass Smoke Detector Within range
Freight elevator lobby at 4036 N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
Room 4017 Pass Horn Strobe
In section 4023
At room 4028 Pass Horn Strobe
At stairwell Pass Manual Pull Station
In communication closet Pass Smoke Detector Within range
In stairwell between four and three Pass Horn Strobe
Third floor at stairwell Pass Manual Pull Station
Pass Horn Strobe
3RD FL Pass
At 3051 Pass Horn Strobe
In room 3057 Pass Smoke Detector Within range
Elevator lobby N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
In room 3041 Pass Duct Detector
Pass Horn Strobe
At 3061 Pass Horn Strobe
In 3036 Pass Heat Detector
In 3064 Pass Horn Strobe
At 3029 Pass Horn Strobe
In 3069 Pass Strobe
Pass Heat Detector
At 3069 Pass Horn Strobe
In 3025 Pass Heat Detector
In 3023 mechanical Pass Manual Pull Station
Pass Horn Strobe
Pass Duct Detector
Pass Duct Detector
Pass Duct Detector
Fail Duct Detector M2-74
Electrical room 3026 Pass Horn Strobe
Pass Smoke Detector Within range
Systems room 3025 Pass Smoke Detector Within range
Elevator lobby N/A Smoke Detector Within range
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
Hallway at elevator lobby
First Office on left Pass Heat Detector
By room 3001 Pass Horn Strobe
In our office 3003 Pass Horn Strobe
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Horn Strobe
At stairwell #2 Pass Manual Pull Station
Pass Horn Strobe
In room 3020 Pass Horn Strobe
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
In printer room Pass Smoke Detector Within range
3020A Pass Smoke Detector Within range
At 3019 Pass Speaker/Strobe
At stair 1 Pass Manual Pull Station
Pass Horn Strobe
Stairwell between floors three and two Pass Horn Strobe
In 3009 Pass Smoke Detector Within range
3009A Pass Smoke Detector Within range
3009B Pass Smoke Detector Within range
3007 Pass Smoke Detector Within range
Pass Smoke Detector Within range
IT/Computer room Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
Pass Smoke Detector Within range
2ND FL
Elevator lobby N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
At elevator Pass Strobe
Research Labs 2034
At 2035 Pass Horn Strobe
Locker room Pass Horn Strobe
Restroom Pass Horn Strobe
At 2038 Pass Horn Strobe
Closet across from 2075 Pass Heat Detector
At 2073 Pass Horn Strobe
At 2070 Pass Horn Strobe
Freight elevator lobby N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
In 2048 Pass Horn Strobe
At 2057 Pass Horn Strobe
In 2064 Pass Smoke Detector Within range
At stairwell Pass Manual Pull Station
Pass Horn Strobe
At stairwell by 2027A Pass Manual Pull Station
Pass Horn Strobe
Administration room 2004
In 2005 Pass Heat Detector
At 2008 Pass Horn Strobe
At 2012 Pass Horn Strobe
At stairwell Pass Manual Pull Station
At 2017 Pass Horn Strobe
At 2020 Pass Horn Strobe
At 2023 Pass Horn Strobe
First floor elevator lobby N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
At elevator Pass Strobe
Mechanical room1010 Pass Manual Pull Station
Pass Horn Strobe
1010A Pass Smoke Detector Within range
1010B Pass Horn Strobe
Pass Horn Strobe
Mechanical room Pass Duct Detector
Pass Duct Detector
Pass Duct Detector
In 1011 Pass Heat Detector
At 1059 Pass Horn Strobe
At 1057 Pass Horn Strobe
At 1054 Pass Horn Strobe
At 1025 Pass Horn Strobe
In 1026 Pass Smoke Detector Within range
Freight elevator lobby
N/A Smoke Detector Within range
Pass Horn Strobe
Men’s restroom Pass Horn Strobe
Women’s restroom Pass Horn Strobe
Inside 1030 Pass Horn Strobe
In 1049 Pass Heat Detector
At 1042 Pass Horn Strobe
In 1050 Pass Smoke Detector Within range
At stairwell Pass Manual Pull Station
Pass Horn Strobe
In stairwell Pass Horn Strobe
Behind elevator at stairwell Pass Manual Pull Station
Pass Horn Strobe
Seminar room 1007 Pass Horn Strobe
Auditorium
At stairwell Pass Manual Pull Station
Pass Horn Strobe
In auditorium Pass Horn Strobe
Pass Horn Strobe
Behind projector screen in hall Pass Manual Pull Station
Pass Horn Strobe
Projection room Pass Smoke Detector Within range
Ground floor at elevator lobby N/A Smoke Detector Within range
Pass Strobe
Pass Horn Strobe
Reception by G-102 Pass Manual Pull Station
In G-102 Pass Heat Detector
By stairwell Pass Manual Pull Station
Pass Horn Strobe
Ground floor stairwell four Pass Manual Pull Station
Pass Horn Strobe
In MAINE electrical room G108 Pass Manual Pull Station
Pass Heat Detector
Pass Horn Strobe
Mechanical room/chiller room JU7 Pass Manual Pull Station
Pass Horn Strobe
Pass Horn Strobe
Pass Heat Detector
Pass Heat Detector
Pass Heat Detector
JU 8 inside bay doors Pass Manual Pull Station
Pass Horn Strobe
JU 11
At restroom Pass Manual Pull Station
Pass Horn Strobe
Restroom Pass Horn Strobe
Restroom Pass Horn Strobe
Hall by CHRIS Lang Office Pass Horn Strobe
Tiffany Ottoson office Pass Smoke Detector Within range
Ground floor stairwell number three Pass Manual Pull Station
Pass Horn Strobe
At JU 12 Pass
Pass Horn Strobe
In JU 12 Pass Heat Detector
At elevator Pass Heat Detector
In JU 13 Pass Smoke Detector Within range
Pass Heat Detector
EXPLANATION OF “NO” ANSWERS, DISCREPANCIES AND RECOMMENDED IMPROVEMENTS:
Recommend having the elevator recall key on site for next annual inspection.
INSPECTOR / TECHNICIAN COMMENTS:
This building sets off the other (2) buildings off in general alarm. Our contact is aware and will be reaching out to Simplex to address this issue.
SOUNDING OF THE HORNS MUST TAKE PLACE ON THE WEEKEND!
Date the system was restored to normal operation on:
03/02/2026
Time:
Name of Owner or Representative: Date:
03/02/2026
Owner or Representative Signature:
Technician's Name:
Dwight Overton
Date:
03/02/2026
Technician's Signature:
Deficiencies & Comments / Fire Alarm Form
DISCREPANCIES AND RECOMMENDED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNER’S REPRESENTATIVE.
NFPA 72 2019 Edition on Table 14.4.5. This testing was performed in accordance with applicable NFPA Standard.
DO Dwight Overton - 3/3/2026 Resolve
Pass/Fail
Duct detector did not activate when testing. Duct detector housing is broken.
Linked Field
Row # Location Pass/Fail Device Zone Sensitivity Remarks
65 Fail Duct Detector M2-74