Full MDNR_Clear Lake State Park A B_ACM LCP Survey Report_2023_0116 (R).pdf
PDF 3 MB Posted
- Solicitation number
- RFP - 171 - 230000000763
- Issued by
- Montmorency County, Michigan
About this file
This document is a pre-demolition asbestos and lead-containing paint survey report for the Toilet and Shower Buildings A and B located at Clear Lake State Park in Atlanta, Michigan. The survey was conducted on behalf of the Michigan Department of Natural Resources. The purpose of the survey was to identify and collect samples of suspect asbestos-containing materials (ACMs) and lead-containing paint (LCP) prior to planned demolition activities.
The survey found that one sample from Toilet and Shower Building A contained 3% chrysotile asbestos, while no asbestos was detected in Toilet and Shower Building B. The survey also identified four paint samples containing lead levels above the laboratory reporting limits. The report provides recommendations for the appropriate handling and disposal of ACMs and LCP during the demolition process to ensure regulatory compliance.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRE-DEMOLITION ASBESTOS AND LIMITED LEAD-CONTAINING PAINT SURVEY
CLEAR LAKE STATE PARK
TOILET AND SHOWER BUILDINGS A (WEST) & B (EAST)
20500 M-33 Atlanta, MI 49709
Project #188BS22765
PREPARED FOR:
Michigan Department of Natural Resources
PREPARED BY:
Atlas Technical Consultants LLC 46555 Humboldt Drive, Suite 100 Novi, Michigan 48377 January 16, 2023
Page | 1
46555 Humboldt Drive, Suite 100 Novi, Michigan 48377
(248) 669-5147 | oneatlas.com
Andrew DeLodder Martin Gamble State of Michigan Asbestos Inspector Project Manager Atlas Technical Consultants LLC Atlas Technical Consultants LLC
Respectfully submitted, If you have any questions, please call us at 248.669.5140.
1987 (AHERA).
Standard (29 CFR 1926.1101), and the Asbestos Hazard and Emergency Response Act of Occupational Safety and Health Administration’s (OSHA) Asbestos Construction Industry inspector. The sampling was conducted in accordance with sampling criteria specified in the 8, 2022 by Industrial Hygienist, Mr. Andrew DeLodder, a State of Michigan certified asbestos The pre-demolition asbestos and lead-containing paint sampling was conducted on December and lead-containing paint (LCP) prior to planned demolition activities.
sampling was to identify and collect samples of suspect asbestos-containing materials (ACMs) limited lead-containing paint survey performed at the above referenced site. The purpose of this Atlas is pleased to present this report detailing the findings of the pre-demolition asbestos and
Dear Mr. Dekett:
Atlanta, MI 49709 20500 M-33 Clear Lake State Park Toilet and Shower Buildings A (West) and B (East)
Subject: Pre-Demolition Asbestos and Limited Lead-Containing Paint Survey
Atlanta, Michigan 49709 20500 M-33 North Clear Lake State Park Unit Supervisor Mr. David M Dekett
January 16, 2023
Page | i
CONTENTS
EXECUTIVE SUMMARY
1. INTRODUCTION
1.1 Purpose
1.2 Pre-Demolition Asbestos Survey
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
2.2 Exterior Finish Descriptions
2.3 Interior Building Descriptions
3. PRE-DEMOLITION ASBESTOS SURVEY
3.1 Homogeneous Areas
3.2 Hazard Assessment Factors
3.3 Laboratory Analytical Methodology
3.4 Sampling Results
4. LEAD-CONTAINING PAINT SAMPLING
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos-Containing Materials
5.2 Lead-Containing Paint
6. ASSUMPTIONS AND LIMITATIONS
TABLES
Table 3-1 ACM Sampling Results
Table 4-1 Lead-Containing Paint Sampling Results
APPENDICES
Appendix A Asbestos Laboratory Report Appendix B Lead-Containing Paint Laboratory Report
Page | 2 levels of lead greater than the laboratory reporting limits.
for analysis by Flame AAS. The results of laboratory testing indicated that all four (4) samples contained “A” and two (2) representative samples from Toilet and Shower Building “B” were collected and submitted Two (2) representative samples of paint, taken from interior and exterior areas of Toilet and Shower Building must be assumed to contain asbestos until sampling and analysis proves otherwise.
If any additional suspect materials are discovered during renovation/demolition activities, such materials indicated that none of the samples from Toilet and Shower Building “B” contained asbestos.
analysis. Of the 24 samples submitted, 43 sample layers were analyzed. The results of laboratory testing Toilet and Shower Building “B” (East), and submitted for laboratory polarized light microscopy (PLM)
Twenty-four (24) asbestos bulk samples, taken from eight (8) homogenous areas, were collected from the indicated that one (1) of the samples collected from Toilet and Shower Building “A” contain asbestos.
analysis. Of the 24 samples submitted, 34 sample layers were analyzed. The results of laboratory testing Toilet and Shower Building “A” (West), and submitted for laboratory polarized light microscopy (PLM)
Twenty-four (24) asbestos bulk samples, taken from eight (8) homogenous areas, were collected from the located in Clear Lake State Park, at 20500 M-33, Atlanta, Michigan on December 8, 2022.
containing paint survey of Toilet and Shower Building A (West) and Toilet and Shower Building B (East), Atlas representative Mr. Andrew DeLodder completed the pre-demolition asbestos and limited lead-
EXECUTIVE SUMMARY
Page | 3
1. INTRODUCTION
1.1 Purpose
The purpose of this project was to conduct a pre-demolition asbestos survey and limited lead containing paint survey of Toilet and Shower Buildings “A” and “B” located in Clear Lake State Park, at 20500 M-33, Atlanta, Michigan (herein referred to as “the property”).
1.2 Pre-Demolition Asbestos Survey
The scope of the pre-demolition asbestos survey included the following:
Review of existing asbestos reports for the building, if available;
Survey of the property building(s);
Identification of accessible suspect asbestos-containing materials (ACMs);
Collection and analysis of bulk samples of suspect friable and non-friable materials.
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
General property and building information is presented in the following table:
General Property and Building Information
Date of Inspection:
Inspectors Andrew Delodder, Inspector # A48677
Property Address: 20500 M-33, Atlanta, MI 49709
Property Owner Michigan Department of Natural Resources
Building Description: Toilet and Shower Buildings “A” and “B” at Clear Lake State Park
2.2 Exterior Finish Descriptions
The exterior of the building included brick and masonry with a shingled-sloped roof.
2.3 Interior Building Descriptions
The interior finishes of the building included plastered walls and ceiling, and floor tiled floors.
3. PRE-DEMOLITION ASBESTOS SURVEY
Atlas representative Mr. Andrew DeLodder conducted the pre-demolition asbestos inspection of the Toilet and Shower buildings on December 14, 2022 and December 15, 2022. Mr. DeLodder is a State of Michigan
Certified Asbestos Inspector’s (Certification No. A48677). The building was visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation
Program (NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e.
fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
> Conducting a visual inspection of the structures;
> Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and miscellaneous materials; and
> Sampling accessible, friable and non-friable suspect materials.
December 8, 2022
Page | 4
3.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance and function. Actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and professional opinion of the inspector.
3.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list. A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor covering, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
All materials were assessed related to their condition in one of the three categories: good (intact), fair
(damaged) or poor (significantly damaged) per Title 40 Code of Federal Regulations Part 763. Material with localized, significant damage was also assessed as poor.
3.3 Laboratory Analytical Methodology
Bulk samples were analysed by Environmental Testing Laboratories, Inc. (ETL) using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No. 103, May
27, 1982 pg. 23376). This laboratory participates in the National Voluntary Laboratory Accreditation Program
(NVLAP #201028-0), a quality assurance program for PLM analysis, and is accredited by the National Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in
Appendix A. Positive sample results are reported in percent asbestos by volume of the sample and the type of asbestos material within the sample. Other common non-asbestos components may also be noted on the analytical reports.
3.4 Sampling Results
Bulk samples were collected from the site building and analyzed by polarized light microscopy (PLM), EPA
Method 600/R-93/116.
The following table provides a summary of accessible suspect and confirmed ACMs from the Site buildings:
Page | 5
Table 3-1 ACM Sampling Results
Sample ID /Material
Location of Materials
Material Estimated Quantity
Asbestos Content
Toilet and Shower Building A (West)
1-RM-A,B,C EA-5 Roofing Material- Asphalt Shingle NA ND
2-CC-A,B,C EA-1,3 Concrete Chip- Exterior Concrete NA ND
3-EC-A,B,C EA-1,2,3
Exterior Caulk-
Gray, Painted Brown, on Wood Siding, Door/Window Frames, & Roofline
NA ND
4-BM-A,B,C EA-4
Brick Mortar-
CMU Foundation, Shower Area
NA ND
5-CC-A,B,C FS-2,4,7
Concrete Chip-
Poured Concrete Foundation Pad 945 SF PLM 3% Chrysotile
6-GM-A,B,C FS-1,3,8
8” Floor & Wall Tile-
Ceramic Tile, Grout, and Mortar
NA ND
7-CB-A,B,C FS-2 Concrete Board- Under Ceramic Tile NA ND
8-CA-A,B,C FS-2
Construction Adhesive- Remnants of Glue on the Wall, Painted White
NA ND
Toilet and Shower Building B (East)
1-RM-A,B,C EA-5 Roofing Material- Asphalt Shingle NA ND
2-CC-A,B,C EA-1,3 Concrete Chip- Exterior Concrete NA ND
3-EC-A,B,C EA-1,2,3
Exterior Caulk-
Gray, Painted Brown, on Wood Siding, Door/Window Frames, & Roofline
NA ND
4-BM-A,B,C EA-4
Brick Mortar-
CMU Foundation, Shower Area
NA ND
5-CC-A,B,C FS-2,4,7
Concrete Chip-
Poured Concrete Foundation Pad
NA ND
6-GM-A,B,C FS-1,3,8
8” Floor & Wall Tile-
Ceramic Tile, Grout, and Mortar
NA ND
7-CB-A,B,C FS-2 Concrete Board- Under Ceramic Tile NA ND
8-CA-A,B,C FS-2
Construction Adhesive- Remnants of Glue on the Wall, Painted White
NA ND
EA=Exterior Area FS Functional Space NA=Not Applicable ND= None Detected
In the event additional suspect material is discovered during renovation activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR
1926.1101 and 1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
Page | 6
Sample ID Sample Location Color Lead
Content
Toilet and Shower Building A (West)
1-LBP-Brown Exterior Paint Brown 0.0033
2- LBP-White Interior Paint White 0.0020
Toilet and Shower Building B (East)
1-LBP-Brown Exterior Paint Brown 0.0100
2- LBP- White Window Paint White 0.0020
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos-Containing Materials
The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that the following materials sampled were found to contain asbestos:
Sample ID /Material
Location of Materials
Material Estimated Quantity
Asbestos Content
Toilet and Shower Building A
5-CC-A,B,C FS-2,4,7
Concrete Chip-
Poured Concrete Foundation Pad 945 SF PLM 3% Chrysotile
Toilet and Shower Building B
None Contain Asbestos
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
Table 4-1 Lead-Containing Paint Sampling Results
The following table provides a summary of the LCP sampling:
analytical report and corresponding chain-of-custody forms are included in Appendix B.
3050B using Flame AAS to determine lead concentration in percent (%) by weight. Copies of the laboratory samples were analyzed using the Environmental Protection Agency's Test Method SW 846 -7420 and Accurate Analytical Testing Laboratory, 30105 Beverly Road, Romulus, Michigan for lead analysis. Bulk Four (4) paint chip samples were collected from Toilet and Shower buildings A and B, then submitted to were deemed representative of the predominant paint coatings observed.
property building on December 8, 2022. The sampling included physical sampling of paint coatings that
Atlas representative Mr. Andrew DeLodder conducted the lead-containing paint (LCP) sampling of the
4. LEAD-CONTAINING PAINT SAMPLING
Page | 7 the risk of said user.
of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs does it warrant against operations or conditions against present ACM material in locations not investigated.
implied. This report does not warrant against changes to material from future operations or conditions, nor environmental science and engineering. This statement is in lieu of other statements either expressed or recommendations prepared in accordance with customary principles and practices in the fields of Our professional services have been performed, our findings obtained, and our conclusions and does not contain, nor should it take the place of technical specifications for ACM removal.
This document does not contain the elements necessary for an Abatement Work plan, and this document to Atlas allowed the proper designation of homogenous materials for each building.
Atlas’s observations, and the assumption that building vintage and renovation history information presented
Atlas. Selection of sample locations and frequency of sampling were based on EPA Guidance documents, conditions that were noted during the NESHAP inspections conducted on December 8, 2022, performed by
The results, findings, conclusions, and recommendations expressed in the report are based only on
6. ASSUMPTIONS AND LIMITATIONS
applicable subcontractors while completing renovation activities.
control, worker protection, and waste disposal should be considered by the general contractor and (1926.1101) and EPA may become operative. Appropriate actions in terms of removal methods, emissions regulatory compliance actions. However, when these materials are disturbed, the requirements of OSHA The presence of Lead-Containing Paint (LCP) and/or Lead Based Paint (LBP) does not, in itself, trigger regulations.
quantitative analysis be performed on these waste steams to ensure compliance with EPA waste disposal construction debris must be evaluated and, on a case-by-case basis depending on this evaluation, worksites within the prior calendar year. In addition, lead-containing paint and lead-coated waste and for the specific activities denoted in 1926.62, on objective data obtained by the contractor on other, similar, coated components, evaluate potential worker exposures to airborne lead. This evaluation can be based, performing renovation, surface preparation, and other activities that impact or potentially impact the lead- The presence of lead-containing paint requires, under OSHA 1926.62 requirements, that the contractor levels of lead greater than the laboratory reporting limits.
the limited lead-containing paint sampling conducted at the property indicate that four (4) samples contained buildings, were collected and submitted for analysis by Flame AAS. The results of laboratory testing during Four (4) representative samples of paint, taken from interior and exterior areas of both the east and west
5.2 Lead-Containing Paint
APPENDIX A
ASBESTOS LABORATORY REPORT
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location: 20500 M-33, Atlanta, MI 49709
Client Project: 188BS22765
253266ETL Job:
Report Date: 12/16/2022
Robert Smith
Lab Sample Number Client Sample Number Sample Type Completed
1432958 Asbestos01-RM-A 12/16/2022
1432959 Asbestos01-RM-B 12/16/2022
1432960 Asbestos01-RM-C 12/16/2022
1432961 Asbestos02-CC-A 12/16/2022
1432962 Asbestos02-CC-B 12/16/2022
1432963 Asbestos02-CC-C 12/16/2022
1432964 Asbestos03-EC-A 12/16/2022
1432965 Asbestos03-EC-B 12/16/2022
1432966 Asbestos03-EC-C 12/16/2022
1432967 Asbestos04-BM-A 12/16/2022
1432968 Asbestos04-BM-B 12/16/2022
1432969 Asbestos04-BM-C 12/16/2022
1432970 Asbestos05-CC-A 12/16/2022
1432971 Asbestos05-CC-B 12/16/2022
1432972 Asbestos05-CC-C 12/16/2022
1432973 Asbestos06-GM-A 12/16/2022
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.
Bldg A; Clear Lake State Park
Lab Sample Number Client Sample Number Sample Type Completed
1432974 Asbestos06-GM-B 12/16/2022
1432975 Asbestos06-GM-C 12/16/2022
1432976 Asbestos07-CB-A 12/16/2022
1432977 Asbestos07-CB-B 12/16/2022
1432978 Asbestos07-CB-C 12/16/2022
1432979 Asbestos08-CA-A 12/16/2022
1432980 Asbestos08-CA-B 12/16/2022
1432981 Asbestos08-CA-C 12/16/2022
Reviewed by:
Summary
Sample Layer MasticMethod
PLM 34Emily Nowacki
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Certificate of Analysis
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432958
01-RM-A
PLM 98% OtherPLM 2% CelluloseGreenRoofing Material
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432958
01-RM-A
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432959
01-RM-B
PLM 98% OtherPLM 2% CelluloseGreenRoofing Material
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432959
01-RM-B
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432960
01-RM-C
PLM 98% OtherPLM 2% CelluloseGreenRoofing Material
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432960
01-RM-C
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Humboldt Dr. Suite 100
To : Atlas - Novi 46555
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432961
02-CC-A
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432962
02-CC-B
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432963
02-CC-C
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432964
03-EC-A
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432965
03-EC-B
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432966
03-EC-C
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432967
04-BM-A
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432968
04-BM-B
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432969
04-BM-C
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM 3% Chrysotile1432970
05-CC-A
PLM 94% OtherPLM 3% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
1432971
05-CC-B
Positive Stop
Analyst: Dave Cousino
Date Analyzed : 12/16/2022
Layer Not Analyzed
1432972
05-CC-C
Positive Stop
Analyst: Dave Cousino
Date Analyzed : 12/16/2022
Layer Not Analyzed
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432973
06-GM-A
PLM 97% OtherPLM 3% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432973
06-GM-A
PLM 97% OtherPLM 3% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432973
06-GM-A
PLM 96% OtherPLM 4% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432974
06-GM-B
PLM 97% OtherPLM 3% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432974
06-GM-B
PLM 97% OtherPLM 3% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432974
06-GM-B
PLM 96% OtherPLM 4% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432975
06-GM-C
PLM 97% OtherPLM 3% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432975
06-GM-C
PLM 97% OtherPLM 3% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432975
06-GM-C
PLM 96% OtherPLM 4% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432976
07-CB-A
PLM 96% OtherPLM 4% CelluloseGrayConcrete Board
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432976
07-CB-A
PLM 98% OtherPLM 2% CelluloseWhiteTape
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432977
07-CB-B
PLM 96% OtherPLM 4% CelluloseGrayConcrete Board
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432977
07-CB-B
PLM 98% OtherPLM 2% CelluloseWhiteTape
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432978
07-CB-C
PLM 96% OtherPLM 4% CelluloseGrayConcrete Board
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432978
07-CB-C
PLM 98% OtherPLM 2% CelluloseWhiteTape
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432979
08-CA-A
PLM 97% OtherPLM 3% CelluloseWhiteConstruction Adhesive
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432980
08-CA-B
PLM 97% OtherPLM 3% CelluloseWhiteConstruction Adhesive
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Polarized Light Microscopy Asbestos Analysis Report
Location :
ETL Job :
Client Project :
253266
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432981
08-CA-C
PLM 97% OtherPLM 3% CelluloseWhiteConstruction Adhesive
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
Lab Supervisor/Other Signatory
Dave Cousino
Analyst:
400 Point Count Results by EPA 600/R-93/116 PLM (denoted by "PC")
Item 198.1: PLM Methods for Identifying and Quantitating Asbestos in Bulk Samples
Item 198.6: PLM Methods for Identifying and Quantitating Asbestos in Non-Friable Organically Bound Bulk Samples
EPA 600/R-93/116: Method for Determination of Asbestos in Bulk Building Materials
EPA 600/M4-82-020: Interim Method for Determination of Asbestos in Bulk Insulation Samples
A % Asbestos result of "Trace" indicates that the analyzed material was found to contain less than 1% asbestos and would not be considered an Asbestos Containing Material (ACM).
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
20500 M-33, Atlanta, MI 49709
Bldg A; Clear Lake State Park
Novi,Michigan 48377
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location:
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
Client Project: 188BS22765
253267ETL Job:
Report Date: 12/19/2022
Robert Smith
Lab Sample Number Client Sample Number Sample Type Completed
1432982 Asbestos01-RM-A 12/16/2022
1432983 Asbestos01-RM-B 12/16/2022
1432984 Asbestos01-RM-C 12/16/2022
1432985 Asbestos02-CC-A 12/16/2022
1432986 Asbestos02-CC-B 12/16/2022
1432987 Asbestos02-CC-C 12/16/2022
1432988 Asbestos03-EC-A 12/16/2022
1432989 Asbestos03-EC-B 12/16/2022
1432990 Asbestos03-EC-C 12/16/2022
1432991 Asbestos04-BM-A 12/16/2022
1432992 Asbestos04-BM-B 12/16/2022
1432993 Asbestos04-BM-C 12/16/2022
1432994 Asbestos05-CC-A 12/16/2022
1432995 Asbestos05-CC-B 12/16/2022
1432996 Asbestos05-CC-C 12/16/2022
1432997 Asbestos06-GM-A 12/16/2022
1432998 Asbestos06-GM-B 12/16/2022
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Lab Sample Number Client Sample Number Sample Type Completed
1432999 Asbestos06-GM-C 12/16/2022
1433000 Asbestos07-CB-A 12/16/2022
1433001 Asbestos07-CB-B 12/19/2022
1433002 Asbestos07-CB-C 12/16/2022
1433003 Asbestos08-CA-A 12/16/2022
1433004 Asbestos08-CA-B 12/16/2022
1433005 Asbestos08-CA-C 12/16/2022
Reviewed by:
Summary
Sample Layer MasticMethod
PLM 40 3Emily Nowacki
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
ETL Job :
Client Project :
253267
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432982
01-RM-A
PLM 99% OtherPLM 1% CelluloseGreenRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432982
01-RM-A
PLM 99% OtherPLM 1% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432982
01-RM-A
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432983
01-RM-B
PLM 99% OtherPLM 1% CelluloseGreenRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432983
01-RM-B
PLM 99% OtherPLM 1% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432983
01-RM-B
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
ETL Job :
Client Project :
253267
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432984
01-RM-C
PLM 99% OtherPLM 1% CelluloseGreenRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432984
01-RM-C
PLM 99% OtherPLM 1% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432984
01-RM-C
PLM 98% OtherPLM 2% CelluloseBlackRoofing Material-Asphalt Shingle
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432985
02-CC-A
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip- Exterior
Concrete Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432986
02-CC-B
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip- Exterior
Concrete Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432987
02-CC-C
PLM 97% OtherPLM 3% CelluloseGrayConcrete Chip- Exterior
Concrete Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
ETL Job :
Client Project :
253267
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432988
03-EC-A
PLM 99% OtherPLM 1% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432989
03-EC-B
PLM 99% OtherPLM 1% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432990
03-EC-C
PLM 99% OtherPLM 1% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432991
04-BM-A
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432992
04-BM-B
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432993
04-BM-C
PLM 98% OtherPLM 2% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
ETL Job :
Client Project :
253267
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432994
05-CC-A
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432995
05-CC-B
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432996
05-CC-C
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432997
06-GM-A
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432997
06-GM-A
PLM 98% OtherPLM 2% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432997
06-GM-A
PLM 97% OtherPLM 3% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Clear Lake State Park, Bldg B
20500 M-33, Atlanta, MI 49709
ETL Job :
Client Project :
253267
188BS22765
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .