FtSill_AIT_RTA - COMPILED_VOLUME 4 OF 4.pdf

PDF 29 MB Posted

Attached to
Advanced Individual Training Barracks, Fort Sill Oklahoma Amendment 0004 Federal contract opportunity
Solicitation number
W912BV21R0003
Issued by
Department of the Army Corps of Engineers Engineering District Tulsa

About this file

This document outlines a federal contract solicitation for construction services. The U.S. Army Corps of Engineers - Tulsa District is seeking proposals to design and build a 180,000 square foot barracks facility at Fort Sill, Oklahoma for 600 soldiers. Key requirements for the project include building systems for fire protection, alarms, secure storage, storm shelters, surveillance, access control and energy monitoring. Special foundations and geothermal systems are required to meet energy efficiency standards. Comprehensive interior design, accessibility features and cybersecurity measures must also be incorporated. Proposals are due in response to Solicitation Number W912BV21R0003. The contract will be a firm-fixed price, design/build agreement awarded following a trade-off evaluation process.

View the file

Other files for this federal contract opportunity

Other files attached to Advanced Individual Training Barracks, Fort Sill Oklahoma Amendment 0004, newest first.
File Type Posted
W912BV21R0003-00004.pdf PDF
W912BV21R0003-0003.pdf PDF
W912BV21R0003-0002.pdf PDF
Site Visit Sign-In Sheet 29 JUL 2021.pdf PDF
AIT Barracks Pre-Bid Site Visit.pdf PDF
W912BV21R0003-0001.pdf PDF
AIT BARRACKS BRAND NAME OR EQUAL NOI.xlsx XLSX spreadsheet
JA Brand Name or Equal AIT Barracks.pdf PDF
FtSill_AIT_RTA - COMPILED_VOLUME 2 OF 4.pdf PDF
FtSill_AIT_RTA - COMPILED_VOLUME 1 OF 4.pdf PDF
AIT_Barracks Solicitation RFP_20210719.pdf PDF
FtSill_AIT_RTA - COMPILED_VOLUME 3 OF 4.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

US Army Corps of Engineers

SOLICITATION NO.:

CONTRACT NO.:

ISSUE DATE:

US Army Corps of Engineers ®

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

A

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

SHEET ID

G-001

C O

VE

R

S H

EE

T

FO

R

T

SI

LL

LA

W

TO

N

, O

KL

AH

O

M A

TU

LS

A D

IS

TR

IC

T

EN

G

IN

EE

R

IN

G

M . H

O O

VE

R

, R .A

S.

K

H

ED

H R

I, R

.A

C H

R

IS

TO

PH

ER

S

TR

U

N K, P .E

S.

E.

C

H

IE

F, M

IL

IT

AR

Y

D

ES

IG

N

S

EC

TI

O

N

M . H

O O

VE

R

, R .A

J

U N

E

W

2B V2

1R

TB

D

100% DESIGN - NOT FOR CONSTRUCTION

AD

VA

N C

ED

IN

D

IV

ID

U

AL

T

R

AI

N

EE

B

AR

R

AC

KS

(A

IT

) C

O M

PL

EX

, P H

AS

E

TULSA DISTRICT

ADVANCED INDIVIDUAL TRAINEE BARRACKS

FORT SILL - LAWTON, OKLAHOMA

W912BV21R0003

TBD

10 JUNE 2021

(AIT) COMPLEX, PHASE 2

VOL #

PN:075953, FY 21

PN

:0

3, F

Y

E

AS

T

ST

S

T

TU

LS

A, O K

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

VOLUME:

AN

SI

D

4 OF 4 DRAWING VOLUMES 1 THRU 4

REPRESENTS A COMPREHENSIVE

DESIGN SET OF BUILDINGS "C" & "D"

SHEET ID

T U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

F

Y

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

FIRE RATED POKE-THRU

PARTITION CIRCUIT SPLIT

POWER POLE

SURFACE RACEWAY

THERMOSTAT

CONTROL RELAY

FIRE FIGHTER'S TELEPHONE JACK

TELEPHONE TERMINAL BOARD

FLOOR MOUNTED TELEPHONE OUTLET

FLOOR MOUNTED TELEPHONE/DATA OUTLET

FLOOR MOUNTED DATA OUTLET

WALL MOUNTED BATTERY PACK EMERGENCY LIGHT

COMBINATION TELEPHONE/DATA OUTLET

-SPECIAL SYSTEMS DEVICES-

PENDANT LUMINAIRE

ADJUSTABLE LUMINAIRE

TRACK LIGHTING

COMBINATION SWITCH AND RECEPTACLE

FLOOR MOUNTED JUNCTION BOX

WALL MOUNTED JUNCTION BOX

JUNCTION BOX

COMBINATION MOTOR STARTER

H

INDICATES PANEL AND CIRCUIT NUMBERS.

BRANCH CIRCUIT HOME RUN TO PANELBOARD, DESIGNATION

LUMINAIRE

POLE MOUNTED LUMINAIRE

WALL WASHER LUMINAIRE

-LIGHTING (REFER TO LUMINAIRE SCHEDULE)-

CONDUIT STUB DOWN (OUT OF DRAWING LIMITS)

CONDUIT STUB UP (OUT OF DRAWING LIMITS)

-GENERAL-

CONDUIT BREAK SYMBOL

LIGHTING, ONE-LINE, AND POWER CIRCUITING

CONDUIT CAP

CONDUIT SEAL OFF

CEILING MOUNTED FOURPLEX RECEPTACLE

CEILING MOUNTED DUPLEX RECEPTACLE

DISCONNECT SWITCH

MOTOR STARTER

FUSED DISCONNECT SWITCH

SINGLE RECEPTACLE

BELL

-POWER-

FLOOR MOUNTED DUPLEX RECEPTACLE

FLOOR MOUNTED FOURPLEX RECEPTACLE

S

DTB DATA TERMINAL BOARD

FUSE WITH SWITCH

-GRAPHIC SYMBOLS-

CLOCK RECEPTACLE OUTLET

MOTOR

CIRCUIT BREAKER

CONTROL FUSE

CONDUIT CHANGE IN ELEVATION

SYMBOL DESCRIPTION

DESCRIPTIONSYMBOL

SYMBOL DESCRIPTION

DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

(UNDERGROUND)

LIGHTING, ONE-LINE, AND POWER CIRCUITING

ARROWS INDICATED)

WALL MOUNTED EXIT LIGHT (WITH FACES & DIRECTION

GROUNDED WYE CONNECTION

WYE CONNECTION

DELTA CONNECTION

SYMBOL

LIGHTNING PROTECTION AIR TERMINAL

BONDING POINT

GROUND BUS

-GROUNDING SYMBOLS-

GROUND TEST WELL

DESCRIPTION

CONTROL WIRING

LIGHTNING ARRESTOR

KEY INTERLOCK

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

METERING DEVICE

SECURITY CAMERA

MICROPHONE OUTLET

S WALL MOUNTED SPEAKER

CONTACT NORMALLY CLOSED - TYPE b

CONTACT NORMALLY OPEN - TYPE a

- ABBREVIATIONS - - ABBREVIATIONS -

(PART)

+XX

A

AB

AC

AF

AFC

AFF

AFG

AIC

AS

AT

ATS

BFC

C

CAM

CB

CCTV

CKT

CLG

DMC

DTC

E/G

EC

ELEC

ELEV

EMERG

EMS

EWC

EX

F

FA

FACP

FAP

FIXT

FLR

FLUOR

FTU

G

EF

GEN

GFCI

GFI

GND

HP

HT

IC

IDF

IG

JB

K

LTG

LTS

LV

MAM

MATV

MCB

MCC

MCSW

MDF

MDP

MH

MLO

MTD

MTG

N

NC

NEC

NF

NIC

NL

NO

PWR

RCPT(S)

SBC

SF

SO

SP

ST

SW

T

TEL

TF

TTB

TV

TVSS

UF

UG

UH

UNO

V

VFD

VV

W

W/

WG

WP

WT

XFMR

PARTIAL CIRCUIT

MOUNTING HEIGHT IN INCHES. AFF UNO

AMP

AMPS BRACING

ABOVE COUNTER TOP

AMP FRAME

ABOVE FINISHED COUNTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AMPS INTERRUPTING CAPACITY

AMPS SENSOR

AMP TRIP

AUTOMATIC TRANSFER SWITCH

BELOW FINISHED CEILING

CONDUIT

CONTROL ADDRESSABLE MODULE

MOLDED CASE CIRCUIT BREAKER

CLOSED CIRCUIT T.V.

CIRCUIT

CEILING

DUAL MODE CONTROLLER

DATA TERMINAL CABINET

ENGINE/GENERATOR

EMPTY CONDUIT

ELECTRIC

ELEVATION

EMERGENCY

ENERGY MANAGEMENT SYSTEM

ELECTRIC WATER COOLER

EXISTING

FUSE

FIRE ALARM

FIRE ALARM CONTROL PANEL

FIRE ALARM PANEL

FIXTURE

FLOOR

FLUORESCENT

FAN TERMINAL UNIT

GROUND (EQUIPMENT)

EXHAUST FAN

GENERATOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND (EQUIPMENT)

HORSEPOWER

HEAT TRACE

INTERRUPTING CAPACITY

INTERMEDIATE DISTRIBUTION FRAME

ISOLATED GROUND

JUNCTION BOX

THOUSAND

LIGHTING

LIGHTS

LOW VOLTAGE

MONITOR ADDRESSABLE MODULE

MASTER ANTENNA TV

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOLDED CASE SWITCH

MAIN DISTRIBUTION FRAME

MAIN DISTRIBUTION PANEL

MANHOLE

MAIN LUGS ONLY

MOUNTED

MOUNTING HEIGHT

NEUTRAL

NORMALLY CLOSED

NATIONAL ELECTRIC CODE

NON FUSED

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

POLE

PULL BOX

POWER

RECEPTACLE(S)

STRANDED BARE COPPER

SUPPLY AIR FAN

SPACE ONLY

SPARE

SWITCH

TRANSFORMER

TELEPHONE

TRANSFER FAN

TELEPHONE TERMINAL BOARD

TELEVISION

TRANSIENT VOLTAGE SURGE SUPPRESSOR

UNDERFLOOR

UNDERGROUND

UNIT HEATER

UNLESS NOTED OTHERWISE

VOLTAGE

VARIABLE FREQUENCY DRIVE

VARIABLE VOLUME UNIT

WIRE

WITH

WIRE GUARD

WEATHERPROOF

WATERTIGHT

TRANSFORMER

EXIT LIGHT (WITH FACES & DIRECTION ARROWS INDICATED)

M

K

M

XXX

XX

PIGTAIL

SWITCH

THERMAL ELEMENT, OVERLOAD RELAY

DUAL SWITCH

METER

GAF

CR

REVISION NUMBER

EF-1

UPS UNINTERRUPTIBLE POWER SUPPLY

AHJ AUTHORITY HAVING JURISDICTION

GFI

J

J

J

H

B

S

W

W

TVSS OR MISC EQUIPMENT

TVSS

SWITCHED RECEPTACLE

M

GENERAL NOTES

V

WALL MOUNTED VOLUME CONTROL

TTB

C

X

TV

P

A

-GENERAL-

K

MGB

TMGB

TGB

GB

TRANSFORMER

ENGINE GENERATORE

D X

A

HG HOSPITAL GRADE

CEILING MOUNTED SPEAKER

X

MASS NOTIFICATION AMBER STROBE

EM

MNS COMBINATION SPEAKER/STROBE LIGHT

TELECOM GROUNDING MAIN BUS

TGB

TGMB

TELECOM GROUNDING BUS

MNS

GROUNDING COUNTERPOISE (RING)

ELECTRICAL GROUND OR GROUND ROD

DOWN CONDUCTOR

MNCP MASS NOTIFICATION CONTROL PANEL

MASS NOTIFICATION SYSTEM

ROOF OR DOWN CONDUCTOR

GROUND ARC-FAULT INTERRUPTER

LSIG

ELECTRICAL SYSTEM GROUND BAREGB

FLUORESCENT LUMINAIRE

FLUORESCENT LUMINAIRE

x X

OS OCCUPANCY SENSOR

PHOTOCELL SENSOR

KEYED NOTE

ST = SHUNT TRIP

IC = INTERCOM

EPO = EMERGENCY POWER OFF

DA = DURESS ALARM

A = ABORT

PUSH BUTTON

-FIRE ALARM / MASS NOTIFICATION SYSTEM DEVICES-

METER

OR

OR

XX

PC

TYP. TYPICAL

XX XX = CANDELA OUTPUT

CU DAY LIGHT SENSOR AND CONTROL UNIT

x = LOWER CASE LETTER IS SWITCH ID

X = UPPER CASE LETTER IS FIXTURE TYPE

FLUORESCENT OR LED LUMINAIRES

KNOX BOX

IAW IN ACCORDANCE WITH

FIRE ALARM CONTROL PANEL

FAAP

MNS

FIRE ALARM ANNUNCIATOR PANEL

FS

TS

FLOW SWITCH

TAMPER SWITCH

MASS NOTIFICATION SYSTEM PANEL

LOC LOCAL OPERATOR CONSOLE

MASS NOTIFICATION SYSTEM

CEILING MOUNTED DATA OUTLET

AV

FAAP FIRE ALARM ANNUNCIATOR PANEL

OR

MANUAL PULL STATION

ACU AUTONOMOUS CONTROL UNIT

MASS NOTIFICATION SYSTEM

ACU

WITH INTEGRAL VOLUME CONTROL

AUDIO / VIDEO SYSTEM AND OUTLET

TELECOMMUNICATIONS GROUND BAR

MAIN GROUND BAR

TELECOMMUNICATIONS MAIN GROUND BAR

WP/GFI

PANELBOARD

SWITCHBOARD, DISTRIBUTION PANELBOARD, OR

TXX TRANSFORMER XX = SIZE

METER

x = TYPE

DUCT SMOKE DETECTOR

XX = CANDELA OUTPUT, IF SHOWN

COMBINATION FA AND MNS STROBE, CEILING MOUNT

FA SPEAKER

DUAL PROJECTION FA SPEAKER

FA STROBE LIGHT

ASSOCIATED CONDENSING UNIT

OR

AUTONOMOUS CONTROL UNIT

WALL MOUNTED LED OR HID LUMINAIRE

HID HIGH INTENSITY DISCHARGE

UL UNDERWRITERS LABORATORIES

LSC L L

(5 SCENE)

LIGHTING SCENE CONTROL

OR STRAIGHT TIP

SHUNT TRIP

FO FIBER OPTIC (CABLE)

SM SINGLE MODE

CU COPPER

OSP OUTSIDE PLANT

DOUBLE DUPLEX RECEPTACLE

SPECIAL PURPOSE RECEPTACLE

BATTERY BACK-UP

ON LIFE SAFETY / EMERGENCY POWER CIRCUIT

EM OR HALF SHADED INDICATES LUMINAIRE

CMH CERAMIC METAL HALIDE

TRT TRIPLE TUBE

EXPLOSION PROOF

SYMBOL

(NOTE: NOT ALL SYMBOLS SHOWN HEREON ARE USED IN THESE DRAWINGS)

PNL PANEL

E-001

E L E

C T

R

IC

A L L

E G

E N

D A

N D S

Y M

B O

L S

FOR CATENARY SYSTEM

LIGHTNING PROTECTION SYSTEM MAST

VM = VIDEO MONITOR

TC = TIME CLOCK

RX = REQUEST TO EXIT PUSH-BUTTON

RT = REMOTE TEST STATION

R = REMOTE INDICATING LIGHT

PS = PRESSURE SWITCH

PM = POWER QUALITY METER

PB = PULLBOX

OS = OCCUPANCY SENSOR

ML = MAGNETIC LOCK

MD = MOTION DETECTOR

MH = MANHOLE

KP = KEYPAD

IC = INTERCOM CALL STATION

HH = HAND HOLE

HC = HANDICAP PUSH-BUTTON

GB = GLASSBREAK DETECTOR

ES = ELECTRIC STRIKE

EL = ELECTRIC LOCK

DS = DOOR STRIKE

DO = DOOR OPERATOR

DC = DOOR CONTACT

DA = DURESS ALARM PUSH-BUTTON

CR = CARD READER

CK = CARD READER/KEYPAD

CH = CHIME

B = BUZZER

SPECIAL SYSTEMS SYMBOLS:

MH

HH

P

MAN HOLE

PEDESTAL

HAND HOLE

CONNECTION

EXP

CATV OUTLET MOUNTED AT +84" AFF UNO

MOUNTED +54" AFF UNO

TELEPHONE OUTLET WITH LUGGED FACEPLATE

DATA OUTLET MOUNTED +18" AFF UNO

CONDUIT

OR

FCP

ANTENNA

WOOD POLE

15 KV UNDERGROUND PRIMARY

480 V UNDERGROUND SECONDARY

XP = EXPLOSION PROOF

x = SMALL LETTER INDICATES LUMINARIES CONTROLLED

WP = WEATHERPROOF

VS = VARIABLE SPEED

TO = THERMAL OVERLOAD

P = WITH PILOT LIGHT

OS = OCCUPANCY SENSOR

M = MOTOR RATED

L = LOW VOLTAGE

K = KEY OPERATED

D = DIMMER

4 = FOUR-WAY

3 = THREE-WAY

2 = DOUBLE POLE

SINGLE POLE (IF BLANK)

SWITCH SYMBOL

ELECTRICAL LEGEND AND SYMBOLS

INSTALLED

GOVERNMENT FURNISHED CONTRACTOR

CFCI

INSTALLED

CONTRACTOR FURNISHED CONTRACTOR

PB

P

PP POWER POLE

FAULT PROTECTION

INSTANTANEOUS, AND GROUND

LONG TIME, SHORT TIME,

LP LIGHT POLE

ATFP ANTI-TERRORISM FORCE PROTECTION

RP RISER POLE

COE CORPS OF ENGINEERS

VFD = VARIABLE FREQUENCY DRIVE

SPD = SURGE PROTECTIVE DEVICE

SAP = SECURITY ALARM PANEL

PIR = PASSIVE INFRARED DETECTOR

MNCP = MASS NOTIFCATION CONTROL PANEL

MAM = MONITOR ADDRESSABLE MODULE

IDS = INTRUSION DETECTION SYSTEM

FSD = FIRE SMOKE DAMPER

EC = ELECTRICAL CONTACTOR

DVR = DIGITAL VIDEO RECORDER

DTC = DATA TERMINAL CABINET

DMA = DOOR MANAGEMENT ALARM

DE = DELAYED EGRESS

CAM = CONTROL ADDRESSABLE MODULE

BMS = BALANCED MAGNETIC STRIP

ATS = AUTOMATIC TRANSFER SWITCH

ASD = ADJUSTABLE SPEED DRIVE

ANN = ANNUNCIATOR

AMP = AMPLIFIER

MISCELLANEOUS SYSTEM COMPONENT:

DC DOOR CONTACT

COMBINATION FA HORN AND STROBE

CO = CARBON MONOXIDE

T = THERMAL TYPE

P = PHOTOELECTRIC TYPE

I = IONIZATION TYPE

F = FLAME

DETECTOR:

RAT RADIO ALARM TRANSCEIVERREQUIREMENTS.

ABBREVIATIONS AND ACTUAL ELECTRICAL

REFER TO MECHANICAL DOCUMENTATION FOR#1)

MECHANICAL EQUIPMENT TAG (eg EF-1 = EXHAUST FAN

OR CLASSIFIED AREA SHALL MEET THE INTENT OF THE APPLICABLE NEC ARTICLE.

6. LOCATIONS AND AREAS IN AND AROUND THE BUILDINGS LABELED AS BEING A HAZARDOUS

THREE (3) SPARES AND/OR SPACES IN FLUSH MOUNTED PANELBOARDS.

5. PROVIDE ONE (1) EMPTY 3/4" CONDUIT FROM PANEL TO AN ACCESSIBLE SPACE FOR EACH

LOCATION OF JUNCTION BOXES TO MEET LOCAL CODES AND NEC.

INDICATED HEREON. CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE PROPER NUMBER AND

4.JUNCTION BOXES FOR LUMINAIRES, RECEPTACLES, EQUIPMENT, ETC, ARE NOT SHOWN OR

RATING.

3.PENETRATIONS OF FIRE RATED OR HAZARDOUS AREA WALLS SHALL BE SEALED TO MAINTAIN

OTHERWISE.

2.120V AND 240 V BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL UNLESS NOTED

NATIONAL ELECTRIC CODE (NEC) EDITIONS.

1.WORK SHALL BE IN ACCORDANCE WITH THE LATEST LOCAL BUILDING CODES AND NFPA 70

OF INDIVIDUAL CONDUITS IS REQUIRED, COORDINATE WITH STRUCTURAL.

STRUCTURAL GRADE BEAMS AND SHALL NOT INTERFERE WITH PIERS. WHERE A PENETRATION

9. UNDERGROUND ELECTRICAL AND COMMUNICATION CONDUITS SHALL BE INSTALLED BELOW

VOLTAGE, FREQUENCY, PHASING, AND AMPERAGE OF THE CIRCUIT.

PHASE, DUPLEX CONVENIENCE OUTLETS WITH THE SUPPLY PANEL AND CIRCUIT NUMBER,

PLATES AND RECEPTACLE COVER PLATES FOR RECEPTACLES OTHER THAN 125 VOLT, SINGLE

LABELS HAVING 6 MILLIMETER, 1/4 INCH EMBOSSED LETTERS. SIMILARLY, MARK DEVICE COVER

PLATES WITH THE SUPPLY PANEL AND CIRCUIT NUMBER OF THE SOURCE. USE SELF-ADHESIVE

DEVICES INCLUDING TOGGLE SWITCHES AND RECEPTACLES. MARK WIRING DEVICE COVER

8. PERMANENTLY LABEL ALL COVERS FOR JUNCTION BOXES AND COVER PLATES FOR WIRING

FOR EACH CIRCUIT WITHIN THE RACEWAY.

7. PROVIDE AN INSULATED, GREEN IN COLOR, SEPARATE EQUIPMENT GROUNDING CONDUCTOR

BC BLOWER COIL

INTERRUPTER

WP/GFI = WEATHER PROOF GROUND FAULT CIRCUIT

GFI = GROUND FAULT CIRCUIT INTERRUPTER

S = SWITCHED (OCCUPANCY SENSOR CONTROLLED)

IG = ISOLATED GROUND

D = DEDICATED DUPLEX GROUNDED RECEPTACLE

DUPLEX RECEPTACLE

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

C

V E

L O

Z

F S

A B E -0

.D

G N

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

N

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

D I

NO SCALE

P-BOX

P-BOX

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

SIGN

SIGN

SIGN

SIGN

SIGN

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6" T-6" T-6" T-6" T-6"

T-6"

T-6"

T-6" T-6"T-6"T-6"

T-6" T-6"

T-6"T-6"

T-6"

T-6" T-6"

T-6"

T-6"

T-6"

T-24"

SIGN

SIGN

B R

A

R

B R

A

THOMAS ST.THOMAS ST. THOMAS ST.

P-XFMR P-MH T-PED

AS

P H

AL

T

AS

P H

AL

T

AS

P H

AL

T

AS

P H

AL

T

T-PED

P-MH

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

GPGPGPGP

FL=1186

.38TR=1197

.34SSMH

FL=1181

.45TR=1188

.97SSMH

M E T E R

THOMAS ST.

WALKER ST.

X

X

W

W

W

U E

UE

UE

B12-27

MH VAULT

SW-B12-14

UE1 UE1

U E

U G

E

U G

E

U E

2 UC2

UGE

UE1

ELECTRIC

EXISTING

E U x E

U x

EUx

E U x E

U x

UE

FUTURE

SW-B12-13

B12-26

MH VAULT

S

E

S

E

E

S

C

E

U G

E

HH

MH-109C

PT PITS

AND

RUNNING TRACK

SW-7S-27

E

S

U G

C

MH-B12-23

U G

E

U G E

MH

MH

ES101

GENERAL NOTES

KEYED NOTES

NORTH

PLAN

120'60'

SCALE IN FEET

060'

MATCHLINE - REFER TO ES103 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

MH-109C

MH-B12-23

SW-7S-27

A

IT

B

LD

G C

SITE ELECTRICAL/TELECOM UTILITY PLAN

AREA A

1 2

6 7

ES101

S

IT

E E

L E

C T

R

IC

A L /T

E L E

C O

M P

L A

N A

R E

A A

R

W A

T S

O N

C

V E

L O

Z

S

K U

N A

P U

L I, P .E

ES502

ES501

CONDUIT UNDERGROUND FROM SWBD TO PANEL MP-2.

PROVIDE FOUR 600 KCMIL THWN CU CONDUCTORS AND ONE #3 CU GND IN 4" SCH 80 PVC13

TO SW-7S-27, TEST AND TERMINATE.

RELOCATED SW-7S-27. REPULL EXISTING 15KV CABLES FROM MH-B12-22 THRU MH-B12-23

PROVIDE NEW 3WAY-5" CONCRETE ENCASED DUCTBANK FROM RELOCATED MH-B12-23 TO12

RELOCATED MH-B12-23.

MH-B12-23 LOCATION. COORDINATE WITH CIVIL SITE WORK FOR EXACT LOCATION OF

2WAY-5" CONCRETE ENCASED DUCTBANK FROM EXISTING SW-7S-27 LOCATION TO NEW

RELOCATE MH-B12-23 AND SW-7S-27 TO NEW LOCATIONS AS SHOWN. REMOVE EXISTING11

TO THE SOUTHWEST WITH SLURRY AND CAP.

AND PULL BACK INTO MH-B12-22. REMOVE RISERS AT SW-7S-27. FILL ABANDONED DUCTBANK

EXISTING MH-B12-23 AND SW-7S-27 LOCATIONS. DISCONNECT 15KV CABLES AT SW-7S-2710

BOTH ENDS. COORDINATE WITH CIVIL SITE WORK FOR EXACT LOCATION OF NEW MANHOLE.

DUCTBANK. FILL WITH SLURRY BETWEEN NEW AND EXISTING MH-109C LOCATIONS AND CAP

INSTALL NEW MH-109C WHERE SHOWN. SAWCUT EXISTING 6WAY-4" CONCRETE ENCASED9

RELOCATE MH-109C TO NEW LOCATION SHOWN. SEE KEYED NOTE 9 FOR NEW WORK.8

TO COMMUNICATION ROOM.

FT SILL NEC WILL PROVIDE 25 PAIR COPPER AND 12 STRAND SMFO CABLES FROM MH-1097

ROOM.

AND ONE (1) WITH 4 - 1" INNER DUCTS FROM MH-109C [NEW LOCATION] TO COMMUNICATION

PROVIDE 4 - 4" CONCRETE ENCASED SCH 40 PVC CONDUITS, THREE (3) WITH PULL ROPES6

SWITCH BOARD.

AND 2 SPARE WITH PULL ROPE FROM PAD MOUNTED TRANSFORMER TO FACILITY MAIN

PROVIDE 9 EA 4" CONCRETE ENCASED SCH 40 PVC CONDUITS, 7 WITH 4 EA #500KCMIL5

PROVIDE 1500KVA, 13.2KV - 480/277V COPPER WOUND PAD MOUNTED TRANSFORMER.4

MOUNTED TRANSFORMER.

OUTER JACKET, AND ONE (1) SPARE WITH PULL ROPE FROM SW-7S-27 TO NEW PAD

RATED 15KV CABLES WITH CONCENTRIC NEUTRAL 133% EPR INSULATION, AND LL DPE

PROVIDE 2 EA 5" CONCRETE ENCASED SCH 40 PVC DUCTS, 1 WITH (3) #2 AWG MV-1053

SLURRY AND CAP BOTH ENDS.

FILL THE EXISTING 2 - 5" CONDUITS FROM SWITCH SW-7S-27 TO STUBUP POINT WITH2

WITH SLURRY AND CAP BOTH ENDS.

FILL THE EXISTING 4 - 4" COMMUNICATION CONDUITS FROM MH-109B TO STUBUP POINT1

INTERFERE WITH PIERS. SEE DETAIL 6 ON SHEET ES501.

BE INSTALLED AT A MINIMUM OF 12" BELOW FOUNDATION ELEMENTS AND SHALL NOT

UNDERGROUND ELECTRICAL AND COMMUNICATION DUCTBANKS AND CONDUITS SHALL12.

ACTUAL INFORMATION ON AS BUILT DRAWINGS.

PLANS HAVE BEEN OBTAINED FROM AVAILABLE RECORDS. FIELD VERIFY AND PROVIDE

THE LOCATIONS OF UNDERGROUND UTILITIES AND ELECTRICAL EQUIPMENT SHOWN ON11.

RECORDS. FIELD VERIFY AND PROVIDE ACTUAL INFORMATION ON AS BUILT DRAWINGS.

EQUIPMENT LOCATIONS SHOWN ON PLANS HAVE BEEN OBTAINED FROM AVAILABLE

UNDERGROUND UTILITIES, SWITCHES, MANHOLES, DUCTBANKS, AND ELECTRICAL10.

AND ALLOWED IF APPROVED BY THE GOVERNMENT.

BORING AND/OR PAVEMENT CUTTING WILL BE CONSIDERED ON A CAS BY-CASE BASIS

BORING WITH STEEL CASING IS REQUIRED FOR PAVED SURFACES, BUT DIRECTIONAL9.

FACILITY'S COMMUNICATION ROOM, AND TEST.

FT SILL NEC WILL SPLICE THE OSP CABLES IN MANHOLES, TERMINATE IN EACH8.

COMMUNICATION ROOM.

FT SILL NEC WILL PROVIDE COPPER AND SMFO OSP CABLES TO EACH FACILITY'S7.

NEW 13.2 KV AND COMMUNICATION DUCT BANKS SHALL BE CONCRETE ENCASED.6.

TO EACH COMMUNICATION ROOM.

PROVIDE COMMUNICATION DUCT BANK FROM THE RELOCATED MAN HOLE SYSTEM5.

EACH FACILITY PAD MOUNTED TRANSFORMER.

PROVIDE 13.2 KV DUCT BANK FROM THE RELOCATED PAD MOUNTED SWITCHES TO4.

REFER TO THE ONE-LINE DIAGRAM FOR MORE INFORMATION.3.

TRANSFORMER PAD, AND SECONDARY SERVICE.

PROVIDE 13.2 KV SERVICE TO EACH NEW FACILITY, AS WELL AS THE TRANSFORMER,2.

ITEMS ARE EXISTING.

ITEMS SHOWN IN BOLD SHALL BE PROVIDED BY THIS CONTRACT. LIGHTLY SHADED1.

F S

A B E

S .D

G N

L1

GM

P -2

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

NO SCALE

A

IT

B /C

O F B

LD

G A

S

P A

C E

S

B L

A

IR

S

T

P O

V P

A R

K

IN

G

E X

IS

T B

D L

G

H C

H C

H C

H C

H C

H C

H C

H C

UE1

U E

U E

UC3

UC3

UE1 UE1

U E

UC3

UE1

495'

6W-4"

UC3

UE1

U C

U E

E

T

T

SW-B12-6

SW-B12-9

MH

T

T

UE2

UE1 UE1

UE2

J

E

C

S

S

E

U E1U

E

U C

U E

U E1

EU

x

U E

EXISTING MH 108

SW-7S-25

MH-109A

EXISTING MH-109

6W-4"-242'

SW-7S-24

E

SE

S

S

SE

U C

U E

UC3

MH-109B

C

MH-B12-22

MH-B12-21

MH-B12-20

MH-B12-19

ES102

ES102

1 NORTH

PLAN

120'60'

SCALE OF FEET

060'

AREA B

MATCHLINE - REFER TO ES103 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

GENERAL NOTES

KEYED NOTES

MH-109 TO AIT BLDG "D" COMMUNICATION ROOM.

STRAND SMFO CABLES FROM TELECOM MANHOLE

2 FT SILL NEC WILL PROVIDE 25 PAIR COPPER AND 12

MH-109 TO AIT BLDG "C" COMMUNICATION ROOM.

STRAND SMFO CABLES FROM TELECOM MANHOLE

FT SILL NEC WILL PROVIDE 25 PAIR COPPER AND 121

BUILT DRAWINGS.

FIELD VERIFY AND PROVIDE ACTUAL INFORMATION ON AS

OBTAINED FROM AVAILABLE RECORDS. CONTRACTOR SHALL

ELECTRICAL EQUIPMENT SHOWN ON PLANS HAVE BEEN

THE LOCATIONS OF UNDERGROUND UTILITIES AND11.

AS BUILT DRAWINGS.

SHALL FIELD VERIFY AND PROVIDE ACTUAL LOCATION ON

THE PLAN ARE FROM PREVIOUS RECORDS. CONTRACTOR

SWITCHES, MANHOLES, DUCT BANK LOCATIONS SHOWN ON10.

AND ALLOWED IF APPROVED BY THE GOVERNMENT.

CUTTING WILL BE CONSIDERED ON A CASE-BY-CASE BASIS

SURFACES, BUT DIRECTIONAL BORING AND/OR PAVEMENT

BORING WITH STEEL CASING IS REQUIRED FOR PAVED9.

AND TEST.

TERMINATE IN EACH FACILITY'S COMMUNICATION ROOM,

8. FT SILL NEC WILL SPLICE THE OSP CABLES IN MANHOLES,

CABLES TO EACH FACILITY'S COMMUNICATION ROOM.

FT SILL NEC WILL PROVIDE COPPER AND SMFO OSP7.

CONCRETE ENCASED.

NEW 13.2 KV AND COMMUNICATION DUCT BANKS SHALL BE6.

ROOM.

RELOCATED MANHOLE SYSTEM TO EACH COMMUNICATION

PROVIDE COMMUNICATION DUCT BANK FROM THE5.

MOUNTED TRANSFORMER.

MOUNTED SWITCHES TO EACH FACILITY PAD

PROVIDE 13.2 KV DUCT BANK FROM THE RELOCATED PAD4.

REFER TO THE ONE-LINE DIAGRAM FOR MORE INFORMATION.3.

SECONDARY SERVICE.

AS THE TRANSFORMER, TRANSFORMER PAD, AND

PROVIDE 13.2 KV SERVICE TO EACH NEW FACILITY, AS WELL2.

CONTRACT. LIGHTLY SHADED ITEMS ARE EXISTING.

ITEMS SHOWN IN BOLD SHALL BE PROVIDED BY THIS1.

SITE ELECTRICAL/TELECOM UTILITY PLAN

U T

IL

IT

Y P

L A

N A

R E

A B

S

IT

E E

L E

C T

R

IC

A L T

E L E

C O

M

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

NO SCALE

S

P A

C E

S

P O

V P

A R

K

IN

G

S T R

E E T B

U

367'

12 STR SM

6W-4" 25PR

E SE

S

E

E 1845652.07

N 479219.96

U E

UE2

C

U C

U

277'

6W-4" 25PR

U C

UC3UC3

UE1

7-312

50-3

J

T

E O x

E O x

E O x

E O x

EOx

EOx

SW-7S-30

SW-7S-29

PHASE 7.62KV-240/120

TRANSFORMER SINGLE

PAD MOUNTED

S

DUCTBANK FOR SECONDARIES

(5) 4"C CONCRETE ENCASED

A

IT

B /C

O F B

LD

G B

FL E: 1183.29

FL N: 1183.12

TR 1186.38

SSMH

BANK FOR MECHANICAL YARD

CONCRETE ENCASED DUCT

(1) 2" AND (1) 1" CONDUIT

MH-108A

MH-B12-15

MH-B12-13

MH-B12-14

UE2UE2

ES103

ES103

1 NORTH

PLAN

120'60'

SCALE OF FEET

060'

AREA C

MATCHLINE - REFER TO ES102 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

GENERAL NOTES

KEYED NOTES

BUILT DRAWINGS.

FIELD VERIFY AND PROVIDE ACTUAL INFORMATION ON AS

OBTAINED FROM AVAILABLE RECORDS. CONTRACTOR SHALL

ELECTRICAL EQUIPMENT SHOWN ON PLANS HAVE BEEN

THE LOCATIONS OF UNDERGROUND UTILITIES AND11.

AS BUILT DRAWINGS.

SHALL FIELD VERIFY AND PROVIDE ACTUAL LOCATION ON

THE PLAN ARE FROM PREVIOUS RECORDS. CONTRACTOR

SWITCHES, MANHOLES, DUCT BANK LOCATIONS SHOWN ON10.

AND ALLOWED IF APPROVED BY THE GOVERNMENT.

CUTTING WILL BE CONSIDERED ON A CASE-BY-CASE BASIS

8. FT SILL NEC WILL SPLICE THE OSP CABLES IN MANHOLES,

CABLES TO EACH FACILITY'S COMMUNICATION ROOM.

FT SILL NEC WILL PROVIDE COPPER AND SMFO OSP7.

CONCRETE ENCASED.

NEW 13.2 KV AND COMMUNICATION DUCT BANKS SHALL BE6.

ROOM.

RELOCATED MANHOLE SYSTEM TO EACH COMMUNICATION

PROVIDE COMMUNICATION DUCT BANKS FROM THE5.

MOUNTED TRANSFORMER.

MOUNTED SWITCHES TO EACH FACILITY PAD

PROVIDE 13.2 KV DUCT BANK FROM THE RELOCATED PAD4.

REFER TO THE ONE-LINE DIAGRAM FOR MORE INFORMATION.3.

SECONDARY SERVICE.

AS THE TRANSFORMER, TRANSFORMER PAD, AND

PROVIDE 13.2 KV SERVICE TO EACH NEW FACILITY, AS WELL2.

CONTRACT. LIGHTLY SHADED ITEMS ARE EXISTING.

ITEMS SHOWN IN BOLD SHALL BE PROVIDED BY THIS1.

SITE ELECTRICAL/TELECOM PLAN - AREA C

U T

IL

IT

Y P

L A

N A

R E

A C

S

IT

E E

L E

C T

R

IC

A L T

E L E

C O

M

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

SEE SHEET ES102 AND ES104 FOR CONTINUATION.

MH-109 TO AIT BLDG "D" COMMUNICATION ROOM.

STRAND SMFO CABLES FROM TELECOM MANHOLE

2 FT SILL NEC WILL PROVIDE 25 PAIR COPPER AND 12

SPARE CONDUIT.

SWITCH 7S-30 TO MH-B12-15. PROVIDE PULL WIRE IN

LLDPE OUTER JACKET, IN EXISTING 5" CONDUIT FROM

CONCENTRIC NEUTRAL 133%, EPR INSULATION AND

1 PROVIDE (3) #2 AWG MV-105 RATED 15KV CABLES WITH

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

N

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

NO SCALE

T R

O O

P A

S S

E M

B L

Y A

R E

A

A W

N

IN

G S

T R

O O

PT

R

A N

S P

O R

T A

T

IO

N D

R O

P O

F F Z

O N

E

DETENTION POND

C O

V E R E D A

R E A

D O D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

T O

W E R

C O

O

LI

N G

O H

D

O H

D

MOW WAY RD.

WILSON ST.

B R

A G

G R

O A

D

UC

E 1845309.66

N 479282.62

UE1UE1UE1

7-252

50-3

7-255

45-3

E 1844216.08

N 479085.47

7-252A

50-3

1 #4/0 ACSR N

3 #1/0 CU PRI

U E

VAULT B12-9

EXISTING

E 1844189.91

N 479132.08

SW-B12-1

U E

E O x

E O x

POLE GUY

POLE RISER

E E

S

E

C

SW-7S-31

S

DUCTBANK

ABANDON EXISTING

FEEDER B12

EXISTING

BANK FOR MECHANICAL YARD

CONCRETE ENCASED DUCT

(1) 2" AND (1) 1" CONDUIT

E

MH-B12-10

MH-B12-11 MH-B12-12

MH-B12-15

UE2

MH-B12-16

UC2

MH

UG

E

L1G

U G

C

UGE

U G E

MH

M P -2

ES104

ES104

NORTH

PLAN

120'60'

SCALE OF FEET

060'

AREA D

MATCHLINE - REFER TO ES101 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

KEYED NOTES

MH-108B

MH-108C9

U T

IL

IT

Y P

L A

N A

R E

A D

S

IT

E E

L E

C T

R

IC

A L T

E L E

C O

M

SITE ELECTRICAL/TELECOM UTILITY PLAN - AREA D

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

SWBD TO PANEL MP-2.

#3 CU GND IN 4" SCH 80 PVC CONDUIT UNDERGROUND FROM

PROVIDE FOUR 600 KCMIL THWN CU CONDUCTORS AND ONE10

LOCATION SHOWN.

PROVIDE NEW TELECOMMUNICATION MANHOLE MH-108C AT9

SMFO CABLES FROM MH-109 TO MAIN TR (TELECOM ROOM).

8 FT SILL NEC WILL PROVIDE 25-PAIR COPPER AND 12-STRAND

TR (TELECOM ROOM).

FOUR (4) 1" INNERDUCTS FROM MH-108B VIA MH-108C TO MAIN

DUCTBANK, THREE (3) WITH PULL ROPE AND ONE (1) WITH

7 PROVIDE 4WAY-4" SCH 40 PVC CONCRETE ENCASED

SWBD.

PULL ROPE FROM PADMOUNTED TRANSFORMER TO FACILITY

SEVEN (7) WITH FOUR (4) #500KCMIL AND TWO (2) SPARES WITH

PROVIDE NINE (9) 4" CONCRETE ENCASED SCH 40 PVC CONDUITS,6

MOUNTED TRANSFORMER.

PROVIDE 1500KVA, 13.2KV - 480/277V COPPER WOUND PAD5

PADMOUNTED TRANSFORMER.

THROUGH NEW MANHOLES MH-B12-15 & MH-B12-16 TO NEW

OUTER JACKET AND A PULL ROPE IN THE SPARE FROM SW-7S-30

CONCENTRIC NEUTRAL 133%EPR INSULATION, AND LLDPE

PROVIDE THREE (3) #2 AWG MV-150 RATED 15KV CABLES WITH4

MANHOLE MH-B12-15 TO NEW PADMOUNTED TRANSFORMER.

EXTEND 2-5" CONCRETE ENCASED CONDUITS FROM NEW3

REQUIRED. SEE DETAIL 4 ON SHEET ES501.

AT LOCATIONS SHOWN. SAWCUT THE EXISTING CONDUITS IF

PROVIDE NEW ELECTRICAL MANHOLES MH-B12-15 & MH-B12-162

BOTH ENDS.

BETWEEN STUBOUT AND NEW MH-B12-15 WITH SLURRY AND CAP

LOCATION. SAWCUT EXISTING 2-5" CONDUITS AND FILL CONDUITS

EXISTING 2-5" CONCRETE ENCASED CONDUITS STUBOUT1

A

IT

B

LD

G "D

SEE DETAIL 6 ON SHEET ES501.

FOUNDATION ELEMENTS AND SHALL NOT INTERFERE WITH PIERS.

AND CONDUITS SHALL BE INSTALLED AT A MINIMUM OF 12" BELOW

UNDERGROUND ELECTRICAL AND COMMUNICATION DUCTBANKS12.

BUILT DRAWINGS.

FIELD VERIFY AND PROVIDE ACTUAL INFORMATION ON AS

OBTAINED FROM AVAILABLE RECORDS. CONTRACTOR SHALL

ELECTRICAL EQUIPMENT SHOWN ON PLANS HAVE BEEN

THE LOCATIONS OF UNDERGROUND UTILITIES AND11.

AS BUILT DRAWINGS.

SHALL FIELD VERIFY AND PROVIDE ACTUAL LOCATION ON

THE PLAN ARE FROM PREVIOUS RECORDS. CONTRACTOR

SWITCHES, MANHOLES, DUCT BANK LOCATIONS SHOWN ON10.

AND ALLOWED IF APPROVED BY THE GOVERNMENT.

CUTTING WILL BE CONSIDERED ON A CASE-BY-CASE BASIS

8. FT SILL NEC WILL SPLICE THE OSP CABLES IN MANHOLES,

CABLES TO EACH FACILITY'S COMMUNICATION ROOM.

FT SILL NEC WILL PROVIDE COPPER AND SMFO OSP7.

CONCRETE ENCASED.

NEW 13.2 KV AND COMMUNICATION DUCT BANKS SHALL BE6.

ROOM.

RELOCATED MANHOLE SYSTEM TO EACH COMMUNICATION

PROVIDE COMMUNICATION DUCT BANK FROM THE5.

MOUNTED TRANSFORMER.

MOUNTED SWITCHES TO EACH FACILITY PAD

PROVIDE 13.2 KV DUCT BANK FROM THE RELOCATED PAD4.

REFER TO THE ONE-LINE DIAGRAM FOR MORE INFORMATION.3.

SECONDARY SERVICE.

AS THE TRANSFORMER, TRANSFORMER PAD, AND

PROVIDE 13.2 KV SERVICE TO EACH NEW FACILITY, AS WELL2.

CONTRACT. LIGHTLY SHADED ITEMS ARE EXISTING.

ITEMS SHOWN IN BOLD SHALL BE PROVIDED BY THIS1.

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

N

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

NO SCALE

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

O H

D

O H

D

T-6"

CONCRETE

P-BOX

P-BOX

P-BOX

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

SIGN

SIGN

SIGN

SIGN

SIGN

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6" T-6" T-6" T-6" T-6"

T-6"

T-6"

T-6" T-6"T-6"T-6"

T-6" T-6"

T-6"T-6"

T-6"

T-6" T-6"

T-6"

T-6"

T-6"

T-24"

T-6"

T-3"

SIGN

SIGN

B R

A

B R

A

THOMAS ST.THOMAS ST. THOMAS ST.

CONCRETE

GRASS

CONCRETECONCRETECONCRETE

GRASS

GRASS

C O

N C

R E T E

GRASS

C O

N C

R E T E

GRASS

P-XFMR P-MH T-PED

AS

P H

AL

T

GRASS

C O

N C

R E T E

GRASS

R U

N N

IN

A C

K

GRASS

OLD COMM MH

P-BOX

AS

P H

AL

T

AS

P H

AL

T

AS

P H

AL

T

T-PED

P-MH

GRAVEL

CONCRETE P

AD

R U

N N

A C

K R

U N

N

A C

K

GRASS

CONCRETE

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

AS

PHALT

GPGPGPGPR

U

N N

A C

K

C O

N C

R E T E

GRASS

GRASS

GRASS

GRASS

GRASS

GRASS

GRASS

GRASS

GRASS

FL=1186

.38TR=1197

.34SSMH

FL=1181

.45TR=1188

.97SSMH

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

O H

D

O H

D

G M

XFMR

THOMAS ST.

WALKER ST.

X

X

W

ELECTRIC

EXISTING

E

PT PITS

AND

RUNNING TRACK

ES105

ES105

GENERAL NOTES

KEYED NOTES

NORTH

PLAN

120'60'

SCALE OF FEET

060'

AREA A

MATCHLINE - REFER TO ES103 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

MH-109C

J

Y

Y

Y

Y

Y Y Y Y Y Y Y Y Y

Y

Y

Y

Y

Y

Y

Y

Y

Y Y

Y

Y

Y

YY

Y

Y

Y

Y

Y

Y

Y

Y

Y

Y

Y A

IT

B

LD

G C

LIGHTING.

POLE FOR EXTERIOR WALKWAY & YARD

IN 1ST FLOOR ELECTRICAL ROOM TO LIGHT

PROVIDE 1" PVC CONDUIT FROM PANEL "SL-1" 2

COVERED AREA FOR POWER AND LIGHTING.

"SL-1" IN 1ST FLOOR ELECTRICAL ROOM TO

PROVIDE 2-1" PVC CONDUITS FROM PANEL 1

SITE LIGHTING PLAN AND UNDERGROUND PLAN - AREA A

P L

A N A

R E

A A

S

IT

E L

IG

H T

IN

G A

N D U

N D

E R

G R

O U

N D

C

V E

L O

Z

X S L1 -2

S L1 -2X

S L1 -2X

S L1 -2X

S L1 -2X

S L1 -2X

CONTROL CORRESPONDING CANOPY LIGHTS.

OUTDOOR CANOPY MOUNTED ON COLUMN TO

PROVIDE WEATHERPROOF SWITCH AT EACH3.

ON SHEET ES501.

NOT INTERFERE WITH PIERS. SEE DETAIL 6

BELOW FOUNDATION ELEMENTS AND SHALL

SHALL BE INSTALLED AT A MINIMUM OF 12"

COMMUNICATION DUCTBANKS AND CONDUITS

UNDERGROUND ELECTRICAL AND2.

OR IP68 RATED.

ALL EXTERIOR DEVICES SHALL BE NEMA 3R1.

X

X

X

X

X

X

X

X

X

X

X

X

Y

Y Y

C

V E

L O

Z

S

K U

N A

P U

L I, P .E

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

N

KEY MAP

AIT B/COF Bldg F FUTURE (NIC)

AIT B/COF Bldg G FUTURE (NIC)

S T R

E E T B

NO SCALE

DETENTION POND

C O

V E R E D A

R E A

D O D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

F F

9.

T O

W E R

C O

O

LI

N G

O H

D

O H

D

T-6"

(PIPES N AND E)FL=1182

.35TR=1184

.55OLD SS

MH

CONCRETE

C O

N C R E T E

BR

ID

G E

GRASS

GRASS

GRASS

LP

LPLP

LP

LP

LPLP

LP

LP

LP

LP

LP

T-PED

SIGN

TRAF BOX

TRAF BOX

TRAF BOX

4" GAS LINE 4" GAS LINE

WV

WV

WV

T-6"T-6"

T-6" T-6" T-6" T-6"

T-24"

T-6" T-6" T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-6"

T-24"

T-12"

T-8"

T-6"

T-18" T-6"T-6"

T-6"

T-6"

T-6"

T-3"

T-3"

T-24"

T-24"

T-36"

T-12"

T-18"

T-8"

B R

A

MOW WAY RD.MOW WAY RD. MOW WAY RD.

B R

A

W

ATER

W

ATER

A T E

R

12" WATER

12" WATER12" WATER

T E

R

T E

R

T E

R

FL=1180

.84TR=1185

.74SSMH

FL=1182

.32TR=1191

.32SSMH

GRASS

AS

PHALT

GRASS

C O

N C

R E T E

GRASS

CONCRETE

GRASS GRASS

GRASS

CONCRETECONCRETE

GRASS

T-24"

P-XFMR

P-MH

4" GAS LINE

T-6"

4" GAS LINE

P-MH

WV

WVWV

GRASS

WVWV

WV

TR=1182

.58OLD SS

MH

CONCRETE

4" GAS LINE

12" Sanitary Sewer

12" Sanitary Sewer

S a n it a ry

S e w e r

FL=1183

.23TR=1186

.73SSMH

CONCRETE P

AD

FH

COMM BOX

T-3"

GRASS

T-6" T-6"

GRASS

CONCRETE

AS

P H

AL

T

AS

P H

AL

T

AS

P H

AL

T

AS

P H

AL

T

AS

PHALT

GPGPGPGP

GPGPGPGPC

O N

C R

E T E

C O

N C

R E T E

EXIST PUG(PER AS-BUILTS)

FL=1181

.45TR=1188

.97SSMH

COMM MH

WV

24"RCP

R

C P

R

C P

R

C P

18"RCP

"R

C P

"R

C P

DETENTION POND

C O

V E R E D A

R E A

D O D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

D O

F F

9.

T O

W E R

C O

O

LI

N G

O H

D

O H

D

MOW WAY RD.

WILSON ST.

B R

A G

G R

O

100'

4W-4" 25PR

S S

FL E&W: 1181.25

TR 1188.90

SSMH

S

S

ES106

ES106

1 NORTH

PLAN

S

K U

N A

P U

L I, P .E

120'60'

SCALE OF FEET

060'

AREA D

MATCHLINE - REFER TO ES101 FOR CONTINUATION

M A

T C

H L

IN

E R

E F

E R T

O E

S F

O R C

O N

T

IN

U A

T

IO

N

KEYED NOTESJ

Y

Y

Y Y Y Y Y Y Y Y Y

Y

Y

Y

Y

Y

Y

Y

SITE LIGHTING AND UNDERGROUND PLAN - AREA D

P L

A N A

R E

A D

S

IT

E L

IG

H T

IN

G A

N D U

N D

E R

G R

O U

N D

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

WALKWAY AND YARD LIGHTING.

ROOM TO LIGHT POLE FOR EXTERIOR

PANEL "SL-1" IN 1ST FLOOR ELECTRICAL

PROVIDE 1" PVC CONDUIT FROM2

AND LIGHTING.

ROOM TO COVERED AREA FOR POWER

PANEL "SL-1" IN 1ST FLOOR ELECTRICAL

PROVIDE 2-1" PVC CONDUITS FROM1

X

S L1 -2

S L1 -2

X

S L1 -2

X S L1 -2

X S L1 -2

X S L1 -2

X

Y

Y

CANOPY LIGHTS.

COLUMN TO CONTROL CORRESPONDING

EACH OUTDOOR CANOPY MOUNTED ON

PROVIDE WEATHERPROOF SWITCH AT3.

ES501.

WITH PIERS. SEE DETAIL 6 ON SHEET

ELEMENTS AND SHALL NOT INTERFERE

A MINIMUM OF 12" BELOW FOUNDATION

CONDUITS SHALL BE INSTALLED AT

COMMUNICATION DUCTBANKS AND

UNDERGROUND ELECTRICAL AND2.

WEATHER PROOF.

ALL EXTERIOR DEVICES SHALL BE1.

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

ES501

S

IT

E P

L A

N D

E T

A

IL

S

T E

L E

C O

M M

U N

IC

A T

IO

N S

P O

W E

R A

N D

ES501

ES501

M

IN

ES501

GROUNDING ROD DETAIL

PAD MOUNT TRANSFORMER GROUNDING DETAIL

NOT TO SCALE

NOT TO SCALE

OPENING

CONDUIT

PRIMARY

OPENING

CONDUIT

SECONDARY

ROD

CLAD STEEL GROUND

10' x 3/4 DIA. COPPER

6"

17"

25"

65" 6.5"

78"

30"

6.5"

3"

EQ. SPACES AT 12" O.C. MAX 3"3"

A A

NOTES:

72"

2"-4"

8"

8 8

ES501

NOT TO SCALE

ENDS @ 12" O.C. MAX.

#4 W/8" HOOKS BOTH

SECTION A-A

PLAN

CENTERED IN THE OPENING

PRIMARY CONDUITS MUST BE

OPENING (MESH NOT SHOWN)

PROVIDE CUT MESH AROUND

SECONDARY CONDUIT OPENING

PRIMARY CONDUIT OPENING

A T

O .C

M A

X

E Q S

P A

C E

S

TO CROSS-HATCHED AREA.

CENTERED IN AND CONFINED

SECONDARY CONDUITS MUST BE

SPACED AS SHOWN

NO. 4 REINF. BARS,

8" COMPACTED GRAVEL BASE

FINISHED GRADE

UNDISTURBED EARTH (TYP.)

FRONT SIDE

OR COMPRESSION CONNECTOR (TYP.)

CONNECT TO GROUND RING WITH EXOTHERMIC

3/4"ø x 10' COPPER CLAD GROUND ROD.

HORIZONTAL FROM TRANSFORMER PAD

BELOW FINISHED GRADE, 36"

4/0 CU STRANDED GROUND RING, 12"

ES501

TEE CONNECTION (TYP.)

EXOTHERMIC OR COMPRESSION

TRANSFORMER PAD

CONCRETE

PRIMARY CONDUIT OPENING SECONDARY CONDUIT OPENING

GROUND TEST WELL

E-501

EXOTHERMIC WELD

GROUND CABLE (TYP.)

STRANDED BARE COPPER

FINISHED GRADE

TRANSFORMER PAD DETAIL

GENERAL NOTES

COOLING SYSTEM FINS).

9. PAD SHALL EXTEND 8" BEYOND ALL SIDES OF THE TRANSFORMER ENCLOSURE (TO INCLUDE

FOR CRACK CONTROL.

8. THOROUGHLY MIX MACRO-FIBER REINFORCEMENT AT A RATE OF 5 LB./YD , INTO CONCRETE

7. REINFORCING BARS SHALL BE ASTM A615 GR 60.

6. THE CONDUIT OPENING SHALL BE FREE AND CLEAR OF CONCRETE.

5. TOP OF CONDUITS SHALL BE FLUSH WITH TOP OF PAD.

4. CONTRACTOR SHALL EXTEND FORMS DOWN TO AT LEAST 3" BELOW AVERAGE GROUND LINE.

3. THE CONCRETE SHALL BE 4,000 PSI MINIMUM ULTIMATE STRENGTH.

THE CORNERS AND EDGES SHALL BE ROUNDED OR BEVELED.

2. THE TOP OF THE TRANSFORMER PAD SHALL RECEIVE A SMOOTH TROWEL FINISH.

1. VERIFY PAD LOCATION, DIMENSIONS & ALL REQUIREMENTS WITH TRANSFORMER.

12" x 12" x 10" DEEP

SUMP

DUCT ENTRANCE. LOCATION TO BE

AS INDICATED

PLAN

A

B8"

A A

CONCRETE OR BLACK

TOP ROADWAY

SLOPE 1:40 TO SUMP

GROUND ROD & CLAMP

FOR MANHOLE FRAME & COVER, SEE FED.

SPEC. A-A-60005, FIG. 1, SIZE 30A AND

FIG. 8, SIZE 30A, RESPECTIVELY

BRICK COLLAR LINED UP WITH

CEMENT MORTAR

8"

10"

B

SECTION A-A

#5 @ 6" EW, T&B

#4 @ 6" EW EF

#4 @ 6" T&B

C

8"

8"

8"

8"

LAP REINF. 24" (TYP.)

6" MIN.

NOTES:

MANHOLE AND COVERS ARE DESIGNED

FOR MAXIMUM WHEEL LOAD IN

ACCORDANCE WITH AASHTO HS20-44.

MINIMUM CONCRETE COMPRESSIVE

STRENGTH SHALL BE 3000 PSI.

1.

2.

CONSTR. JTS. (TYP.)

WATERSTOP AT ALL

MANHOLE DIMENSIONS

8'-0"

A

8'-0"

B C (AT HIGH PT.)

7'-0"

9-1/2"

12"

ES501

NOT TO SCALE

STANDARD ELECTRICAL MANHOLE

SIZE OF CONDUITS AND FEEDERS.

REFER TO SHEETS ES101 AND ES104 FOR EQUIPMENT SCHEDULE 3.

VERIFY ALL REQUIREMENTS WITH MECHANICAL PLANS.2.

ALL EXTERIOR DEVICES SHALL BE WEATHER PROOF.1.

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

NOT TO SCALEES501

NOTES:

(M

IN

IM

U M

MARKER TAPE TO COMPENSATE FOR SETTLING.

MATCH ADJACENT AREAS. MOUND

TOP SOIL-PLANT WITH GRASSES TO

UNDERGROUND DEVICES #4W30-2.

DUCT SPACERS 5'-0" O.C.

CONCRETE ENCASEMENT

24" O.C. (TYPICAL)

#4 REBAR HOOP

(TYPICAL)

#4 REBAR CONTINUOUS

DUCT TIE-DOWN

EPC-40-PVC

#4 REBAR

2" ROCK SCREEN

5 5 5

S

A N

D

(M

IN

FOR ADDITIONAL REQUIREMENTS)

(REFERENCE SPECIFICATIONS

85% ASTM D-1557 8" LOOSE LIFTS

GENERAL FILL UNPAVED:

(M

IN

3. REINFORCING ONLY REQUIRED WHERE DUCT BANK CROSSES PAVED AREAS.

CONCRETE SHALL BE 3000 PSI AT 28 DAYS.

2. PROVIDE 3" MINIMUM COVER ALL SIDES FOR ALL CONCRETE ENCASEMENT.

1. TAPE COLOR SHALL BE RED. TAPE TEXT SHALL BE "HIGH VOLTAGE DUCTS".

PRIMARY SERVICE DUCTBANK DETAIL

ES501

NOT TO SCALE

ELECTRICAL CONDUIT ENTRANCE DETAIL

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

ES502

S

IT

E P

L A

N D

E T

A

IL

S

T E

L E

C O

M M

U N

IC

A T

IO

N S

P O

W E

R A

N D

HIGH VOLTAGE SECTION LOW VOLTAGE SECTION

ES501

NOT TO SCALE

X0

A

B

T

ES502

NOT TO SCALE

ES502

NOT TO SCALEES502

PAD MOUNT TRANSFORMER TERMINATION AND GROUNDING DETAIL

THREE PHASE PAD MOUNT TRANSFORMER DETAIL

5 5

ES502

(M

IN

IM

U M

(M

IN

PRIMARY SERVICE DUCTBANK DETAIL

NOT TO SCALE

NOTES:

3. REINFORCING ONLY REQUIRED WHERE DUCT BANK CROSSES PAVED AREAS.

CONCRETE SHALL BE 3000 PSI AT 28 DAYS.

2. PROVIDE 3" MINIMUM COVER ALL SIDES FOR ALL CONCRETE ENCASEMENT.

1. TAPE COLOR SHALL BE RED. TAPE TEXT SHALL BE "HIGH VOLTAGE DUCTS".

#4 REBAR

2" ROCK SCREEN

UNDERGROUND DEVICES #4W30-2.

DUCT SPACERS 5'-0" O.C.

CONCRETE ENCASEMENT

24" O.C. (TYPICAL)

#4 REBAR HOOP

(TYPICAL)

#4 REBAR CONTINUOUS

DUCT TIE-DOWN

EPC-40-PVC

MARKER TAPE

FOR ADDITIONAL REQUIREMENTS)

(REFERENCE SPECIFICATIONS

85% ASTM D-1557 8" LOOSE LIFTS

GENERAL FILL UNPAVED:

TO COMPENSATE FOR SETTLING.

MATCH ADJACENT AREAS. MOUND

TOP SOIL-PLANT WITH GRASSES TO

S

A N

D

(M

IN

NOTES:

BAYONET OIL-IMMERSED EXPULSION FUSES

PRIMARY COMPARTMENT

OIL-IMMERSED CURRENT-LIMITING FUSES

2 POSITION LOAD BREAK SWITCH (TYP. OF 3)

TRANSFORMER BUSHING WELL

BUSHING INSERT

PRIMARY NEUTRAL

CABLE WELL

PRIMARY CIRCUIT

SPARE CONDUIT

SECONDARY COMPARTMENT

LOW VOLTAGE CABLE TERMINATIONS

GROUND PAD (TYP. OF 2)

CONCRETE TRANSFORMER PAD

FINISHED GRADE

SECONDARY CIRCUITS

SEE ONE-LINE DIAGRAM FOR SIZING ON E-701

GROUND ROD (TYP.)

COPPER GROUNDING CONDUCTORS

#4/0 BSDC

CONCRETE PAD MIN. 18" BELOW FINISHED GRADE

#4/0 BARE COPPER GROUND LOOP ENCIRCLING

2'-0" (MIN.)

NOTES:

PRESSURE VACUUM GAUGE

PRESSURE RELIEF

LIQUID LEVEL GAUGE

DIAL TYPE THERMOMETER

LOW VOLTAGE BUSHING

2 HOLE LONG BARREL COMPRESSION LUGS

MAINTAIN ROOM TO ACCESS DRAIN VALVE

GROUNDING BUSHING IF METALLIC CONDUIT IS USED (TYP.)

TO GROUND LOOP

PVC COATED RGS PRIMARY CONDUIT

CONCRETE TRANSFORMER PAD

FINISHED GRADE

GROUNDING BUSHING (TYP.)

CONDUCTOR W/600V INSULATION

GREEN GROUNDING

MEDIUM VOLTAGE CABLE

INSTALLED ON CONNECTOR PARKING STANDS

INSULATED STANDOFF BUSHING

LOAD BREAK FUSE HOLDER (TYP.)

PAD MOUNTED TRANSFORMER

GROUND PAD AND XO STRAP

LOAD BREAK SWITCH (TYP.)

TAP CHANGER

GROUND BAR

ES501

BREAK ELBOW (TYP.)

SURGE ARRESTER / LOAD

WITH COMBINATION

HIGH VOLTAGE BUSHING

PAD MOUNTED TRANSFORMER WITH COPPER WINDINGS

SECONDARY SERVICE ENTRANCE DUCTBANK TO "MDP" DETAIL

SPARE 4" CONDUITS

AND FOR ELBOWS, PVC SCHEDULE 80 TO BUILDING.

PVC COATED RGS SERVICE CONDUITS ABOVE GRADE

SIDE FOR FUTURE EXTENSION.

1. PROVIDE SPARE CONDUITS FOR BOTH PRIMARY AND SECONDARY

4 4

ES502

(M

IN

IM

U M

(M

IN

NOT TO SCALE

NOTES:

#4 REBAR

2" ROCK SCREEN

UNDERGROUND DEVICES #4W30-2.

DUCT SPACERS 5'-0" O.C.

CONCRETE ENCASEMENT

24" O.C. (TYPICAL)

#4 REBAR HOOP

(TYPICAL)

#4 REBAR CONTINUOUS

DUCT TIE-DOWN

EPC-40-PVC

MARKER TAPE

TO COMPENSATE FOR SETTLING.

MATCH ADJACENT AREAS. MOUND

TOP SOIL-PLANT WITH GRASSES TO

S

A N

D

(M

IN

COMMUNICATION DUCTBANK DETAIL

LOAD BREAK CONNECTOR

WITH 8.4 KV MCOV RATING

10 KV ELBOW TYPE SURGE ARRESTOR

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

REQUIREMENTS)

FOR ADDITIONAL

SPECIFICATIONS

(REFERENCE

LOOSE LIFTS

ASTM D-1557 8"

UNPAVED: 85%

GENERAL FILL

(M

IN

IM

U M

MARKER TAPE

FOR ADDITIONAL REQUIREMENTS)

(REFERENCE SPECIFICATIONS

85% ASTM D-1557 8" LOOSE LIFTS

GENERAL FILL UNPAVED:

TO COMPENSATE FOR SETTLING.

MATCH ADJACENT AREAS. MOUND

TOP SOIL-PLANT WITH GRASSES TO

UNDERGROUND DEVICES #4W30-2.

DUCT SPACERS 5'-0" O.C.

CONCRETE ENCASEMENT

24" O.C. (TYPICAL)

#4 REBAR HOOP

(TYPICAL)

#4 REBAR CONTINUOUS

DUCT TIE-DOWN

EPC-40-PVC

#4 REBAR

2" ROCK SCREEN

4 4 4

4 4 4

44 4

(M

IN

3. REINFORCING ONLY REQUIRED WHERE DUCT BANK CROSSES PAVED AREAS.

CONCRETE SHALL BE 3000 PSI AT 28 DAYS.

2. PROVIDE 3" MINIMUM COVER ALL SIDES FOR ALL CONCRETE ENCASEMENT.

ENTRANCE DUCTS".

1. TAPE COLOR SHALL BE RED. TAPE TEXT SHALL BE "ELECTRICAL SERVICE

S

A N

D

(M

IN

3. REINFORCING ONLY REQUIRED WHERE DUCT BANK CROSSES PAVED AREAS.

CONCRETE SHALL BE 3000 PSI AT 28 DAYS.

2. PROVIDE 3" MINIMUM COVER ALL SIDES FOR ALL CONCRETE ENCASEMENT.

1. TAPE COLOR SHALL BE ORANGE. TAPE TEXT SHALL BE "COMMUNICATION DUCTS".

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

ES701

ES701

KEYED NOTES

600A

NC

600A

MH-B12-15

600A

NC

600A

NC

NC

200A

NC

200A

MH-B12-13

1 2

SW-7S-30

MH-B12-14

BARRACKS 'B'

4400 AIT

SW-7S-24

600A

NC

600A

NC

NO

600A

NC

600A

MH-B12-20

MH-B12-21

200A

NC

600A

NC

NO

200A

NC

600A

1 2

1 2

480/277V Y

1000 KVA

13.2 DELTA

600A

NC

600A

NC

NO

200A

NF

NO

200A

1 2

MH-B12-22

SW-7S-25

SW 7S-26

MH-B12-23

600A

NC

200A

NC

NO

200A

NO

600A

1 2

600A

NC

600A

NC

10AF

NC

200A

NF

NO

200A

MH-B12-19

1 2

NO

600A

SW-7S-29

'A'

4400 AIT BARRACKS

NC

600A

NC

WORK

FUTURE

WORK

FUTURE

WORK

FUTURE

SW-7S-27

70MH-B12-12

MH-B12-18

FROM MH-B12-24

480/277V Y

1500 KVA

13.2 DELTA

BARRACKS 'C'

NEW AIT

BARRACKS 'D'

NEW AIT

E L E

C T

R

IC

A L S

IT

E O

N E L

E

IA

G R

A M

ELECTRICAL SITE ONE LINE DIAGRAM

480/277V Y

1500 KVA

13.2 DELTA

480/277V Y

1000 KVA

13.2 DELTA

SW-7S-28

150A

150A

MH-B12-15

IN LIGHTER SHADE ARE EXISTING.

SWITCHES, MANHOLES, CONDUTS AND CABLES SHOWN1.

MH-B12-16

CONDUITS AND CONDUCTORS.

REFER TO PLAN ES101 AND ES104 FOR SECONDARY3

TRANSFORMER.

MANHOLE MH-B12-14 TO NEW PAD MOUNTED

LLDPE OUTER JACKET FROM SW-7S-30 THROUGH

RATED MV-105 WITH 133% EPR INSULATION AND

(3) #2 AWG 15KV CONCENTRIC NEUTRAL CABLES

NEW PAD MOUNTED TRANSRFORMER. PROVIDE

EXTEND 2 - 5" CONCRETE ENCASED DUCTS TO2

WITH PULL ROPE.

INSULATION AND LLDPE OUTER JACKET, 1 SPARE

NEUTRAL CABLES RATED MV-105 WITH 133% EPR

1 CONTAINING (3) #2AWG 15KV CONCENTRIC

SW-7S-27 TO NEW PAD MOUNTED TRANSFORMER,

PROVIDE 2 - 5" CONCRETE ENCASED DUCTS FROM1

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

F S

A B E

S .D

U

L S

A

O K

E

A S

T

S

T S

T

T U

L S

A D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

D R

A W

N B

Y

C H

E C

K E

D B

Y

S U

B M

IT

T E

D B

Y

C S

T R

U N

K P .E S .E

S

IZ

E

A N

S I

D

IS

S

U E D

A T

E

S O

L

IC

IT

A T

IO

N N

O

C O

N T

R A

C T N

O

W

B V

R

T B

D

C A

T E

G O

R Y C

O D

E of Engineers ® US Army Corps

A

D E

S

IG

N E

D B

Y

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

P N

(A

IT

C O

M P

L E

X P

H A

S E

A D

V A

N C

E D I

N D

IV

ID

U A

L T

R A

IN

E E B

A R

R A

C K

S

F O

R T S

IL

L L

A W

T O

N

O K

L A

H O

M A

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

100% DESIGN - NOT FOR CONSTRUCTION

J

U N

E

ES702

ES702

GENERAL NOTES KEYED NOTES

O C

T

MH-109

E F

O C

T

MH-108

6W-4"

N6F4 (96STR)

T FO

(PHASE 1)

BARRACKS 'A'

ATI

12 STR

25 PR

N6C4-(1-25)

T E F O

C

4W-4"

MH-109A

FOC

T

FOC

T

FOC

T

FOC

T

6W-4"

N6C4-(51-75)

N6C4-(26-50)

N6C4-(1-25)

MH-109B

MH-109C

FOC

T

FOC

T

6W-4"

T FO

12 STR

25 PR

N6C4-(51-75)

T F O

C

6W-4"

FOC

T

FOC

T

FOC

T

6W-4"

N6C4-(326-350)

N6C4-(301-325)

N6C4-(276-300)

F O

C T

MH-108A

T FO (PHASE 1)

BARRACKS 'B'

ATI

12 STR

25 PR

300)

N6C4-(276-

4W-4"

6W-4"

FOC

T

FOC

T

MH-108B

T FO

12 STR

25 PR

350)

N6C4-(326-

T F O

C

4W-4"

N6C4-(1-600)

SWITCH NODE 6

CABLE DESIGNATION 4

FIRST COPPER PAIR NUMBER

ENDING COPPER PAIR NUMBER

N6F4-(1-144)

SWITCH NODE 6

FIBER DESIGNATION 4

FIRST FIBER NUMBER

ENDING FIBER DESIGNATOR

T

EFOC

FOC

T

FO

T

LEGEND:

NEW AIT BARRACKS 'C'

NEW AIT BARRACKS 'D'

EXISTING DUCT BANK

4W-4"

COMMUNICATIONS SITE ONE LINE DIAGRAM

EFOC EFOC

EFOC EFOC

O N

E L

IN

E D

IA

G R

A M

T E

L E

C O

M S

IT

EXISTING FIBER OPTIC CABLE.

COPPER TELEPHONE PAIR.

NEC.

FIBER OPTIC CABLE PROVIDED BY FORT SILL

NEC.

COPPER TELEPHONE PROVIDED BY FORT SILL

NEC.

CABLE SPLICE KIT PROVIDED BY FORT SILL

TERMINATION BY FORT SILL NEC.

FIBER OPTIC SERVICE ENTRANCE AND

TERMINATION BY FORT SILL NEC.

TELEPHONESERVICE ENTRANCE AND

AND TEST. (NIC)

WILL PROVIDE CABLES, WILL SPLICE AND TERMINATE

SHADE ARE EXISTING TO REMAIN. FORT SILL NEC

CABLES AND SPLICE KITS SHOWN IN LIGHTER2.

ARCHITECTURE (I3A) DATED FEB 2010.

INSTALLATION INFORMATION INFRASTRUCTURE

ACCORDANCE WITH THE TECHNICAL CRITERIA FOR

ALL OSP COMMUNICATION WORK SHALL BE IN1.

CABLES FROM MANHOLE MH-109 TO EACH FACILITY.

PROVIDE 25 PAIR COPPER AND 12 STRAND SMFO

SHALL HAVE PULL ROPES. FORT SILL NEC WILL

HAVE THREE (3) 1" INNER DUCTS AND THREE (3)

COMMUNICATION ROOMS. ONE CONDUIT SHALL

BANK FROM THE NEAREST MANHOLE TO

1 PROVIDE 4 WAY 4" CONCRETE ENCASED DUCT

MH-108C

S

K U

N A

P U

L I, P .E

C

V E

L O

Z

R

W A

T S

O N

F S

A B E

S .D

EG101

BUILD ID

P A

R T

IA

L R

O O

F L

IG

H T

N

IN

G P

R O

T E

C T

IO

N

P L

A N A

R E

A A

F O

R T S

IL

L A

R M

Y P

O S

T L

A W

T O

N

O K

L A

H O

M A

T U

L S

A D

IS

T R

IC

T

E N

G

IN

E E

R

IN

G

R

W A

T S

O N

C

V E

L O

Z

S

K U

N A

P U

L I P .E

T B

D

F

IL

E N

A M

E

A

IT

B

A R

R A

C K

S P

H A

S E I I

P N :0

F

Y

E

A S

T

S

T S

T

T U

L S

A

O K

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

1/8" = 1'-0"A

PARTIAL ROOF LIGHTNING PROTECTION PLAN - AREA A

PLAN

NORTHTRUE

NORTH

BLDG "D"

TRUE

NORTH

BLDG "C"

8'4' 16'0

SCALE: 1/8"=1'-0"

KEY PLAN

AREA A AREA BAREA C

AREA D

GENERAL NOTES KEYNOTES

ROD OR GROUND LOOP.

WHICH ENTER THE STRUCTURE TO THE NEAREST DOWN CONDUCTOR, GROUND

BOND ALL METALLIC PIPES INCLUDING WATER, FIRE, GAS, SEWER, STORM, ETC.9.

RIDGE-MOUNTED AIR TERMINALS SHALL BE PLACED ON 25'-0" MAXIMUM SPACING.

PERIMETER AND WITHIN 2'-0" OF OUTSIDE EDGE UNLESS OTHERWISE NOTED.

AND LOCATED INTERMEDIATELY ON 20'-0" MAXIMUM SPACING AROUND THE ROOF

AIR TERMINALS SHALL BE PLACED AT ALL UNPROTECTED OUTSIDE CORNERS8.

THAN 3'-0" MAXIMUM SPACING.

ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED NOT MORE7.

THE ARCHITECT AND ENGINEER OF RECORD FOR A RESOLUTION.

THIS WORK AND OTHER TRADES SHALL BE BROUGHT TO THE ATTENTION OF

ROOFING CONTRACTOR PRIOR TO INSTALLATION. DISCREPANCIES BETWEEN

COORDINATE THE LIGHTNING PROTECTION SYSTEM (LPS) INSTALLATION WITH6.

MINIMIZE APPEARANCE OF CONDUCTORS.

BUILDING FEATURES AND GUTTER DOWN SPOUTS WHERE POSSIBLE TO

PENETRATE ROOFING SYSTEMS. COURSE DOWN CONDUCTORS TIGHT TO

LIGHTNING PROTECTION SYSTEM AND DOWN CONDUCTORS SHALL NOT5.

SEE ARCHITECTURAL ROOF PLANS FOR ADDITIONAL BUILDING DETAILS.4.

BENEFICIAL OCCUPANCY.

BE PROVIDED TO THE GOVERNMENT NO LATER THAN 30 DAYS AFTER

THE COMPLETED SYSTEM SHALL BEAR THE UL MASTER LABEL, WHICH SHALL3.

SYSTEMS. ALL CONDUCTORS SHALL BE LABELED EVERY 10' WITH UL LISTING.

ALL SYSTEM MATERIALS SHALL BE UL LISTED FOR LIGHTNING PROTECTION2.

APPLICABLE STANDARDS AND SPECIFICATIONS.

SHALL DESIGN AND INSTALL THE LIGHTNING PROTECTION SYSTEM PER

ACCORDANCE WITH NFPA 780. LIGHTNING PROTECTION INSTALLER (LPI)

PROVIDE A FRANKLIN ROD TYPE LIGHTNING PROTECTION SYSTEM IN1.

CONNECT DOWN CONDUCTOR DIRECTLY TO GROUND RODS.

MATERIALS PER NFPA 780. TYPICAL FOR ALL BUILDING TERMINALS.

PROVIDE LIGHTNING AIR TERMINAL. AIR TERMINALS SHALL BE CLASS 1

PROVIDE CLASS 1 ALUMINUM LIGHTNING PROTECTION MAIN CONDUCTOR.

POSSIBLE.

CONDUCTOR SHALL BE ROUTED BEHIND OR BESIDE DOWN SPOUTS WHERE

ALUMINUM CONDUCTOR IN PVC CONDUIT PAINTED TO MATCH BUILDING.

PROVIDE LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR, CLASS 1

COPPER LEAD SHALL CONNECT DOWN TO GROUND RODS.

AND SHALL TRANSITION TO A COPPER LEAD VIA A BI-METALLIC CONNECTOR.

PROVIDE ALUMINUM DOWN CONDUCTORS, EXTEND TO 18" ABOVE GRADE

PROVIDE TEST WELL.

C H

R

IS

T O

P H

E R S

T R

U N

K P .E S .E

C H

IE

F

M

IL

IT

A R

Y D

E S

IG

N S

E C

T

IO

N

100% DESIGN - NOT FOR CONSTRUCTION

S O

L

IC

IT

A T

IO

N N

O

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

A

M A

R K

S

IZ

E

S U

B M

IT

T E

D B

Y

D A

T E

C O

N T

R A

C T N

O

C H

E C

K E

D B

Y

D R

A W

N B

Y

IS

S

U E D

A T

E

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

SHEET ID

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

US Army Corps of Engineers

W

B V

R

A N

S I

D

M A

T C

H L

IN

E R

E F

E R T

O E

G F

O R C

O N

T

IN

U A

T

IO

N

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

PROTECTION SYSTEM.

OR BONDED METAL BODY SHALL BE INTERCONNECTED TO THE LIGHTNING

LOUVERS, AND DOOR FRAMES SITUATED WITHIN 6' OF A LIGHTNING CONDUCTOR

FLASHING, GRAVEL STOPS, ROOF DRAINS, SOIL PIPE VENTS, INSULATION VENTS,

METAL BODIES OF INDUCTANCE LOCATED ABOUT THE ROOF SUCH AS: METAL15.

GRADE AND A MINIMUM OF 5' AWAY FROM BUILDING FOUNDATION.

PROVIDE 4/0 STRANDED COPPER BURIED AT A DEPTH OF 30" BELOW FINISHED14.

ALUMINUM CONDUCTORS SHALL BE CLASS 1 MATERIALS PER NFPA 780.13.

CONSTRUCTION.

LICENSED PROFESSIONAL ENGINEER QUALIFIED TO PERFORM THE DESIGN FOR

PROVIDE AS BUILT LIGHTNING PROTECTION DRAWINGS CERTIFIED BY A12.

BE FURNISHED AND INSTALLED.

ALL CONDUIT, CONDUIT FASTENERS AND MISCELLANEOUS ACCESSORIES SHALL11.

ENGINEER.

TERMINAL AND GROUND ROD LOCATIONS WITH FINAL APPROVAL FROM THE

ACTUAL JOB-SITE CONDITIONS MAY NECESSITATE SLIGHT ALTERATIONS IN AIR10.

J

U N

E

F S

A B E

G .D

EG102

P A

R T

IA

L R

O O

F L

IG

H T

N

IN

G P

R O

T E

C T

IO

N

P L

A N A

R E

A B

F O

R T S

IL

L A

R M

Y P

O S

T L

A W

T O

N

O K

L A

H O

M A

T U

L S

A D

IS

T R

IC

T

E N

G

IN

E E

R

IN

G

R

W A

T S

O N

C

V E

L O

Z

S

K U

N A

P U

L I P .E

T B

D

F

IL

E N

A M

E

A

IT

B

A R

R A

C K

S P

H A

S E I I

P N :0

F

Y

E

A S

T

S

T S

T

T U

L S

A

O K

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

1/8" = 1'-0"B

PARTIAL ROOF LIGHTNING PROTECTION PLAN - AREA B

KEY PLAN

AREA A AREA BAREA C

AREA D

PLAN

NORTHTRUE

NORTH

BLDG "D"

TRUE

NORTH

BLDG "C"

8'4' 16'0

SCALE: 1/8"=1'-0"

GENERAL NOTES KEYNOTES

ROD OR GROUND LOOP.

WHICH ENTER THE STRUCTURE TO THE NEAREST DOWN CONDUCTOR, GROUND

BOND ALL METALLIC PIPES INCLUDING WATER, FIRE, GAS, SEWER, STORM, ETC.9.

RIDGE-MOUNTED AIR TERMINALS SHALL BE PLACED ON 25'-0" MAXIMUM SPACING.

PERIMETER AND WITHIN 2'-0" OF OUTSIDE EDGE UNLESS OTHERWISE NOTED.

AND LOCATED INTERMEDIATELY ON 20'-0" MAXIMUM SPACING AROUND THE ROOF

AIR TERMINALS SHALL BE PLACED AT ALL UNPROTECTED OUTSIDE CORNERS8.

THAN 3'-0" MAXIMUM SPACING.

ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED NOT MORE7.

THE ARCHITECT AND ENGINEER OF RECORD FOR A RESOLUTION.

THIS WORK AND OTHER TRADES SHALL BE BROUGHT TO THE ATTENTION OF

ROOFING CONTRACTOR PRIOR TO INSTALLATION. DISCREPANCIES BETWEEN

COORDINATE THE LIGHTNING PROTECTION SYSTEM (LPS) INSTALLATION WITH6.

MINIMIZE APPEARANCE OF CONDUCTORS.

BUILDING FEATURES AND GUTTER DOWN SPOUTS WHERE POSSIBLE TO

PENETRATE ROOFING SYSTEMS. COURSE DOWN CONDUCTORS TIGHT TO

LIGHTNING PROTECTION SYSTEM AND DOWN CONDUCTORS SHALL NOT5.

SEE ARCHITECTURAL ROOF PLANS FOR ADDITIONAL BUILDING DETAILS.4.

BENEFICIAL OCCUPANCY.

BE PROVIDED TO THE GOVERNMENT NO LATER THAN 30 DAYS AFTER

THE COMPLETED SYSTEM SHALL BEAR THE UL MASTER LABEL, WHICH SHALL3.

SYSTEMS. ALL CONDUCTORS SHALL BE LABELED EVERY 10' WITH UL LISTING.

ALL SYSTEM MATERIALS SHALL BE UL LISTED FOR LIGHTNING PROTECTION2.

APPLICABLE STANDARDS AND SPECIFICATIONS.

SHALL DESIGN AND INSTALL THE LIGHTNING PROTECTION SYSTEM PER

ACCORDANCE WITH NFPA 780. LIGHTNING PROTECTION INSTALLER (LPI)

PROVIDE A FRANKLIN ROD TYPE LIGHTNING PROTECTION SYSTEM IN1.

CONNECT DOWN CONDUCTOR DIRECTLY TO GROUND RODS.

MATERIALS…