FRCC BCC Lighting Upgrade Qs & As RFP #FRCC-15-21-B.docx
DOCX document 12 KB Posted
- Solicitation number
- RFP GJEA 2015000158 4
- Issued by
- Boulder County, Weston CDP, Colorado
About this file
This is a Questions and Answers document for Request for Proposal #FRCC-15-21-B issued by Front Range Community College for a lighting upgrade project at its Boulder County Campus (BCC). The document, dated March 12, 2015, addresses clarifications regarding the scope of work for the facility lighting upgrade. Key questions addressed include the specification of emergency tube lighting fixtures and the application of occupancy sensors throughout the campus. The RFP requires bidders to understand that existing emergency tube lighting fixtures are currently wired for 24/7 operation without battery backup systems, and that occupancy sensors will only be added to rooms where they are indicated with a "yes" designation in the project documentation.
The document provides technical clarification essential for accurate bid preparation but does not specify pricing terms, contract duration, award dates, or funding sources. No information regarding set-asides, incumbent contractors, or specific budget allocations is contained in this questions and answers document. Interested parties should refer to the primary RFP documentation for complete project specifications, submission deadlines, evaluation criteria, and contract terms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pre-bid attendee list.pdf | ||
| Update to Pre-Submission Meeting FRCC-15-21-Bdocx.docx | DOCX document | |
| RFP FRCC-15-21-B.doc | DOC document | |
| Mod 1 RFP FRCC-15-21-B.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FRONT RANGE COMMUNITY COLLEGE
Boulder County Campus (BCC) Faculties
RFP #FRCC-15-21-B
Lighting Upgrade Boulder County Campus Questions and Answers March 12, 2015 Question 1: The drawings show Emergency Tube Lighting fixtures. Are these fixtures simply wired on an EM circuit (24 hours on) or are they equipped with emergency battery backup ballasts that would need to be replaced to match the replacement lamps.
Answer 1: At present the tube fixtures are wired for 24/7; no battery backup.
Question 2: Regarding adding occupancy sensors, in the list of room if it is noted Yes under occupancy sensor heading, does that indicate we need add the occupancy sensor?
Just want to clarify which rooms we will need to add them.
Answer 2: The ‘yes’ means there is an occupy sensor in the room, the ‘no’ means no occupy sensor.
End