Forest Hills Nature Center - Bid Set - Electrical.pdf
PDF 18 MB Posted
- Attached to
- Forest Hill Nature Center - New Building
- Solicitation number
- RFP GIR 260000001926 3
- Issued by
- Ingham County, Michigan
About this file
This is an electrical bid set for the Forest Hills Nature Center New Building project located at 1297 N Rich Road, Alma, Michigan 48801, in Seville Township, Gratiot County. The project encompasses comprehensive electrical design and installation for a new nature center facility, including two construction phases. The electrical work includes lighting design with multiple fixture types (recessed troffers, linear suspended fixtures, surface-mounted linear fixtures, emergency lighting, exterior wallpacks, and LED track lighting), power distribution systems, mechanical equipment connections, fire alarm systems, security and card access systems, occupancy sensors, lighting controls, and emergency generator installation. The design specifies a 230KW/287KVA generator, new utility transformer, 800-amp main distribution panel with automatic transfer switch capability, and distributed sub-panels throughout the facility. All work must comply with the National Electrical Code, Michigan Energy Code, and ASHRAE 90.1 2019 standards.
The electrical specifications require all conductors to be copper with 12 AWG minimum for lighting and power circuits, 14 AWG minimum for control conductors, dedicated neutrals for all circuits, and equipment grounding conductors throughout. Lighting controls include fixture-integrated occupancy sensors, daylight harvesting per ASHRAE requirements, dimming capabilities, and zone-based controls with touchscreen controllers in the main hall. The project requires split-controlled receptacles with wireless power packs in offices and breakrooms, all receptacles in the garage area mounted at 48 inches above finished floor, and tamper-resistant receptacles where required by code. GFCI protection is specified for wet areas and required locations. All exterior lighting must be controlled via photocell, and emergency lighting circuits require handle lock-on breakers. The design basis assumes complete electrical system installation per code requirements with coordination among electrical, architectural, structural, and mechanical trades.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCPS
V
M C
VI
AV
B
C
DC
M
B
KP
SSCP
CR
SS
AS
TS
G
NCC
M P
E
A L B1 B2
S
SRS
X
X
X
CB
EMERGENCY PUSH STATION
CODE BLUE STATION
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVE
GLASS BREAK
DS
DUPLEX RECEPTACLE
TEACHER STATION
ADMINISTRATION STATION
STUDENT STATION
CARD READER
CO CARBON MONOXIDE DETECTOR
H
DOCK LIGHT FIXTURE
CONTROL MODULE
S
TELEPHONE / DATA OUTLET
DUTY STATION
STAFF STATION
STAFF REGISTER STATION
DOME LIGHT
DUAL BED STATION
SINGLE BED STATION
BED / LIGHT INTERFACE
PENDENT INTERFACE
EMERGENCY PULL STATION
MASTER STATION
NURSE CALL CONTROLLER
NURSE CALL
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
BELL
AUDIO / VIDEO INPUT
VIDEO INPUT
WALL MOUNTED SPEAKER / CLOCK COMBO
WALL MOUNTED SPEAKERS
DUAL FACE CLOCK
CCTV CONTROL PANELCCTV
SECURITY SYSTEM CONTROL PANEL
KEY PAD
BEAM DETECTOR
MOTION DETECTOR
DOOR CONTACT
CAMERA
MONITOR MODULE
FIRE CONTROL POWER SUPPLY
VISUAL ONLY UNIT
ELECTRICAL SYMBOLS LEGEND
DH
V
S
C
M
I
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SINGLE FACE CLOCK
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SOUND and SIGNAL
INTERCOM OUTLET
MICROPHONE OUTLET
TELEVISION OUTLET
CHIME
BUZZER
VOLUME CONTROL
SPEAKER
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
FUSED DISCONNECT SWITCH
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
FIRE ALARM
TAMPER SWITCH (furnished by FP/C) FLOW SWITCH (furnished by FP/C)
FIREFIGHTER COMMUNICATION JACK
MAGNETIC DOOR HOLDER
REMOTE INDICATING LIGHT, CLG. MTD.
REMOTE INDICATING LIGHT, WALL MTD.
END OF LINE DEVICE
ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
PULL STATION
SPEAKER & LIGHT
SPEAKER
HORN
DUCT SMOKE DETECTOR
HEAT DETECTOR
SMOKE DETECTOR
HORN & LIGHT
DESIGNATIONS
(by E.C.)
(by others)
TT
FACP
ANN
EOL
G
WW
PC
CT
TS
T
H
TC
IC
F
FC
F
T
1,3
OR
PM
WM
BD
UFD
B
F S
J
J
D
WH
PP
J
SWITCH STYLE OCCUPANCY SENSOROC
DIGITAL TIME SWITCH
POWER PACK
DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT
DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
OCCUPANCY SENSOR / PHOTOCELL
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
DUCT SMOKE DETECTORF/S
CEILING MOUNTED WIFI
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERRUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST./EX.
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
4' SURFACE MOUNTED LINEAR FIXTURE.
FIXTURE
MOUNTING
HEIGHT
LIGHT ENGINEDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.
LIGHTING FIXTURE SCHEDULE
LITHONIA
ELITE
OR EQUAL
CLX-L48-3000LM-HEF-FDL-MVOLT-GZ10-40K-80CRI
OEC4-LED-3000L/4000L/5000L-DIM10-MVOLT-25K/40K/50K-85
SL2L-XXFT-FLP-80CRI-40K-400LMF-MIN1-MVOLT-NLTAIR2-API
EV1D-A-HE-840-XX-G1-U-FSD-1-W
LDN6-40/10-LO6-MVOLT-GZ1
6DR-L10-8-40-DIM-UNV-O-M-CS
LITHONIA
H.E. WILLIAMS
OR EQUAL
LG
LD
LA
RECESSED LINEAR FIXTURE WITH INTEGRATED OCCUPANCY SENSORS. COORDINATE
FIXTURE RUN LENGTH WITH FLOORPLAN.
6" LED DOWNLIGHT
SURFACE
MOUNTED
3000 LUMENS
25W, 4000K
LED
RECCESSED
1000 LUMENS
9W, 4000K
LED
RECESSED
DIMMING INFO
S2PID-XXFT-MSL8-80CRI-40K-400LMF-I80CRI-140K-I300LMF-MIN1
-FLL-MVOLT-NLTAIR2-APIR-SAPIR
EX2DI-A-HE-840-840-XX-ACXJB-U-OL5-1-W-SNSLM
SUSPENDED LINEAR FIXTURE WITH DIRECT/INDIRECT LIGHTING AND INTEGRATED
SENSORS. COORDINATE FIXTURE RUN LENGTH WITH FLOORPLAN. PROVIDE REQUIRED
SUSPENSION MOUNTING HARDWARE.
700LUMENS/FT
5.1W/FT, 4000K
LED
LC 8'-6" AFF0-10V
400LUMENS/FT
3.14W/FT, 4000K
LED
0-10V
0-10V
4' SURFACE MOUNTED LINEAR FIXTURE WITH 10W EMERGENCY BATTERY PACK.
LITHONIA
ELITE
OR EQUAL
CLX-L48-3000LM-HEF-FDL-MVOLT-GZ10-40K-80CRI-E10W
OEC4-LED-3000L/4000L/5000L-DIM10-MVOLT-25K/40K/50K-85-
O-EMG-LED
LAEM SURFACE
MOUNTED
3000 LUMENS
25W, 4000K
LED
S2PID-XXFT-MSL4-80CRI-40K-600LMF-I80CRI-I40K-I300LMF-MIN1
-FLL-MVOLT-1E10WLCP-NLTAIR2-APIR-SAPIR
EX2DI-A-HE-840HO-840-XX-ACXJB-U-OL5-1-W-FSB-SNSLM
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
LBEM
4' SUSPENDED LINEAR FIXTURE WITH DIRECT/INDIRECT LIGHTING, INTEGRATED
SENSORS, AND 10W EMERGENCY BATTERY PACK. PROVIDE REQUIRED SUSPENSION
MOUNTING HARDWARE.
0-10V
900LUMENS/FT
6.6W/FT, 4000K
LED
S2PID-XXFT-MSL4-80CRI-40K-400LMF-I80CRI-140K-I300LMF-MIN1
-FLL-MVOLT-1E10WLCP-NLTAIR2-APIR-SAPIR
EX2DI-A-HE-840-840-XX-ACXJB-U-OL5-1-W-FSB-SNSLM
4' SUSPENDED LINEAR FIXTURE WITH DIRECT/INDIRECT LIGHTING, INTEGRATED SENSORS
AND 10W EMERGENCY BATTERY PACK. PROVIDE REQUIRED SUSPENSION MOUNTING
HARDWARE.
700LUMENS/FT
5.1W/FT, 4000K
LED
LCEM 8'-6" AFF0-10V
SL2L-XXFT-FLP-80CRI-40K-400LMF-MIN1-MVOLT-NLTAIR2-API
-1E10WLCP
EV1D-A-HE-840-XX-G1-U-FSD-1-W-FSB
LDEM
4' RECESSED LINEAR FIXTURE WITH INTEGRATED SENSORS AND 10W EMERGENCY
BATTERY PACK.
400LUMENS/FT
3.14W/FT, 4000K
LED
0-10V
LE
RECESSED 2X4 TROFFER WITH INTEGRATED SENSORS
3000 LUMENS
21W, 4000K
LED
0-10V
LATSM2-A-120-L07-40K-CR90-MFR
HORNET-HP-11-WT-TN1-120-WF-409-LE/TE
LUMENPULSE
AMERLUX
OR EQUAL
LH
LED TRACK LIGHTING
700 LUMENS
7W, 4000K
LED
SURFACE0-10V
WHSPR-LCTR-2X4-80CRI-40K-3000LM-MIN1-MVOLT-SWC-
NLTAIR2-PIR
TR24-W-G9-U-OL2-1-W
RECCESSED
RECCESSED
REFER TO
FLOOR PLAN
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
S2PID-60FT-MSL8-80CRI-40K-600LMF-I80CRI-I40K-I300LMF-MIN1
-FLL-MVOLT-NLTAIR2-APIR-SAPIR
EX2DI-A-HE-840HO-840-60-ACXJB-U-OL5-1-W-SNSLM
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
LB60
60' SUSPENDED LINEAR FIXTURE WITH DIRECT/INDIRECT LIGHTING AND INTEGRATED
SENSORS. PROVIDE REQUIRED SUSPENSION MOUNTING HARDWARE.
REFER TO
FLOOR PLAN0-10V
42000LUMENS
396W, 4000K
LED
VIAWETS-D-PYC-HLO-SW-90CRI-500LMF-27K-4FT-UNV-D1
EX3-WET-N-827-XX-BOR-S-U-FSD-1
LUMENWERX
PINNACLE
OR EQUAL
LI
SURFACE MOUNTED WET RATED FIXTURE
2000 LUMENS
23W, 2700K
LED
SURFACE0-10V
WDGE2-LED-P2-40K-80CRI-TFTM-MVOLT
MUR-SA-CL
LITHONIA
BEGHELLI
OR EQUAL
LJ
EXTERIOR WALLPACK
2000 LUMENS
18W, 4000K
LED
BUILDING
MOUNTED0-10V
LF
4' SURFACE MOUNTED LINEAR FIXTURE WITH INTEGRATED OCCUPANCY SENSORS.
600LUMENS/FT
4.7W/FT, 4000K
LED
0-10V
S2SD-LLP-XXFT-80CRI-40K-600LMF-SCT-MIN1-FLL-MVOLT-
NLTAIR2-APIR
EV1D-A-HE-840HO-XX-G1-U-FSD-1-W-FSB
SURFACE
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
LFEM
4' SURFACE MOUNTED LINEAR FIXTURE WITH INTEGRATED OCCUPANCY SENSORS AND
10W EMERGENCY BATTERY PACK.
0-10V
S2SD-LLP-XXFT-80CRI-40K-400LMF-SCT-MIN1-FLL-MVOLT-
E10WLCP-NLTAIR2-APIR
EV1D-A-HE-840HO-XX-G1-U-FSD-1-W-FSB
SURFACE
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
600LUMENS/FT
4.7W/FT, 4000K
LED
LQM-S-3-G-MVOLT-EL-HO
EPX-SA-ATG-B
LITHONIA
BEGHELLI
OR EQUAL
XA
LED EXIT SIGN WITH BLACK FACE AND GREEN LETTERING
LEDUNIVERSAL0-10V
AIP AI PHONE
LEEM
RECESSED 2X4 TROFFER WITH INTEGRATED SENSORS AND 10W EMERGENCY BATTERY
PACK.
3000 LUMENS
21W, 4000K
LED
0-10V
WHSPR-LCTR-2X4-80CRI-40K-3000LM-MIN1-MVOLT-SWC-E10W
NLTAIR2-PIR
TR24-W-G9-U-OL2-1-FSB-W
RECCESSED
MARK ARCHITECTURAL
PINNACLE
OR EQUAL
ERE-GY-T-SQ-WP
PR2-WP
LITHONIA
PACO
OR EQUAL
XB
LED BATTERY POWERED EXTERIOR EM LIGHTING
LEDUNIVERSAL0-10V
CSVT-L48-4000LM-MVOLT-40K-80CRI
STPH2-4-52LC-U-CC-C1
LITHONIA
BEGHELLI
OR EQUAL
LK
WALL MOUNTED STRIP LIGHT
4000 LUMENS
34W, 4000K
LED
WALL MOUNTED0-10V
0-10V
0-10V
GENERAL ELECTRICAL NOTES:
1. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ACCEPTED EDITION OF THE NATIONAL
ELECTRICAL CODE, NEC, AND ALL STATE AND LOCAL CODES.
2. COORDINATE THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT AND CONNECTIONS WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND EQUIPMENT DRAWINGS.
3. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL POWER, CONDUITS, CABLETRAY, AND OTHER COMPONENTS AS SHOWN ON THE EQUIPMENT PROVIDER DRAWINGS FOR INSTALLATION OF SYSTEM.
4. "BACK TO BACK" OR THROUGH THE WALL BOXES SHALL NOT BE USED.
5. INSTALL HANDLE LOCK-ON, ON ALL CIRCUIT BREAKERS CONTROLLING NIGHT LIGHT, EMERGENCY LIGHT AND EXIT
LIGHT CIRCUITS.
6. ALL RECEPTACLES SHALL BE HARD USE, SPECIFICATION GRADE.
7. PROVIDE TAMPER RESISTANT RECEPTACLES WHERE REQUIRED BY APPLICABLE CODES.
8. RECEPTACLES INDICATED AS GROUND FAULT CIRCUIT INTERRUPTER TYPE SHALL BE MOUNTED IN AN ACCESIBLE
LOCATION, PER CODE OR PROVIDED WITH A GFCI BREAKER.
9. ALL CONDUCTORS SHALL BE COPPER. ALUMINUM WIRES SHALL NOT BE USED.
10. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR POWER FEEDS AND 1" FOR DATA FEEDS.
11. FINAL CONNECTION TO ITEMS SUBJECT TO VIBRATION SHALL BE MADE WITH LIQUIDTIGHT FLEXIBLE METALLIC
CONDUIT.
12. 120/208VAC CIRCUIT WIRING FOR ANY ROOM OR AREA MAY BE GROUPED INTO RACEWAYS UNLESS SEPARATE RACEWAYS ARE REQUIRED BY THE NEC. COMPLY WITH NEC REQUIREMENTS FOR CONDUCTOR DERATING.
13. PROVIDE EQUIPMENT GROUNDING CONDUCTORS FOR ALL POWER AND LIGHTING CIRCUITS.
14. ALL LIGHTING AND POWER CONDUCTORS SHALL BE 12 AWG MINIMUM. ALL CONTROL CONDUCTORS SHALL BE
14 AWG MINIMUM OR AS SPECIFIED BY MANUFACTURER.
15. DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL CIRCUITS. SHARED NEUTRALS ARE NOT ALLOWED.
16. BASIS OF DESIGN IS FOR A COMPLETE ELECTRICAL SYSTEM, INSTALLED PER CODE REQUIREMENTS.
17. PROVIDE AN UNSWITCHED HOT TO ALL EMERGENCY BATTERY PACKS, LIGHTING INVERTERS AND EMERGENCY LIGHTING UNITS AHEAD OF AN LIGHTING CONTROLS FROM THE BRANCH CIRCUIT SERVING LIGHTING IN THE
SURROUNDING AREA.
18. ALL RECEPTACLES IN GARAGE AREA SHALL BE MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-100
OC
O C
LA LAEM LA
LA LAEM LA
LB60
12'-8"
AFF
LF
LF
LF
LCLCLC
LC LC LC LC LC LC
LA
LC
LG
LG LGLK LK LK LK
LK LK
D D
D
MAIN HALL
VESTIBULE
ENTRY HALL
OFFICE
OFFICE
LAUNDRY
106 TOILET
STORAGE
109 MECHANICAL
MEN
WOMEN
JANITOR
MECHANICAL
CLASSROOM
CLASSROOM
CLASSROOM
HALL
LG
LG LG LG
PC
LBEM
LBEM
LBEM
LFEMLCEM
LCEM
LCEM
LCEM
LCEM
LCEM
LE
LCEM
LA
LAEM LA
LEEMLELEEMLEEM
D D
LH
LH
LH
LH
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-1
MP1-2
MP1-2
MP1-2
MP1-2
MP1-2
LB60
12'-8" AFF
LB60
12'-8" AFF
MP1-3
MP1-3
MP1-3MP1-3MP1-3 MP1-3 MP1-3
MP1-3
MP1-3
MP1-5
MP1-5
OC
OC
D
PANEL MP1
PANEL MDP
XA
XA XA
XA
XA
TO EM
LIGHTING
XA
XA
TO EM
LIGHTING
XA XA
XA XA
3 3
LILILI
LI
LILI
LILI
D
D
OC
MP1-3
LJ
MP1-1
LI
LI
3 3
MP1-5
TO EM
LIGHTING
LEEM
LFLFEM
XA
LE
LE
LE
LE
LEEM
LEEM
LE
LE
LE
LEEM
LEEM
LE LEEM
LE LEEM
LE LEEM
LE LE
MP1-1
LE
LE
LE LE
LEEM
LE
XA
XB
XB
XB
XB
XB
XB
XB
LIGHTING
CONTROLLER
ELECTRICAL KEY NOTES - PHASE 1
ALL EXTERIOR FIXTURES SHALL BE CONTROLLED VIA PHOTOCELL.
CONTRACTOR SHALL PROVIDE DAYLIGHT HARVESTING CONTROLS PER
ASHRAE CODE REQUIREMENTS IN SPECIFIED ROOMS.
COORDINATE FIXTURE MOUNTING LOCATION WITH MECHANICAL EQUIPMENT
IN THIS ROOM.
CONTRACTOR SHALL SURFACE MOUNT FIXTURES TO THE BOTTOM OF
EXPOSED TRUSSES IN THIS AREA.
CONTRACTOR SHALL PROVIDE AND INSTALL ACUITY TOUCHSCREEN
LIGHTING CONTROLLER nTS7IN-WH + PROGRAMMING OR APPROVED EQUAL
TO CONTROL LIGHTING IN THE MAIN HALL.
O C
O C
LC
LC
LC
LC
LC
LC
LDEM
LDEM
LG
LG
LK
LK
LK
LK
D D
LI
VESTIBULE
VESTIBULE
HALL
CLASSROOM
CLASSROOM
LI
LCEM
LCEM
LCLCEM LCEM
LDEM
LE
LEEM
MP1-4
MP1-4
MP1-4
MP1-4
MP1-4
MP1-4
MP1-4
LE
MP1-5
MP1-5
MP1-5
XA
XA
XA
LI
LI
LI
MP1-4
MP1-4
XA
TO EM
LIGHTING
XA
XA
XB
XB
XB
XB
XA
ELECTRICAL KEY NOTES - PHASE 2
ALL EXTERIOR FIXTURES SHALL BE CONTROLLED VIA PHOTOCELL. REFER
TO PHASE 1 DRAWINGS FOR PHOTOCELL LOCATION.
CONTRACTOR SHALL PROVIDE DAYLIGHT HARVESTING CONTROLS PER
ASHRAE CODE REQUIREMENTS IN SPECIFIED ROOMS.
COORDINATE FIXTURE MOUNTING LOCATION WITH MECHANICAL EQUIPMENT
IN THIS ROOM.
CONTRACTOR SHALL SURFACE MOUNT FIXTURES TO THE BOTTOM OF
EXPOSED TRUSSES IN THIS AREA.
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-400
N FLOOR PLAN - PHASE 1 - LIGHTING NEW
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N FLOOR PLAN - PHASE 2 - LIGHTING NEW
SCALE: 1/8" = 1'-0"
0 1 5 10 20
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-401
ELECTRICAL EMERGENCY PHOTOMETRICS
SCALE: N.T.S.
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I
E-402
Propane
CT
SE G
48" AFF
GFI
48" AFF
GFI
GFI
J
CHANGING
STATION
GFI
EWC
EWC
F
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
DRYER
48" AFF
GFI
48" AFF
GFI
GFI
HP-3
HP-2
HP-1
CT-1
18.2A-240V-1Ø
MAIN HALL
VESTIBULE
ENTRY HALL
STAFF
103OFFICE
OFFICE
LAUNDRY
TOILET
STORAGE
109 MECHANICAL
MEN
111 WOMEN
JANITOR
MECHANICAL
CLASSROOM
CLASSROOM
CLASSROOM
HALL
WP
GFI
F
GFI
WP
GFIGFI
GFI GFI
GFI
GFI
GFI
UTILITY
TRANSFORMER
MP1-6
MP1-6
MP1-6
MP1-7
MP1-7
MP1-7
MP1-7
MP1-8
MP1-8MP1-8
MP1-8
MP1-8
MP1-9MP1-10
MP1-10
MP1-10
MP1-11
MP1-11
MP1-12
MP1-12
MP1-12
MP1-12
MP1-13
MP1-14MP1-14MP1-14
MP1-14 MP1-14
MP1-15
MP1-16
MP1-14
MP1-17
MP1-17
MP1-18
MP1-18MP1-18
MP1-19MP1-19
MP1-22
MP1-22
MP1-23
MP1-23
MP1-24
MP1-24
MP1-24
MP1-25
MP-27,29
MP1-31
48" AFF
GFI
NEW
GENERATOR
HP-7
240V-1Ø, 14.3FLA
HP-5
240V-1Ø, 14.3FLA
HP-6
240V-1Ø, 14.3FLA
240V-1Ø, 29.4 FLA
240V-1Ø, 29.4 FLA
240V-1Ø, 17.5FLA
E-700
FENCE
PANEL MP2
240/120V-1Ø
MP2-3
UTILITY METER4
30A/2P N.F.
60A/2P N.F.
MDP-3MDP-4MDP-5
ERV-1
240V-1Ø, 20FLA
ERV-2
240V-1Ø, 6.6A
30A/2P N.F.
MDP-12
30A/2P N.F.
MDP-116
30A/2P N.F.
30A/2P N.F.
30A/2P N.F.
MDP-7MDP-8
MDP-9
J
J
J
J
MP1-26
MP1-28
MP1-30
MP1-32
J
J J
J
J
J
J
MP1-34
MP1-36
MP1-33
MP1-35
MP1-37 MP1-39
WP
GFI
MP2-5
J
J
WP
BATTERY CHARGER
8.3A-120V
BLOCK HEATER
20.8A-240V-1Ø
MP2-1
MP2-27
7 7
CR
CR
CR
CR
CR
CR
CR
CRCR
CR
CR
CR
CRCR
CR
CR CR
CRCR
CR
CR
AIP
MP1-38
F
FACP
S
F
F
F
V
V
F
F F
F F
F
S
SS S
CUH-1
240V-1Ø, 3kW
CUH-2
240V-1Ø, 3kW
MP1-41,43
MP1-40,42
CUH-3
240V-1Ø, 3kW
MP1-45,47
MP2-4
MP2-46
WP
GFI
MP1-22
MP1-24
WP
GFI
MP1-49 MP1-50
MP1-23
WP
GFI
MP1-10
GEN E-STOP
GFI
GP-1
240V-1Ø, 9FLA
GP-2
240V-1Ø, 9FLAMP2-8
MP2-7
HD
HD
CT9
MP1-51
WP
WP
48" AFF
GFI
WP
GFI
WP
GFI
WP
GFI HP-9
240V-1Ø, 14.3FLA
HP-8
240-1Ø, 14.3FLA
VESTIBULE
VESTIBULE
HALL
CLASSROOM
CLASSROOM
WP
GFI
MP1-20
MP1-21
MP1-22
MP1-22
MP1-22
MP1-23
MP1-23
MP1-18
MDP-10
MDP-14
30A/2P N.F.
30A/2P N.F.
CR
CR
CR
CR
CR
CR
S S
S
F
F F
F
S
WP
GFI
MP1-23
ERV-3
240V-1Ø, 7.7 MCA
30A/2P
ELECTRICAL KEY NOTES - PHASE 1
CONTRACTOR SHALL INSTALL SPECIFIED RECEPTACLES ABOVE
DECORATIVE STONE WAINSCOT.
COORDINATE FINAL LOCATION WITH LOCAL UTILITY COMPANY.
(3) #10, (1) #10 GND, (1) 3/4" CND.
COORDINATE MOUNTING HEIGHT AND LOCATION WITH DECORATIVE STONE
WAINSCOT.
GENERAL RECEPTACLES SHALL BE SWITCHED WITH LIGHTING. REFER TO
RECEPTACLE CONTROL DETAILS. PROVIDE POWERPACKS PER BRANCH
CIRCUIT IN BREAKROOMS, OFFICES, AND CLASSROOMS AS REQUIRED.
(2) #8, (1)#10 GND. (1) 3/4" CND.
(2) #10, (1) #10 GND, (1) 3/4" CND.
VERIFY EQUIPMENT LOCATIONS WITH OWNER PRIOR TO INSTALLATION.
ELECTRICAL KEY NOTES - PHASE 2
GENERAL RECEPTACLES SHALL BE SWITCHED WITH LIGHTING. REFER TO
RECEPTACLE CONTROL DETAILS. PROVIDE POWERPACKS PER BRANCH
CIRCUIT IN BREAKROOMS, OFFICES, AND CLASSROOMS AS REQUIRED.
CONTRACTOR SHALL INSTALL SPECIFIED RECEPTACLES ABOVE
DECORATIVE STONE WAINSCOT.
(2) #10, (1) #10 GND, (1) 3/4" CND.
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-500
N FLOOR PLAN - PHASE 1 - POWER NEW
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N FLOOR PLAN - PHASE 2 - POWER NEW
SCALE: 1/8" = 1'-0"
0 1 5 10 20
UTILITY CO.
FROM
UTILITY
C.T.
CABINET M
UTILITY CO.
PANEL
NEW
MP1
240/120V 1Ø,3W
400A/MLO
4" CND
COORDINATE
WITH UTILITY
2 SETS OF
(3) 600KCMIL
3" CND
(3) #600KCMIL
(1) #3 GND
3" CND
NEW UTILITY
TRANSFORMER
G
NEW GENERATOR
240/120V-1Ø, 3W
230KW/287KVA
REHLKO MODEL KD250
BATTERY CIRCUIT
BLOCK HEATER CIRCUIT
GENERATOR ANNUNCIATOR
WITH E-STOP PUSHBUTTON
TO IT RACK FOR
MONITORING
MP2-1
MP2-2
800A/2P 1Ø/3W
NEMA #1
FUSED
FLSR
800A
PANEL
NEW
MDP
240/120V 1Ø, 3W
800A/MLO
800A/2P
#3/0 REFER TO
GROUNDING
DETAIL
(1) 1" CONDUIT.
VERIFY EXACT QTY AND
SIZE/TYPE OF WIRE
REQUIRED
100% RATED
2 SETS OF
(3) 600KCMIL
3" CND
2 SETS OF
(3) 600KCMIL
(1) #1/0 GND
3" CND
800A/2P
AUTOMATIC
TRANSFER
SWITCH
PANEL
NEW
MP2
240/120V 1Ø, 3W
100A/MCB
(3) #2
(1) #8 GND
1-1/2" CND
2 SETS OF
(3) 600KCMIL
(1) #1/0 GND
3" CND
2 SETS OF
(3) 600KCMIL
(1) #1/0 GND
3" CND
MDP-ATS
TO EXISTING
GRANARY PANEL
(APPROX 230' AWAY)
(3) #1
(1) #6 GND
2" CND
SIZED FOR
VOLTAGE DROP
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-600
ELECTRICAL RISER DIAGRAM
SCALE: N.T.S.
GEN E-STOP
B-1 6A-120V
HP-4
240V-1Ø, 14.3FLA
GFI
GFI
MP1-18
MECHANICAL
PANEL MDP
240/120V, 1Ø
MDP
ATS
MP1-44
MP1-46
B-2 6A-120V
BOILER E-STOP
MDP-61
SE RATED
DISC
GENERATOR REMOTE
ANNUNCIATOR
PANEL MP1
240/120V, 1Ø
DWH-1
240V-1Ø, 4500W
MDP-13
30A/2P N.F.
30A/2P
GFI
GFU-1
P-4
1.5HP-240V-1Ø
P-3
1.5HP-240V-1Ø
P-1
2HP-240V-1Ø
P-2
2HP-240V-1Ø
MDP-15 MDP-16
MDP-18
MDP-17
GFIF
VFD
VFD
VFD
120V-1/2HP
H
ELECTRICAL KEY NOTES
(2) #10, (1) #10 GND, (1) 3/4" CND.
COORDINATE ATTIC ACCESS WITH CONDUITS/DUCTWORK/PIPING TO AVOID
CONFLICTS WITH THE ATTIC ACCESS PANEL.
CONTRACTOR SHALL PROVIDE APPROVED FIRE STOPPING MATERIALS AT
ALL WALL PENETRATIONS OF MECHANICAL ROOMS.
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I X
E-700
N
ENLARGED FLOOR PLAN
MECHANICAL ROOM
POWER1
E-700
SCALE: 1/4" = 1'-0"
0 1 5 10
SERVICE
EQUIPMENT NEUTRAL
REFER TO E-600
FOR WIRE SIZING
SIZE PER NEC
(3)5/8" X 8'-0"
GROUND RODS, 10'
O.C.
BONDING JUMPER
IT RACK
#6 AWG
CU MIN.
GROUND BUS
MAKE GROUNDING CONNECTION
WITHIN 5 FT OF POINT OF
ENTRANCE OF METAL PIPE WHEN
PROVIDED.
COPPER GROUND
BUS BAR
UNDERGROUND METAL
WATER PIPE WHEN PROVIDED.
CONCRETE-ENCASED
ELECTRODE
#4 AWG
CU MIN.
BUILDING STEEL
2 GROUNDING AND BONDING WITH GROUND BAR
SCALE: N.T.S.
S
1.
BASIS OF DESIGN:
PROVIDE ACUITY #WSX-PDT
OS
1.
2.
3.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE.
MANUAL ON, ON/OFF OVERRIDE, AUTOMATIC OFF.
TOILETS AND STORAGE CLOSETS SHALL BE
AUTOMATIC ON/OFF.
1.
2.
3.
APPROVED ALTERNATES:
EATON
LEVITON
HUBBELL
1 TYPICAL WALL MOUNTED OCCUPANCY SENSOR
SCALE: N.T.S.
SIZE PER NEC
NOTES:
1. CONTRACTOR SHALL PROVIDE ALL CONDUIT FROM EACH DEVICE TO A JUNCTION BOX LOCATED
ABOVE DOOR.
2. CONTRACTOR SHALL PROVIDE 6 INCH X 6 INCH X 4 INCH DEEP JUNCTION BOXES.
3. TYPICAL DRAWING INDICATE MAG-LOCK OR ELECTRIC STRIKES FOR TYPICAL CONDUIT.
CONTRACTOR SHALL COORDINATE WITH THE HARDWARE CONTRACTOR FOR ACTUAL LOCATION
AND TYPE OF LOCKING DEVICE. THESE DETAILS ARE TYPICAL AND NOT EVERY TYPE IS UTILIZED
ON THIS PROJECT.
4. PUSHBUTTONS, CARD READERS, KEY PADS, ETC. SHALL BE INSTALLED AT ADA MOUNTING
HEIGHTS AND CENTERED ON LIGHT SWITCHES.
5. CARD ACCESS SYSTEM BY OWNER, ROUGH-IN AND 120 VOLT POWER TO SYSTEM BY
CONTRACTOR.
A. OWNER WILL PURCHASE AND INSTALL ALL DOOR CARD ACCESS COMPONENTS.
B. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUIT, BOXES, FITTINGS AND
WIRE.
C. CARD READER MOUNT ON A 4 INCHES SQUARE BOX WITH SINGLE GANG MUD RING. PROVIDE
A 3/4 INCHES CONDUIT TO ABOUT 12 INCHES ABOVE THE CEILING GRID AND TURN A 90
DEGREE BEND OUTWARD.
D. BETWEEN THE CARD READER BOX AND DOOR STRIKE OR FRAME POCKET PROVIDE A 1/2
INCH CONDUIT.
E. PROVIDE A BOX CONNECTOR AND PLASTIC BUSHING ON ENDS OF ALL CONDUITS.
F. ALL WIRE SHALL BE PLENUM RATED WIRE. IN WAREHOUSE INSTALLATION PROVIDE A 10
FOOT SECTION OF 3/4 INCH CONDUIT UP, INSTALL THE BOX CONNECTOR AND BUSHING AND
MAKE THE REST OF THE RUN IN "FREE AIR" USING BRIDAL RINGS.
G. (WE WILL SHOW ON DRAWINGS) IT ROOM WHERE ALL THE MAIN EQUIPMENT WILL BE
INSTALLED A SERIES OF 1-1/2 INCH OR 2 INCH CONDUIT COMING INTO THE SPACE WITH THE
WIRES NEATLY BUNDLED.
H. ALL WIRES SHALL BE LABELED WITH THE CORRESPONDING DOOR NUMBERS ON EACH END
AND DRAPE DOWN AND COIL ON THE FLOOR.
I. THE AXION/TRINE DOOR STRIKES COME IN EITHER 1/2 INCH OR 3/4 INCH THICKNESS
DEPENDING ON THE DOOR HARDWARE.
J. VERIFY CARD READER MOUNTING HEIGHTS WITH OWNER PRIOR TO ROUGHING IN CARD
READER BACK BOXES.
6. FIRE ALARM INTERFACE TO RELEASE LOCKING ON AC FAIL AND ACTIVATION OF FIRE ALARM
SYSTEM. COORDINATE WITH FIRE ALARM CONTRACTOR.
7. SIZE MAGNETIC LOCKING WIRE BASED ON IN RUSH CURRENT AND MANUFACTURES
INSTALLATION SHEETS.
DOOR CONTACT
ELECTRIC STRIKE
MAGNETIC LOCK (OPTION)
CARD READER OR KEYPAD
PLACED ON NON SECURED SIDE
OF DOOR. FOR EXTERIOR
MOUNTING DEVICE WILL BE RATED
FOR OUTSIDE USE.
JUNCTION BOX
FIRE ALARM INTERFACE (IF REQUIRED)
TO SECUIRTY CONTROL PANEL
1/2" CND.
3/4" CND.
3/4" CND.
1/2" CND.
TYPE-A
RECESSED
FINSH FLOOR
FINISH FLOOR
DROP CEILING
DROP CEILING
JUNCTION BOX
FIRE ALARM INTERFACE (IF REQUIRED)
TO SECURITY CONTROL PANEL
1/2" CND.
CARD READER
OR KEYPAD
CARD READER
OR KEYPAD
TYPE-C
3/4" CND.
3/4" CND. 1/2" CND.
DOOR CONTACT
RECESSED
3/4" CND.
FINSH FLOOR
DROP CEILING
4 TYPICAL CARD ACCESS WIRING DETAIL
SCALE: N.T.S.
ON/OFF
D
POWER CIRCUIT
LIGHTING LOAD
WITH INTEGRATED SENSORS
S S D
TYPICAL DIMMING LAYOUTS
POWER PACK
(TYP.)
LIGHTING LOAD
(TYPICAL)
1.
2.
3.
4.
APPROVED MANUFACTURERS:
ACUITY nLIGHT
HUBBELL NX
EATON
LEVITON
1.
2.
3.
4.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE, BASED UPON ASHRAE 90.1, 2019.
MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,
AUTOMATIC OFF.
PROVIDE SINGLE (1) COVERPLATE. SIZE BASED ON
SWITCHES REQUIRED.
SEE PLANS FOR SPECIFIC QUANTITY AND LOCATION OF
SWITCH TYPES.
3 TYPICAL LIGHTING CONTROL DETAILS
SCALE: N.T.S.
ON
TYPICAL SWITCH LAYOUT
OFF
S
TYPICAL ZONE CONTROLS
CLASSROOMS
ALL CLASSROOMS SHALL HAVE FIXTURE INTEGRATED
OCCUPANCY SENSORS WITH SINGLE ZONE DIMMING
CONTROLS. REFER TO LIGHTING KEYNOTES FOR
ADDITIONAL CONTROLS.
MAIN HALL
MAIN HALL SHALL HAVE FIXTURE INTEGRATED OCCUPANCY
SENSORS WITH MULTI ZONE DIMMING CONTROLS, AND A
TOUCHSCREEN CONTROLLER CAPABLE OF VARIOUS
LIGHTING SCENES. REFER TO LIGHTING KEYNOTES FOR
ADDITIONAL CONTROLS.
HALLWAYS
ALL HALLWAYS SHALL HAVE FIXTURE INTEGRATED
OCCUPANCY SENSORS. DURING BUILDING OPERATIONAL
HOURS LIGHTS SHALL DIM TO 50% UPON VACANCY. FULL
OFF OUTSIDE OF OPERATIONAL HOURS.
OTHER SPACES
FOR ALL OTHER SPACES REFER TO FLOOR PLAN AND
DEVICE LAYOUT FOR CONTROLS.
TOP CONTROL
BOTTOM CONTROL
POWER PACK
(TYP.)
EACH RECEPTACLE CIRCUIT
5 TYPICAL RECEPTACLE CONTROL DETAILS
SCALE: N.T.S.
HOT LEG
LIGHTING LOAD
WITH INTEGRATED SENSORS
SEQUENCE OF OPERATION
1. ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE BASED UPON ASHRAE 90.1, 2019.
2. ALL CONTROLLED RECEPTACLES SHALL BE
PERMANENTLY MARKED IN ACCORDANCE WITH NFPA
70.
3. CONTROLLED RECEPTACLE TO ACTIVATE UPON
DETECTION OF OCCUPANCY.
4. CONTROLLED RECEPTACLE TO TURN OFF UPON
VACANCY.
5. 50% OF ALL SPECIFIED RECEPTACLES IN OFFICES
AND BREAKROOMS TO BE SPLIT CONTROLLED VIA
OCCUPANCY. PROVIDE WIRELESS POWER PACKS AS
REQUIRED.
PROVIDE REQUIRED POWER PACKS AND
ACCESSORIES TO SPLIT CONTROL RECEPTACLES
VIA FIXTURE INTEGRATED OCCUPANCY SENSORS.
REFER TO E-600
FOR WIRE SIZING
ELECTRIC STRIKE
120V-1Ø TO 20 AMP
1 POLE BREAKER IN
PANEL
BOILER (B-1)
120V-1Ø TO 20 AMP
1 POLE BREAKER IN
PANEL
BOILER (B-2)
REPO
BUTTON(S)
6 BOILER EMERGENCY OFF SWITCH
SCALE: N.T.S.
#2 4-
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I
E-800
Fo re st H ill s N at ur e C en te r N ew N at ur e C en te r
N
R ic h Rd
, A lm a, M
I 4
Se vi lle
T ow ns hi p, G ra tio t C ou nt y
Al m a, M ic hi ga n
M A
T R
I
E-900
File details come from the government source that posted it. Updated .