260424 - Forest Hills Nature Center - Bid set - Civil.pdf

PDF 1 MB Posted

Attached to
Forest Hill Nature Center - New Building
Solicitation number
RFP GIR 260000001926 3
Issued by
Ingham County, Michigan

About this file

This is a civil engineering bid set document for the Forest Hills Nature Center New Building project located at 1297 N Rich Road, Alma, Michigan 48801, in Seville Township, Gratiot County. The document provides detailed technical specifications and construction drawings for critical infrastructure components including a duplex sump pump lift station with dual pump redundancy, a sanitary sewer system with cleanout details, a septic tank system designed for H-25 loading with 0.0' to 3.0' earth cover, and a drain field measuring 40' in width. The sump pump station includes five operational levels with low water alarms, pump sequencing controls, and high water alarms, with both pumps capable of running simultaneously. All piping specifications call for Schedule 80 PVC with tracer wire and warning tape for force mains, and perforated HDPE N12 pipe for cooling tower drains. The septic tank and drain field design comply with Mid-Michigan Health Department criteria and are manufactured per AASHTO 17th Edition and ASTM specifications.

The specifications detail concrete pad requirements of 6'x6' with #4 rebar at 8" on-center spacing in each direction, 5000 PSI concrete at 28 days, and pipe and fitting materials meeting ASTM A-615 and A-496 standards. Tank covers must be sealed with 1-1/2" EZ-STIK or equivalent material. The document notes that pipe and fittings for inlets and outlets are not included in the specified scope, casting and adjustment to finish grade are not included, and the contractor is responsible for providing and installing all building controls necessary to meet the specified sequence of operations. The project reflects municipal infrastructure requirements for a nature center facility in Michigan.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C-4

GENERAL NOTES

1. PIPE/ FORCE MAIN - SCHEDULE 80 PVC WITH

TRACER WIRE AND WARNING TAPE.

2. COOLING TOWER DRAIN - PERFORATED HDPE

N12 PIPE.

EXISTING LEGEND

-4

F o re st

H il ls N a tu re C en te r N ew N a tu re C en te r N

R ic h R d A lm a

M I

S ev il le

T o w n sh ip , G ra ti o t

C o u n ty

A lm a , M ic h ig a n 4

M A

T R

I X

C-400

BASIN COVER

BASIN

NON-SLAM

(TYPICAL)

CHECK VALVE

2"

GATE VALVE

LEVEL 4: PUMP 2 (LAG)

'ON' HIGH WATER ALARM

2"-OUTLET AS

NOTED ON PLANS

LEVEL 5: REDUNDANT

HIGH WATER ALARM

GAS TIGHT COVER

EXISTING GRADE

BASIN (60"Øx112" DEEP)

DISCHARGE PIPE

PUMP CASE

VOLUTE

LEVEL 1: LOW WATER ALARM

NOTE:

WATER LEVEL MINIMUM 1'-6" ABOVE PUMP

CASE

PROVIDE TIE DOWNS PER THE

MANUFACTURER'S WRITTEN SPECIFICATIONS.

4' 6"

6" 1'-

6"

SUPPORT POLE

6'x6' CONCRETE PAD

#4 REBAR 8" O.C.

EACH DIRECTION

GATE VALVE

2"

3'- 9"

LEVEL 3: PUMP 1 'ON'

LEVEL 2: PUMPS 'OFF'

FF ELEV. = 815.27

2"

2' 6"

4" SAN

812.00

PUMP STATION SEQUENCE OF OPERATION:

- LEVEL 1 - LOW WATER ALARM

- LEVEL 2 - BOTH PUMPS 'OFF'

- LEVEL 3 - START LEAD PUMP; PUMPS SHALL

ALTERNATE ON EACH CALL

- LEVEL 4 - START LAG PUMP; BOTH PUMPS

RUNNING SIMULTANEOUSLY; HIGH WATER

ALARM

- LEVEL 5 - REDUNDANT HIGH WATER LEVEL

ALARM

*CONTRACTOR IS RESPONSIBLE FOR PROVIDING

AND INSTALLING ALL CONTROLS ON THE BUILDING

AS NEEDED TO MEET THE SEQUENCE OF

OPERATIONS.

LIFT STATION

4D

2.5D

1D

D FLOW

1D

8"

24"

PVC FEMALE CLEANOUT ADAPTER WITH

INVERTED NUT SCREW CAP OR FLAT SLOTTED

SCREW CAP

PVC PIPE

45° BEND

SEWER LATERAL

E.J.I.W. 1040 M3 MANHOLE FRAME LID

INSTALLED FLUSH WITH FINISHED SURFACE

EXISTING GRADE

CONCRETE COLLAR POURED AROUND

CLEANOUT COVER (3,500 PSI)

KOR-N-SEAL NO. S406-10 AWS*

6"x6" TWO-WAY TEE

SEWER LATERAL

45° BEND

SEWER

TOP ELEVATION

4"

6"6" 10'-8-1/2" 11'-8-1/2"

6'- 0-

1/4

PVC SCHEDULE

40 BY OTHERS

5'- 6-

1/2

11'-8-1/2"

4"

4"x24" OPENING

7K KOR-N-SEAL

FOR 4" PVC

TYP-(2) PLACES

24" ACCESS (ABOVE)

TYP-(2) PLACES

7'-2-1/2" 3'-6"

5"x1" KEYWAY

TYP-(3) SIDES

CAULK ALL AROUND

TYP- BOTH SIDES

4'- 0-

1/4

2'- 0"

6"

4'-

-1 /4"

7"

5'-6-1/2" 4'-6-1/2"6" 6"

56"

CASTING & ADJUSTMENT TO

FINISH GRADE NOT INCLUDED

NOTES:

SEPTIC TANK SECTIONS TO BE MANUFACTURED PER AASHTO 17TH ED. AND

ASTM SPECIFICATIONS W/H-25 LOADING AND 0.0' TO 3.0' OF EARTH COVER.

CONCRETE: 5000 PSI @ 28 DAYS

REINFORCEMENT PER ASTM A-615 & A-496

COVER TO BE SEALED W/1-1/2" EZ-STIK OR EQUAL

PIPE AND FITTINGS FOR INLETS & OUTLETS ARE NOT INCLUDED

4" I.E.=814.80

I.E.=814.90

RIM ELEV. = 818.40 RIM ELEV. = 818.20

6'x6' CONCRETE PAD

12" 12"6"

6" OVERFILL

4" PERF.

PVC, TYP. 5 MDOT 6A

DRAIN FIELD WIDTH - 40'

NOTE: SEPTIC TANK AND DRAINFIELD DETAILS AND DESIGN

CRITERIA BASED ON THE MID-MICHIGAN HEALTH DEPARTMENT

4' 3'

18"

C-800

-4

F o re st

H il ls N a tu re C en te r N ew N a tu re C en te r

N

R ic h R d

A lm a M

I

S ev il le

T o w n sh ip

, G ra ti o t C o u n ty

A lm a , M ic h ig a n 4

M A

T R

I X

2 ROCK RIPRAP DISSIPATOR

SCALE: NTS

3 DOUBLE SANITARY CLEANOUT DETAIL

SCALE: NTS1 SUMP PUMP DUPLEX DETAIL

SCALE: NTS

4 SEPTIC TANK DETAIL

SCALE: NTS

1 DRAIN FIELD SECTION VIEW

SCALE: NTS

24-0569 TOPO_PRELIMINARY-new-Layout1-Ttlb 30x42
C800-25034900-Layout1