Fire_Sprinkler_Description_of_Systems_03-09-2026_(2).xlsx
XLSX spreadsheet 17 KB Posted
- Solicitation number
- RFQ197145
- Issued by
- Santa Clara County, California
About this file
This is a Fire Sprinkler System Description of Systems spreadsheet prepared for the City of Palo Alto, California, detailing automatic fire extinguishing system specifications across 29 municipal facilities comprising approximately 1.3 million square feet. The document provides comprehensive technical descriptions of wet pipe sprinkler systems, standpipe systems, fire detection and alarm control panels (FACP), water motor gongs (WMG), fire department connections (FDC), main control valves (MCV), sectional control valves (SCV), hose valves, and hydrant connections across community centers, libraries, parking garages, fire stations, and municipal buildings. The systems inventory includes 52 total wet sprinkler systems, 7 dry sprinkler systems, pre-action systems, and a diesel engine-driven fire pump at the Civic Center facility. Each facility entry documents the specific riser configurations, valve types (including Swing, Wafer, Butterfly, and OS&Y valves), flow switches, main drains, inspector test valves, and specialized components such as electric bells and water motor gongs. The spreadsheet serves as the technical baseline for the City of Palo Alto's three-year Automatic Fire Extinguishing System Inspection, Testing, and Repair contract commencing June 1, 2026, with quarterly and annual inspections scheduled for June, September, December, and March, and five-year maintenance service tests and certifications required in accordance with NFPA 25 2025 Edition standards.
The contract procurement specifies that all inspections and repairs must comply with NFPA 25 2025 Edition and California Code of Regulations Title 19. Contractors must hold a valid California State Contractor's License (C-16 classification), maintain current Department of Industrial Relations registration, and provide completed inspection forms to designated City representatives within five days of completion. The estimated project value is approximately $500,000 across the three-year contract period with 275 hours of straight-time labor budgeted annually for repair work and a dedicated repair budget that contractors will bill against as maintenance and repairs are required. Bid proposals were due March 23, 2026 at 3:00 p.m. through the City's OpenGov portal, with questions submission deadline of March 13, 2026 at 1:00 p.m. and no pre-bid conference scheduled. The City identified eleven pre-qualified California-based contractors eligible to submit proposals. Contractors must obtain 100 percent Performance and Payment Surety Bonds within ten business days of award notification and comply with California prevailing wage requirements, certified payroll records, and apprenticeship employment requirements, with liquidated damages assessed at $500 per day for unexcused delays.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 Note: “Description of Systems” may not include all system components, but contractor is responsible for inspecting systems in their entirety.
| Item | Location Address | Wet Sprinkler/#Systems | Standpipe Type/#Hose Valves | FDC | Private Service Main/#Hydrant | FACP/ WMG | Description of Systems. |
| 1 | Cubberley Community Center Theater | Y | N | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV, alarm CV One riser, Two gauges, One main drain, flow switch and inspector test valve. | |
| 4000 Middlefield Rd | 1 | ||||||
| 2 | Cubberley Community Center H & FH Buildings | Y | N | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV, alarm CV One riser, Two gauges, One main drain, flow switch and inspector test valve. | |
| 4000 Middlefield Rd. | 1 | ||||||
| 3 | Cubberley Community Center Auditorium | Y | CL 2 WET HV | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV, alarm CV One riser, Two gauges, One main drain, flow switch and inspector test valve. | |
| 4000 Middlefield Rd. | 1 | 2 | |||||
| 4 | Lucie Stern Children’s Theater | Y | N | Y | Y/Y | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. | |
| 1305 Middlefield Rd. | 1 | 1 | |||||
| 5. | Lucie Stern Community Center | Y | CL 2 WET HV/ Hoses Removed | Y | Y/N | One riser, OSY MCV (SCV off Theater riser), Butterfly SCV in storage room, flow switch in ceiling hatch, shares FDC with Community Theater riser. | |
| 1305 Middlefield Rd. | 1 | 3 | 1 | ||||
| 6a. | Lucie Stern Community Theater | Y | CL 2 WET HV/ Hoses Removed | Y | Y/N | Riser 1 of 2. One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, (Shared with Lucie Stern system) OS&Y SCV in attic, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. | |
| 1305 Middlefield Rd. | 2 | 2 | 1 | ||||
| 6b. | Lucie Stern Community Theater Scene Shop | Riser 2 of 2. One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, (Shared with Lucie Stern system) Two gauges, One main drain, flow switch, and inspector test valve. | |||||
| 7 | Rinconada Library | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV in basement, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, and inspector test valve. |
| 1213 Newell Rd. | 1 | ||||||
| 8 | Baylands Nature Interpretive Center | Y | N | Y | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, Two gauges, One main drain, flow switch, water motor gong and inspector test valve. |
| 2775 Embarcadero Rd. | 1 | ||||||
| 9 | Utility Control Center | Y | N | Y | Y /N | One 2 inlet FDC, Wafer FDCCV @ riser, PIV MCV, alarm CV One riser, One gauge, One main drain, flow switch, and inspector test valve. *(Building also has existing Halon System NIC) | |
| 3241 East Bayshore Rd. | 1 | 1 |
| 10a | Art Center | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. |
| 1313 Newell Rd. | 2 | ||||||
| 10b | Pre-action fire sprinkler system | ||||||
| Section off riser 2, Swing CV, OS&Y SV, Alarm CV, Three gauges, Two drains, One FS | |||||||
| 11 | Municipal Service Center Building A | Y | CL 2 WET HV/ Hoses Removed | Y | Y | Y/N | Wet pipe fire sprinkler system with hose drops |
| 3201 East Bayshore Rd. | 2 | 2 | 1 | One 2 inlet FDC shared with riser 2, Riser 1 of 2 x-connected, OS&Y SCV, alarm CV, One gauge, One main drain, flow switch, inspector test valve. | |||
| 12 | Municipal Service Center Building B | Y | CL 2 WET HV/ Hoses Removed | Y | Y | Y/N | Wet pipe fire sprinkler system with hose drops |
| 3201 East Bayshore Rd. | 1 | 4 | 1 | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, Butterfly SCV @ paint booth, alarm CV One riser, One gauge, One main drain, flow switch, inspector test valve. | |||
| 13 | Municipal Service Center Building C | Y | CL 2 WET HV/ Hoses Removed | Y/N | Wet pipe fire sprinkler system with hose drops | ||
| 3201 East Bayshore Rd. | 2 | 4 | One 2 inlet FDC shared with riser 2, Riser 2 of 2 x-connected, OS&Y SCV, alarm CV, One gauge, One main drain, flow switch, inspector test valve. | ||||
| 14 | Ted Thompson Parking Garage | Y | Class 1 Wet/Hoses Removed | Y | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, water motor gong and inspector test valve. |
| 275 Cambridge Avenue | 1 | 4 | 1 | ||||
| 15a | Lot S/L Parking Garage | Y | CL 1 DRY | Y | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, and inspector test valve per system |
| 445 Bryant St. | 7 | 24 | 1SPR/2ST | ||||
| 15b | Bryant Street Community Center | Y | N | Shared w/SL | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. FACP, OS&Y/FDC Shared with Lot S/L Riser in Trash Enclosure |
| 429 Bryant | 1 | ||||||
| 16 | Lot R Parking Garage | Y | CL 1 DRY | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, and inspector test valve per system | |
| 528 High Street | 4 | 12 | 1SPR/1ST | ||||
| 17 | Children’s Library | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, and inspector test valve. (3) Wharf Hydrants |
| 1275 Harriet St | 1 | 1 | 3 Wharf | ||||
| 18 | Rinconada Pool | Y | N | N | N | N/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, electric bell and inspector test valve. |
| 777 Embarcadero Road | 1 | ||||||
| 19 | College Terrace Library | Y | N | Y | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, electric bell and inspector test valve. |
| 2300 Wellesley St. | 1 | ||||||
| 20 | Arastradero Preserve Buildings | Y | N | Y | N | N?N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, electric bell and inspector test valve. Hydrant is not fed from 4" OS&Y |
| 1530 Arastradero Rd. | 2 | 1 | |||||
| 21 | Golf Course Club House | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, electric bell and inspector test valve. |
| 1875 Embarcadero Road | 1+Basement | 1 | |||||
| 22a. | Civic Center | Y | CL 1 Wet Combination/CL2 Wet HV Hoses removed | Y | N | Y/N | Riser 1 of 3 x-connected, shared FDC ET AL, OS&Y SV, Alarm CV, Two gauges, One main drain, FS, ITV. 1 6" Main PRV 1 4" Main PRV |
| 250 Hamilton Avenue | 3 Garage 10 Tower 1 Police 2 Pre-Act | 13CL1/14CL2 | 1, 4WAY | ||||
| 22b. | Riser 2 of 3 x-connected, Shared FDC ET AL, OS&Y SV, Alarm CV, 10 BFLY SV’s, 12 gauges, 10 MD, 10 FS & ITV, 9 – 1 ½” & 12 – 2 ½” outlet valves, PRV | ||||||
| 22c. | Riser 3 of 3 x-connected, shared FDC ET AL, OS&Y SV, @ riser, One BFLY SV, Three gauges, Three drains, Two FS, ITV, 8 – 2 ½” outlet valves | ||||||
| 22d. | Pre-action fire sprinkler system | ||||||
| Section off riser 2, Swing CV, OS&Y SV, Alarm CV, Three gauges, Two drains, One FS | |||||||
| Located in garage Level A | |||||||
| 22e. | Pre-action fire sprinkler system | ||||||
| Section off riser 2, Swing CV, MCV, Two BFLY SV, Alarm CV, Five gauges, Three drains, One FS. Two tampers at 2nd Floor | |||||||
| Located in closet for computer room | |||||||
| 22f. | Diesel Engine Driven Fire Pump | ||||||
| One horizontal centrifugal, Diesel driven 750 GPM, Controller, Jockey pump, Supplied by water main, Churn and flow meter present, no test header. | |||||||
| 22g. | Fire Pump diesel engine annual maintenance service | ||||||
| 23 | Mitchell Park Library | Y | N | Y | Y | Y/N | Two 2 inlet FDC, Wafer FDCCV @ riser, PIV MCV, alarm CV One riser, One gauge, One main drain, flow switch, and inspector test valve. P.S.M HYD+ 1 Wharf Hydrant |
| 3700 Middlefield Road | 2 | 1 | 2+1Wharf | ||||
| 23b | Mitchell Park Community Center – Building B | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, water motor gong and inspector test valve. | |||
| 3700 Middlefield Road | 1 | ||||||
| 23c | Mitchell Park Community Center – Building C | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, water motor gong and inspector test valve. | |||
| 3700 Middlefield Road | 1 | ||||||
| 24 | Fire Station 8 | Y | N | N | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, water motor gong and inspector test valve. |
| 3300 Pagemill Road | 1 | ||||||
| 25 | Fire Station 3 | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. |
| 799 Embarcadero Road | 1(2Floors | 1 | 1 | ||||
| 26 | JR. Museum | Y | N | Y | Y | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. |
| 1451 Middlefield Road | 1 | 1 | |||||
| 27 | Sherman Parking Garage | Y | CL 1 WET | Y | N | Y/N | Two 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, One gauge, One main drain, flow switch, electric bell and inspector test valve Per floor control assembly. One electric fire pump. |
| 350 Sherman Ave. | 7 | 21 | 1 |
| 28 | Pets In Need Modular Building | Y | N | Y | N | Y/N | One 2 inlet FDC, Swing FDCCV, OS&Y MCV @ riser, alarm CV One riser, Two gauges, One main drain, flow switch, electric bell and inspector test valve. |
| 3281 E. Bayshore Road | 1 | 1 |
| 29a | Public Safety Building | Y | CL 1 WET Combination | Y | N | Y/N | Risers w/ butterfly control valves, check valves, flow switches, drains, gauges and hose valves |
| 250 Sherman Ave. | 6 + 2 DI Pre-Action | 4Risers/17 HVs | 2 | 500 GPM horizontal split case electric pump, gravity fed from external water storage tank , 2 Double Interlock Preaction Systems. | |||
| 29b | Double interlock pre action system w/ (2) butterfly control valve, check valve, flow switch, (2) drains, 3 gauges, air compressor and alarm panel. | ||||||
| 29c | Double interlock pre action system w/ (2) butterfly control valve, check valve, flow switch, (2) drains, 3 gauges, air compressor and alarm panel. |