Text Box FPE Review (Tuazon): 2016 NFPA 72 - 17.14.8.4 requires a manual pull station within 5 feet of each exit door, however if there are already two (2) other manual pull stations in the room, and one of them is within 20 feet of this exit door (as appears per photo), the pull station locations are considered acceptable and do not create a significant life safety risk.
| SITK FA 64374 - 2020 Priest Quarters |
| SITK FA 64540 - 2020 Old School |
| SITK FA 64367 - 2020 Visitor Center |