FIO_Drawings_B4511 Tower Camp Courtney_1of2.pdf
PDF 43 MB Posted
- Solicitation number
- W912HV25Z0007
About this file
The file is a draft drawing (FIO_Drawings_B4511 Tower Camp Courtney_1of2.pdf) related to a U.S. Army Corps of Engineers pre-solicitation for a design-bid-build construction project at Camp Courtney, Okinawa, Japan. The project involves a comprehensive renovation of Tower 4511, a senior non-commissioned officer family housing facility with 68 three-bedroom units, with an estimated project value between $25-100 million and a performance period of approximately 912 days.
The renovation scope encompasses extensive interior and exterior improvements, including architectural repairs (door replacements, repainting, floor and ceiling updates), complete replacement of HVAC, plumbing, and electrical systems, life safety and fire protection upgrades, environmental remediation, and site improvements. The project is exclusively for local sources physically located and licensed in Japan, with a Japanese civil or architectural construction license required. The government anticipates issuing an Invitation for Bids in the 4th quarter of FY25, with interested firms requested to submit a capabilities survey response by close of business on 18 April 2025 to the specified U.S. Army Corps of Engineers, Japan District contacts.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FIO_Specifications_B4511 Tower Camp Courtney.pdf | ||
| W912HV25Z00007_Sources Sought Capabilities Survey Questions (2).docx | DOCX document | |
| FIO_Drawings_B4511 Tower Camp Courtney_2of2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
205 N. MICHIGAN AVE.
SUITE 3800
CHICAGO, IL 60601
www.expFederal.com proj. no.:
C
D
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n o
IS
O
A
E X
P F
E D
E R
A L
PROJECT NO.:
US Army Corps of Engineers ®
US Army Corps of Engineers ®
JAPAN DISTRICT,
FY24 FSRM RENOVATE MFH TOWER 4511
CAMP COURTNEY, OKINAWA, JAPAN
W912HV19D0008
MARCH 2024
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
C O
V E
R S
H E
E T
G-001
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T
O K
IN
A
W A
A R
E A
O F
F
IC
E
E X
P F
E D
E R
A L
E K
O N
D O
Y P
A R
K
M A
R C
H
- W H
V D
C H
I- -A
C A
B T
A
.R V
T .r v t
RTA SUBMITTAL
CHI-22022320-A0
C A
B T
CABT184709
CABT 184709
OKINAWA AREA OFFICE
sealed: 17 Mar 2024 expires: 30 Nov 2024
3.15.2024
W912HV-24-B-0008
R T
A S
U B
M
IT
T A
L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
N O
NLY
R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
IN
D
E X
S H
E E
T
G-002
R T
A S
U B
M
IT
T A
L
E K
O N
D O
E K
O N
D O
P Z
IN
N
I
M A
R C
H
C H
I- -A
C A
B T
#SHEET LIST
SHEET NUMBER SHEET NAME
MH402
ENLARGED HVAC DWELLING UNIT 2ND - 9TH FL PLAN
TYPE A & B AND SECTION - NEW
MH403 ENLARGED PIPE SPACE HVAC PLAN & SECTION - NEW
MH404
ENLARGED TYPICAL DOAS ROOF FLOOR PLAN & SECTION
- NEW
MH405
ENLARGED EXHAUST SYSTEM PH1 FLOOR PLAN &
SECTION - NEW
MH601 DOAS AND EXHAUST SYSTEM AIRFLOW DIAGRAMS
MP101 A/C SYSTEM 1ST FLOOR PLAN - NEW
MP102 A/C SYSTEM 2ND-8TH FLOOR PLAN - NEW
MP103 A/C SYSTEM 9TH FLOOR PLAN - NEW
MP104 A/C SYSTEM 1ST FLOOR PLAN AREA B, C & E - NEW
MP105 A/C SYSTEM 1ST FLOOR PLAN AREA A&D - NEW
MP106 A/C SYSTEM 2ND-8TH FLOOR PLAN AREA B, C & E - NEW
MP107 A/C SYSTEM 2ND-8TH FLOOR PLAN AREA A&D - NEW
MP108 A/C SYSTEM 9TH FLOOR PLAN AREA B, C & E - NEW
MP109 A/C SYSTEM 9TH FLOOR PLAN AREA A&D - NEW
MP601 A/C CONDENSATE PIPING SCHEMATIC DIAGRAM
MI601 MECHANICAL SYSTEM CONTROL SEQUENCE - 1
MI602 MECHANICAL SYSTEM CONTROL SEQUENCE - 2
M-501 MECHANICAL DETAILS - 1
M-502 MECHANICAL DETAILS - 2
M-601 MECHANICAL EQUIPMENT SCHEDULE - 1
M-602
MECHANICAL EQUIPMENT SCHEDULE - 2 AND REGISTER
LIST
ELECTRICAL
E-001
GENERAL NOTES, LEGEND, ABBREVIATIONS AND
ELECTRICAL REFERENCES
ED101 SITE ELECTRICAL PLAN - DEMOLITION
ED102
OVERALL LIGHTING AND RECEPTACLE PLAN, 1ST FLOOR -
DEMOLITION
ED103
OVERALL LIGHTING AND RECEPTACLE PLAN, 2ND TO 9TH
FLOOR - DEMOLITION
ED104
ENLARGED TYPICAL UNIT TYPE A AND B LIGHTING PLAN -
DEMOLITION
ED401
ENLARGED POWER PLAN, 1ST FLOOR ELECTRICAL AND
MECHANICAL ROOM - DEMOLITION
ED601 SITE ONE LINE DIAGRAM - DEMOLITION
ED602
TRANSFORMER STATION SINGLE LINE DIAGRAM -
DEMOLITION
ES101 SITE ELECTRICAL PLAN - NEW
EL101
OVERALL LIGHTING AND RECEPTACLE PLAN, 1ST FLOOR -
NEW
EL102
OVERALL LIGHTING AND RECEPTACLE PLAN, 2ND TO 9TH
FLOOR - NEW
EL103 ENLARGED RECEPTACLE PLAN, ROOF FLOOR - NEW
EL104
ENLARGED TYPICAL UNIT TYPE A AND B LIGHTING PLAN -
NEW
EL501 LIGHTING FIXTURE DETAIL AND SCHEDULE - NEW
EP101 OVERALL POWER FEEDER PLAN, 1ST FLOOR - NEW
EP102
OVERALL POWER FEEDER PLAN, 2ND TO 9TH FLOOR -
NEW
EP103 ENLARGED POWER FEEDER PLAN, ROOF FLOOR - NEW
EP501 DETAILS (1) - NEW
EP502 DETAILS (2) - NEW
EP503 DETAILS (3) - NEW
EP601 SITE ONE LINE DIAGRAM - NEW
EP602
TRANSFORMER STATION "SET#4511" AND SECONDARY
SWITCHBOARD SINGLE LINE DIAGRAM - NEW
EP603 POWER FEEDER ONE LINE DIAGRAM - NEW
EP604 PANEL ONE-LINE DIAGRAM AND SCHEDULE (1) - NEW
EP605 PANEL ONE-LINE DIAGRAM AND SCHEDULE (2) - NEW
EP606 PANEL ONE-LINE DIAGRAM AND SCHEDULE (3) - NEW
EP607 PANEL ONE-LINE DIAGRAM AND SCHEDULE (4) - NEW
EP608 PANEL ONE-LINE DIAGRAM AND SCHEDULE (5) - NEW
EP609 PANEL ONE-LINE DIAGRAM AND SCHEDULE (6) - NEW
EP610
PANEL ONE-LINE DIAGRAM AND SCHEDULE (7) -
MODIFICATION
EP611
PANEL ONE-LINE DIAGRAM AND SCHEDULE (8) -
MODIFICATION
TELECOM
TT501 MODIFIED TELECOM CABINET “1A00” DETAIL
#SHEET LIST
SHEET NUMBER SHEET NAME
PD401
ENLARGED DWELLING UNIT 1ST FLOOR PLAN TYPE A, B &
CORE AREA - DEMOLITION
PD402
ENLARGED DWELLING UNIT 2ND-9TH FLOOR PLAN TYPE A
& B - DEMOLITION
PD403 ENLARGED MECH ROOM PLAN - DEMOLITION
PP101 PLUMBING SYSTEM 1ST FLOOR PLAN - NEW
PP102 PLUMBING SYSTEM 2ND-8TH FLOOR PLAN - NEW
PP103 PLUMBING SYSTEM 9TH FLOOR PLAN - NEW
PP104
PLUMBING SYSTEM PH1, PH2, PH RF & ROOF FLOOR PLAN
- NEW
PP105 PLUMBING SYSTEM 1ST FLOOR PLAN AREA B, C & E - NEW
PP106 PLUMBING SYSTEM 1ST FLOOR PLAN AREA A & D - NEW
PP107
PLUMBING SYSTEM 2ND - 8TH FLOOR PLAN AREA B, C & E
- NEW
PP108
PLUMBING SYSTEM 2ND - 8TH FLOOR PLAN AREA A & D -
NEW
PP109 PLUMBING SYSTEM 9TH FLOOR PLAN AREA B, C & E - NEW
PP110 PLUMBING SYSTEM 9TH FLOOR PLAN AREA A & D - NEW
PP111
PLUMBING SYSTEM PH1, PH2, PH RF & ROOF FLOOR PLAN
AREA B, C & E - NEW
PP112 PLUMBING SYSTEM ROOF FLOOR PLAN AREA A & D - NEW
PP401
ENLARGED DWELLING UNIT 1ST FLOOR PLAN TYPE A, B &
CORE AREA - NEW
PP402
ENLARGED DWELLING UNIT 2ND-9TH FLOOR PLAN TYPE A
& B - NEW
PP403 ENLARGED MECH RM PLAN & SECTION - NEW
PP404
ENLARGED PIPE SPACE PLUMBING PLAN & SECTION -
NEW
PP601
DOMESTIC COLD AND HOT WATER PIPING SCHEMATIC
DIAGRAM
PP602 SEWER & VENT PIPING SCHEMATIC DIAGRAM
P-501 PLUMBING DETAILS-1
P-502 PLUMBING DETAILS-2
P-503 PLUMBING DETAILS-3
P-504 PLUMBING DETAILS-4
P-601 PLUMBING EQUIPMENT SCHEDULE
MECHANICAL
M-001
GENERAL DESCRIPTION OF WORK GENERAL NOTES,
LEGEND AND SYMBOLS, ABBREVIATIONS
MD101 FCU SYSTEM 1ST FLOOR PLAN - DEMOLITION
MD102 FCU SYSTEM 2ND - 8TH FLOOR PLAN - DEMOLITION
MD103 FCU SYSTEM 9TH FLOOR PLAN - DEMOLITION
MD104 FCU SYSTEM PH & ROOF FLOOR PLAN - DEMOLITION
MD105 DUCT SYSTEM 1ST FLOOR PLAN - DEMOLITION
MD106 DUCT SYSTEM 2ND-8TH FLOOR PLAN - DEMOLITION
MD107 DUCT SYSTEM 9TH FLOOR PLAN - DEMOLITION
MD108
DUCT SYSTEM PH1, PH2, PH RF & ROOF FLOOR PLAN -
DEMOLITION
MD109
FCU SYSTEM 1ST FLOOR PLAN AREA B, C & E -
DEMOLITION
MD110 FCU SYSTEM 1ST FLOOR PLAN AREA A & D - DEMOLITION
MD111
FCU SYSTEM 2ND - 8TH FLOOR PLAN AREA B, C & E -
DEMOLITION
MD112
FCU SYSTEM 2ND - 8TH FLOOR PLAN AREA A & D -
DEMOLITION
MD113
FCU SYSTEM 9TH FLOOR PLAN AREA B, C & E -
DEMOLITION
MD114 FCU SYSTEM 9TH FLOOR PLAN AREA A & D - DEMOLITION
MD115 FCU SYSTEM PH1 FLOOR PLAN - DEMOLITION
MD116
DUCT SYSTEM 1ST FLOOR PLAN AREA B, C & E -
DEMOLITION
MD117 DUCT SYSTEM 1ST FLOOR PLAN AREA A&D - DEMOLITION
MD118
DUCT SYSTEM 2ND - 8TH FLOOR PLAN AREA B, C & E -
DEMOLITION
MD119
DUCT SYSTEM 2ND - 8TH FLOOR PLAN AREA A & D -
DEMOLITION
MD120
DUCT SYSTEM 9TH FLOOR PLAN AREA B, C & E -
DEMOLITION
MD121 DUCT SYSTEM 9TH FLOOR PLAN AREA A&D - DEMOLITION
MD122
DUCT SYSTEM PH1, PH2 & ROOF FLOOR PLAN AREA B, C
& E - DEMOLITION
MD123 DUCT SYSTEM ROOF PLAN AREA A & D - DEMOLITION
MD401
ENLARGED MECH RM & CHILLER YARD PLAN -
DEMOLITION
MH101 DUCT SYSTEM 1ST FLOOR PLAN - NEW
MH102 DUCT SYSTEM 2ND - 8TH FLOOR PLAN - NEW
MH103 DUCT SYSTEM 9TH FLOOR PLAN - NEW
MH104 DUCT SYSTEM PH1, PH2 & ROOF FLOOR PLAN - NEW
MH105 DUCT SYSTEM 1ST FLOOR PLAN AREA B, C & E - NEW
MH106 DUCT SYSTEM 1ST FLOOR PLAN AREA A&D - NEW
MH107
DUCT SYSTEM 2ND - 8TH FLOOR PLAN AREA B, C & E -
NEW
MH108 DUCT SYSTEM 2ND - 8TH FLOOR PLAN A&D - NEW
MH109 DUCT SYSTEM 9TH FLOOR PLAN AREA B, C & E - NEW
MH110 DUCT SYSTEM 9TH FLOOR PLAN AREA A&D - NEW
MH111 DUCT SYSTEM PH1 & ROOF FLOOR PLAN - NEW
MH401
ENLARGED HVAC DWELLING UNIT 1ST FL PLAN TYPE A &
B AND SECTION - NEW
#SHEET LIST
SHEET NUMBER SHEET NAME
A-501 INTERIOR PARTITION TYPES AND DETAILS
A-502 WINDOW DETAILS
A-504 DOOR DETAILS
A-505 DOOR DETAILS
A-506 DOOR DETAILS
A-507 DOOR DETAILS
A-515 DETAILS
A-516 DETAILS
A-517 CEILING DETAILS
A-518 ROOF EXTERIOR DETAILS
A-601 DOOR SCHEDULE
A-602 DOOR SCHEDULE
A-603 WINDOW SCHEDULE
INTERIOR DESIGN
I-101 FIRST FLOOR OVERALL INTERIOR ELEMENTS PLAN
I-102 TYPICAL FLOOR OVERALL INTERIOR ELEMENTS PLAN
I-401 ENLARGED TYPICAL UNIT INTERIOR ELEMENTS PLANS
I-601 MILLWORK ELEVATIONS
I-602 MILLWORK ELEVATIONS & DETAILS
IN101 FIRST FLOOR OVERALL FINISH PLAN
IN102 TYPICAL FLOOR OVERALL FINISH PLAN
IN401 ENLARGED TYPICAL UNIT FINISH PLANS
IN501 ROOM FINISH SCHEDULES
IN601 INTERIOR LEGENDS
FIRE PROTECTION
FA001 FIRE ALARM GENERAL NOTES
FA101A 1ST FLOOR FIRE ALARM PLAN - AREA A
FA101B 1ST FLOOR FIRE ALARM PLAN - AREA B
FA101C 1ST FLOOR FIRE ALARM PLAN - AREA C
FA101D 1ST FLOOR FIRE ALARM PLAN - AREA D
FA102A
2ND, 4TH, 6TH, AND 8TH FLOOR FIRE ALARM PLAN - AREA
A
FA102B
2ND, 4TH, 6TH, AND 8TH FLOOR FIRE ALARM PLAN - AREA
B
FA102C
2ND, 4TH, 6TH, AND 8TH FLOOR FIRE ALARM PLAN - AREA
C
FA102D
2ND, 4TH, 6TH, AND 8TH FLOOR FIRE ALARM PLAN - AREA
D
FA103A 3RD AND 7TH FLOOR FIRE ALARM PLAN - AREA A
FA103B 3RD AND 7TH FLOOR FIRE ALARM PLAN - AREA B
FA103C 3RD AND 7TH FLOOR FIRE ALARM PLAN - AREA C
FA103D 3RD AND 7TH FLOOR FIRE ALARM PLAN - AREA D
FA104A 5TH AND 9TH FLOOR FIRE ALARM PLAN - AREA A
FA104B 5TH AND 9TH FLOOR FIRE ALARM PLAN - AREA B
FA104C 5TH AND 9TH FLOOR FIRE ALARM PLAN - AREA C
FA104D 5TH AND 9TH FLOOR FIRE ALARM PLAN - AREA D
FA105 PENTOUSE LEVEL 1 AND 2 FIRE ALARM PLAN
FA401 FIRE ALARM INPUT/OUTPUT MATRIX
FX001 FIRE SPRINKLER GENERAL NOTES
FX101A 1ST FLOOR FIRE SPRINKLER PLAN - AREA A
FX101B 1ST FLOOR FIRE SPRINKLER PLAN - AREA B
FX101C 1ST FLOOR FIRE SPRINKLER PLAN - AREA C
FX101D 1ST FLOOR FIRE SPRINKLER PLAN - AREA D
FX102A 2ND TO 9TH FLOOR FIRE SPRINKLER PLAN - AREA A
FX102B 2ND TO 9TH FLOOR FIRE SPRINKLER PLAN - AREA B
FX102C 2ND TO 9TH FLOOR FIRE SPRINKLER PLAN - AREA C
FX102D 2ND TO 9TH FLOOR FIRE SPRINKLER PLAN - AREA D
PLUMBING
P-001
GENERAL DESCRIPTION OF WORK, GENERAL NOTES,
LEGEND AND SYMBOLS, ABBREVIATIONS
PD101 PLUMBING SYSTEM 1ST FLOOR PLAN - DEMOLITION
PD102 PLUMBING SYSTEM 2ND-7TH FLOOR PLAN - DEMOLITION
PD103 PLUMBING SYSTEM 8TH FLOOR PLAN - DEMOLITION
PD104 PLUMBING SYSTEM 9TH FLOOR PLAN - DEMOLITION
PD105
PLUMBING SYSTEM PH1, PH2, PH RF & ROOF FLOOR PLAN
- DEMOLITION
PD106
PLUMBING SYSTEM 1ST FLOOR PLAN AREA B, C & E -
DEMOLITION
PD107
PLUMBING SYSTEM 1ST FLOOR PLAN AREA A & D -
DEMOLITION
PD108
PLUMBING SYSTEM 2ND-7TH FLOOR PLAN AREA B, C & E -
DEMOLITION
PD109
PLUMBING SYSTEM 2ND-7TH FLOOR PLAN AREA A & D -
DEMOLITION
PD110
PLUMBING SYSTEM 8TH FLOOR PLAN AREA B, C & E -
DEMOLITION
PD111
PLUMBING SYSTEM 8TH FLOOR PLAN AREA A & D -
DEMOLITION
PD112
PLUMBING SYSTEM 9TH FLOOR PLAN AREA B, C & E -
DEMOLITION
PD113
PLUMBING SYSTEM 9TH FLOOR PLAN AREA A & D -
DEMOLITION
PD114
PLUMBING SYSTEM PH1, PH2, PH RF & ROOF FLOOR PLAN
AREA B, C & E - DEMOLITION
PD115
PLUMBING SYSTEM ROOF FLOOR PLAN AREA A & D -
DEMOLITION
#SHEET LIST
SHEET NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 INDEX SHEET
GC001 TEMPORARY CONTRACTOR'S LAYDOWN AREA PLAN
GC002 CONTRACTOR'S ACCESS AND HAUL ROUTE
GI001 LIFE SAFETY CODE ANALYSIS
GI002 LIFE SAFETY OCCUPANCY CALCULATIONS
GI003 LIFE SAFETY CODE COMPLIANCE SITE PLAN
GI101 1ST FLOOR LIFE SAFETY PLAN - OVERALL
GI101A 1ST FLOOR LIFE SAFETY PLAN - AREA A
GI101B 1ST FLOOR LIFE SAFETY PLAN - AREA B
GI101C 1ST FLOOR LIFE SAFETY PLAN - AREA C
GI101D 1ST FLOOR LIFE SAFETY PLAN - AREA D
GI102 2ND TO 9TH FLOOR LIFE SAFETY PLAN - OVERALL
GI102A 2ND TO 9TH FLOOR LIFE SAFETY PLAN - AREA A
GI102B 2ND TO 9TH FLOOR LIFE SAFETY PLAN - AREA B
GI102C 2ND TO 9TH FLOOR LIFE SAFETY PLAN - AREA C
GI102D 2ND TO 9TH FLOOR LIFE SAFETY PLAN - AREA D
GI103 PENTHOUSE LEVEL 1 & 2 LIFE SAFETY PLAN
HAZARDOUS MATERIALS
H-101 ASBESTOS ABATEMENT
H-102 ASBESTOS ABATEMENT
H-103 ASBESTOS ABATEMENT
H-104 LEAD/CADMIUM/CHROMIUM ABATEMENT
H-105 LEAD/CADMIUM/CHROMIUM ABATEMENT
H-106 LEAD/CADMIUM/CHROMIUM ABATEMENT
H-107 LEAD/CADMIUM/CHROMIUM ABATEMENT
CIVIL
C-001 ABBREVIATIONS, GENERAL NOTES AND LEGEND
CD101 DEMOLITION PLAN
CS101 SITE PLAN
CU101 UTILITIES PLAN
C-501 MISCELLANEOUS DETAILS - 1
C-502 MISCELLANEOUS DETAILS - 2
C-503 MISCELLANEOUS DETAILS - 3
C-504 MISCELLANEOUS DETAILS - 4
C-505 MISCELLANEOUS DETAILS - 5
ARCHITECTURAL
A-001 GENERAL NOTES, ABBREVIATIONS
AD101 OVERALL FIRST FLOOR PLAN - DEMOLITION
AD102
OVERALL TYPICAL FLOOR PLAN - 2ND TO 9TH FL -
DEMOLITION
AD111 OVERALL FIRST FLOOR RCP - DEMOLITION
AD112 OVERALL TYPICAL RCP - 2ND TO 7TH FL - DEMOLITION
AD121 OVERALL ROOF PLAN AT PH1 - DEMOLITION
AD201 OVERALL BUILDING ELEVATIONS - DEMOLITION
AD202 OVERALL BUILDING ELEVATION - DEMOLITION
AD401
ENLARGED PARTIAL FIRST FLOOR PLAN - AREA B,C,E -
DEMOLITION
AD402
ENLARGED PARTIAL FIRST FLOOR PLAN - AREA A, D -
DEMOLITION
AD403
ENLARGED PARTIAL FLOOR PLAN - 2ND TO 9TH FL - AREA
E - DEMOLITION
AD404
ENLARGED TYPICAL UNITS A AND B FLOOR PLANS -
DEMOLITION
AD411
ENLARGED PARTIAL FIRST FLOOR RCP - AREA B,C,E -
DEMOLITION
AD412
ENLARGED PARTIAL FIRST FLOOR RCP - AREA A, D -
DEMOLITION
AD413
ENLARGED PARTIAL FLOOR PLAN - 2ND TO 7TH FL - AREA
E
AD414 ENLARGED TYPICAL UNIT A AND B RCP - DEMOLITION
AD415 ENLARGED PARTIAL RCP - 8 TH FL - AREA E - DEMOLITION
AD416 ENLARGED PARTIAL RCP - 9TH FL - AREA E - DEMOLITION
A-101 OVERALL FIRST FLOOR PLAN
A-102 OVERALL TYPICAL FLOOR PLAN - 2ND TO 9TH FL
A-111 OVERALL FIRST FLOOR REFLECTED CEILING PLAN
A-112
OVERALL TYPICAL REFLECTED CEILING PLAN - 2ND TO
7TH FL
A-121 OVERALL ROOF PLAN AT PH1 AND PH2
A-201 OVERALL BUILDING ELEVATIONS
A-202 OVERALL BUILDING ELEVATIONS
A-301 OVERALL BUILDING SECTIONS
A-401 ENLARGED PARTIAL FIRST FLOOR PLAN - AREA B, C, E
A-402 ENLARGED PARTIAL FIRST FLOOR PLAN - AREA A, D
A-403
ENLARGED PARTIAL FLOOR PLAN - 2ND TO 9TH FL - AREA
E
A-404 ENLARGED TYPICAL UNIT TYPE A AND B FLOOR PLANS
A-411 ENLARGED PARTIAL FIRST FLOOR RCP - AREA B, C, E
A-412 ENLARGED PARTIAL FIRST FLOOR RCP - AREA A, D
A-413 ENLARGED PARTIAL RCP - 2ND TO 7TH FL - AREA E
A-414
ENLARGED TYPICAL UNIT A AND B REFLECTED CEILING
PLANS
A-415 ENLARGED PARTIAL RCP - 8TH FL - AREA E
A-416 ENLARGED PARTIAL RCP - 9TH FL - AREA E
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
PIV
E
E
DN
E
A1 SCALE: 1:300
TEMPORARY CONTRACTOR'S LAYDOWN AREA PLAN
SCALE 1:300
0 15000mm5000
PLAN NORTH
GENERAL SHEET NOTES
1. THE CONSTRUCTION LAYDOWN AREA SHOWN MUST BE
COORDINATED FOR REVIEW AND APPROVAL BY THE 718
CES/CENPL. THIS LAYOUT IS ALSO SUBJECT TO
CONFIRMATION BY THE CONTRACTING OFFICER PRIOR TO
MOBILIZATION.
2. THE CONSTRUCTION TRAILER LOCATION CAN ALSO BE
ACCOMMODATED WITHIN THE DESIGNATED LAYDOWN AREA
UPON COORDINATION WITH THE CONTRACTING OFFICER.
3. AFTER COMPLETION OF PROJECT, REMOVE TRAILERS,
MATERIALS, AND EQUIPMENT INCLUDING TEMPORARY
FENCING, SIGNS, BARRICADES AND OTHER TEMPORARY
STRUCTURES FROM THE SITE. RESTORE TO THE ORIGINAL
OR BETTER CONDITION FOR ALL AREAS USED BY THE
CONTRACTOR FOR THE STORAGE OF MATERIALS OR
EQUIPMENT OR OTHER USE.
4. THE EXISTING SEWAGE PUMP STATION WILL REMAIN
OPERATIONAL DURING THE CONSTRUCTION PERIOD.
CONTRACTOR MUST ALLOW GOVERNMENT WATER SHOP
REPRESENTATIVES TO ENTER THE PROJECT SITE AND
ACCESS THE SEWAGE PUMP STATION FOR PERIODIC
MAINTENANCE/CHECK OR NECESSARY REPAIRS.
LEGEND
BUILDING
SIDEWALK
AC PAVEMENT
CONCRETE CURB AND GUTTER
SODDING
CHAIN LINK FENCE
GRAVEL GROUNDCOVER
DECORATIVE BLOCK ENCLOSURE
CONCRETE CURB
DESCRIPTION
SODDING
RETRACTABLE BOLLARDS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
1 2 3 4 5
B
A
C
D
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N . M
IC
H
IG
AN
A
VE
SU
IT
E
C
H
IC
AG
O
, I L w w w
.e xp
Fe de ra l.c om pr oj . n o.
IS
O
A
EX
P
FE
D
ER
AL
US Army Corps of Engineers ®
JA
PA
N D
IS
TR
IC
T, O
KI
N
AW
A
AR
EA
O
FF
IC
E U
SA
ED
-J , U
N
IT
, A
PO
A
P
4-
AP
O
, A P
3-
L.
S
AB
AD
O
L.
M
AL
AB
AN
AN
K.
B
U
LL
C H
I-2
0- A0
FY
F
SR
M R
EN
O
VA
TE
M
FH
T O
W
ER
C
AM
P
C O
U R
TN
EY
, O
KI
N
AW
A, J
AP
AN
R
TA
S U
BM
IT
TA
L
M
AR
C H
- W
2H V1
9D
C
AB
T1
TE
M
PO
R
AR
Y
C O
N
TR
AC
TO
R 'S
LA
YD
O W
N A
R
EA
P
LA
N
GC001
C
AB
T1
9_
G C
1.
dw g
C
IV
IL
LAYDOWN AREA
LAYDOWN AREA
POINT OF
CONNECTION TO
EXST PERIMETER
FENCE (TYP)
TEMPORARY CONSTRUCTION FENCE
LA
YD
O W
N A
R
EACONTRACTOR'S
TEMPORARY
CONSTRUCTION
FENCE
EXISTING INSTALLATION
PERIMETER FENCE
FIRE TRUCK
ACCESS ONLY
(NORMALLY
CLOSED GATE)
POINT OF
CONNECTION TO
EXST PERIMETER
FENCE (TYP)
1S T
M
AR
IN
ES
S
TR
EE
T
CONTRACTOR'S MAIN
ENTRANCE/EXIT GATE
TENGAN RIVER
C-505 A1
C-505 A1
ALTERNATE VEHICLE
ENTRANCE/EXIT
TEMPORARY GATE (ACCORDION TYPE)
EXST SEWAGE PUMP STATION
(SEE GENERAL SHEET NOTE 4)
PROVIDE SIGNAGE INDICATING
THIS SPACE AS A RESERVED
PARKING FOR GOVERNMENT
WATER SHOP PERSONNEL
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X
X X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
PAVED
STORAGE
X
X
PAVED PARKING
PAVED PARKING
UNPAVED PARKING
CONC
CONC
CONC
CONCCONC
CONC
44944404
4496TS
4335 4332
43064228TS
4207 4205
4219TS
34458
4331 4458
4411TS
7TS
42434242
TOMBS
4201-A
4219B
4223TS
3B
4223A
4219C
4461TS
4409TS
4456 4456C
4456TS
4456B
456345624558TH4
457145 704547
44494439
4424A
4440A
4507 4511
POOL
4409A
44054405
4412TS
BRIDGE
4544A
PREF ROAD NO. 75
22nd MARINES DRIVE 4TH MARINE AVE.
BROWN STREET
BENHAN STREET
KELLEY ROAD
JACKSON STREET
BASE BALL FIELD
4417G
4417A
PLAY GROUND
4468A
24445
4417C
24458 2445934459
2444334443
2444234442 24444344442445734457
X
2441134411
PREF ROAD NO. 224
A1 SCALE: 1:3000
CONTRACTOR'S ACCESS AND HAUL ROUTE
SCALE 1:3000
0 150m50
PLAN NORTH
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
1 2 3 4 5
B
A
C
D
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N . M
IC
H
IG
AN
A
VE
SU
IT
E
C
H
IC
AG
O
, I L w w w
.e xp
Fe de ra l.c om pr oj . n o.
IS
O
A
EX
P
FE
D
ER
AL
US Army Corps of Engineers ®
JA
PA
N D
IS
TR
IC
T, O
KI
N
AW
A
AR
EA
O
FF
IC
E U
SA
ED
-J , U
N
IT
, A
PO
A
P
4-
AP
O
, A P
3-
L.
S
AB
AD
O
L.
M
AL
AB
AN
AN
K.
B
U
LL
C H
I-2
0- A0
FY
F
SR
M R
EN
O
VA
TE
M
FH
T O
W
ER
C
AM
P
C O
U R
TN
EY
, O
KI
N
AW
A, J
AP
AN
R
TA
S U
BM
IT
TA
L
M
AR
C H
- W
2H V1
9D
C
AB
T1
C O
N
TR
AC
TO
R 'S
A C
C
ES
S
AN
D H
AU
L
R O
U
TE
GC002
C
AB
T1
9_
G C
2.
dw g
C
IV
IL
CONTRACTOR'S HAUL
ROUTE
GATE #1
(MAIN GATE)
PROJECT SITE
GATE #3
(BLDG 4501)
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
CODE ANALYSIS - GENERAL
BUILDING USE DESCRIPTION
1. THE EXISTING COURTNEY TOWER, BUILDING 4511 WILL BE
SELECTIVELY DEMOLISHED AND RENOVATED.
2. THE BUILDING IS FULLY SPRINKLERED AND WILL BE EVALUATED
PER IBC BUILDING AREA/HEIGHT REQUIREMENTS FOR A
RESIDENTIAL GROUP R-2 OCCUPANCY. THE RENOVATED INTERIOR
PORTION OF THE BUILDING TO BE REPAIRED TO COMPLY WITH ALL
APPLICABLE LIFE SAFETY CODES FOR AN EXISTING APARTMENT
BUILDING OCCUPANCY.
APPLICABLE CODES, STANDARDS AND CRITERIA
1. INTERNATIONAL BUILDING CODE (IBC); 2021
2. NFPA 1, FIRE CODE; 2021 EDITION
3. NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS; 2022
EDITION
4. NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS; 2022 EDITION
5. NFPA 70, NATIONAL ELECTRICAL CODE; 2023 EDITION
6. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE; 2022
EDITION
7. NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES; 2022 EDITION
8. NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS; 2021 EDITION
9. NFPA 101, LIFE SAFETY CODE; 2021 EDITION
10. UFC 1-200-01, DOD BUILDING CODE (GENERAL BUILDING
REQUIREMENTS); 1 SEPT 2022
11. UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES;
CHANGE 6, 6 MAY 2021
12. UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEMS; 9
APR 2008; CHANGE 1, JAN 2010
13. UFC 4-010-01 - DOD MINIMUM ANTITERRORISM STANDARDS FOR
BUILDING: CHANGE 2; 30 JULY 2022
14. USACE ECB 2018-17, NEW REQUIREMENTS FOR VISUAL
NOTIFICATION FOR MASS NOTIFICATION SYSTEMS, REV 2, JAN 2022
15. JED FIRE PROTECTION DESIGN GUIDE
USE AND OCCUPANCY CLASSIFICATION ANALYSIS (UFC 3-600-01)
1. THE IBC SHALL BE UTILIZED TO DETERMINE THE OCCUPANCY
CLASSIFICATION AS IT RELATES TO ALLOWABLE CONSTRUCTION
TYPE, BUILDING HEIGHT, BUILDING AREA, BUILDING SEPARATION
DISTANCE, OCCUPANCY SEPARATION AND ASSOCIATED
REQUIREMENTS [§3-2.1.2]
2. NFPA 101 MUST BE UTILIZED TO DETERMINE THE OCCUPANCY
CLASSIFICATION AS IT RELATES TO FIRE/SMOKE RESISTANCE
RATING OF INTERIOR NON-LOAD BEARING PARTITIONS, MEANS OF
EGRESS, INTERIOR FINISH, FEATURES OF FIRE PROTECTION AND
ASSOCIATED REQUIREMENTS [§3-3.1.1]
3. COMPLY WITH NFPA 101 FOR ALL COMPONENTS AND FEATURES
RELATED TO MEANS OF EGRESS. IBC MUST NOT BE USED FOR ANY
MEANS OF EGRESS FEATURES [§10-1.1]
4. WHERE SPECIFIC CRITERIA IS PROVIDED IN NFPA 101 RELATED TO
OCCUPANCY LOCATION WITHIN A BUILDING, CONFORM TO THE
REQUIREMENTS OF NFPA BASED ON THE EQUIVALENT
CONSTRUCTION TYPE [§3-3.1.2]
EXISTING FACILITIES ANALYSIS (UFC 3-600-01)
1. THE COURTNEY TOWER, BUILDING 4511 REPAIR IS CLASSIFIED AS
MODIFICATION IN ACCORDANCE WITH NFPA 101 CHAPTER 43.
A. EXISTING FACILITIES MUST MEET THE REQUIREMENTS OF
NFPA 101, FOR EXISTING OCCUPANCIES AND ANY
DEFICIENCIES MUST BE REPAIRED TO MEET THE EXISTING
OCCUPANCY CHAPTERS OF NFPA 101 [§34-1.1 AND 34-1.2].
REFER TO LIFE SAFETY FLOOR PLANS FOR DEFICIENCIES
AND CORRECTIONS.
B. NEWLY CONSTRUCTED ELEMENTS, COMPONENTS, AND
SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF NEW
CONSTRUCTION IN NFPA 101 AND UFC 3-600-01.
LIFE SAFETY DEFICIENCIES WITH CORRESPONDING CORRECTION
1. THE EXIT ACCESS PATH FROM THE DWELLING UNIT TO THE
EXTERIOR BALCONY HAS A 100 MM THRESHOLD DIRECTLY IN
FRONT OF THE SLIDING DOOR LEADING TO THE BALCONY
EXCEEDING THE ALLOWABLE 13MM THRESHOLD.
A. PAINT THRESHOLD WITH YELLOW REFLECTIVE MATERIAL
PER USACE FPE.
2. THE EXISTING EXTERIOR STAIRWAYS DO NOT ALLOW RE-ENTRY
TO THE INTERIOR OF THE BUILDING.
A. NO RE-ENTRY PERMITTED DUE TO SECURITY ISSUES PER
USACE FPE.
3. THE INTERIOR EXIT STAIR WAS OBSERVED TO HAVE THE DOORS
ON EACH LEVEL HELD OPEN BY EITHER A DOOR BLOCK ON THE
FLOOR OR TIED OPEN USING A PLASTIC BAG.
A. LOCAL FIRE DEPARTMENT AND BUILDING MANAGER SHALL
ENFORCE AND EDUCATE OCCUPANTS OF THE ISSUE AND
POST SIGNS ON THE DOORS.
4. THE KNOX BOX IS LOCATED INSIDE THE BUILDING ADJACENT TO
THE FIRE ALARM MASS NOTIFICATION PANEL NEAR THE FRONT
ENTRANCE.
A. KNOX BOX TO BE RELOCATED OUTSIDE THE FRONT
ENTRANCE DOORS PER LOCAL FIRE DEPARTMENT REQUEST.
5. LED TEXTURAL SIGNS ARE NOT PROVIDED WITHIN THE BUILDING IN
ACCORDANCE WITH UFC 4-021-01.
A. PROVIDE LED TEXTURAL SIGNS AT ALL MAIN EXITS ON THE
EGRESS LEVEL AND AT THE DOORS TO THE INTERIOR EXIT
STAIR ON ALL LEVELS.
6. LOCAL OPERATING CONSOLES (LOC) SHALL BE PROVIDED IN
ACCORDANCE WITH UFC 4-021-01.
A. EACH LOC SHALL BE SECURED BUT NOT LOCKED AND
INCLUDE A TAMPER SWITCH THAT SENDS A SUPERVISORY
SIGNAL TO THE FACP AND THE FIRE DEPARTMENT.
CODE ANALYSIS - INTERNATIONAL BUILDING CODE
OCCUPANCY CLASSIFICATION
BUILDING HEIGHT AND AREA SUMMARY
BUILDING CONSTRUCTION TYPE
SPRINKLER SYSTEM
IB
FULLY SPRINKLERED
BUILDING HEIGHT (R-2 & S-2)
ACTUAL MAXIMUM ALLOWED
30 M 54.9 M
NUMBER OF STORIES (R-2 & S-2) 9 STORIES 12 STORIES
TABULAR FLOOR AREA PER STORY
OCCUPANCY
BUILDING AREA ANALYSIS
FLOOR AREA PER STORY ACTUAL MAXIMUM ALLOWED
SECOND - NINTH FLOOR
TOTAL BUILDING AREA
IBC CODE COMPLIANT YES
STRUCTURAL FIRE RESISTANCE RATING [TABLE 601 AND TABLE 705.5]
REQUIRED STRUCTURAL FIRE RESISTANCE RATING SUMMARY - TYPE IB
STRUCTURAL ELEMENT
BEARING WALLS
FIRE RESISTANCE
RATING
EXTERIOR
INTERIOR
NON-LOAD
BEARING WALLS
EXTERIOR: < 9.14 M SEPARATION
≥ 9.14 M SEPARATION
INTERIOR
PRIMARY STRUCTURAL MEMBERS
FLOOR CONSTRUCTION (INCLUDING BEAMS)
ROOF CONSTRUCTION AND ASSOCIATED SECONDARY
STRUCTURAL MEMBERS
2-HOUR
2-HOUR
1-HOUR
0-HOUR
0-HOUR
2-HOUR
2-HOUR
1-HOUR
OCCUPANCY CLASSIFICATION BY FLOOR - IBC
FLOOR
FIRST LEVEL
SECOND - NINTH LEVEL
RESIDENTIAL GROUP R-2,
STORAGE GROUP S-2
RESIDENTIAL GROUP R-2
OCCUPANCY CLASSIFICATION
STORAGE GROUP S-2
ACCESSORY OCCUPANCY
N/A
TYPE OF CONSTRUCTION
1. TYPE IB
OCCUPANCY SEPARATION
1. MIXED NON-SEPARATED OCCUPANCY USE
BUILDING HEIGHT AND AREA ANALYSIS [TABLE 504.3, TABLE 504.4, AND TABLE 506.2]
FIRST FLOOR 1,634 SM
13,746 SM
GROUP R-2
GROUP S-2
UNLIMITED SM
22,000 SM
SPRINKLERED
CODE ANALYSIS - GENERAL (CON'T)
FIRE PROTECTION SYSTEMS
1. FIRE SPRINKLER SYSTEM - GENERAL
A. THE BUILDING IS CURRENTLY PROTECTED WITH A
SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM WITH
ALLOWABLE OMISSIONS.
2. FIRE STANDPIPE SYSTEM - GENERAL
A. THE BUILDING IS CURRENTLY PROVIDED WITH AN AUTOMATIC
CLASS I STANDPIPE SYSTEM.
3. FIRE PUMP - GENERAL
A. THE BUILDING'S FIRE SUPPRESSION AND STANDPIPE
SYSTEMS FLOWS AND PRESSURES ARE SUPPLIED BY A
REMOTE FIRE PUMP SYSTEM.
4. PORTABLE FIRE EXTINGUISHERS - GENERAL
A. GENERAL PURPOSE PORTABLE FIRE EXTINGUISHERS
PROVIDED IN ACCORDANCE WITH NFPA 101, INSTALLED IN
ACCORDANCE WITH NFPA 10.
FIRE ALARM AND MASS NOTIFICATION SYSTEMS
1. FIRE DETECTION/ALARM SYSTEMS - GENERAL
A. ADDRESSABLE FIRE ALARM SYSTEM PROVIDED
THROUGHOUT THE BUILDING.
2. NOTIFICATION
A. NOTIFICATION DEVICES PROVIDED THROUGHOUT THE
BUILDING IN ALL AREAS WHERE REQUIRED BY NFPA 101 AND
UFC 3-600-01.
3. MASS NOTIFICATION SYSTEM
A. MASS NOTIFICATION SYSTEM PROVIDED THROUGHOUT USING
SINGLE CLEAR STROBE AND LED TEXT SIGNS IN
ACCORDANCE WITH UFC 4-021-01.
1,514 SM
22,000 SM
UNLIMITED SM
HAZARDOUS AREA PROTECTION
1. ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO
THE GENERAL OCCUPANCY [§8.7.1.1]
A. 1-HOUR FIRE BARRIER WALL
B. AUTOMATIC SPRINKLER SYSTEM [§8.7.1.1]
C. BOTH 1-HOUR FIRE RESISTANCE RATING AND SPRINKLER SYSTEM IF
SEVERE HAZARD IS PRESENT
OTHER REQUIRED MINIMUM FIRE RESISTANCE RATED SEPARATION
OPENING PROTECTIVES [TABLE 8.3.3.2.2]
BUILDING USE AREA REQUIRED FIRE BARRIER
VERTICAL OPENINGS AND EXIT ENCLOSURES REQUIRED FIRE BARRIER
VERTICAL OPENINGS REQUIRED FIRE BARRIER
EXIT ENCLOSURES
COMPONENT WALL &
PARTITIONS
FIRE DOOR
ASSEMBLIES
MINIMUM FIRE-RATED WINDOWS RATING
FIRE PROTECTION FIRE RESISTANCE
FIRE
BARRIERS
2-HOUR 1 1/2-HOUR 2-HOURNOT PERMITTED
FIRE
BARRIERS
1-HOUR 3/4-HOUR 3/4-HOUR3/4-HOUR
INTERIOR FINISH ANALYSIS WITH SPRINKLER PROTECTION
OCCUPANCY EXIT ENCLOSURES
EXISTING APARTMENT
BUILDINGS
FLOOR FINISH
CLASS B
[§31.3.3.2]
NO REQ
[§31.3.3.3]
MEANS OF EGRESS GENERAL
1. OCCUPANT LOAD FACTOR [TABLE 7.3.1.2 / UFC 3-600-01 TABLE 10-1]
A. RESIDENTIAL: 18.6 SM/PERSON
B. MECH,ELEC, BUILDING EQUIP. USE: 46.5 SM/PERSON
C. STORAGE ROOMS: 46.5 SM/PERSON
2. CAPACITY OF MEANS OF EGRESS
A. EGRESS WIDTH REQUIRED PER PERSON [TABLE 7.3.3.1]
a. HORIZONTAL EGRESS TRAVEL: 5 MM/PERSON
b. VERTICAL EGRESS TRAVEL: 7.6 MM/PERSON
B. MINIMUM EGRESS WIDTH REQUIRED
a. CORRIDORS : 914 MM [§7.3.4.1]
b. CORRIDORS: 1120 MM [§38.2.3.3]
c. EXIT DOOR OPENING: 813 MM [§7.2.1.2.3.2]
3. NUMBER AND ARRANGEMENT OF MEANS OF EGRESS, INCLUDING EXIT
DISCHARGE
A. MINIMUM NUMBER OF EXITS FROM ROOMS AND AREAS: 2 [§7.4.1.1]
4. ARRANGEMENT OF EXITS
A. WHERE 2 OR MORE EXITS ARE REQUIRED, THEY MUST BE
SPACED APART A MINIMUM OF 1/3 THE LENGTH OF THE MAXIMUM
DIAGONAL OF THE BUILDING OR AREA BEING SERVED [§7.5.1.3.3]
5. EXIT DISCHARGE
A. EXITS SHALL DISCHARGE DIRECTLY TO THE BUILDING EXTERIOR
[§7.7.1]
B. THE EXIT DISCHARGE SHALL PROVIDE DIRECT AND
UNOBSTRUCTED ACCESS TO A PUBLIC WAY [§7.7.3.2]
C. ACCESS TO AN EXIT IS NOT TO BE THROUGH KITCHENS,
STOREROOMS, RESTROOMS, WORKROOMS, CLOSETS OR OTHER
ROOMS OR SPACES SUBJECT TO LOCKING [§7.5.2.1]
MEANS OF EGRESS COMPONENTS
1. DOORS
A. MINIMUM CLEAR WIDTH: 810 MM [§7.2.1.2.3.2]
B. SWING IN DIRECTION OF EGRESS TRAVEL WHEN USED IN AN EXIT
ENCLOSURE OR WHERE SERVING A HIGH HAZARD CONTENTS
AREA [§7.11.6]
C. DOORS ARE TO BE ARRANGED TO BE OPENED READILY FROM
THE EGRESS SIDE WHENEVER THE IS OCCUPIED. LOCKS, IF
SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
EGRESS SIDE [§7.2.1.5.1/§7.2.1.5.2]
2. HANDRAILS
A. HANDRAILS ARE TO BE LOCATED ON EACH SIDE OF THE
STAIRWAYS OR RAMPS [§7.2.2.4.1.1]
B. HANDRAIL HEIGHT TO BE NOT LESS THAN 865 MM AND NOT MORE
THAN 965 MM ABOVE THE SURFACE OF THE TREAD [§7.2.2.4.5.1]
C. THE HEIGHT OF REQUIRED HANDRAILS THAT FORM PART OF A
GUARD SHALL BE PERMITTED TO EXCEED 965 MM BUT SHALL NOT
EXCEED 1065 MM [§7.2.2.4.5.3]
D. HANDRAILS ARE TO BE PROVIDED WITHIN 760 MM OF ALL
PORTIONS OF THE REQUIRED EGRESS WIDTH OF STAIRS [§
7.2.2.4.1.2]
CODE ANALYSIS - LIFE SAFETY CODE (NFPA 101)
OCCUPANCY SEPARATION
1. MIXED NON-SEPARATED OCCUPANCY USE
OCCUPANCY CLASSIFICATION
OCCUPANCY CLASSIFICATION BY FLOOR - NFPA 101
FLOOR LEVEL
FIRST
OCCUPANCY CLASSIFICATION INCIDENTAL
OCCUPANCY
STORAGE
CLASS C
[§42.3.3.2]
CLASS II
[§42.3.3.3.1]
SECOND - NINTH
EXISTING APARTMENT BLDG, STORAGE
EXISTING APARTMENT BUILDING
UTILITY
STORAGE/UTILITY
TRASH COLLECTION ROOMS
CORRIDORS 1/2-HOUR [§31.3.6.1]
SHAFTS CONNECTING 4 STORIES OR MORE 2-HOUR [§8.6.5(1)]
EXIT ENCLOSURES CONNECTING 4 STORIES OR MORE 2-HOUR [EXISTING]
VERTICAL
SHAFTS
2-HOUR 1 1/2-HOUR 2-HOURNOT PERMITTED
INTERIOR FINISH
CLASS B
[§31.3.3.2]
CLASS C
[§42.3.3.1]
LOBBIES AND
CORRIDORS
OTHER
SPACES
CLASS C
[§31.3.3.2]
CLASS C
[§42.3.3.1]
EXIT TRAVEL DISTANCES
1. EXISTING APARTMENT BUILDINGS
A. TRAVEL DISTANCE
a. WITHIN GUEST ROOM - 38 M [§31.2.6.1]
b. CORRIDOR DOOR TO EXIT - 61 M [§31.2.6.2]
B. COMMON PATH OF TRAVEL
a. 15 M [§31.2.5.2.1]
C. DEAD END
a. 15 M [§31.2.5.3]
2. STORAGE
A. TRAVEL DISTANCE
a. 122 M [TABLE 42.2.6]
B. COMMON PATH OF TRAVEL
a. 30 M [TABLE 42.2.5]
C. DEAD END
a. 30 M [TABLE 42.2.5]
MARKING OF MEANS OF EGRESS
1. SIGNAGE
A. EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
VISIBLE FROM ANY DIRECTION OF EXIT ACCESS [§7.10.1.2]
B. SIGN PLACEMENT SHALL BE SUCH THAT NO POINT IN THE EXIT
ACCESS CORRIDOR IS MORE THAN 30 METERS FROM THE
NEAREST EXTERNALLY ILLUMINATED SIGN AND IS NOT IN
EXCESS OF THE MARKED RATING FOR INTERNALLY ILLUMINATED
SIGNS [§7.10.1.5.2]
C. A DIRECTIONAL SIGN READING "EXIT" WITH A DIRECTIONAL
INDICATOR SHOWING THE DIRECTION OF TRAVEL SHALL BE
PLACED IN EVERY LOCATION WHERE THE DIRECTION OF TRAVEL
TO REACH THE NEAREST EXIT IS NOT APPARENT [§7.10.2/7.10.3.1]
D. AT EACH DOOR INTO AN EXIT STAIR ENCLOSURE OR EXIT,
TACTILE SIGNAGE STATING "EXIT" AND COMPLYING WITH
ICC/ANSI A117.1 SHALL BE INSTALLED [§7.10.6.1.1]
2. ILLUMINATION
EVERY EXIT SIGN SHALL BE ILLUMINATED AT ALL TIMES. THE
ILLUMINATION SHALL BE FOR 90 MINUTES IN THE CASE OF
PRIMARY POWER LOSS [§7.8.2.2/§7.9.2.1]
EMERGENCY LIGHTING
1. EMERGENCY LIGHTING REQUIRED FOR EXIT ACCESS, EXITS AND EXIT
DISCHARGE AT ALL TIMES THAT THE BUILDING IS OCCUPIED [§7.8.1.1]
2. EMERGENCY ILLUMINATION IS REQUIRED TO BE AS FOLLOWS
A. ILLUMINATION OF MEANS OF EGRESS SHALL BE FOR A DURATION
OF 90 MIN AND THE EMERGENCY POWER SHALL BE FROM
BATTERIES, UNTIL EQUIPMENT OR GENERATORS [§7.8.2.2/§7.9.2.1]
B. REQUIRED ILLUMINATION SHALL BE ARRANGED SO THAT INITIAL
ILLUMINATION IS AT LEAST AN AVERAGE OF 10.8 LUX AND A
MINIMUM AT ANY POINT OF 1.1 LUX [§7.9.2.1]
C. A DECLINE TO 6.5 LUX AVERAGE ILLUMINATION AT THE FLOOR
WITH A MINIMUM .65 LUX AT ANY POINT IS PERMITTED AT THE
END OF THE EMERGENCY LIGHTING DURATION [§7.9.2.1].
D. A MAXIMUM TO MINIMUM ILLUMINATION UNIFORMITY RATIO OF
40:1 SHALL NOT BE EXCEEDED [§7.9.2.1]
CODE ANALYSIS - LIFE SAFETY CODE (NFPA 101) - (CON'T)
PENTHOUSE STORAGE
1-HOUR OR SPRINKLERS [§31.3.2.1.1]
SHEET NOTES
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
FIRE
BARRIERS
1/2-HOUR 1/3-HOUR 1/3-HOUR1/3-HOUR
ALL DOORS OPENING ONTO AN EXIT ACCESS CORRIDOR SHALL HAVE NOT LESS
A 20-MIN FIRE PROTECTION RATING AND SHALL BE SELF-CLOSING AND
SELF-LATCHING.
ALL DUCT PENTRATIONS OF 2-HOUR FIRE BARRIER WALLS SHALL HAVE A 1 1/2-HR
FIRE DAMPER INSTALLED. ALL AIR-TRANSFER OPENING IN FIRE RATED WALL SHALL
HAVE A FIRE DAMPER INSTALLED ALL OTHER PENETRATIONS (PIPE, CONDUIT, ETC)
SHALL BE SEALED USING A LISTED FIRE STOPPING SYSTEM.
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
L
IF
E S
A F
E T
Y C
O D
E A
N A
L Y
S
IS
GI001
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
DOOR EGRESS CAPACITY FACTOR 5 MM / PERSON
MINIMUM NUMBER OF EXITS REQUIRED 2 EXITS
MINIMUM NUMBER OF EXITS PROVIDED 7 EXITS
CODE COMPLIANT YES
EGRESS CAPACITY ANALYSIS - FIRST FLOOR
EXIT 8
EXIT 2
EXIT NUMBER
STAIR EGRESS CAPACITY FACTOR 7.6 MM / PERSON
DOOR CAPACITY STAIR CAPACITY LIMITING CAPACITY
170 175
2,379 PERSONSTOTAL EGRESS CAPACITY
95 PERSONSCALCULATED NUMBER OF OCCUPANTS
NUMBER OF EXITS SUMMARY
EGRESS CAPACITY SUMMARY
EXIT 3
EXIT 4
EXIT 5
340 N/AEXIT 6
340 EXIT 7
N/A
N/A
DOOR EGRESS CAPACITY FACTOR 5 MM / PERSON
MINIMUM NUMBER OF EXITS REQUIRED 2 EXITS
MINIMUM NUMBER OF EXITS PROVIDED 5 EXITS
CODE COMPLIANT YES
EGRESS CAPACITY ANALYSIS - SECOND THROUGH NINTH FLOORS
EXIT 2
EXIT NUMBER
STAIR EGRESS CAPACITY FACTOR 7.6 MM / PERSON
DOOR CAPACITY STAIR CAPACITY LIMITING CAPACITY
170 175
849 PERSONSTOTAL EGRESS CAPACITY
90 PERSONSCALCULATED NUMBER OF OCCUPANTS
NUMBER OF EXITS SUMMARY
EGRESS CAPACITY SUMMARY
EXIT 3
EXIT 4
EXIT 5
EXIT 1 170 169 169
DOOR EGRESS CAPACITY FACTOR 5 MM / PERSON
MINIMUM NUMBER OF EXITS REQUIRED 1 EXITS
MINIMUM NUMBER OF EXITS PROVIDED 1 EXITS
CODE COMPLIANT YES
EGRESS CAPACITY ANALYSIS - PENTHOUSE
EXIT 1
EXIT NUMBER
STAIR EGRESS CAPACITY FACTOR 7.6 MM / PERSON
DOOR CAPACITY STAIR CAPACITY LIMITING CAPACITY
170 169
169 PERSONSTOTAL EGRESS CAPACITY
9 PERSONSCALCULATED NUMBER OF OCCUPANTS
NUMBER OF EXITS SUMMARY
EGRESS CAPACITY SUMMARY
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
SHEET NOTES
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
L
IF
E S
A F
E T
Y O
C C
U P
A N
C Y
C A
L C
U L A
T
IO
N S
GI002
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
OCCUPANT LOAD SCHEDULE - FLOOR 1
ROOM NAME Number Area
OCCUPANCY LOAD
FACTOR (PER
PERSON) OCCUPANCY USE
OCCUPANT
LOAD Level
DWELLING
UNIT
103 131 m² 19 m² RESIDENTIAL (NFPA 101)
8 LEVEL 1
DWELLING
UNIT
104 131 m² 19 m² RESIDENTIAL (NFPA 101)
8 LEVEL 1
DWELLING
UNIT
105 131 m² 19 m² RESIDENTIAL (NFPA 101)
8 LEVEL 1
DWELLING
UNIT
105 131 m² 19 m² RESIDENTIAL (NFPA 101)
8 LEVEL 1
ELEV LOBBY L01 164 m² 19 m² RESIDENTIAL (NFPA 101)
9 LEVEL 1
PIPE SPACE L02 4 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 1
PIPE SPACE L03 6 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 1
PIPE SPACE L04 4 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 1
PIPE SPACE L05 3 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 1
JAN L06 3 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
MECH RM L07 11 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 1
TOILET L08 3 m² 19 m² RESIDENTIAL (NFPA 101)
1 LEVEL 1
STORAGE L09 19 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
TRASH L10 44 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
EBS L10A 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
EBS L10B 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
EBS L10C 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
EBS L10D 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
STORAGE L12 57 m² 46 m² STORAGE (NFPA 101) 2 LEVEL 1
STORAGE L13 58 m² 46 m² STORAGE (NFPA 101) 2 LEVEL 1
STORAGE L14 58 m² 46 m² STORAGE (NFPA 101) 2 LEVEL 1
COMMUNITY
RM
L15 40 m² 1 m² ASSEMBLY -
UNCONCENTRATED
(NFPA 101)
29 LEVEL 1
STORAGE L16 40 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 1
ELEC RM L17 92 m² 46 m² BUILDING UTILITY (UFC) 2 LEVEL 1
MECH RM L18 114 m² 46 m² BUILDING UTILITY (UFC) 3 LEVEL 1
OCCUPANT LOAD SCHEDULE - FLOOR 2-9
ROOM NAME Number Area
OCCUPANCY LOAD
FACTOR (PER
PERSON) OCCUPANCY USE
OCCUPANT
LOAD Level
DWELLING
UNIT
201 132 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
202 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
203 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
204 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
205 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
206 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
207 130 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
DWELLING
UNIT
208 131 m² 19 m² RESIDENTIAL (NFPA 101) 8 LEVEL 2
ELEV LOBBY C01 171 m² 19 m² RESIDENTIAL (NFPA 101) 10 LEVEL 2
PIPE SPACE C02 6 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 2
PIPE SPACE C03 4 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 2
PIPE SPACE C04 4 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 2
PIPE SPACE C05 4 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 2
JC C06 3 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
STORAGE C07 3 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
MECH/ELEC C08 7 m² 46 m² BUILDING UTILITY (UFC) 1 LEVEL 2
STORAGE C09 3 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10A 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10B 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10C 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10D 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10E 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10F 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10G 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
EBS C10H 2 m² 46 m² STORAGE (NFPA 101) 1 LEVEL 2
OCCUPANT LOAD SCHEDULE - PENTHOUSE
ROOM NAME Number Area
OCCUPANCY LOAD
FACTOR (PER
PERSON) OCCUPANCY USE
OCCUPANT
LOAD Level
PIPE SPACE P02 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
LOBBY P02 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
PIPE SPACE P03 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
PIPE SPACE P04 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
PIPE SPACE P05 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
MECH RM P06 7 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
MECH/ELEC P08 6 m² 46 m² BUILDING UTILITY (UFC) 1 PH1FL
STORAGE P09 5 m² 46 m² STORAGE (NFPA 101) 1 PH1FL
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
CJP
CJP E
E
CJP
P
DN
PIV
E
E
E
E
4 45
14.4M
TO FDC
.5
M T
O F
D C
63.8M TO FDC
BUILDING 4511
BUILDING 4511
LIFE SAFETY KEYNOTE
EXISTING UNDERGROUND DOMESTIC WATER
SUPPLY LINE.
EXISTING UNDERGROUND SECTIONAL CONTROL
VALVE.
EXISTING FIRE HYDRANT.
4 EXISTING UNDERGROUND FIRE SUPPLY LINE.
5 EXISTING POST INDICATOR VALVE.
6 EXISTING FIRE DEPT. CONNECTION.
7 EXISTING 200 MM FIRE SUPPLY LINE FROM FIRE
PUMP HOUSE
FIRE SAFETY GENERAL NOTES
1. ALL INFORMATION SHOWN ON THIS SHEET IS FOR
INFORMATION ONLY TO SHOW SITE CODE
COMPLIANCE IN ACCORDANCE WITH UFC 3-600-01.
REFER TO CIVIL DRAWINGS FOR CIVIL SITE AND
UTILITY INFORMATION.
SYMBOL DESCRIPTION
LIFE SAFETY LEGEND
FIRE HOSE LAYOUT DISTANCE
DIST.
UNDERGROUND WATER SUPPLY
FIRE DEPARTMENT TRUCK ACCESS ROUTE
FD FIRE DEPARTMENT ACCESS
K KNOX BOX
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
PLAN NORTH
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
L
IF
E S
A F
E T
Y C
O D
E C
O M
P L
IA
N
C E
S
IT
E P
L A
N
GI003
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
1 : 300 A1
LIFE SAFETY CODE COMPLIANCE SITE PLAN
0 15000 mm
1:300
SCALE
K
FD
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
S
P PP P
P P
P
1 2 3 4 5 6 7
8 9
A
B
C
D
E
F
G
H
MECHANICAL RM
L18
STORAGE
L16
STORAGE ROOM
L13
STORAGE
L12
STORAGE
L14
STAIR (2)
ELECTRICAL RM
L17
TRASH STORAGE
L10
PIPE SPACE
L02
ELEV
ELEV
JAN CLOSET
L06
MECH & ELEC RM
L07
TOILET
L08
PIPE SPACE
L04
EBS
L10A
STORAGE
L09
PIPE SPACE
L03
STAIR (1)
EBS
L10D
PIPE SPACE
L05
EBS
L10B
STAIR (2)
STAIR (2)
STAIR (2)
COMMUNITY
ROOM
L15
F A
M N
A1 / GI101BA1 / GI101A
A1 / GI101D
A1 / GI101C
A G
I1 B
A G
I1 A
A G
I1 D
A G
I1 C
ENTRANCE
PORCH
L11
DWELLING UNIT
DWELLING UNIT
DWELLING UNIT
DWELLING UNIT
TD3 - 20 M
TD2 - 24 M
TD1 - 30 M
TD4 - 19 M
EXIT8
EXIT7
EXIT6
170 175
7.6
EXIT3
170 175
7.6
EXIT2
170 175
7.6
EXIT4
170 175
7.6
EXIT5
TD5 - 22 M
ASSEMBLY USE
RESIDENTIAL USE
MECH/ELEC/BUILDING EQUIP. USE
STORAGE USE
OCCUPANCY USE LEGEND
SYMBOL DESCRIPTION
ROOM TAG
LIFE SAFETY LEGEND
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
EXIT
DEAD END
ABC FIRE EXTINGUISHER
1-HOUR FIRE RATED BARRIER
P P SMOKE PARTITION
DOOR
A
B
C
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
DOOR
A
B
C
D: STAIR CLEAR WIDTH (MM)
E: CAPACITY FACTOR (MM/PERSON)
F: EGRESS CAPACITY (PERSONS)
STAIR
D
E
F
2-HOUR FIRE RATED BARRIER
RM #
ROOM NAME
1/2-HOUR FIRE RATED BARRIER
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
SHEET NOTES
KEY PLAN
A B
C D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
PLAN NORTH
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
S
T F
L O
O R
L
IF
E S
A F
E T
Y P
L A
N
O V
E R
A L L
GI101
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
1 : 120 A1
1ST FLOOR LIFE SAFETY PLAN - OVERALL
0 6 m
1:120
2.4
SCALE
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
1 2 3 4
F
G
H
ELEV
ELEV
STAIR (2)
STAIR (2)
2 m² 1
S46 m²
L10D
EBS
L10D
2 m² 1
S46 m²
L10C
EBS
L10C
11 m² 1
BU46 m²
L07
MECH RM
L07
3 m² 1
S46 m²
L06
JAN
L06
2 m² 1
S46 m²
L10B
EBS
L10B
3 m² 1
BU46 m²
L05
PIPE
SPACE
L05
131 m² 7
R19 m²
DWELLING
UNIT
131 m² 7
R19 m²
DWELLING
UNIT
170 175
7.6
EXIT2
TD2 - 24 M
2 3
2 3
TD5 - 22 M
170 175
7.6
EXIT3
LIFE SAFETY KEYNOTE
THE THRESHOLD OF THE SLIDING GLASS DOOR TO
THE EXIT STAIR EXCEEDS THE 13MM HEIGHT AND
SHALL BE PAINTED WITH REFLECTIVE MATERIAL
TO WARN OCCUPANTS OF A TRIP HAZARD.
THE NEW STAIRWELL DOORS SHALL HAVE A 1 1/2-
HR FIRE RESISTANCE RATING WITH AUTOMATIC
SELF-CLOSURES AND A MAXIMUM 13MM DOOR
THRESHOLD.
THE NEW DOOR HARDWARE SHALL ONLY
REQUIRE ONE ACTION TO OPEN FROM THE
EGRESS SIDE.
THE EBS SPACE IS TENANT STORAGE
ASSEMBLY USE
RESIDENTIAL USE
MECH/ELEC/BUILDING EQUIP. USE
STORAGE USE
OCCUPANCY USE LEGEND
SYMBOL DESCRIPTION
ROOM TAG
LIFE SAFETY LEGEND
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
EXIT
DEAD END
ABC FIRE EXTINGUISHER
1-HOUR FIRE RATED BARRIER
P P SMOKE PARTITION
DOOR
A
B
C
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
DOOR
A
B
C
D: STAIR CLEAR WIDTH (MM)
E: CAPACITY FACTOR (MM/PERSON)
F: EGRESS CAPACITY (PERSONS)
STAIR
D
E
F
2-HOUR FIRE RATED BARRIER
RM #
ROOM NAME
1/2-HOUR FIRE RATED BARRIER
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
SHEET NOTES
KEY PLAN
A B
C D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
PLAN NORTH
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
S
T F
L O
O R
L
IF
E S
A F
E T
Y P
L A
N
A R
E A
A
GI101A
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
0 5 m
1:100
SCALE
1 : 100 A1
1ST FLOOR LIFE SAFETY PLAN - AREA A
EXIT TRAVEL DISTANCE 1ST FLOOR
TYPE START LOCATION MEASURED LENGTH (M) MAX LENGTH (M)
FLOOR
LEVEL
CPT1 STORAGE RM L14 30 30 FIRST
TD 2 CORRIDOR L01 24 61 FIRST
TD 3 DWELLING UNIT 105 20 38 FIRST
TD 4 MECH RM L18 19 122 FIRST
TD 5 DWELLING UNIT 104 22 122 FIRST
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
P PP P
P P
P
5 6 7
8 9
E
F
G
H
STAIR (2)
ELEV
ELEV
STAIR (2)
58 m² 2
S46 m²
L14
STORAGE
L14
40 m² 29
AU1 m²
L15
COMMUNITY
RM
L15
57 m² 2
S46 m²
L12
STORAGE
L12
164 m² 9
R19 m²
L01
ELEV
LOBBY
L01
3 m² 1
S46 m²
L06
JAN
L06
44 m² 1
S46 m²
L10
TRASH
L10
92 m² 3
BU46 m²
L17
ELEC RM
L17
4 m² 1
BU46 m²
L02
PIPE
SPACE
L02
EXIT8
EXIT6
170 175
7.6
EXIT3
170 175
7.6
EXIT2
2 3
LIFE SAFETY KEYNOTE
THE THRESHOLD OF THE SLIDING GLASS DOOR TO
THE EXIT STAIR EXCEEDS THE 13MM HEIGHT AND
SHALL BE PAINTED WITH REFLECTIVE MATERIAL
TO WARN OCCUPANTS OF A TRIP HAZARD.
THE NEW STAIRWELL DOORS SHALL HAVE A 1 1/2-
HR FIRE RESISTANCE RATING WITH AUTOMATIC
SELF-CLOSURES AND A MAXIMUM 13MM DOOR
THRESHOLD.
THE NEW DOOR HARDWARE SHALL ONLY
REQUIRE ONE ACTION TO OPEN FROM THE
EGRESS SIDE.
THE EBS SPACE IS TENANT STORAGE
ASSEMBLY USE
RESIDENTIAL USE
MECH/ELEC/BUILDING EQUIP. USE
STORAGE USE
OCCUPANCY USE LEGEND
SYMBOL DESCRIPTION
ROOM TAG
LIFE SAFETY LEGEND
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
EXIT
DEAD END
ABC FIRE EXTINGUISHER
1-HOUR FIRE RATED BARRIER
P P SMOKE PARTITION
DOOR
A
B
C
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
DOOR
A
B
C
D: STAIR CLEAR WIDTH (MM)
E: CAPACITY FACTOR (MM/PERSON)
F: EGRESS CAPACITY (PERSONS)
STAIR
D
E
F
2-HOUR FIRE RATED BARRIER
RM #
ROOM NAME
1/2-HOUR FIRE RATED BARRIER
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
SHEET NOTES
KEY PLAN
A B
C D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
PLAN NORTH
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
S
T F
L O
O R
L
IF
E S
A F
E T
Y P
L A
N
A R
E A
B
GI101B
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
1 : 100 A1
1ST FLOOR LIFE SAFETY PLAN - AREA B
EXIT TRAVEL DISTANCE 1ST FLOOR
TYPE START LOCATION MEASURED LENGTH (M) MAX LENGTH (M)
FLOOR
LEVEL
CPT1 STORAGE RM L14 30 30 FIRST
TD 2 CORRIDOR L01 24 61 FIRST
TD 3 DWELLING UNIT 105 20 38 FIRST
TD 4 MECH RM L18 19 122 FIRST
TD 5 DWELLING UNIT 104 22 122 FIRST
0 5 m
1:100
SCALE
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
A
B
C
D
ELEV
STAIR (1)
STAIR (2)
STAIR (2)
2 m² 1
S46 m²
L10A
EBS
L10A
4 m² 1
BU46 m²
L04
PIPE
SPACE
L04
3 m² 1
R19 m²
L08
TOILET
L08
2 m² 1
S46 m²
L10D
EBS
L10D
2 m² 1
S46 m²
L10C
EBS
L10C
11 m² 1
BU46 m²
L07
MECH RM
L07
131 m² 7
R19 m²
DWELLING
UNIT
131 m² 7
R19 m²
DWELLING
UNIT
170 175
7.6
EXIT4
TD3 - 20 M
2 3
2 3
170 175
7.6
EXIT3 4
LIFE SAFETY KEYNOTE
THE THRESHOLD OF THE SLIDING GLASS DOOR TO
THE EXIT STAIR EXCEEDS THE 13MM HEIGHT AND
SHALL BE PAINTED WITH REFLECTIVE MATERIAL
TO WARN OCCUPANTS OF A TRIP HAZARD.
THE NEW STAIRWELL DOORS SHALL HAVE A 1 1/2-
HR FIRE RESISTANCE RATING WITH AUTOMATIC
SELF-CLOSURES AND A MAXIMUM 13MM DOOR
THRESHOLD.
THE NEW DOOR HARDWARE SHALL ONLY
REQUIRE ONE ACTION TO OPEN FROM THE
EGRESS SIDE.
THE EBS SPACE IS TENANT STORAGE
ASSEMBLY USE
RESIDENTIAL USE
MECH/ELEC/BUILDING EQUIP. USE
STORAGE USE
OCCUPANCY USE LEGEND
SYMBOL DESCRIPTION
ROOM TAG
LIFE SAFETY LEGEND
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
EXIT
DEAD END
ABC FIRE EXTINGUISHER
1-HOUR FIRE RATED BARRIER
P P SMOKE PARTITION
DOOR
A
B
C
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
DOOR
A
B
C
D: STAIR CLEAR WIDTH (MM)
E: CAPACITY FACTOR (MM/PERSON)
F: EGRESS CAPACITY (PERSONS)
STAIR
D
E
F
2-HOUR FIRE RATED BARRIER
RM #
ROOM NAME
1/2-HOUR FIRE RATED BARRIER
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING
STAMP WITH SIGNATURE TO THE AS-BUILT DRAWINGS AND
FINAL CALCULATIONS INDICATING APPROVAL PRIOR TO
SUBMITTING TO USACE FOR REVIEW AND APPROVAL. UPON
USACE APPROVAL THE AS-BUILT DRAWINGS AND
CALCULATIONS WILL BE SENT TO THE AHJ FOR REVIEW AND
APPROVAL.
SHEET NOTES
KEY PLAN
A B
C D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
F
IL
E N
A M
E
IS
S
U E
D A
T E
1 2 3 4 5
B
A
C
D
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
M
IC
H
IG
A
N A
V E
S U
IT
E
C H
IC
A
G O
IL
w w w .e xp F e d e ra l.
c o m p ro j.
n
A
E X
P F
E D
E R
A L
PLAN NORTH
US Army Corps of Engineers ®
G E
N E
R A
L
F Y
F
S R
M R
E N
O V
A T
E M
F H
T O
W E
R
C A
M P
C O
U R
T N
E Y
O
K
IN
A W
A J A
P A
N
S
T F
L O
O R
L
IF
E S
A F
E T
Y P
L A
N
A R
E A
C
GI101C
R T
A S
U B
M
IT
T A
L
J A
P A
N D
IS
T
R
IC
T U
S A
E D
-J U
N
IT
A P
O A
P
-5
E X
P F
E D
E R
A L
T C
H R
IS
T
E N
S E
N
Y P
A R
K
M A
R C
H
W H
V D
C H
I- -A
C A
B T
F
P .r v t
C A
B T
1 : 100 A1
1ST FLOOR LIFE SAFETY PLAN - AREA C
EXIT TRAVEL DISTANCE 1ST FLOOR
TYPE START LOCATION MEASURED LENGTH (M) MAX LENGTH (M)
FLOOR
LEVEL
CPT1 STORAGE RM L14 30 30 FIRST
TD 2 CORRIDOR L01 24 61 FIRST
TD 3 DWELLING UNIT 105 20 38 FIRST
TD 4 MECH RM L18 19 122 FIRST
TD 5 DWELLING UNIT 104 22 122 FIRST
0 5 m
1:100
SCALE
R
T A
S U
B M
IT
T
A L
/2
/2
S O
L
IC
IT
A
T
IO
N N
O
W H
V -2
-B
-0
FOR IN
FORMATIO
5 6 7 8 9
A
B
C
D
STAIR (2)
ELEV
STAIR (1)
STAIR (2)
57 m² 2
S46 m²
L12
STORAGE
L12
40 m² 1
S46 m²
L16
STORAGE
L16
58 m² 2
S46 m²
L13
STORAGE
L13
114 m² 3
BU46 m²
L18
MECH RM
L18
19 m² 1
S46 m²
L09
STORAGE
L09
6 m² 1
BU46 m²
L03
PIPE
SPACE
L03
164 m² 9
R19 m²
L01
ELEV
LOBBY
L01
2 m² 1
S46 m²
L10A
EBS
L10A
EXIT8
EXIT7
170 175
7.6
EXIT3
170 175
7.6
EXIT4
CPT1 - 30 M
TD4 - 19 M
F A
M N
2 3
LIFE SAFETY KEYNOTE
THE THRESHOLD OF THE SLIDING GLASS DOOR TO
THE EXIT STAIR EXCEEDS THE 13MM HEIGHT AND
SHALL BE PAINTED WITH REFLECTIVE MATERIAL
TO WARN OCCUPANTS OF A TRIP HAZARD.
THE NEW STAIRWELL DOORS SHALL HAVE A 1 1/2-
HR FIRE RESISTANCE RATING WITH AUTOMATIC
SELF-CLOSURES AND A MAXIMUM 13MM DOOR
THRESHOLD.
THE NEW DOOR HARDWARE SHALL ONLY
REQUIRE ONE ACTION TO OPEN FROM THE
EGRESS SIDE.
THE EBS SPACE IS TENANT STORAGE
ASSEMBLY USE
RESIDENTIAL USE
MECH/ELEC/BUILDING EQUIP. USE
STORAGE USE
OCCUPANCY USE LEGEND
SYMBOL DESCRIPTION
ROOM TAG
LIFE SAFETY LEGEND
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
EXIT
DEAD END
ABC FIRE EXTINGUISHER
1-HOUR FIRE RATED BARRIER
P P SMOKE PARTITION
DOOR
A
B
C
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
A: DOOR CLEAR WIDTH (MM)
B: CAPACITY FACTOR (MM/PERSON)
C: EGRESS CAPACITY (PERSONS)
EGRESS CAPACITY TAG
DOOR
A
B
C
D: STAIR CLEAR WIDTH (MM)
E: CAPACITY FACTOR (MM/PERSON)
F: EGRESS CAPACITY (PERSONS)
STAIR
D
E
F
2-HOUR FIRE RATED BARRIER
RM #
ROOM NAME
1/2-HOUR FIRE RATED BARRIER
1. LIFE SAFETY AS-BUILT CONSTRUCTION DRAWINGS AND FINAL
CALCULATIONS SHALL BE PREPARED BY THE QFPE. THE
QFPE MUST AFFIX…