FINAL PLANS S30254.pdf

PDF 790 KB Posted

Attached to
S30254 Kahului Harbor, Replace Fire Risers at Pier 1 Shed, Maui
Solicitation number
B26002764
Issued by
Maui County, Hawaii

About this file

This is a final plans document for the State of Hawaii, Department of Transportation, Harbors Division, related to Project S30254 at Kahului Harbor on Maui. The project scope consists of replacing two fire risers and repairing a portion of the fire suppression system at Pier 1 Shed in Kahului Harbor. The plans provide detailed engineering specifications, drawings, and technical requirements necessary for contractors to bid on and execute the work. The document includes comprehensive design plans showing the location of existing fire risers, proposed replacement components, connection details, and repair specifications for the fire suppression infrastructure at the shed facility.

The final plans establish the technical baseline and performance standards that bidders must follow in submitting proposals for this harbor infrastructure improvement project. The plans contain detailed specifications regarding materials, installation methods, testing procedures, and compliance requirements for the fire riser replacement and suppression system repairs. Contract start and end dates are estimated in the HIePRO solicitation, with exact dates to be provided by written notice from the Harbors Construction Engineer. The project is located in Hawaii and represents a maintenance and upgrade initiative for critical fire safety infrastructure at this active port facility.

View the file

Other files

File Type Posted
FINAL SPECIFICATIONS w NTB S30254.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HARBORS

STATE OF HAWAII

DEPARTMENT OF TRANSPORTATION

SHEET

1 2

0F SHTS.

STATE OF HAWAII

DEPARTMENT OF TRANSPORTATION

DATE

APPROVED BY:

HAWAII

MAUI

LANAI

MOLOKAI

OAHU

KAUAI

HAWAIIAN ISLANDS

P A C I F I C O

C E A N

PROJECT

N O

R T

H

PROJECT

LOCATION

LOCATION

FOR DIRECTOR OF TRANSPORTATION

N

O R

T H

ISLAND OF MAUI

N O

R T

H

PIER 2

HOBRON AVENUE

W H

A R F

S T R E E T

P U

U N E

N E

A V E

N U E

K A

A H

U M

A N

U

A V

E N

U E

P I E

R

PIER 1APIER 1B

OFFICE

DISTRICT

HARBORS

P A C I F I C O

C E A N

PIER 1 SHED

KAHULUI HARBOR

NTS

AT PIER 1 SHED, MAUI, HAWAII

KAHULUI HARBOR, REPLACE FIRE RISERS

S30254

04/21/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAA5oB1JCyHzYmR1drYJ7kdyjxnkwMIQPdx

REV DATE DESCRIPTION BY APPROVED

SHEET TITLE

JOB TITLE

JOB NUMBER

DESIGNED BY:

DRAWN BY:

CHECKED BY:

DATE:

SCALE:

SHEET

AS SHOWN

JM

JM

0F SHTS.2 2

S T A T E O F H A W A I I

DEPARTMENT OF TRANSPORTATION

HARBORS

S30254

FIRE RISER LAYOUT & DETAILS

PIER SHED PLAN & SECTIONS,

GENERAL NOTES:

AF

MAR. 2026

SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.11.

ACCESSIBLE AND AVAILABLE.

CONTACT INFORMATION MUST BE IN LOCATIONS THAT ARE READILY

CONSTRUCTION ENGINEER IMMEDIATELY (I.E. WITHIN 24-HOURS). SUCH

HARBORS ENVIORNMENTAL HOTLINE (808-587-1962) AND THE HARBORS

AGENCIES FOLLOWING NOTIFICATION PROCEDURES, AND SHALL NOTIFY

FACILITY PERSONNEL, EMERGENCY RESPONSE AGENCIES, AND REGULATORY

SUBSTANCE OR OIL, THE CONTRACTOR SHALL NOTIFY APPROPRIATE

IN CASE OF SPILL, LEAK, OR OTHER RELEASE CONTAINING A HAZARDOUS 10.

ADJACENT HARBOR WATERS.

THROUGHT THE HARBORS SMALL MS4 OR OTHER POTENTIAL PATHWAYS INTO

POLLUTANTS ARE ALLOWED TO BE DISCHARGED DIRECTLY OR INDIRECTLY

STATE OF HAWII DOT HARBORS STORMWATER MANAGEMENT PROGRAM. NO

THE CONTRACTOR SHALL COMPLY WITH THE CLEAN WATER ACT AND THE 9.

423-7287.

HAWAII ONE CALL CENTER (HOCC) BEFORE EXCAVATION (811) OR (866)-

ENGINEER PRIOR TO THE START OF ANY CONSTRUCTION WORK. CLEAR WITH

(BMPs) PLAN AND HEALTH & SAFETY PLAN TO HARBORS CONSTRUCTION

CONTRACTOR SHALL SUBMIT A SITE-SPECIFC BEST MANAGEMENT PRACTICES 8.

SUCH DISCHARGES, OR APPROVED ACTIONS.

OBTAINING A NOTICE OF GENERAL PERMIT CONVERAGE (NGPC) AUTHORIZING

THE CONTRACTOR SHALL CONTACT THE HDOH CLEAN WATER BRANCH FOR

WATER FROM TESTING AND/OR DISINFECTION CANNOT BE CONTAINED,

AWWA STANDARD C651. FLUSH MAINS TO FIRE RISERS AND IF RESULTING

AND 13. THE NEW SYSTEM SHALL BE DISINFECTED AS SET FORTH IN THE

THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA STANDARD NO. 1 7.

ON ALL NEW HANGER RINGS, WHEN APPLICABLE.

BRACING) IN ACCORDANCE WITH NFPA 13 AND USE SURGE RESISTANT CLIPS

CONTRACTOR SHALL PROVIDE EARTHQUAKE PROTECTION (SWAY STRUTS &6.

SHALL BE UL LISTED OR FM APPROVED.

FIRE RISERS AND SUPPRESSION SYSTEM. ALL DEVICES AND EQUIPMENT

CONTRACTOR SHALL PREPARE AND PAINT ALL EXPOSED SURFACES OF NEW 5.

MEET ALL REQUIREMENTS OF THE LOCAL AUTHORITIES.

OF THE NATIONAL BOARD OF FIRE UNDERWRITERS (NBFU) STANDARDS TO

THE MANUFACTURER'S RECOMMENDATIONS, AND ALL APPLICABLE PROVISIONS

ASSOCIATION (NFPA) STANDARDS NO. 1 & 13, MAUI FIRE DEPARTMENT,

ALL WORK SHALL CONFORM TO THE NATIONAL FIRE PROTECTION 4.

ANY FIRE WHILE THE SYSTEM IS SHUT DOWN.

WATCHMEN SERVICES MAY BE REQUIRED TO ASSURE PROMPT DETECTION OF

THE SYSTEM SHALL NOT BE OFF-LINE MORE THAN 24 HOURS. SPECIAL

THE AMOUNT OF TIME THE FIRE PROTECTION SYSTEM IS OUT OF SERVICE.

INTERFERENECE WITH THE PIER AND SHED OPERATIONS AND TO MINIMIZE

MANAGER, CONSTRUCTION ENGINEER, AND TENANTS TO MINIMIZE ANY

ALL WORK SHALL BE COORDINATED WITH THE HARBORS MAUI DISTRICT 3.

STRUCTURES, UTILITIES AND EQUIPMENT IN THE AREA.

CONTRACTOR SHALL EXERCISE CAUTION TO PREVENT DAMAGE TO EXISTING 2.

ORDERING MATERIALS AND THE START OF WORK.

CONDITIONS, DIMENSIONS, AND QUANTIIES TO BE REPLACED PRIOR TO

SHALL BE VERIFIED PRIOR TO BIDDING. CONTRACTOR SHALL VERIFY FIELD

DIMENSIONS AND QUANTITIES ARE SHOWN FOR BIDDING PURPOSES AND 1.

AT PIER 1 SHED, MAUI, HAWAII

KAHULUI HARBOR, REPLACE FIRE RISERS

SCALE: 1" = 30'

SHED

WORK

APRON

EXISTING PIER

18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 COLUMN NOS.

NORTH

SOUTH

EAST

WEST

STORAGE SHED

PIER EDGE

STATION

COMFORT

17 BAYS @ 22' = 374'

STATION

COMFORT

PASSENGER TERMINAL

PIER 1 SHED FIRE SPRINKLER PLAN

VAULT

TRANS.

TO REMAIN

SYSTEM

SPRINKLER

EXIST. FIRE

TYPICAL

DOOR OPENING,

EXIST. ROLL-UP

SEE DETAIL AND SPECS.

CONNECTION INSIDE OF SHED.

REPLACE PIPING FROM TEE

REPLACE 8" FIRE RISER (NO. 1),

FENCE

EXIST.

SEE DETAIL AND SPECS.

CONNECTION INSIDE OF SHED.

REPLACE PIPING FROM TEE

REPLACE 8" FIRE RISER (NO. 2),

SHEDS

STORAGE DOORS, TYP.

EXIST. ROLL-UP

TO REMAIN

SYSTEM

SPRINKLER

EXIST. FIRE

PIER SHED SECTION

SCALE: 1" = 20' - 0"

WALL

EXIST. CONC.

RISER

NEW 8"

LINE

EXIST. F.S.

MAIN AND LATERALS

EXIST. CROSS

77' - 0" +55' - 0" +

ROOFING, TYP.

EXIST. BUILT-UP

TRUSSES, TYP.

EXIST. STEEL

& RISER PIPE

EXIST. SUPPLY LINE

AREA

ROOF

EXIST.

WALL

EXIST. PARAPET

SCALE: ¼" = 1' - 0"

ELEV. = + 25.5'

FEEDER LINE

NEW 8" 0

& LATERAL TO REMAIN

EXIST. CROSS MAIN

1'- 0"±

PURLINS, TYP.

EXIST. WOOD

NEW FIRE SUPPRESSION LAYOUT SECTION

4'- 8"±

NOTE: PREPARE AND PAINT ALL EXPOSED SURFACES OF NEW FIRE SUPPRESSION SYSTEM COMPONENTS.

W/ SPRINKLER HEADS TO REMAIN

EXIST. FIRE SPRINKLER LATERALS

INSIDE OF SHED.

REPLACE UP TO TEE CONNECTION

NEW 8" 0 FIRE RISER.

CONDUIT

EXIST. ELECTRICAL

& 4" CROSS MAIN

EXIST. 8" TEE CONNECTION

TRUSSES

EXIST. STEEL

FIXTURE, TYP.

EXIST. LIGHT MORE INFORMATION.

SEE DETAILS AND SPECS FOR

NEW SWAY STRUT ASSEMBLIES.

CONC. WALL

EXIST.

FOR MORE INFO.

SEE DETAILS AND SPECS

TO NEW FIRE RISER SYSTEM

TO MATCH EXISTING CONDITIONS.

SHALL BE REMOVED & REINSTALLED

ACCESS AND WINDOW PROTECTION

NEW FIRE RISER DETAIL

NOT TO SCALE

SEE SECTION VIEWS FOR DETAILS

TO FIRE SUPPRESSION SYSTEM.

WALL BEYOND

EXIST. CONC.

(SIZE TO FIT)

THREE (3) PER RISER

W/ RISER CLAMP, GALV.,

SWAY STRUT ASSEMBLY

PAVMENT

EXIST. A.C.

W/ MECHANICAL JOINT

EXIST. SUPPLY PIPING

THRUST BLOCK

EXIST. CONC.

NEW ALARM BELL

CHAMBER

NEW RETARD

NEW CHECK VALVE

DRAIN VALVE

NEW MAIN

VALVE

NEW CONTROL

CONNECTION

NEW FIRE DEPT.

IN PLACE

COMPONENTS TO REMAIN

EXIST. FIRE RISER

RISER PIPE

EXIST. 8" 0

NEW TEE CONNECTION

SGAGE

NEW PRESSURE

VALVE

NEW ALARM

RISER COMPONENTS

REPLACE WITH NEW FIRE

RISER COMPONENTS AND

REMOVE EXIST. FIRE

(SIZE TO FIT)

W/ RISER CLAMP, GALV.,

SWAY STRUT ASSEMBLY

TYP.

O.C., 10'- 9"

A A

B B

C C

A

HEAD, TYP.

EXIST. SPRINKLER

(N.I.C.), TYP.

EXIST. LATERALS,

EXIST. CONC. WALL

SCALE: ⅛" = 1' - 0"

PARTIAL NEW FIRE RISER LAYOUT PLAN

TO REMAIN

LINE (N.I.C.)

EXIST. 8" 0 FEEDER

SHED TO THE FEEDER LINE. SEE NEW RISER DETAIL.

PIPING FROM TEE CONNECTION INSIDE THE

FOR BOTH NEW 8" FIRE RISERS, REPLACE

CONTRACTOR SHALL PREPARE AND PAINT ALL EXPOSED SURFACES OF THE NEW FIRE RISER COMPONENTS.

NOTE: CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS AND DIMENSIONS IN FIELD PRIOR TO COMMENCING NEW WORK.

CONNECTION

TEE

EXIST. 8"

TO REMAIN

CROSS MAIN

EXIST. 4"

SEE LAYOUT SECTION

NEW 8" 0 FEEDER LINE.

3 P2-P5 r07.23.25.pdf

2026-04-23T06:04:06+0000
Certified by Adobe Acrobat Sign

File details come from the government source that posted it. Updated .