FINAL PLANS S30254.pdf
PDF 790 KB Posted
- Solicitation number
- B26002764
- Issued by
- Maui County, Hawaii
About this file
This is a final plans document for the State of Hawaii, Department of Transportation, Harbors Division, related to Project S30254 at Kahului Harbor on Maui. The project scope consists of replacing two fire risers and repairing a portion of the fire suppression system at Pier 1 Shed in Kahului Harbor. The plans provide detailed engineering specifications, drawings, and technical requirements necessary for contractors to bid on and execute the work. The document includes comprehensive design plans showing the location of existing fire risers, proposed replacement components, connection details, and repair specifications for the fire suppression infrastructure at the shed facility.
The final plans establish the technical baseline and performance standards that bidders must follow in submitting proposals for this harbor infrastructure improvement project. The plans contain detailed specifications regarding materials, installation methods, testing procedures, and compliance requirements for the fire riser replacement and suppression system repairs. Contract start and end dates are estimated in the HIePRO solicitation, with exact dates to be provided by written notice from the Harbors Construction Engineer. The project is located in Hawaii and represents a maintenance and upgrade initiative for critical fire safety infrastructure at this active port facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FINAL SPECIFICATIONS w NTB S30254.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HARBORS
STATE OF HAWAII
DEPARTMENT OF TRANSPORTATION
SHEET
1 2
0F SHTS.
STATE OF HAWAII
DEPARTMENT OF TRANSPORTATION
DATE
APPROVED BY:
HAWAII
MAUI
LANAI
MOLOKAI
OAHU
KAUAI
HAWAIIAN ISLANDS
P A C I F I C O
C E A N
PROJECT
N O
R T
H
PROJECT
LOCATION
LOCATION
FOR DIRECTOR OF TRANSPORTATION
N
O R
T H
ISLAND OF MAUI
N O
R T
H
PIER 2
HOBRON AVENUE
W H
A R F
S T R E E T
P U
U N E
N E
A V E
N U E
K A
A H
U M
A N
U
A V
E N
U E
P I E
R
PIER 1APIER 1B
OFFICE
DISTRICT
HARBORS
P A C I F I C O
C E A N
PIER 1 SHED
KAHULUI HARBOR
NTS
AT PIER 1 SHED, MAUI, HAWAII
KAHULUI HARBOR, REPLACE FIRE RISERS
S30254
04/21/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAA5oB1JCyHzYmR1drYJ7kdyjxnkwMIQPdx
REV DATE DESCRIPTION BY APPROVED
SHEET TITLE
JOB TITLE
JOB NUMBER
DESIGNED BY:
DRAWN BY:
CHECKED BY:
DATE:
SCALE:
SHEET
AS SHOWN
JM
JM
0F SHTS.2 2
S T A T E O F H A W A I I
DEPARTMENT OF TRANSPORTATION
HARBORS
S30254
FIRE RISER LAYOUT & DETAILS
PIER SHED PLAN & SECTIONS,
GENERAL NOTES:
AF
MAR. 2026
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.11.
ACCESSIBLE AND AVAILABLE.
CONTACT INFORMATION MUST BE IN LOCATIONS THAT ARE READILY
CONSTRUCTION ENGINEER IMMEDIATELY (I.E. WITHIN 24-HOURS). SUCH
HARBORS ENVIORNMENTAL HOTLINE (808-587-1962) AND THE HARBORS
AGENCIES FOLLOWING NOTIFICATION PROCEDURES, AND SHALL NOTIFY
FACILITY PERSONNEL, EMERGENCY RESPONSE AGENCIES, AND REGULATORY
SUBSTANCE OR OIL, THE CONTRACTOR SHALL NOTIFY APPROPRIATE
IN CASE OF SPILL, LEAK, OR OTHER RELEASE CONTAINING A HAZARDOUS 10.
ADJACENT HARBOR WATERS.
THROUGHT THE HARBORS SMALL MS4 OR OTHER POTENTIAL PATHWAYS INTO
POLLUTANTS ARE ALLOWED TO BE DISCHARGED DIRECTLY OR INDIRECTLY
STATE OF HAWII DOT HARBORS STORMWATER MANAGEMENT PROGRAM. NO
THE CONTRACTOR SHALL COMPLY WITH THE CLEAN WATER ACT AND THE 9.
423-7287.
HAWAII ONE CALL CENTER (HOCC) BEFORE EXCAVATION (811) OR (866)-
ENGINEER PRIOR TO THE START OF ANY CONSTRUCTION WORK. CLEAR WITH
(BMPs) PLAN AND HEALTH & SAFETY PLAN TO HARBORS CONSTRUCTION
CONTRACTOR SHALL SUBMIT A SITE-SPECIFC BEST MANAGEMENT PRACTICES 8.
SUCH DISCHARGES, OR APPROVED ACTIONS.
OBTAINING A NOTICE OF GENERAL PERMIT CONVERAGE (NGPC) AUTHORIZING
THE CONTRACTOR SHALL CONTACT THE HDOH CLEAN WATER BRANCH FOR
WATER FROM TESTING AND/OR DISINFECTION CANNOT BE CONTAINED,
AWWA STANDARD C651. FLUSH MAINS TO FIRE RISERS AND IF RESULTING
AND 13. THE NEW SYSTEM SHALL BE DISINFECTED AS SET FORTH IN THE
THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA STANDARD NO. 1 7.
ON ALL NEW HANGER RINGS, WHEN APPLICABLE.
BRACING) IN ACCORDANCE WITH NFPA 13 AND USE SURGE RESISTANT CLIPS
CONTRACTOR SHALL PROVIDE EARTHQUAKE PROTECTION (SWAY STRUTS &6.
SHALL BE UL LISTED OR FM APPROVED.
FIRE RISERS AND SUPPRESSION SYSTEM. ALL DEVICES AND EQUIPMENT
CONTRACTOR SHALL PREPARE AND PAINT ALL EXPOSED SURFACES OF NEW 5.
MEET ALL REQUIREMENTS OF THE LOCAL AUTHORITIES.
OF THE NATIONAL BOARD OF FIRE UNDERWRITERS (NBFU) STANDARDS TO
THE MANUFACTURER'S RECOMMENDATIONS, AND ALL APPLICABLE PROVISIONS
ASSOCIATION (NFPA) STANDARDS NO. 1 & 13, MAUI FIRE DEPARTMENT,
ALL WORK SHALL CONFORM TO THE NATIONAL FIRE PROTECTION 4.
ANY FIRE WHILE THE SYSTEM IS SHUT DOWN.
WATCHMEN SERVICES MAY BE REQUIRED TO ASSURE PROMPT DETECTION OF
THE SYSTEM SHALL NOT BE OFF-LINE MORE THAN 24 HOURS. SPECIAL
THE AMOUNT OF TIME THE FIRE PROTECTION SYSTEM IS OUT OF SERVICE.
INTERFERENECE WITH THE PIER AND SHED OPERATIONS AND TO MINIMIZE
MANAGER, CONSTRUCTION ENGINEER, AND TENANTS TO MINIMIZE ANY
ALL WORK SHALL BE COORDINATED WITH THE HARBORS MAUI DISTRICT 3.
STRUCTURES, UTILITIES AND EQUIPMENT IN THE AREA.
CONTRACTOR SHALL EXERCISE CAUTION TO PREVENT DAMAGE TO EXISTING 2.
ORDERING MATERIALS AND THE START OF WORK.
CONDITIONS, DIMENSIONS, AND QUANTIIES TO BE REPLACED PRIOR TO
SHALL BE VERIFIED PRIOR TO BIDDING. CONTRACTOR SHALL VERIFY FIELD
DIMENSIONS AND QUANTITIES ARE SHOWN FOR BIDDING PURPOSES AND 1.
AT PIER 1 SHED, MAUI, HAWAII
KAHULUI HARBOR, REPLACE FIRE RISERS
SCALE: 1" = 30'
SHED
WORK
APRON
EXISTING PIER
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 COLUMN NOS.
NORTH
SOUTH
EAST
WEST
STORAGE SHED
PIER EDGE
STATION
COMFORT
17 BAYS @ 22' = 374'
STATION
COMFORT
PASSENGER TERMINAL
PIER 1 SHED FIRE SPRINKLER PLAN
VAULT
TRANS.
TO REMAIN
SYSTEM
SPRINKLER
EXIST. FIRE
TYPICAL
DOOR OPENING,
EXIST. ROLL-UP
SEE DETAIL AND SPECS.
CONNECTION INSIDE OF SHED.
REPLACE PIPING FROM TEE
REPLACE 8" FIRE RISER (NO. 1),
FENCE
EXIST.
SEE DETAIL AND SPECS.
CONNECTION INSIDE OF SHED.
REPLACE PIPING FROM TEE
REPLACE 8" FIRE RISER (NO. 2),
SHEDS
STORAGE DOORS, TYP.
EXIST. ROLL-UP
TO REMAIN
SYSTEM
SPRINKLER
EXIST. FIRE
PIER SHED SECTION
SCALE: 1" = 20' - 0"
WALL
EXIST. CONC.
RISER
NEW 8"
LINE
EXIST. F.S.
MAIN AND LATERALS
EXIST. CROSS
77' - 0" +55' - 0" +
ROOFING, TYP.
EXIST. BUILT-UP
TRUSSES, TYP.
EXIST. STEEL
& RISER PIPE
EXIST. SUPPLY LINE
AREA
ROOF
EXIST.
WALL
EXIST. PARAPET
SCALE: ¼" = 1' - 0"
ELEV. = + 25.5'
FEEDER LINE
NEW 8" 0
& LATERAL TO REMAIN
EXIST. CROSS MAIN
1'- 0"±
PURLINS, TYP.
EXIST. WOOD
NEW FIRE SUPPRESSION LAYOUT SECTION
4'- 8"±
NOTE: PREPARE AND PAINT ALL EXPOSED SURFACES OF NEW FIRE SUPPRESSION SYSTEM COMPONENTS.
W/ SPRINKLER HEADS TO REMAIN
EXIST. FIRE SPRINKLER LATERALS
INSIDE OF SHED.
REPLACE UP TO TEE CONNECTION
NEW 8" 0 FIRE RISER.
CONDUIT
EXIST. ELECTRICAL
& 4" CROSS MAIN
EXIST. 8" TEE CONNECTION
TRUSSES
EXIST. STEEL
FIXTURE, TYP.
EXIST. LIGHT MORE INFORMATION.
SEE DETAILS AND SPECS FOR
NEW SWAY STRUT ASSEMBLIES.
CONC. WALL
EXIST.
FOR MORE INFO.
SEE DETAILS AND SPECS
TO NEW FIRE RISER SYSTEM
TO MATCH EXISTING CONDITIONS.
SHALL BE REMOVED & REINSTALLED
ACCESS AND WINDOW PROTECTION
NEW FIRE RISER DETAIL
NOT TO SCALE
SEE SECTION VIEWS FOR DETAILS
TO FIRE SUPPRESSION SYSTEM.
WALL BEYOND
EXIST. CONC.
(SIZE TO FIT)
THREE (3) PER RISER
W/ RISER CLAMP, GALV.,
SWAY STRUT ASSEMBLY
PAVMENT
EXIST. A.C.
W/ MECHANICAL JOINT
EXIST. SUPPLY PIPING
THRUST BLOCK
EXIST. CONC.
NEW ALARM BELL
CHAMBER
NEW RETARD
NEW CHECK VALVE
DRAIN VALVE
NEW MAIN
VALVE
NEW CONTROL
CONNECTION
NEW FIRE DEPT.
IN PLACE
COMPONENTS TO REMAIN
EXIST. FIRE RISER
RISER PIPE
EXIST. 8" 0
NEW TEE CONNECTION
SGAGE
NEW PRESSURE
VALVE
NEW ALARM
RISER COMPONENTS
REPLACE WITH NEW FIRE
RISER COMPONENTS AND
REMOVE EXIST. FIRE
(SIZE TO FIT)
W/ RISER CLAMP, GALV.,
SWAY STRUT ASSEMBLY
TYP.
O.C., 10'- 9"
A A
B B
C C
A
HEAD, TYP.
EXIST. SPRINKLER
(N.I.C.), TYP.
EXIST. LATERALS,
EXIST. CONC. WALL
SCALE: ⅛" = 1' - 0"
PARTIAL NEW FIRE RISER LAYOUT PLAN
TO REMAIN
LINE (N.I.C.)
EXIST. 8" 0 FEEDER
SHED TO THE FEEDER LINE. SEE NEW RISER DETAIL.
PIPING FROM TEE CONNECTION INSIDE THE
FOR BOTH NEW 8" FIRE RISERS, REPLACE
CONTRACTOR SHALL PREPARE AND PAINT ALL EXPOSED SURFACES OF THE NEW FIRE RISER COMPONENTS.
NOTE: CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS AND DIMENSIONS IN FIELD PRIOR TO COMMENCING NEW WORK.
CONNECTION
TEE
EXIST. 8"
TO REMAIN
CROSS MAIN
EXIST. 4"
SEE LAYOUT SECTION
NEW 8" 0 FEEDER LINE.
3 P2-P5 r07.23.25.pdf
| 2026-04-23T06:04:06+0000 | |
| Certified by Adobe Acrobat Sign |
File details come from the government source that posted it. Updated .