FINAL PLANS P30253.pdf
PDF 2 MB Posted
- Solicitation number
- B26003523
- Issued by
- Maui County, Hawaii
About this file
Summary
This is a final electrical plans document prepared by WSP for the State of Hawaii Department of Transportation Harbors for the Kahului Pier 1 Electrical Upgrade and Standardization project (Job No. P30253) located in Kahului, Maui, Hawaii. The scope of work consists of the removal and replacement of existing electrical equipment, conductors, and conduit, along with the installation of new concrete-encased conduit and conductors to serve existing high mast pole lights at the harbor facility. The project involves replacing existing feeders to multiple light poles (HM-0 through HM-18-2 and additional poles P-1), upgrading distribution panels, installing new transformers, and reconfiguring the electrical one-line distribution system to accommodate the existing photovoltaic system. The plans include detailed electrical schematics, equipment elevations, site plans with three enlarged sections, equipment schedules, wiring schedules for copper conductors, and duct details for conduit installation. The contractor is responsible for verifying existing conditions prior to work commencement, coordinating with the construction manager and owner regarding service outages, obtaining all required permits and licenses, and delivering certificates of completion and inspection upon project conclusion.
The electrical plans specify copper conductor wiring sizes, conduit materials and dimensions (primarily 1-1/2 inch and 2-inch PVC Schedule 40 concrete-encased), and equipment ratings in accordance with the National Electrical Code and applicable Maui County building, fire, and electrical codes. Key equipment includes three MECO meters (514250, 514251, and 515049), multiple distribution panels (S, NC, L, X, 2S, P, A, 1A, and REEFER), three transformers (T-X1 45KVA, T-S1 15KVA, and T-P1 45KVA), and a new 600-ampere distribution panel to accommodate the existing photovoltaic system. The contractor must follow the existing conduit routing path to minimize trenching, ensure all existing conduits and wiring are properly abandoned after new installations are operational, and provide updated typed panel schedules at project conclusion. The engineer of record is WSP located at 1001 Bishop Street, Suite 2400, Honolulu, Hawaii 96813.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FINAL ADDENDUM NO 1 P30253.pdf | ||
| FINAL SPECIFICATIONS w NTB P30253.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE
NORTH
SHEET
DATE
OF SHTS
FOLDERFILE DRAWER
NOT TO SCALE
CONSULTANTS
NORTH
LOCATION MAP SHEET INDEX
ELECTRICAL ENGINEER:
WSP
1001 BISHOP STREET, SUITE 2400
HONOLULU, HI 96813
P (808) 536-1737 www.wsp.com
T-1
KAHULUI, PIER 1, ELECTRICAL UPGRADE AND STANDARDIZATION
KAHULUI HARBOR, MAUI, HAWAII
STATE OF HAWAII
DEPARTMENT OF TRANSPORTATION
HARBORS
JOB NO. P30253
APPROVED BY
DIRECTOR OF TRANSPORTATION
SHEET TITLE
E-1036
ED-3017
ED-601
E-001 ELECTRICAL NOTES AND LEGEND
E-100
E-101
E-102
E-301
E-501
E-502
E-601
DWG
ELECTRICAL OVERALL SITE PLAN
ELECTRICAL ENLARGED SITE PLAN 1
ELECTRICAL ENLARGED SITE PLAN 2
ELECTRICAL ENLARGED SITE PLAN 3
ELECTRICAL EQUIPMENT ELEVATIONS - DEMO
ELECTRICAL EQUIPMENT ELEVATIONS
ELECTRICAL SCHEDULES 1
ELECTRICAL SCHEDULES 2
ELECTRICAL ONE-LINE DIAGRAM - DEMO
ELECTRICAL ONE-LINE DIAGRAM
E-401 ELECTRICAL DETAILS
T-1 PROJECT TITLE SHEEET
VICINITY MAP
LOCATON MAP
NORTH
NOT TO SCALE
..\..\..\..\Downloads\T-1.png
LOCATON MAP
ISLAND OF MAUI
for 05/28/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAARFJ0HP39C5Qr1B7_dnsH_07xhY1hNdCC
SUBSCRIPT KEY
CONDUCTORS PER CONDUIT
NONE 3 PHASE CONDUCTORS, CONDUIT GROUND
G
3 PHASE CONDUCTORS, 1 GROUNDING
CONDUCTOR
N 3 PHASE CONDUCTORS, 1 NEUTRAL
CONDUCTOR, CONDUIT GROUND
NG
3 PHASE CONDUCTORS, 1 NEUTRAL
CONDUCTOR, 1 GROUNDING CONDUCTOR
NOTES:
** PARALLEL CONDUCTORS ARE NOT PERMITTED
UNDER 1/0.
1. SCHEDULE IS BASED ON 3 CURRENT CARRYING
CONDUCTORS IN RACEWAY, CABLE OR EARTH AT
AMBIENT AIR TEMPERATURE OF 30°C (86°F).
2. MODIFY IF USE OF 600 MCM OR LARGER
CONDUCTORS IS DESIRED. CONFIRM LUG SIZES
ARE AVAILABLE.
WIRING SCHEDULE - COPPER
CONDUCTORS (0-600V)
CIRCUIT
RATING
CONDUIT SIZE (INCHES) CONDUCTOR SIZE
G N NG
PHASE/
NEUTRAL
GND
15 12 12
30 10 10
40 1 8
50 1 1 1.25 6
60 1.25 1.25 4
70 8
80 3
90 1.5 2
100 1.5 1.5 2 1
110 1 6
150 2 2 1/0
175 2/0
200 2.5 3/0
225 2.5 2.5 2.5 4/0 4
250 2.5 2.5 3 250 4
300 3 3 3.5 350 4
350 4 500 2
400 500 2
450 2@2.5 2@2.5 2@2.5 4/0 2
500 250 1
600 350 1
700 500 1/0
800 2@4 2@4 2@4 500 1/0
1000 3@3 3@3 3@3.5 400 2/0
1200 3@4 3@4 3@4 3/0
2500 7@4 7@4 7@4 350
3000 8@4 8@4 8@4
0.75 0.75 0.75
4 4
4@4 4@4 4@4 4/0
5@4 5@4 5@4 250
8@4 8@4 8@4 600
8@4 8@4 8@4
8@4 8@4 8@4 500
500500
12120.75
0.75
0.75 0.75
0.75 0.75
0.75 0.75
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.5 1.5
1.5 1.5
2 2
2 2
2@2.5 2@2.5 2@3
2@3 2@3 2@3.5
2@4 2@4 2@4
44 4
ELECTRICAL LEGEND
NEW
DUPLEX RECEPTACLE, +18" UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, GFCI TYPE, +18" UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, GFCI TYPE, WITH WEATHERPROOF COVER +18" UNLESS
OTHERWISE NOTED
DESCRIPTION
EQUIPMENT CONNECTION
CEILING MOUNTED JUNCTION BOX, 4-11/16" SQUARE
WALL MOUNTED JUNCTION BOX, 4-11/16" SQUARE
JUNCTION BOX, SIZE AS NOTED
PANELBOARD
DISCONNECT SWITCH, SIZE AND RATING AS NOTED
DRY TYPE TRANSFORMER, SIZE AND RATING AS INDICATED
RACEWAY AND CONDUCTORS ABOVE GRADE
CONDUIT STUB OUT
EQUIPMENT ID NUMBER, SEE EQUIPMENT SCHEDULE, SAME SHEET
WP
E
J
J
J
REVISION DELTA1
LIGHTING CONTROL PANEL OR CONTROL STATIONLCP
ELECTRICAL GENERAL NOTES
A. REFER TO COMPLETE CONTRACT DOCUMENTS AND SPECIFICATIONS FOR OTHER DETAILS AND REQUIREMENTS.
B. CONFORM TO THE BUILDING, FIRE, AND ELECTRICAL CODES OF MAUI COUNTY, LAWS AND REGULATIONS OF MAUI
COUNTY AND THE STATE OF HAWAII.
C. OBTAIN AND PAY FOR REQUIRED PERMITS, LICENSES, FEES, AND OTHER CHARGES. DELIVER CERTIFICATES OF
COMPLETION AND INSPECTION TO THE OWNER. SUBCONTRACTORS SHALL BE LICENSED FOR THE WORK THEY
PERFORM.
D. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY AND HAVE NOT BEEN VERIFIED BY THE OWNER OR
THEIR REPRESENTATIVE. ENGINEER DESIGN IS BASED ON LIMITED SITE OBSERVATION CAPABILITIES WITHOUT ANY
AVAILABLE AS-BUILT DRAWINGS. CONTRACTOR SHALL VISIT THE JOB SITE AND CONFIRM EXISTING CONDITIONS
PRIOR TO WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A NEW COMPLETE ELECTRICAL SYSTEM
WITH CONNECTION AND FUNCTIONALITY TO MATCH EXISTING SYSTEM AND SERVE ALL CURRENTLY SERVED LOADS.
E. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION.
F. DRAWINGS ARE OF SMALL SCALE AND ARE SCHEMATIC. LOCATIONS OF EQUIPMENT AND SYSTEM ELEMENTS ARE
APPROXIMATE.
G. INSTALL RACEWAY PARALLEL WITH OR AT RIGHT ANGLES TO CEILINGS, WALLS, AND STRUCTURAL MEMBERS.
H. PROVIDE AND INSTALL ALL JUNCTION BOXES AND PULL BOXES REQUIRED FOR INSTALLATION OF ELECTRICAL
DEVICES AND EQUIPMENT, WHETHER OR NOT SPECIFICALLY INDICATED ON THE PLANS. SIZING OF BOXES SHALL BE
PER NEC.
I. LABEL ALL JUNCTION BOXES AND PULL BOXES INDICATION PANEL NAME AND CIRCUIT NUMBERS OF ALL BRANCH
CIRCUIT CONDUCTORS CONTAINED WITHIN THE BOX.
J. PROVIDE UPDATED TYPED PANEL SCHEDULES AT THE CONCLUSION OF THE PROJECT.
RACEWAY AND CONDUCTORS BELOW GRADE
SHEET NOTE, SEE SAME SHEET
EXISTING
TO REMAIN
EXISTING
TO BE
DEMOLISHED
WP
E
J
J
J
LCP
WP
E
J
J
J
LCP
POLE WITH ARM MOUNTED LUMINAIRE
DUCT SECTION INDICATOR, RE: DUCT SCHEDULE, SAME SHEET1
AFF ABOVE FINISHED FLOOR
DIST PNL DISTRIBUTION PANEL
DS DISCONNECT SWITCH
ECB ENCLOSED CIRCUIT BREAKER
ELEC ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EXST/(E) EXISTING
GND GROUND
IAW IN ACCORDANCE WITH
HH HANDHOLE
MECO MAUI ELECTRIC COMPANY
MH MANHOLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NFPA NATIONAL FIRE PROTECTION AGENCY
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
PB PULLBOX
PNL PANEL
PV PHOTOVOLTAIC
UFC UNIFORM FIRE CODE
UL UNDERWRITER'S LABORATORIES, INC.
TYP TYPICAL
WP WEATHERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
LUMINAIRE, ONE-LINE DIAGRAM
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
E-001
E-101
E-102
E-103
ELECTRICAL OVERALL SITE PLAN
NORTH
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
E-100
E-301
ED-301
ED-301
E-301
HM-7
HM-8 HM-10
HM-13
HM-18-2
HM-1A
E-301
ED-301
MECO TRANSFORMER VAULT
MECO METERS (3)
S-27,29,31,33
31,33
24,26
P-1
S-20,22,24,26
S-16,18,35,37
HM-18
ELECTRICAL ENLARGED SITE PLAN 1
NORTH
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
GENERAL NOTES:
A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS
DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER
PRIOR TO WORK.
B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.
INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,
AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW
WIRING THROUGH NEW RACEWAY.
C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE
READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE
SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING
WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND
COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.
E-101
E-101E-102
E-101
E-103
DUCT SCHEDULE:
(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED
REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.
2 [(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40], CONCRETE ENCASED
REFER TO E-401, DUCT DETAIL TYPE 2 FOR ADDITIONAL REQUIREMENTS.
SHEET NOTES:
1. HIGH MAST POLE LIGHTS SERVED FROM EXISTING 480V 1PH 2P30A CIRCUITS FROM EXISTING
PANEL 'S'. CIRCUIT TO NEW PANEL 'S' AS INDICATED.
HM-1E HM-1D HM-0
HM-2
HM-1
HM-3 HM-5
HM-4 HM-6
1 1
1 35,37
ELECTRICAL ENLARGED SITE PLAN 2
NORTH
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
E-102
E-101E-102
DUCT SCHEDULE:
(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED
REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.
2 [(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40], CONCRETE ENCASED
REFER TO E-401, DUCT DETAIL TYPE 2 FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES:
A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS
DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER
PRIOR TO WORK.
B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.
INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,
AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW
WIRING THROUGH NEW RACEWAY.
C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE
READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE
SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING
WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND
COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.
HM-9
HM-11
HM-14
HM-12
HM-15
HM-16
HM-17
ELECTRICAL ENLARGED SITE PLAN 3
NORTH
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
E-103
E-101
E-103
DUCT SCHEDULE:
(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED
REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES:
A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS
DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER
PRIOR TO WORK.
B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.
INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,
AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW
WIRING THROUGH NEW RACEWAY.
C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE
READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE
SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING
WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND
COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.
17 17
19 20 20
35 35 35 35
17 17
10 14
31 31
TO EXISTING
METER #514250
ON REVERSE SIDE
TO EXISTING
FEEDERS/LOADS
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING FEEDERTO EXISTING
CRANE POWER
TO EXISTING
SWITCH BOX ON
REVERSE SIDE
TO EXISTING
FEEDERS/LOADS
TO EXISTING LOADS
TO EXISTING LOADS
TO EXISTING
PV INVERTER
TO EXISTING PV
SYSTEM ON ROOF
TO EXISTING
METER #514251
ON REVERSE SIDE
1 1 1
METER #514250
METER #515049 METER #514251
TO: 1
TO: 7
UTILITY TRANSFORMER ROOM
TO: 7
TO: 1
UTILITY TRANSFORMER ROOM
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
ELECTRICAL EQUIPMENT ELEVATION - DEMO
GENERAL NOTES:
A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK
AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.
SHEET NOTES:
1. TRACE EXISTING FEEDERS AND LOADS, AND VERIFY EXISTING CONDUIT AND
CONDUCTOR SIZES. CUT AND STUB EXISTING CONDUIT AND WIRING. REMOVE
ABANDONED CONDUIT AND WIRING FOR ANY LOADS NO LONGER IN USE.
ED-301
ELECTRICAL EQUIPMENT ELEVATION - DEMO
ELECTRICAL EQUIPMENT ELEVATION - DEMO
35 35
35 35 35 35
31 31
4 6
8 7 10
12 11
TO EXISTING
PV INVERTER
TO EXISTING PV
SYSTEM ON ROOF
TO EXISTING
METER #514250
ON REVERSE SIDE
TO EXISTING LOADS
TO EXISTING FEEDERTO EXISTING
CRANE POWER
TO EXISTING
SWITCH BOX ON
REVERSE SIDE
TO EXISTING FEEDER
TO EXISTING LOADS
TO EXISTING LOADS TO EXISTING LOADS TO EXISTING LOADSTO EXISTING LOADS
TO EXISTING FEEDERS/LOADS
1 1
1 1 1 1 1
METER #514250
METER #515049 METER #514251
TO: 1
TO: 7
UTILITY TRANSFORMER ROOM
TO: 1
TO: 7
UTILITY TRANSFORMER ROOM
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
ELECTRICAL EQUIPMENT ELEVATION
GENERAL NOTES:
A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK
AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.
SHEET NOTES:
1. INTERCEPT EXISTING CONDUITS AND WIRING REMAINING FROM DEMOLITION WITH
PULLBOX AND CONNECT EXISTING TO NEW CONDUITS AND WIRING.
E-301
ELECTRICAL EQUIPMENT ELEVATION
ELECTRICAL EQUIPMENT ELEVATION
DUCT DETAIL TYPE 1
DUCT DETAIL TYPE 2
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
E-401
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
E-501
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
E-502
(E)MECO
METER #514250
3P100A(E)MECO
SECONDARY
SERVICE
(E)MECO
METER #514251
3P200A(E)MECO
SECONDARY
SERVICE
(E)TRANSFORMER "T-X1"
480-208/120V, 45KVA
2P70A
(E)PNL "X"
208/120V, 3Ø, 4W
225A, 10KAIC
(E)TO MAIN GATE HOUSE
3P70A
(E)TO PANEL '2A'
2P100A
(E)TO PASHA TRAILER
3P70A
(E)PNL "S"
480/277V, 3Ø, 4W
225A, 10KAIC
3P70A
3P25A
2P15A
(E)PNL "NC"
480/277V, 3Ø, 3W
100A, 10KAIC
(E)PNL "L"
480/277V, 3Ø, 4W
225A, 10KAIC
3P70A
(E)TRANSFORMER "T-S1"
480-208/120V, 15KVA
(E)PNL "2S"
208/120V, 3Ø, 4W
100A, 10KAIC
3P50A
3P70A
(E)PNL "P"
480/277V, 3Ø, 3W
350A, 22KAIC
3P150A
2P30A
(E)TRANSFORMER "T-P1"
480-208/120V
3P50A
2P50A
2P70A
3P50A
3P70A
3P125A
(E)PNL "A"
208/120V, 3Ø, 4W
225A, 10KAIC
3P50A
(E)ENCLOSED
CIRCUIT BREAKER
(E)TRANSFORMER "T-S2"
480-208/120V, 5KVA
2P20A
(E)RELAY MAIN
2P30A
(E)RELAY CONTROL 2 (E)SWITCH BOX
(E)RELAY CONTROL 1
(E)GUTTER
(E)TO PANEL '4H2'
(E)TO SHED 1B
(E)LIFT STATION
PFB
(E)PNL "1A"
208/120V, 3Ø, 4W
100A, 10KAIC
3P60A
(E)JB
(E)JB
(E)PULLBOX 1
3P200A DS
200A FUSE
AC
DC
(E)PV INVERTER
(E)PV
DISCONNECT
(E)PV ARRAY
(E)PNL "PV LOADCENTER"
208/120V, 3Ø, 4W
150A, 10KAIC
(E)TO PV SOLARGUARD
(E)TO PV DECK MONITOR
3P100A
C
M
M
C
(E)TO PNL '1B'
(E)TO
RESTROOMS
(E)FEEDER1
(E)PNL "REEFER"
208/120V, 3Ø, 3W
400A, 22KAIC
3P50A
2P30A
3P100A
(E)FEEDER1
(E)REEFER OUTLETS (TYP)
(E)EXST LOAD R.1
(E)CRANE POWER
ELECTRICAL ONE-LINE DIAGRAM - DEMO
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
ED-601
GENERAL NOTES:
A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK
AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.
SHEET NOTES:
1. TRACE EXISTING FEEDERS AND LOADS, AND VERIFY EXISTING CONDUIT AND
CONDUCTOR SIZES. CUT AND STUB EXISTING CONDUIT AND WIRING. REMOVE
ABANDONED CONDUIT AND WIRING FOR ANY LOADS NO LONGER IN USE.
(E)MECO
METER #514250
3P100A(E)MECO
SECONDARY
SERVICE
(E)MECO
METER #514251
3P200A(E)MECO
SECONDARY
SERVICE
3P200A DS
200A FUSE
AC
DC
(E)PV INVERTER
(E)PV
DISCONNECT
(E)PV ARRAY
(E)TO PV SOLARGUARD
(E)TO PV DECK MONITOR
M
M
(E)TRANSFORMER "T-X1"
480-208/120V, 45KVA
2P70A
(E)PNL "X"
208/120V, 3Ø, 4W
225A, 10KAIC
(E)TO MAIN GATE HOUSE
3P70A
(E)TO PANEL '2A'
2P100A
(E)TO PASHA TRAILER
3P70A
PNL "S"
480/277V, 3Ø, 4W
225A, 10KAIC
3P25A3P200A
TRANSFORMER "T-S1"
480-208/120V, 15KVA
PNL "NC"
480/277V, 3Ø, 3W
100A, 10KAIC
2P30A
PNL "2S"
208/120V, 3Ø, 4W
100A, 10KAIC
3P50A
RELAY CONTROL 1
C
(E)SWITCH BOX
JB
RELAY CONTROL 2
C JB
TS
TS
3P70A
PNL "P"
480/277V, 3Ø, 3W
600A, 22KAIC
3P150A
TRANSFORMER "T-P1"
480-208/120V, 45KVA
2P70A
3P70A
3P125A
PNL "A"
208/120V, 3Ø, 4W
225A, 10KAIC
3P50A(E)TO PANEL '4H2'
(E)TO SHED 1B
(E)LIFT STATION
PNL "1A"
208/120V, 3Ø, 4W
100A, 10KAIC(E)TO PNL '1B'
(E)TO RESTROOMS
PULLBOX
PULLBOX
PULLBOX
(E)FEEDER
PULLBOX
PULLBOX
PULLBOX
PULLBOX
PULLBOX
RELAY CONTROL 1
CTS
PULLBOX
(E)PNL "PV LOADCENTER"
208/120V, 3Ø, 4W
150A, 10KAIC
PULLBOX
PULLBOX 3
2"C,4#3/0,1#4G
2"C,4#3/0,1#6G
1-1/2"C,4#4,1#8G
2"C,4#3/0,1#6G
4 41"C,4#8,1#10G
3P200A
3P350A
3/4"C,4#12,1#12G
1"C,4#8,1#10G
1-1/2"C,4#4,1#8G
1#8G
1#4G
2"C,4#1,1#8G
2P30A
27,29
HM-7 HM-8 HM-9
2P30A
31,33
PNL "REEFER"
208/120V, 3Ø, 3W
400A, 22KAIC
3P50A
2P30A
3P100A
(E)FEEDER1
(E)REEFER OUTLETS (TYP)
(E)EXST LOAD R.1
(E)CRANE POWER
3P300A
HM-10 HM-11 HM-12
2P30A
16,18
HM-5 HM-3
2P30A
35,37
HM-1 HM-0 HM-1D
HM-6 HM-4
HM-1E
HM-2
2P30A
20,22
HM-1A HM-13
2P30A
24,26
HM-18 HM-17 HM-16
P-1 HM-18-2HM-14 HM-15
RE: ENLARGED SITE PLANS AND DUCT SCHEDULES FOR LIGHT POLE FEEDER SIZES, TYP.
EXISTING PULLBOXES BUILT IN TO LIGHT POLE BASES
ELECTRICAL ONE-LINE DIAGRAM
DRAWING NO.
SHEET
AS NOTEDAS NOTED
DRAWN BY:
WSP HI
SCALE:
DESIGNED BY:
APPROVED BY:
DL
DL
DATE
JOB NO.
CHECKED BY:
THIS WORK WAS PREPARED BY ME
OR UNDER MY SUPERVISION
NO.
REVISION SYM.
DESCRIPTION
WORKS ADMINISTRATOR
APPROVED: PUBLICDATE
OF SHTS
FOLDERFILE DRAWER
License Expiration Date: 4/30/2028
NKS
KAHULUI, PIER 1, ELECTRICAL
UPGRADE AND STANDARDIZATION
GENERAL NOTES:
A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.
CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK
AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.
SHEET NOTES:
1. TO EXISTING FEEDER OR LOAD REMAINING FROM DEMOLITION.
2. PANEL RATING BASED ON ASSUMED FEEDER SIZE AND VOLTAGE RATING. PROVIDE
NEW PANEL WITH APPROPRIATE RATINGS TO MATCH EXISTING FEEDER.
3. INTERCEPT EXISTING CONDUITS AND WIRING REMAINING FROM DEMOLITION WITH
PULLBOX AND CONNECT EXISTING TO NEW CONDUITS AND WIRING.
4. PROVIDE CONDUIT AND WIRING AS SPECIFIED (IN ONE-LINE DIAGRAM OR PANEL
SCHEDULE) OR TO MATCH EXISTING, WHICHEVER IS LARGER.
5. NEW UPSIZED 600A DISTRIBUTION PANEL TO ACCOMMODATE EXISTING PV SYSTEM.
E-601