FINAL PLANS P30253.pdf

PDF 2 MB Posted

Attached to
P30253 KAHULUI, PIER 1, ELECTRICAL UPGRADE AND STANDARDIZATION
Solicitation number
B26003523
Issued by
Maui County, Hawaii

About this file

Summary

This is a final electrical plans document prepared by WSP for the State of Hawaii Department of Transportation Harbors for the Kahului Pier 1 Electrical Upgrade and Standardization project (Job No. P30253) located in Kahului, Maui, Hawaii. The scope of work consists of the removal and replacement of existing electrical equipment, conductors, and conduit, along with the installation of new concrete-encased conduit and conductors to serve existing high mast pole lights at the harbor facility. The project involves replacing existing feeders to multiple light poles (HM-0 through HM-18-2 and additional poles P-1), upgrading distribution panels, installing new transformers, and reconfiguring the electrical one-line distribution system to accommodate the existing photovoltaic system. The plans include detailed electrical schematics, equipment elevations, site plans with three enlarged sections, equipment schedules, wiring schedules for copper conductors, and duct details for conduit installation. The contractor is responsible for verifying existing conditions prior to work commencement, coordinating with the construction manager and owner regarding service outages, obtaining all required permits and licenses, and delivering certificates of completion and inspection upon project conclusion.

The electrical plans specify copper conductor wiring sizes, conduit materials and dimensions (primarily 1-1/2 inch and 2-inch PVC Schedule 40 concrete-encased), and equipment ratings in accordance with the National Electrical Code and applicable Maui County building, fire, and electrical codes. Key equipment includes three MECO meters (514250, 514251, and 515049), multiple distribution panels (S, NC, L, X, 2S, P, A, 1A, and REEFER), three transformers (T-X1 45KVA, T-S1 15KVA, and T-P1 45KVA), and a new 600-ampere distribution panel to accommodate the existing photovoltaic system. The contractor must follow the existing conduit routing path to minimize trenching, ensure all existing conduits and wiring are properly abandoned after new installations are operational, and provide updated typed panel schedules at project conclusion. The engineer of record is WSP located at 1001 Bishop Street, Suite 2400, Honolulu, Hawaii 96813.

View the file

Other files

File Type Posted
FINAL ADDENDUM NO 1 P30253.pdf PDF
FINAL SPECIFICATIONS w NTB P30253.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE

NORTH

SHEET

DATE

OF SHTS

FOLDERFILE DRAWER

NOT TO SCALE

CONSULTANTS

NORTH

LOCATION MAP SHEET INDEX

ELECTRICAL ENGINEER:

WSP

1001 BISHOP STREET, SUITE 2400

HONOLULU, HI 96813

P (808) 536-1737 www.wsp.com

T-1

KAHULUI, PIER 1, ELECTRICAL UPGRADE AND STANDARDIZATION

KAHULUI HARBOR, MAUI, HAWAII

STATE OF HAWAII

DEPARTMENT OF TRANSPORTATION

HARBORS

JOB NO. P30253

APPROVED BY

DIRECTOR OF TRANSPORTATION

SHEET TITLE

E-1036

ED-3017

ED-601

E-001 ELECTRICAL NOTES AND LEGEND

E-100

E-101

E-102

E-301

E-501

E-502

E-601

DWG

ELECTRICAL OVERALL SITE PLAN

ELECTRICAL ENLARGED SITE PLAN 1

ELECTRICAL ENLARGED SITE PLAN 2

ELECTRICAL ENLARGED SITE PLAN 3

ELECTRICAL EQUIPMENT ELEVATIONS - DEMO

ELECTRICAL EQUIPMENT ELEVATIONS

ELECTRICAL SCHEDULES 1

ELECTRICAL SCHEDULES 2

ELECTRICAL ONE-LINE DIAGRAM - DEMO

ELECTRICAL ONE-LINE DIAGRAM

E-401 ELECTRICAL DETAILS

T-1 PROJECT TITLE SHEEET

VICINITY MAP

LOCATON MAP

NORTH

NOT TO SCALE

..\..\..\..\Downloads\T-1.png

LOCATON MAP

ISLAND OF MAUI

for 05/28/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAARFJ0HP39C5Qr1B7_dnsH_07xhY1hNdCC

SUBSCRIPT KEY

CONDUCTORS PER CONDUIT

NONE 3 PHASE CONDUCTORS, CONDUIT GROUND

G

3 PHASE CONDUCTORS, 1 GROUNDING

CONDUCTOR

N 3 PHASE CONDUCTORS, 1 NEUTRAL

CONDUCTOR, CONDUIT GROUND

NG

3 PHASE CONDUCTORS, 1 NEUTRAL

CONDUCTOR, 1 GROUNDING CONDUCTOR

NOTES:

** PARALLEL CONDUCTORS ARE NOT PERMITTED

UNDER 1/0.

1. SCHEDULE IS BASED ON 3 CURRENT CARRYING

CONDUCTORS IN RACEWAY, CABLE OR EARTH AT

AMBIENT AIR TEMPERATURE OF 30°C (86°F).

2. MODIFY IF USE OF 600 MCM OR LARGER

CONDUCTORS IS DESIRED. CONFIRM LUG SIZES

ARE AVAILABLE.

WIRING SCHEDULE - COPPER

CONDUCTORS (0-600V)

CIRCUIT

RATING

CONDUIT SIZE (INCHES) CONDUCTOR SIZE

G N NG

PHASE/

NEUTRAL

GND

15 12 12

30 10 10

40 1 8

50 1 1 1.25 6

60 1.25 1.25 4

70 8

80 3

90 1.5 2

100 1.5 1.5 2 1

110 1 6

150 2 2 1/0

175 2/0

200 2.5 3/0

225 2.5 2.5 2.5 4/0 4

250 2.5 2.5 3 250 4

300 3 3 3.5 350 4

350 4 500 2

400 500 2

450 2@2.5 2@2.5 2@2.5 4/0 2

500 250 1

600 350 1

700 500 1/0

800 2@4 2@4 2@4 500 1/0

1000 3@3 3@3 3@3.5 400 2/0

1200 3@4 3@4 3@4 3/0

2500 7@4 7@4 7@4 350

3000 8@4 8@4 8@4

0.75 0.75 0.75

4 4

4@4 4@4 4@4 4/0

5@4 5@4 5@4 250

8@4 8@4 8@4 600

8@4 8@4 8@4

8@4 8@4 8@4 500

500500

12120.75

0.75

0.75 0.75

0.75 0.75

0.75 0.75

1.25

1.25

1.25

1.25

1.25

1.25

1.25

1.25

1.25

1.5 1.5

1.5 1.5

2 2

2 2

2@2.5 2@2.5 2@3

2@3 2@3 2@3.5

2@4 2@4 2@4

44 4

ELECTRICAL LEGEND

NEW

DUPLEX RECEPTACLE, +18" UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, GFCI TYPE, +18" UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, GFCI TYPE, WITH WEATHERPROOF COVER +18" UNLESS

OTHERWISE NOTED

DESCRIPTION

EQUIPMENT CONNECTION

CEILING MOUNTED JUNCTION BOX, 4-11/16" SQUARE

WALL MOUNTED JUNCTION BOX, 4-11/16" SQUARE

JUNCTION BOX, SIZE AS NOTED

PANELBOARD

DISCONNECT SWITCH, SIZE AND RATING AS NOTED

DRY TYPE TRANSFORMER, SIZE AND RATING AS INDICATED

RACEWAY AND CONDUCTORS ABOVE GRADE

CONDUIT STUB OUT

EQUIPMENT ID NUMBER, SEE EQUIPMENT SCHEDULE, SAME SHEET

WP

E

J

J

J

REVISION DELTA1

LIGHTING CONTROL PANEL OR CONTROL STATIONLCP

ELECTRICAL GENERAL NOTES

A. REFER TO COMPLETE CONTRACT DOCUMENTS AND SPECIFICATIONS FOR OTHER DETAILS AND REQUIREMENTS.

B. CONFORM TO THE BUILDING, FIRE, AND ELECTRICAL CODES OF MAUI COUNTY, LAWS AND REGULATIONS OF MAUI

COUNTY AND THE STATE OF HAWAII.

C. OBTAIN AND PAY FOR REQUIRED PERMITS, LICENSES, FEES, AND OTHER CHARGES. DELIVER CERTIFICATES OF

COMPLETION AND INSPECTION TO THE OWNER. SUBCONTRACTORS SHALL BE LICENSED FOR THE WORK THEY

PERFORM.

D. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY AND HAVE NOT BEEN VERIFIED BY THE OWNER OR

THEIR REPRESENTATIVE. ENGINEER DESIGN IS BASED ON LIMITED SITE OBSERVATION CAPABILITIES WITHOUT ANY

AVAILABLE AS-BUILT DRAWINGS. CONTRACTOR SHALL VISIT THE JOB SITE AND CONFIRM EXISTING CONDITIONS

PRIOR TO WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A NEW COMPLETE ELECTRICAL SYSTEM

WITH CONNECTION AND FUNCTIONALITY TO MATCH EXISTING SYSTEM AND SERVE ALL CURRENTLY SERVED LOADS.

E. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION.

F. DRAWINGS ARE OF SMALL SCALE AND ARE SCHEMATIC. LOCATIONS OF EQUIPMENT AND SYSTEM ELEMENTS ARE

APPROXIMATE.

G. INSTALL RACEWAY PARALLEL WITH OR AT RIGHT ANGLES TO CEILINGS, WALLS, AND STRUCTURAL MEMBERS.

H. PROVIDE AND INSTALL ALL JUNCTION BOXES AND PULL BOXES REQUIRED FOR INSTALLATION OF ELECTRICAL

DEVICES AND EQUIPMENT, WHETHER OR NOT SPECIFICALLY INDICATED ON THE PLANS. SIZING OF BOXES SHALL BE

PER NEC.

I. LABEL ALL JUNCTION BOXES AND PULL BOXES INDICATION PANEL NAME AND CIRCUIT NUMBERS OF ALL BRANCH

CIRCUIT CONDUCTORS CONTAINED WITHIN THE BOX.

J. PROVIDE UPDATED TYPED PANEL SCHEDULES AT THE CONCLUSION OF THE PROJECT.

RACEWAY AND CONDUCTORS BELOW GRADE

SHEET NOTE, SEE SAME SHEET

EXISTING

TO REMAIN

EXISTING

TO BE

DEMOLISHED

WP

E

J

J

J

LCP

WP

E

J

J

J

LCP

POLE WITH ARM MOUNTED LUMINAIRE

DUCT SECTION INDICATOR, RE: DUCT SCHEDULE, SAME SHEET1

AFF ABOVE FINISHED FLOOR

DIST PNL DISTRIBUTION PANEL

DS DISCONNECT SWITCH

ECB ENCLOSED CIRCUIT BREAKER

ELEC ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EXST/(E) EXISTING

GND GROUND

IAW IN ACCORDANCE WITH

HH HANDHOLE

MECO MAUI ELECTRIC COMPANY

MH MANHOLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NFPA NATIONAL FIRE PROTECTION AGENCY

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

PB PULLBOX

PNL PANEL

PV PHOTOVOLTAIC

UFC UNIFORM FIRE CODE

UL UNDERWRITER'S LABORATORIES, INC.

TYP TYPICAL

WP WEATHERPROOF

XFMR TRANSFORMER

ABBREVIATIONS

LUMINAIRE, ONE-LINE DIAGRAM

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

E-001

E-101

E-102

E-103

ELECTRICAL OVERALL SITE PLAN

NORTH

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

E-100

E-301

ED-301

ED-301

E-301

HM-7

HM-8 HM-10

HM-13

HM-18-2

HM-1A

E-301

ED-301

MECO TRANSFORMER VAULT

MECO METERS (3)

S-27,29,31,33

31,33

24,26

P-1

S-20,22,24,26

S-16,18,35,37

HM-18

ELECTRICAL ENLARGED SITE PLAN 1

NORTH

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

GENERAL NOTES:

A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS

DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER

PRIOR TO WORK.

B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.

INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,

AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW

WIRING THROUGH NEW RACEWAY.

C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE

READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE

SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING

WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND

COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.

E-101

E-101E-102

E-101

E-103

DUCT SCHEDULE:

(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED

REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.

2 [(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40], CONCRETE ENCASED

REFER TO E-401, DUCT DETAIL TYPE 2 FOR ADDITIONAL REQUIREMENTS.

SHEET NOTES:

1. HIGH MAST POLE LIGHTS SERVED FROM EXISTING 480V 1PH 2P30A CIRCUITS FROM EXISTING

PANEL 'S'. CIRCUIT TO NEW PANEL 'S' AS INDICATED.

HM-1E HM-1D HM-0

HM-2

HM-1

HM-3 HM-5

HM-4 HM-6

1 1

1 35,37

ELECTRICAL ENLARGED SITE PLAN 2

NORTH

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

E-102

E-101E-102

DUCT SCHEDULE:

(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED

REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.

2 [(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40], CONCRETE ENCASED

REFER TO E-401, DUCT DETAIL TYPE 2 FOR ADDITIONAL REQUIREMENTS.

GENERAL NOTES:

A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS

DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER

PRIOR TO WORK.

B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.

INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,

AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW

WIRING THROUGH NEW RACEWAY.

C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE

READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE

SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING

WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND

COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.

HM-9

HM-11

HM-14

HM-12

HM-15

HM-16

HM-17

ELECTRICAL ENLARGED SITE PLAN 3

NORTH

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

E-103

E-101

E-103

DUCT SCHEDULE:

(2-#6,1-#6G) 1-1/2" PVC SCHEDULE 40, CONCRETE ENCASED

REFER TO E-401, DUCT DETAIL TYPE 1 FOR ADDITIONAL REQUIREMENTS.

GENERAL NOTES:

A. REPLACE EXISTING FEEDERS TO LIGHT POLES AS SHOWN. ROUTING SHOWN IS

DIAGRAMMATIC, COORDINATE EXACT TRENCHING PATH AND ANY OBSTACLES WITH OWNER

PRIOR TO WORK.

B. TONE EXISTING WIRING TO VERIFY WHICH ANGLE CONDUIT ENTERS LIGHT POLE BASE.

INSTALL NEW CONDUIT TO FOLLOW SIMILAR ROUTE AS EXISTING TO MINIMIZE TRENCHING,

AND INTERCEPT EXISTING CONDUIT AS CLOSE AS POSSIBLE TO LIGHT POLE BASE. PULL NEW

WIRING THROUGH NEW RACEWAY.

C. REMOVE EXISTING WIRING ONLY AFTER NEW CONDUIT AND WIRING ARE INSTALLED AND ARE

READY TO INTERCEPT EXISTING CONDUIT NEAR POLE BASE. EXISTING CONDUIT MAY BE

SUBMERGED OR IN OTHERWISE DAMAGED CONDITION. FOLLOWING REMOVAL OF EXISTING

WIRE, ABANDON EXISTING CONDUIT. MINIMIZE DOWNTIME AS MUCH AS POSSIBLE AND

COORDINATE OUTAGES WITH CONSTRUCTION MANAGER AND OWNER.

17 17

19 20 20

35 35 35 35

17 17

10 14

31 31

TO EXISTING

METER #514250

ON REVERSE SIDE

TO EXISTING

FEEDERS/LOADS

TO EXISTING LOADS

TO EXISTING LOADS

TO EXISTING FEEDERTO EXISTING

CRANE POWER

TO EXISTING

SWITCH BOX ON

REVERSE SIDE

TO EXISTING

FEEDERS/LOADS

TO EXISTING LOADS

TO EXISTING LOADS

TO EXISTING

PV INVERTER

TO EXISTING PV

SYSTEM ON ROOF

TO EXISTING

METER #514251

ON REVERSE SIDE

1 1 1

METER #514250

METER #515049 METER #514251

TO: 1

TO: 7

UTILITY TRANSFORMER ROOM

TO: 7

TO: 1

UTILITY TRANSFORMER ROOM

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

ELECTRICAL EQUIPMENT ELEVATION - DEMO

GENERAL NOTES:

A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.

CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK

AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.

SHEET NOTES:

1. TRACE EXISTING FEEDERS AND LOADS, AND VERIFY EXISTING CONDUIT AND

CONDUCTOR SIZES. CUT AND STUB EXISTING CONDUIT AND WIRING. REMOVE

ABANDONED CONDUIT AND WIRING FOR ANY LOADS NO LONGER IN USE.

ED-301

ELECTRICAL EQUIPMENT ELEVATION - DEMO

ELECTRICAL EQUIPMENT ELEVATION - DEMO

35 35

35 35 35 35

31 31

4 6

8 7 10

12 11

TO EXISTING

PV INVERTER

TO EXISTING PV

SYSTEM ON ROOF

TO EXISTING

METER #514250

ON REVERSE SIDE

TO EXISTING LOADS

TO EXISTING FEEDERTO EXISTING

CRANE POWER

TO EXISTING

SWITCH BOX ON

REVERSE SIDE

TO EXISTING FEEDER

TO EXISTING LOADS

TO EXISTING LOADS TO EXISTING LOADS TO EXISTING LOADSTO EXISTING LOADS

TO EXISTING FEEDERS/LOADS

1 1

1 1 1 1 1

METER #514250

METER #515049 METER #514251

TO: 1

TO: 7

UTILITY TRANSFORMER ROOM

TO: 1

TO: 7

UTILITY TRANSFORMER ROOM

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

ELECTRICAL EQUIPMENT ELEVATION

GENERAL NOTES:

A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.

CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK

AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.

SHEET NOTES:

1. INTERCEPT EXISTING CONDUITS AND WIRING REMAINING FROM DEMOLITION WITH

PULLBOX AND CONNECT EXISTING TO NEW CONDUITS AND WIRING.

E-301

ELECTRICAL EQUIPMENT ELEVATION

ELECTRICAL EQUIPMENT ELEVATION

DUCT DETAIL TYPE 1

DUCT DETAIL TYPE 2

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

E-401

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

E-501

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

E-502

(E)MECO

METER #514250

3P100A(E)MECO

SECONDARY

SERVICE

(E)MECO

METER #514251

3P200A(E)MECO

SECONDARY

SERVICE

(E)TRANSFORMER "T-X1"

480-208/120V, 45KVA

2P70A

(E)PNL "X"

208/120V, 3Ø, 4W

225A, 10KAIC

(E)TO MAIN GATE HOUSE

3P70A

(E)TO PANEL '2A'

2P100A

(E)TO PASHA TRAILER

3P70A

(E)PNL "S"

480/277V, 3Ø, 4W

225A, 10KAIC

3P70A

3P25A

2P15A

(E)PNL "NC"

480/277V, 3Ø, 3W

100A, 10KAIC

(E)PNL "L"

480/277V, 3Ø, 4W

225A, 10KAIC

3P70A

(E)TRANSFORMER "T-S1"

480-208/120V, 15KVA

(E)PNL "2S"

208/120V, 3Ø, 4W

100A, 10KAIC

3P50A

3P70A

(E)PNL "P"

480/277V, 3Ø, 3W

350A, 22KAIC

3P150A

2P30A

(E)TRANSFORMER "T-P1"

480-208/120V

3P50A

2P50A

2P70A

3P50A

3P70A

3P125A

(E)PNL "A"

208/120V, 3Ø, 4W

225A, 10KAIC

3P50A

(E)ENCLOSED

CIRCUIT BREAKER

(E)TRANSFORMER "T-S2"

480-208/120V, 5KVA

2P20A

(E)RELAY MAIN

2P30A

(E)RELAY CONTROL 2 (E)SWITCH BOX

(E)RELAY CONTROL 1

(E)GUTTER

(E)TO PANEL '4H2'

(E)TO SHED 1B

(E)LIFT STATION

PFB

(E)PNL "1A"

208/120V, 3Ø, 4W

100A, 10KAIC

3P60A

(E)JB

(E)JB

(E)PULLBOX 1

3P200A DS

200A FUSE

AC

DC

(E)PV INVERTER

(E)PV

DISCONNECT

(E)PV ARRAY

(E)PNL "PV LOADCENTER"

208/120V, 3Ø, 4W

150A, 10KAIC

(E)TO PV SOLARGUARD

(E)TO PV DECK MONITOR

3P100A

C

M

M

C

(E)TO PNL '1B'

(E)TO

RESTROOMS

(E)FEEDER1

(E)PNL "REEFER"

208/120V, 3Ø, 3W

400A, 22KAIC

3P50A

2P30A

3P100A

(E)FEEDER1

(E)REEFER OUTLETS (TYP)

(E)EXST LOAD R.1

(E)CRANE POWER

ELECTRICAL ONE-LINE DIAGRAM - DEMO

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

ED-601

GENERAL NOTES:

A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.

CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK

AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.

SHEET NOTES:

1. TRACE EXISTING FEEDERS AND LOADS, AND VERIFY EXISTING CONDUIT AND

CONDUCTOR SIZES. CUT AND STUB EXISTING CONDUIT AND WIRING. REMOVE

ABANDONED CONDUIT AND WIRING FOR ANY LOADS NO LONGER IN USE.

(E)MECO

METER #514250

3P100A(E)MECO

SECONDARY

SERVICE

(E)MECO

METER #514251

3P200A(E)MECO

SECONDARY

SERVICE

3P200A DS

200A FUSE

AC

DC

(E)PV INVERTER

(E)PV

DISCONNECT

(E)PV ARRAY

(E)TO PV SOLARGUARD

(E)TO PV DECK MONITOR

M

M

(E)TRANSFORMER "T-X1"

480-208/120V, 45KVA

2P70A

(E)PNL "X"

208/120V, 3Ø, 4W

225A, 10KAIC

(E)TO MAIN GATE HOUSE

3P70A

(E)TO PANEL '2A'

2P100A

(E)TO PASHA TRAILER

3P70A

PNL "S"

480/277V, 3Ø, 4W

225A, 10KAIC

3P25A3P200A

TRANSFORMER "T-S1"

480-208/120V, 15KVA

PNL "NC"

480/277V, 3Ø, 3W

100A, 10KAIC

2P30A

PNL "2S"

208/120V, 3Ø, 4W

100A, 10KAIC

3P50A

RELAY CONTROL 1

C

(E)SWITCH BOX

JB

RELAY CONTROL 2

C JB

TS

TS

3P70A

PNL "P"

480/277V, 3Ø, 3W

600A, 22KAIC

3P150A

TRANSFORMER "T-P1"

480-208/120V, 45KVA

2P70A

3P70A

3P125A

PNL "A"

208/120V, 3Ø, 4W

225A, 10KAIC

3P50A(E)TO PANEL '4H2'

(E)TO SHED 1B

(E)LIFT STATION

PNL "1A"

208/120V, 3Ø, 4W

100A, 10KAIC(E)TO PNL '1B'

(E)TO RESTROOMS

PULLBOX

PULLBOX

PULLBOX

(E)FEEDER

PULLBOX

PULLBOX

PULLBOX

PULLBOX

PULLBOX

RELAY CONTROL 1

CTS

PULLBOX

(E)PNL "PV LOADCENTER"

208/120V, 3Ø, 4W

150A, 10KAIC

PULLBOX

PULLBOX 3

2"C,4#3/0,1#4G

2"C,4#3/0,1#6G

1-1/2"C,4#4,1#8G

2"C,4#3/0,1#6G

4 41"C,4#8,1#10G

3P200A

3P350A

3/4"C,4#12,1#12G

1"C,4#8,1#10G

1-1/2"C,4#4,1#8G

1#8G

1#4G

2"C,4#1,1#8G

2P30A

27,29

HM-7 HM-8 HM-9

2P30A

31,33

PNL "REEFER"

208/120V, 3Ø, 3W

400A, 22KAIC

3P50A

2P30A

3P100A

(E)FEEDER1

(E)REEFER OUTLETS (TYP)

(E)EXST LOAD R.1

(E)CRANE POWER

3P300A

HM-10 HM-11 HM-12

2P30A

16,18

HM-5 HM-3

2P30A

35,37

HM-1 HM-0 HM-1D

HM-6 HM-4

HM-1E

HM-2

2P30A

20,22

HM-1A HM-13

2P30A

24,26

HM-18 HM-17 HM-16

P-1 HM-18-2HM-14 HM-15

RE: ENLARGED SITE PLANS AND DUCT SCHEDULES FOR LIGHT POLE FEEDER SIZES, TYP.

EXISTING PULLBOXES BUILT IN TO LIGHT POLE BASES

ELECTRICAL ONE-LINE DIAGRAM

DRAWING NO.

SHEET

AS NOTEDAS NOTED

DRAWN BY:

WSP HI

SCALE:

DESIGNED BY:

APPROVED BY:

DL

DL

DATE

JOB NO.

CHECKED BY:

THIS WORK WAS PREPARED BY ME

OR UNDER MY SUPERVISION

NO.

REVISION SYM.

DESCRIPTION

WORKS ADMINISTRATOR

APPROVED: PUBLICDATE

OF SHTS

FOLDERFILE DRAWER

License Expiration Date: 4/30/2028

NKS

KAHULUI, PIER 1, ELECTRICAL

UPGRADE AND STANDARDIZATION

GENERAL NOTES:

A. EXISTING ELECTRICAL SHOWN IS BASED ON VISUAL OBSERVATION ONLY.

CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK

AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND ON SITE.

SHEET NOTES:

1. TO EXISTING FEEDER OR LOAD REMAINING FROM DEMOLITION.

2. PANEL RATING BASED ON ASSUMED FEEDER SIZE AND VOLTAGE RATING. PROVIDE

NEW PANEL WITH APPROPRIATE RATINGS TO MATCH EXISTING FEEDER.

3. INTERCEPT EXISTING CONDUITS AND WIRING REMAINING FROM DEMOLITION WITH

PULLBOX AND CONNECT EXISTING TO NEW CONDUITS AND WIRING.

4. PROVIDE CONDUIT AND WIRING AS SPECIFIED (IN ONE-LINE DIAGRAM OR PANEL

SCHEDULE) OR TO MATCH EXISTING, WHICHEVER IS LARGER.

5. NEW UPSIZED 600A DISTRIBUTION PANEL TO ACCOMMODATE EXISTING PV SYSTEM.

E-601

2026-05-28T19:34:37+0000