Final_CD_Drawings - AE Lighting - Audie Murphy - 20201028_v2.pdf

PDF 11 MB Posted

Attached to
Y1DA--671-15-132 Install Lighting Upgrade for Energy Efficiency (VA-22-00003947)
Solicitation number
36C25722B0007
Issued by

About this file

This document provides details for a federal construction contract opportunity to install lighting upgrades at the Audie Murphy VA Medical Center in San Antonio, Texas. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17 will award a firm-fixed-price construction contract with an estimated value between $1,000,000 to $5,000,000. The scope of work involves replacing existing lamps and fixtures with more energy efficient devices, installing lighting control devices, upgrading fixtures and bulbs, integrating sensors and controls, and designing light harvesting systems. Interested parties should monitor the Federal Business Opportunities website for solicitation number 36C25722B0007 with an anticipated issue date of October 15, 2021 and bid due date of November 15, 2021. This opportunity is set aside exclusively for service-disabled veteran-owned small businesses. The work must be completed within 365 calendar days of the notice to proceed.

View the file

Other files

File Type Posted
Pre-Bid Sign In_11.15.21.pdf PDF
36C25722B0007 0002.docx DOCX document
36C25722B0007 0001.docx DOCX document
36C25722B0007_1.docx DOCX document
Final_CD_Specs - AE Lighting - Audie Murphy - 20201028.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JOB NO:

DATE:

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

AUDIE L. MURPHY MEMORIAL VETERANS HOSPITAL

SAN ANTONIO, TEXAS

PROJECT NUMBER: 671-15-132

INSTALL LIGHTING UPGRADES FOR ENERGY EFFICIENCY

SHEET

NUMBER

MAIN ENTRANCE

MAIN HOSPITAL

SICU

WAREHOUSE

TOWER

CANTEEN

COVER, DRAWING INDEX

G-001

GF301 FIRST LEVEL MASTER PLAN

GF301-1 FIRST LEVEL - AREA 1

GF301-2 FIRST LEVEL - AREA 2

GF301-3 FIRST LEVEL - AREA 3

GF301-4 FIRST LEVEL - AREA 4

GF301-5 FIRST LEVEL - AREA 5

GF301-6 FIRST LEVEL - AREA 6

GF301-7 FIRST LEVEL - AREA 7

GF301-8 FIRST LEVEL - AREA 8

GF301-9 FIRST LEVEL - AREA 9

GF301-10 FIRST LEVEL - AREA 10

GF301-11 FIRST LEVEL - AREA 11

GF301-12 FIRST LEVEL - AREA 12

GF301-13 FIRST LEVEL - AREA 13

GF301-14 FIRST LEVEL - AREA 14

GF301-15 FIRST LEVEL - AREA 15

GF301-16 FIRST LEVEL - SURVEY TABLE

G-001 COVER & DRAWING INDEX

G-002 ELECTRICAL SYMBOLS & ABBREVIATIONS

G-003 INFECTIOUS AND CONSTRUCTION NOTES

E-101 TYPICAL DETAILS FOR ROOM EQUIPMENT PLACEMENT

E-102 TYPICAL DETAILS FOR SINGLE ROOM CONTROL

E-103 TYPICAL DETAILS FOR DUAL ROOM CONTROL TYPICAL

E-104 DETAILS FOR MULTI-FUNCTION SWITCH

E-105 TYPICAL DETAILS FOR SMART OCCUPANCY SENSOR

E-106 TYPICAL DETAILS FOR OCCUPANCY SENSOR SWITCH

E-201 CANTEEN LIGHTING CONTROLS

E-202 CANTEEN REFLECTED CEILING LIGHTING PLAN

E-203 TYPICAL DETAIL FOR MASTER INTERFACE (1 OF 2)

E-204 TYPICAL DETAIL FOR MASTER INTERFACE (2 OF 2)

E-205 TYPICAL DETAIL FOR SBB1 (1 OF 2)

E-206 TYPICAL DETAIL FOR SBB1 (2 OF 2)

E-207 TYPICAL DETAIL FOR LRM (1 OF 3)

E-208 TYPICAL DETAIL FOR LRM (2 OF 3)

E-209 TYPICAL DETAIL FOR LRM (3 OF 3)

E-210 TYPICAL DETAIL FOR COLOR WALL STATION (1 OF 2)

E-211 TYPICAL DETAIL FOR COLOR WALL STATION (2 OF 2)

E-212 TYPICAL DETAILS FOR DUAL ROOM CONTROL

E-213 CANTEEN TYPICAL DETAIL FOR MASTER INTERFACE

E-214 CANTEEN RISER DIAGRAM

E-215 CANTEEN LIGHTING AS-BUILTS - FOR REFERENCE ONLY

DEPARTMENT

OF

VETERANS AFFAIRS

BASE BID / ADDITIVE ALTERNATES

ALL WORK SHOWN FOR CANTEEN SHALL BE BASE BID

ALL WORK SHOWN ON FIRST FLOOR IN SINGLE OCCUPANCY ROOMS & RESTROOMS SHALL BE ADDITIVE ALTERNATE NUMBER 1

ALL WORK SHOWN ON FIRST FLOOR IN MULTI-OCCUPANCY ROOMS AND RESTROOMS SHALL BE ADDITIVE ALTERNATE NUMBER 2

ALL WORK SHOWN ON FIRST FLOOR IN MULTI-ROOM SYSTEMS SHALL BE ADDITIVE ALTERNATE NUMBER 3

SHEET

DESCRIPTION

VICINITY MAP

SCALE: N.T.S.

SHEET

NUMBER

SHEET

DESCRIPTION

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

ALTERNATE CURRENT

ADJACENT

ABOVE FINISH FLOOR

AGGREGATE

ALUMINUM

ALTERNATE

APPROXIMATELY

ARCHITECT(URAL)

ASPHALT

BARRIER

BRACKET

BUILDING

BLOCKING

BELOW

BOTTOM OF CURB

BOTTOM OF SIDEWALK/PAD

BOTTOM

BRACE, BRACING

CENTERLINE

CEILING

COLUMN

COMPOSITION

CONCRETE

CONNECTION

CONSTRUCTION

CONTINUOUS

CONCRETE SEALER

DIRECT CURRENT

DEMOLISH(ION)

DIMENSION

DOWN

DOOR

DUAL TECHNOLOGY

DETAIL

DRAWING(S)

EAST

EACH

ELEVATION

ELECTRIC(AL)

END OF CURB

EDGE OF PAVEMENT

EQUAL

EQUIPMENT

EACH SIDE

EXPOSED TO STRUCTURE

EXISTING

EXTERIOR

FIRE ALARM

FLOOR DRAIN

FIRE EXTINGUISHER (CABINET)

FACTORY FINISH

FINISH FLOOR BREAK

FINISH FLOOR LINE

FINISH(ED)

FLASHING

FLOOR(ING)

FOUNDATION

FACE OF SHEATHING (GB)

FIRE PROOF

FRAME

FOOT, FEET

FOOTING

FURRING

FURNISHED

GAGE, GAUGE

GYPSUM WALL BOARD

GOVT FURN GOVT INSTALLED

GOVERNMENT

GYPSUM

HARDWARE

HOLLOW METAL

HEIGHT

INCLUDE(D,ING)

INSULATION

INTERIOR

AC

ADJ

AFF

AGG

ALUM

ALT

APPROX

ARCH

AS

BARR

BKT

BLDG

BLKG

BLW

BOC

BOS

BOT

BRC

CL/℄

CLG

COL

COMP

CONC

CONN

CONST

CONT

CS

DC

DEMO

DIM

DN

DR

DT

DTL

DWG

E

EA

EL(EV)

ELEC

EOC

EOP

EQ

EQUIP

ES

ETS

EX(IST)

EXT

FA

FD

FE(C)

FF

FFB

FFL

FIN

FLASH

FLR

FNDN

FOS

FP

FRM

FT

FTG

FUR

FURN

GA

GB/GWB

GFGI

GOVT

GYP

HDWE

HM

HT

INCL

INSUL

INT

JT

KV

LAM

LT

MAT

MAX

MECH

MFR

MIN

MISC

MTL

N

NTS

OC

OCC

OPNG

OPP

OVHD

P

PC

PRFB

PL,PLYWD

PLAM

PNL

PS

PVMT

REF

REINF

REQ

RM

RO

S

SCHED

SEC

SF

SHG

SHT

SIM

SM

SPEC

SQ

SST

STDG

STL

STOR

STRUCT

SUSP

SV

SYS

THK

THRESH

TOC

TOS

TPH

TRANS

TS

TYP

UNO

VAR

VB

VERT

VIF

W/

WD

WDW

WP

WR

WT

JOINT

KILOVOLT

LAMINATE(D)

LIGHT

MATERIAL(S)

MAXIMUM

MECHANIC(AL)

MANUFACTURE(R)

MINIMUM

MISCELLANEOUS

METAL

NORTH

NOT TO SCALE

ON CENTER(S)

OCCUPANCY

OPENING

OPPOSITE

OVERHEAD

PAINT

PRECAST CONCRETE

PREFABRICATED

PLYWOOD

PLASTIC LAMINATE

PANEL

PLASTIC

PAVEMENT

REFERENCE

REINFORCE(D,ING)

REQUIRED

ROOM MANAGER

ROUGH OPENING

SOUTH

SCHEDULE

SECTION

SQUARE FEET

SHINGLES

SHEET

SIMILAR

SEAM

SPECIFICATION

SQUARE

STAINLESS STEEL

STANDING

STEEL

STORAGE

STRUCTURAL

SUSPENDED

SHEET VINYL

SYSTEM

THICK(NESS)

THRESHOLD

TOP OF CURB

TOP OF SIDEWALK/PAD

TOILET PAPER HOLDER

TRANSITION

TOUCH SCREEN

TYPICAL

UNLESS NOTED OTHERWISE

VARIES

VAPOR BARRIER

VERTICAL

VERIFY IN FIELD

WITH

WOOD

WINDOW

WATERPROOF(ING)

WATER RESISTANT

WOOD TRIM

SYMBOLS

DETAIL NUMBERING OR SECTION LETTER

SHEET TITLE

SHEET SCALE

NORTH ARROW

TOUCHSCREEN WALL STATION, SW-TS-M

LOCAL RELAY MODULE

SMAOS CEILING SMART SENSOR DUAL

TECHNOLOGY SURFACE MOUNT

ROOM MANAGER

ELECTRICAL SYMBOLS,

ABBREVIATIONS & SCHEDULES

G-002

0 4' 8' 16'

1/8" = 1'-0"SCALE:

AREA 1

FLOOR PLAN

LRM

RM

SYMBOL DESCRIPTION

WALL MOUNTED SWITCH. LETTER INDICATES AS FOLLOWS:

Mo - LIGHTING CONTROL MOTION DETECTOR SWITCH.

ELECTRICAL SYMBOLSELECTRICAL ABBREVIATIONS

LIGHT FIXTURE SCHEDULE

TYPE MANUFACTURER MODEL NUMBER VOLTAGE FIXTURE TYPE LUMENS DESCRIPTION

A PORTFOLIO LD6B AS REQUIRED LED

6" RECESSED DOWN LIGHT

B METALUX 22FP2135C LED

2X2 FLAT PANEL

C METALUX 24FP3135C LED

2X4 FLAT PANEL

D METALUX 4ST2L4035R LED

4' INDUSTRIAL

E METALUX 24FP4735C LED

2X4 FLAT PANEL

F METALUX 24FP6435C LED

2X4 FLAT PANEL

G

METALUX 24FP4735C LED

2X4 FLAT PANEL

H METALUX 22FP3235C LED

2X2 FLAT PANEL

J METALUX

2BCLED-LD4-20SL-F-UNV-L835-CD1

LED

2' WALL MOUNT LED

K METALUX

4BCLED-LD4-32SL-F-UNV-L835-CD1

LED

4' WALL MOUNT LED

MASTER INTERFACE SERIES 2

MSTR

PASSIVE BRANCH BOOSTER & SPLITTER MODULE

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AS REQUIRED

AutoCAD SHX Text Mo

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

INFECTION PREVENTION NOTES:

1. ALL CONTRACTORS, CONSTRUCTION WORKERS, AND CORS MUST ATTEND THE INFECTION PREVENTION

TRAINING ANNUALLY AND BRING PROOF OF NEGATIVE TB WITH THEM AT THAT TIME.

2. THE INFECTION PREVENTION OFFICE SHALL BE NOTIFIED OF ALL PRE-CONSTRUCTION MEETINGS.

3. THE ICRA (INFECTION CONTROL RISK ASSESSMENT) SHALL BE WRITTEN INTO THE CONTRACT AND

SPECIFICATIONS FOR ALL CONTRACTORS AND SUBCONTRACTORS.

4. THE CONTRACTOR SHALL CLEAN THE WHEELS AND OUTSIDE OF ALL CARTS AND EQUIPMENT BROUGHT INTO

AND OUT OF THE MAIN HOSPITAL OR POLYTRAUMA FACILITIES.

5. INFECTION PREVENTION OFFICE MUST BE NOTIFIED OF ALL WATER SHUT-OFF OR INTERRUPTIONS.

6. THE CONTRACTOR SHALL WET MOP HEAVY TRAFFIC AREAS AT LEAST TWO (2) TIMES A DAY OR MORE IF SITE

HAS AN ICRA LEVEL OF 3 OR 4 AND/OR IF THE AREA HAS HIGH VOLUME OF DUST. WATER SHALL BE CHANGED

DAILY. DO NOT LEAVE STANDING WATER OVER NIGHT.

7. CONSTRUCTION WORKERS SHALL WEAR DUPONT TYVEK COVERALLS OR EQUIVALENT OVER CLOTHES AND

SHOE COVERS IN MODERATE TO HIGH DUST AREAS IN MAIN HOSPITAL OR POLYTRAUMA FACILITIES TO

PREVENT CONTAMINATION OF EMPLOYEE CLOTHES AND TRACKING DUST AND DIRT INTO THESE FACILITIES.

CONSTRUCTION WORKERS SHALL REMOVE COVERALLS BEFORE LEAVING THE AREA.

8. THE INFECTION PREVENTION OFFICE NEEDS TO BE NOTIFIED IF THE HVAC MUST BE INTERRUPTED IN AREAS

THAT AFFECT PATIENT CARE.

9. THE INFECTION PREVENTION OFFICE SHALL BE NOTIFIED OF ANY ANTICIPATED ALTERATIONS TO THE ACCESS

ROUTES USED DURING CONSTRUCTION ACTIVITIES.

10. ALL ICRA LEVEL 3 PROJECT SITES MUST HAVE, AT A MINIMUM, POP-UP CONTAINMENT BARRIER(S) WITH

SCRUBBER(S); SINCE THIS IS AN ICRA 3 LEVEL PROJECT.

11. ALL ICRA LEVEL 4 PROJECT SITES MUST HAVE AM ANTE-ROOM TO MAINTAIN NEGATIVE AIRFLOW AND BE

LARGE ENOUGH TO REMOVE COVERALLS AND HAVE A TRASH CONTAINER. THE ANTE-ROOM MUST BE

CLEARLY IDENTIFIED ON THE DRAWINGS.

12. AIR FILTRATION WITH HEPA FILTERS SHALL BE USED ON SITE FOR SMALL CLEAN-UPS IN PATIENT CARE AREAS

THAT HAVE AN ICRA LEVEL OR 1 OR 2.

13. THE CONTRACTOR SHALL PROVIDE A DAILY LOG FOR THE VA STAFF LOCATED ON SITE THAT CONTAINS

UPDATES NOTING THE READING ON THE PRESSURE SENSOR. CERTIFYING THAT THE SITE HAS BEEN

CONTINUALLY MAINTAINING NEGATIVE AIR PRESSURE DURING CONSTRUCTION FOR ALL ICRA LEVEL 3 AND 4

PROJECT SITE. INFECTION PREVENTION MEASURES.

14. THE PRIME CONTRACTOR WILL ENSURE THAT CONTRACTORS IMPLEMENT THE REQUIREMENTS OF VAMC'S

INFECTION RISK ASSESSMENT (ICRA) TEAM. ICRA GROUP MAY MONITOR DUST IN THE VICINITY OF THE

CONSTRUCTION WORK AND REQUIRE THE CONTRACTOR TO TAKE CORRECTIVE ACTION IMMEDIATELY IF THE

SAFE LEVELS ARE EXCEEDED.

15. THE PRIME CONTRACTOR WILL ENSURE THAT THE CONTRACTOR ESTABLISHES AND MAINTAINS A DUST

CONTROL PROGRAM AS PART OF THE CONTRACTOR'S INFECTION PREVENTION MEASURES IN ACCORDANCE

WITH THE GUIDELINES PROVIDED TO THE PRIME CONTRACTOR. PRIOR TO START OF WORK THE

CONTRACTOR SHALL PREPARE A PLAN DETAILING BEST MANAGEMENT PRACTICES.

16. PROJECT-SPECIFIC DUST PROTECTION MEASURES INCLUDE PERIODIC STATUS REPORTS WHICH ARE TO BE

SUBMITTED TO RESIDENT ENGINEER AND FACILITY ICRA TEAM FOR REVIEW FOR COMPLIANCE WITH

CONTRACT REQUIREMENTS IN ACCORDANCE WITH SECTION 01 33 23, SHOP DRAWINGS. PRODUCT DATA AND

SAMPLE. ALL PERSONAL INVOLVED IN THE CONSTRUCTION OR RENOVATION ACTIVITY SHALL BE EDUCATED

AND TRAINED IN INFECTION PREVENTION MEASURES ESTABLISHED BY THE MEDICAL CENTER.

17. THE PRIME CONTRACTOR WILL ENSURE CERTIFICATION THAT THE CONTRACTOR HAS A MEDICAL PROGRAM

THAT ADDRESSES TUBERCULOSIS. THE MEDICAL PROGRAM SHALL INCLUDE WRITTEN ASSURANCE THAT

EACH EMPLOYEE HAS NO ACTIVE TUBERCULOSIS. ALL CONTRACT EMPLOYEES ASSIGNED TO THE WORK SITE

SHALL HAVE A PRE-PLACEMENT TUBERCULIN SCREENING WITHIN 90 DAYS PRIOR TO ASSIGNMENT TO THE

WORK SITE AS RECOMMENDED BY THE CENTER FOR DISEASE CONTROL (CDC). THIS CAN BE THE CDC

TWO-STEP SKIN TESTING OR FOOD AND DRUG ADMINISTRATION (FDA) APPROVED BLOOD TEST. EMPLOYEES

MANIFESTING POSITIVE SCREENING REACTIONS TO THE TUBERCULIN SHALL BE EXAMINED PER CURRENT

CDC GUIDELINES PRIOR TO WORKING ON VA PROPERTY. IF THE EMPLOYEE IS FOUND WITHOUT EVIDENCE OF

ACTIVE INFECTIOUS PULMONARY TUBERCULOSIS (TB). A STATEMENT DOCUMENTING EXAMINATION BY A

PHYSICIAN MUST BE ON FILE WITH THE EMPLOYER (CONSTRUCTION CONTRACTOR). NOTING THAT THE

EMPLOYEE WITH A POSITIVE TUBERCULIN SCREENING TEST IS WITHOUT EVIDENCE OF ACTIVE INFECTIOUS

PULMONARY TB. THE EMPLOYEE FOUND WITH ACTIVE DISEASE WOULD REQUIRE TREATMENT WITH A

SUBSEQUENT STATEMENT OUTLINED ABOVE BEFORE BEING ALLOWED TO RETURN TO WORK ON VA

PROPERTY.

18. CONTRACTOR SHALL MONITOR FOR AIRBORNE DISEASE (EG. ASPERGILLOSIS) AS APPROPRIATE DURING

CONSTRUCTION A BASELINE OF CONDITIONS MAY BE ESTABLISHED BY THE MEDICAL CENTER PRIOR TO THE

START OF WORK AND PERIODICALLY DURING THE CONSTRUCTION STAGES. TO DETERMINE IMPACT OF

CONSTRUCTION ACTIVITIES ON INDOOR AIR QUALITY. IN ADDITION; IN CASE OF ANY PROBLEM, THE MEDICAL

CENTER, ALONG WITH ASSISTANCE FROM THE CONTRACTOR, SHALL CONDUCT AN ENVIRONMENTAL

ASSESSMENT TO FIND AND ELIMINATE THE SOURCE CONTRACTOR RESPONSIBLE FOR MONITORING AND

MAINTAINING NEGATIVE AIR PRESSURE THROUGHOUT ENTIRE AREA UNDER CONSTRICTION IN ICRA LEVEL 3 &

4 CONSTRUCTION SITE.

19. THE FOLLOWING PREVENTION MEASURES SHALL BE ADOPTED DURING CONSTRUCTION TO KEEP DOWN DUST

AND PREVENT MOLD.

20. DAMPEN DEBRIS TO KEEP DUST DOWN IN EXISTING STRUCTURES WHERE DIRECTED BY RESIDENT ENGINEER.

DO NOT PERFORM DUST PRODUCING TASKS WITHIN OCCUPIED AREAS WITHOUT THE APPROVAL OF THE

RESIDENT ENGINEER.

CONSTRUCTION SAFETY NOTES:

1. CONSTRUCTION BARRIER SHALL CONSIST OF: 1 HOUR RATED GYPSUM BOARD PARTITION FROM FLOOR TO CEILING AND FIRE RATED POLY BARRIER FROM CEILING TO UNDERSIDE OF DECK ABOVE, DUST BARRIER WALLS EXTENDING PERPENDICULAR TO A CORRIDOR SHALL BE BUILT AT A 45° ANGLE IN REFERENCE TO THE CORRIDOR FLOW OF EGRESS. BARRIERS SHALL BE WIPED DOWN PRIOR

TO BEING REMOVED.

2. DIRECTIONAL SIGNS MUST BE POSTED TO DISPLAY MEANS OF EGRESS AND LIFE SAFETY INFORMATION.

3. ILLUMINATED EXIT SIGNS SHALL BE RELOCATED WHEN OBSTRUCTED BY CONSTRUCTION.

4. GENERAL CONTRACTOR SHALL WORK CLOSELY WITH THE RESIDENT ENGINEER AND/OR CONTRACTING OFFICER TECHNICAL REPRESENTATIVE (COTR) WHEN LIFE SAFETY HAZARDS ARE PRESENT.

THE RESIDENT ENGINEER AND/OR COTR SHALL COMMUNICATE ALL SAFETY CONCERNS TO THE SAFETY OFFICE.

5. GENERAL CONTRACTOR SHALL KEEP DUST CONTAINMENT BARRIER PRESSURE AT NEGATIVE AT ALL TIMES. HVAC EXHAUST AND SUPPLY DUCTS SHALL BE COVERED DURING DEMOLITION.

6. GENERAL CONTRACTOR SHALL MEASURE CONSTRUCTION DUST CONTAINMENT BARRIER PRESSURE ON A DAILY BASIS, AND SHALL REPORT READING TO THE SAFETY OFFICE AND DESIGN OFFICE.

7. GENERAL CONTRACTOR SHALL INSPECT THE INTEGRITY OF THE DUST CONTAINMENT BARRIER AND SHALL REPAIR AS REQUIRED. DUST CONTAINMENT BARRIER INTEGRITY MUST BE MAINTAINED TO

THE UPPER DECKING OF THE CONSTRUCTION SITE.

8. WORK SITE SHALL BE SECURED BY LOCK WHEN NO EMPLOYEES ARE PRESENT ON SITE.

9. FLOOR MATS AND STICKY MATS LOCATED AT THE ENTRANCE TO THE CONSTRUCTION AREA SHALL BE REPLACED AS NEEDED (AT APPROXIMATELY 75% USED).

10. GOOD HOUSEKEEPING - TRASH AND DEBRIS SHALL BE REMOVED PROMPTLY, AT LEAST DAILY.

11. HAZARDOUS MATERIALS SHALL BE STORED APPROPRIATELY.

12. SAFETY DATA SHEETS (SDS) SHALL BE POSTED ON JOB SITE.

13. ICRA SHALL BE POSTED ON JOB SITE.

14. SMOKING REGULATIONS SHALL BE FOLLOWED.

15. FIRE EXTINGUISHERS SHALL BE READILY AVAILABLE IN THE CONSTRUCTION AREA.

16. HOT WORK PERMITS SHALL BE ISSUED WHEN NECESSARY.

17. SAFETY AND TEMPORARY SIGN SHALL BE IN PLACE AT ALL TIMES THROUGH DURATION OF CONSTRUCTION.

18. SUBCONTRACTORS SHALL BE AWARE OF AND TRAINED IN SAFETY AND ENVIRONMENTAL ISSUES.

19. MEANS OF EGRESS SHALL BE CLEARLY DESIGNATED IN BOTH CONSTRUCTION AND ADJACENT AREAS. ACCESS FOR THE FIRE DEPARTMENT AND EMERGENCY SERVICES SHALL BE CLEAR. STATUS OF

THE FIRE DETECTION/SPRINKLER SYSTEM SHALL BE:

a. FIRE SPRINKLER SYSTEM IS ACTIVE

b. FIRE ALARM SYSTEM IS ACTIVE

c. SMOKE DETECTORS ARE ACTIVE

d. TEMPORARY SYSTEMS ARE IN PLACE

20. EXTENSION CORDS SHALL BE PROTECTED AND DISCONNECTED AT THE END OF EACH DAY

21. CONTRACTOR SHALL COORDINATE WITH COR, ENGINEERING SERVICE, INFECTION CONTROL, SAFETY SERVICE, AND ALL SERVICES AFFECTED BY DEMOLITION, REMOVAL, AND REINSTALLATION OF ALL

EQUIPMENT, ITEMS, COMPONENTS.

22. CONTRACTOR SHALL COORDINATE START DATE OF OUTAGE AND LENGTH OF DOWN TIME FOR EACH PHASE 14 DAYS IN ADVANCE. CONTRACTOR SHALL INFORM MAINTENANCE AND OPERATIONS

(M&O), ELECTRIC SHOP, INFECTION CONTROL, SAFETY SERVICE, COR, AND ADMINISTRATIVE OFFICES FOR ALL AFFECTED SERVICES.

23. FOR PHASING OF WORK, CONTRACTOR SHALL PROVIDE MINIMUM OF 14 WORKING DAYS’ NOTICE PRIOR TO START OF EACH PHASE.

24. CONTRACTOR SHALL IMPLEMENT ALL NECESSARY PROTECTIVE AND DUST CONTAINMENT MEASURES WHEN WORKING ABOVE PATIENT/STAFF AREAS (E.G. MOVING/REMOVING CEILING TILES), AND

WHILE WORKING IN THE INTERSTITIALS ABOVE PATIENT/STAFF AREAS.

25. CONTRACTOR MUST FOLLOW ALL ESTABLISHED HOSPITAL POLICIES AND NFPA STANDARDS INCLUDING NFPA 101 LIFE SAFETY CODE.

INFECTIOUS/SAFETY AND

CONSTRUCTION NOTES

G-003

CONTRACTOR INSTRUCTIONAL NOTES:

1. CONTRACTOR SHALL MAKE A SURVEY OF THE ROOMS LISTED IN THIS CONTRACT TO VERIFY NUMBERS AND TYPES OF LIGHTING FIXTURES AND CONTROLS. CONTRACTOR SHALL SUBMIT FOR REVIEW

AND COORDINATION THE RESULTS OF THIS SURVEY TO CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR TO ISSUING PURCHASE ORDER FOR LIGHTING FIXTURE AND/OR COMPONENTS. NOTE

THAT ONGOING RENOVATIONS TO THE HOSPITAL MAY HAVE AFFECTED THE ROOMS CALLED OUT.

2. IT HAS BEEN ESTIMATED THAT UP TO 50% OF LIGHT SWITCHES IN THE HOSPITAL HAVE BEEN INSTALLED USING 3-CONDUCTOR (3/C) TYPE MC CABLE INSTEAD OF CONDUIT AND WIRE. IN THESE CASES, THE CONTRACTOR WILL BE REQUIRED TO CUT A CHANNEL UP THE WALL FROM THE SWITCH TO AT OR ABOVE THE CEILING AND REPLACE THE 3/C CABLE WITH 4-CONDUCTOR CABLE IN THE CASE OF

WALL MOUNTED OCCUPANCY SWITCHES OR WITH CAT 6E CABLE IN THE CASE OF TOUCH SCREEN WALL STATIONS. THE CONTRACTOR IS REQUIRED TO PATCH, FLOAT AND PAINT THE WALL TO MATCH

PREVIOUS FINISH.

3. CONTRACTOR SHALL INSTALL A MASTER PANEL ON EACH FLOOR NEAR THE ELEVATORS IN A LOCATION VERIFIED WITH THE COR. CAT 6E CABLING SHALL BE RUN ABOVE THE CEILING IN ALL FOUR

DIRECTIONS AND SHALL BE CONNECTED TO ALL RM'S AND LRM'S INSTALLED AS PART OF THIS PROJECT. THIS DOES NOT INCLUDE THE MASTER PANEL ASSOCIATED WITH THE WORK TO BE DONE IN THE

CANTEEN. LOCATION AND USE OF LRM'S AND RM'S SHALL BE DETERMINED BY CONTRACTOR BASED UPON LOCATION REQUIREMENTS AND VERIFIED WITH COR.

4. EXPECT TO WORK ON WEEKENDS, AFTER HOURS, HOLIDAYS, AS REQUIRED WHEN LARGE, LONG POWER DISRUPTIONS ARE NEEDED. CONTRACTOR SHALL COORDINATE POWER OUTAGES 14 DAYS IN

ADVANCE.

INFECTION CONTROL RISK ASSESSMENT:

· TYPE C ACTIVITY

· MEDIUM HIGH RISK CLASS

LEVEL/CLASS I PRECAUTIONS:

1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST.

2. IMMEDIATELY REPLACE ANY CEILING TILE DISPLACED FOR VISUAL INSPECTION.

LEVEL/CLASS II PRECAUTIONS:

1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPENSING INTO ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.

3. SEAL UNUSED DOORS WITH DUCT TAPE.

4. BLOCK OFF AND SEAL AIR VENTS.

5. CONTAIN AND TRANSPORT WASTE IN COVERED CONTAINERS.

6. WET MOP AND/OR VACUUM WITH HIGH-EFFICIENCY PARTICULATE ABSORPTION (HEPA) FILTERED VACUUM

BEFORE LEAVING AREA.

7. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.

8. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

9. POST SIGN CAUTIONING ABOUT SPREAD OF DUST

LEVEL/CLASS III PRECAUTIONS:

1. NOTIFY IC FOR APPROVAL BEFORE CONSTRUCTION BEGINS.

2. REMOVE OR ISOLATE HVAC SYSTEM.

3. COMPLETE ALL BARRIERS BEFORE CONSTRUCTION BEGINS. DUST BARRIERS MUST BE CONSTRUCTED OF

FIRE RETARDANT MATERIAL FROM CEILING TO DECKING AT INTERSTITIAL LEVEL. DUST BARRIERS

CONSTRUCTED AT FLOOR LEVEL MUST HAVE A ONE HOUR FIRE RATING. NOTE: NONRATED WALLS AND

OPENING PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS

INSTALLED.

4. DO NOT REMOVE BARRIERS UNTIL COMPLETED PROJECT IS THOROUGHLY CLEANED.

5. VACUUM WORK WITH HEPA FILTER VACUUM AS REQUIRED.

6. WET MOP WITH DISINFECTANT.

7. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZED SPREADING OF DIRT AND DEBRIS.

8. CONTAIN AND TRANSPORT WASTE IN COVERED CONTAINERS.

9. POST SIGN CAUTIONING ABOUT SPREAD OF DUST.

10. MAINTAIN NEGATIVE PRESSURE WITH HEPA FILTRATION, EXHAUST MUST BE ROUTED TO MAIN

VENTILATION OR OUTSIDE OF BUILDING.

INFECTION CONTROL RISK ASSESSMENT NOTES:

· OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS.

· ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF THE DUCT

SYSTEM, AS REQUIRED

· COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD (I.E., A CART WITH A PLASTIC

COVERING AND A SEALED CONNECTION TO THE WORK SITE WITH A HEPA VACUUM TO CLEAN THE AREA

PRIOR TO EXIT FROM THE AREA) BEFORE CONSTRUCTION BEGINS.

· MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.

· SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

· DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE

OWNER'S SAFETY DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL

SERVICES (EMS) DEPARTMENT.

· REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

· CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

· COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

· VACUUM WORK AREA WITH HEPA FILTERED VACUUMS. WET MOP AREA WITH DISINFECTANT. REMOVE

ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

· COVER ALL RETURNS AND SUPPLY DUCTS AT THE GRATE/DIFFUSES WITH FILTER MEDIA OR BLANKED OFF

ENTIRELY PER ICRA REQUIREMENTS.

· KEEP CONSTRUCTION SITE CLEAN & NEAT AT ALL TIMES.

· CONTRACTOR TO CLEAN THE CONSTRUCTION AREA, AND PREPARE FOR SAFETY AND INFECTION

CONTROL'S INSPECTION AND FINAL CLEANING BY VA EMS STAFF. VA EMS STAFF WILL PERFORM FINAL

VERIFICATION OF CLEANING AND SANITATION.

INTERIM LIFE SAFETY MEASURES (ILSM) NOTES:

IF APPLICABLE:

· HOT WORK PERMITS. PERMITS MUST BE OBTAINED 24 HOURS PRIOR TO COMMENCEMENT OF WORK, WHENEVER POSSIBLE. ORIGINAL PERMIT TO BE POSTED WHERE WORK IS BEING PERFORMED;

CONTRACTOR MUST RETURN PERMIT TO SAFETY OFFICE WHEN WORK IS COMPLETED.

· FIRE WATCH. CONTRACTOR MUST INITIAL, DATE AND TIME EVERY 30 MINUTES AFTER HOT WORK HAS

STARTED. CONTRACTOR TO PROVIDE WARNING SIGNAGE AND DIRECTIONAL SIGNAGE THAT SHALL BE

POSTED IN CONSTRUCTION AREA WHILE WORK IS PERFORMED.

· CONFINED SPACE. CONTRACTOR TO OBTAIN CONFINED SPACE PERMIT PRIOR TO ENTRY INTO

MECHANICAL CHASE. ENSURE IT IS APPROVED BY VA SAFETY DEPARTMENT AND COR.

GENERAL NOTES:

1. CONTRACTOR SHALL VISIT ALL AREAS OF WORK, INCLUDING WALKING THE SITE, MEASURING EXISTING DIMENSIONS AND OBSERVING EXISTING CONDITIONS BEFORE BEGINNING WORK, ORDERING

MATERIALS, OR STARTING ANY CONSTRUCTION. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS OF EXISTING SITE CONDITION PRIOR TO START OF WORK AND ORDERING OF MATERIALS.

2. CONTRACTOR SHALL RECYCLE REMOVED MATERIALS WHENEVER POSSIBLE. SEE SPECIFICATION SECTION 01 74 19.

3. CONTRACTOR TO PROTECT AREA ADJACENT TO THE DEMOLITION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES. (IF DAMAGED, REPAIR, RE-PATCH, SAND SMOOTH AND REFINISH TO MATCH

EXISTING.)

4. CONTRACTOR SHALL REPORT TO COR IMMEDIATELY WHEN DISCREPANCIES TO THE DRAWINGS ARE FOUND IN THE FIELD.

5. CONTRACTOR MUST ADHERE TO ALL NFPA, NEC, OSHA, CFR, ASSE, ETC., STANDARDS AND ALL APPLICABLE [FEDERAL, STATE, AND LOCAL] LAWS, ORDINANCES, CRITERIA, RULES AND REGULATIONS. CONTRACTOR MUST ADHERE TO VA MASTER SPECIFICATIONS, SECTION 01 35 26, SAFETY REQUIREMENTS FOUND AT

HTTP://WWW.CFM.VA.GOV/TIL/SPEC.ASP#01.

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

LIGHT CONTROL DEVICES

SW-TS-M

SMART SENSOR DUAL TECHNOLOGY LOW (< 20') SURFACE MOUNT

SMAOS-D-360L-S-W

TOUCHSCREEN WALL STATION

SYMBOL DESCRIPTION

EQUIPMENT

MODEL NUMBER

MAXIMUM DISTANCE BETWEEN SENSORS IS 12'

MAXIMUM DISTANCE BETWEEN SENSOR AND A WALL IS 6'

ADDITIONAL SENSORS MUST BE ADDED AS NEEDED TO MEET REQUIREMENTS

SENSOR COVERAGE AREA MUST BE DISTRIBUTED EVENLY

RM

ROOM MANAGER

SW-O-D-WHT-S2

OCCUPANCY SWITCH DUAL TECHNOLOGY

PAGE NOTES:

MAXIMUM DISTANCE BETWEEN SENSORS SHALL BE 12'.

ROOM MANAGER SHALL BE CONCEALED IN CEILING WHEN INSTALLED.

FOR LOCATIONS WHERE A SINGLE ROOM MANAGER CAN BE USED TO

CONTROL TWO ADJACENT ROOMS, THE RM SHALL BE LOCATED TO

SIMPLIFY CAPTURE OF LIGHTING SWITCHLEG CONDUCTORS AND

CONTROL INTERFACES. SEE DETAIL 1 ON SHEET E-103.

ROOM LENGTH

ROOM LENGTH

ROOM LENGTH

TYPICAL DETAILS FOR ROOM

EQUIPMENT PLACEMENT

E-101

RM

RM

RM

RM

NOTE:

ANY RESTROOM WITH STALL(S) SHALL HAVE ONE CENTRALLY LOCATED FIXTURE TO BE UNSWITCHED.

0 4' 8' 16'

3/4" = 1'-0"SCALE:

WALL SENSOR ROOM EQUIPMENT PLACEMENT

AND SINGLE OCCUPANCY RESTROOMS

1/2" = 1'-0"SCALE:

1' 2' 4'

CEILING SENSOR ROOM EQUIPMENT PLACEMENT

1/2" = 1'-0"SCALE:

1' 2' 4'

RESTROOM MULTI OCCUPANCY, ANY RESTROOM WITH STALL

1/2" = 1'-0"SCALE:

1' 2' 4'

MULTI ROOM EQUIPMENT PLACEMENT

AutoCAD SHX Text Mo

AutoCAD SHX Text Mo

AutoCAD SHX Text Mo

AutoCAD SHX Text Mo

AutoCAD SHX Text Mo

Mo

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

PAGE ID: SWITCH-TOUCH SCREEN MULTIFUNCTION

DESCRIPTION: MONOCHROME TOUCH SCREEN

PRODUCT ID: SW-TS-M

(4)

PAGE ID: SMART MICRO AMBIENT OCCUPANCY SENSOR

DESCRIPTION: CEILING SENSOR

PRODUCT ID: SMAOS-(D/P)-360(L/H)-(F/S)-W

PAGE ID: ROOM MANAGER

DESCRIPTION: ROOM MANAGER

PRODUCT ID: RM

PAGE NOTES:

UP TO 20 DEVICES CAN BE CONNECTED TO A SINGLE ROOM MANAGER. DIGITAL INPUT

DEVICES (SWITCH-SINGLE FUNCTION) DO NOT COUNT IN TOTAL DEVICE QUANTITY.

QUANTITY OF DEVICES MAY VARY DUE TO ROOM SIZE AND CONFIGURATION. DASHED

LINE SHOWN FOR CONNECTING OF ADDITIONAL DEVICES.

LINE VOLTAGE WIRING CONNECTED ON BACK SIDE OF ROOM MANAGER.

SWITCH-TOUCH SCREEN-TYPE M (SW-TS-M) OR SWITCH-TOUCH SCREEN-TYPE C

(SW-TS-C) MAY BE INTERCHANGED ON THE LOCAL PRIMARY NETWORK.

NOTE: SW-TS-C USED ON CANTEEN REWORK ONLY.

UP TO (16) ZONES OF CONTROL WHEN ROOM IS CONFIGURED FOR SINGLE ROOM

CONTROL. ZONES SHALL BE DEFINED AS TYPES OF FIXTURES, SUCH AS DOWN LIGHTS,

OR AREAS OF ROOM, SUCH AS END OF ROOM WITH PROJECTION SCREEN. CONTRACTOR

TO VERIFY ZONES WITH CONTRACTING OFFICER REPRESENTATIVE (COR).

SWITCH BUTTON SIZE, QUANTITY, FUNCTION AND LABELING TO BE CONFIGURED VIA

PROGRAMMING TO MATCH SPACE.

LEGEND:

CABLE TYPE SCHEDULE

ID

DESCRIPTION TYPE NOTES

LOCAL PRIMARY NETWORK

CAT 6E (MIN)

TOTAL LOCAL BRANCH LENGTH NOT TO EXCEED 1000'

SMART BUS NETWORK

CAT 6E (MIN)

TOTAL SMART BUS LENGTH NOT TO EXCEED 400'

(BOOSTER NOT PERMITTED)

0-10V DIMMING** 18 GAUGE / 2C

CONDUCTOR COLOR CODE: (+) VIOLET, (-) GRAY

SMAOS

120/277V

LINE IN

SW-TS-M

RM

LOAD A

TO ADDITIONAL

SENSORS IF REQUIRED

TO ADDITIONAL SW-TS

SWITCHES IF REQUIRED

**IF USED WITH FIXTURE WITH 0-10V DIMMING CAPABILITY

TYPICAL DETAILS FOR SINGLE

ROOM CONTROL

E-102

M

F

L L

M

L

F

SCALE: NONE

TYPICAL ROOM WITH CEILING SENSOR(S) - SINGLE ROOM

SEQUENCE OF OPERATIONS:

· ROOM MANAGER AND WALL STATION CAN BE CONFIGURED TO SWITCH/DIM LIGHTS

BASED ON OCCUPANCY AND/OR TOUCH SCREEN COMMANDS.

· OCCUPANCY SENSORS WILL TURN LIGHTS OFF IF VACANCY IS DETECTED WITHIN

CONFIGURED TIME PERIOD (TYPICAL MAX OF 20-30 MINUTES).

· TOUCH SCREEN CAN BE CONFIGURED WITH DESIRED FUNCTIONS SUCH AS

INDIVIDUAL ZONE/DIMMING CONTROL.

1 5

2 4 6

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

RM

SMAOS

120/277V

LINE IN

SW-TS-M

CABLE TYPE SCHEDULE

ID DESCRIPTION

TYPE

NOTES

LOCAL PRIMARY NETWORK

CAT 6E (MIN) TOTAL LOCAL BRANCH LENGTH NOT TO EXCEED 1000'

SMART BUS NETWORK

CAT 6E (MIN)

TOTAL SMART BUS LENGTH NOT TO EXCEED 400'

(BOOSTER NOT PERMITTED)

0-10V DIMMING 18 GAUGE / 2C

CONDUCTOR COLOR CODE: (+) VIOLET, (-) GRAY

LOAD B

LOAD A

SMAOS

SMAOS

SW-TS-M

SMAOS

R O

O M

A

R O

M

B

NOTE: DESIGNATED AS OPTIONAL DEVICE ADDITIONS TO LOCAL PRIMARY BRANCH

TYPICAL DETAILS FOR DUAL

ROOM CONTROL

E-103

PAGE ID: SWITCH-TOUCH SCREEN MULTIFUNCTION

DESCRIPTION: MONOCHROME TOUCH SCREEN

PRODUCT ID: SW-TS-M

(4)

PAGE ID: SMART MICRO AMBIENT OCCUPANCY SENSOR

DESCRIPTION: CEILING SENSOR

PRODUCT ID: SMAOS-(D/P)-360(L/H)-(F/S)-W

PAGE ID: ROOM MANAGER

DESCRIPTION: ROOM MANAGER

PRODUCT ID: RM

PAGE NOTES:

UP TO 20 DEVICES CAN BE CONNECTED TO A SINGLE ROOM MANAGER. DIGITAL INPUT

DEVICES (SWITCH-SINGLE FUNCTION) DO NOT COUNT IN TOTAL DEVICE QUANTITY.

QUANTITY OF DEVICES MAY VARY DUE TO ROOM SIZE AND CONFIGURATION. DASHED

LINE SHOWN FOR CONNECTING OF ADDITIONAL DEVICES.

LINE VOLTAGE WIRING CONNECTED ON BACK SIDE OF ROOM MANAGER.

SWITCH-TOUCH SCREEN-TYPE M (SW-TS-M) OR SWITCH-TOUCH SCREEN-TYPE C

(SW-TS-C) MAY BE INTERCHANGED ON THE LOCAL PRIMARY NETWORK.

NOTE: SW-TS-C USED ON CANTEEN REWORK ONLY.

UP TO (16) ZONES OF CONTROL WHEN ROOM IS CONFIGURED FOR SINGLE ROOM

CONTROL. ZONES SHALL BE DEFINED AS TYPES OF FIXTURES, SUCH AS DOWN LIGHTS,

OR AREAS OF ROOM, SUCH AS END OF ROOM WITH PROJECTION SCREEN. CONTRACTOR

TO VERIFY ZONES WITH CONTRACTING OFFICER REPRESENTATIVE (COR).

SWITCH BUTTON SIZE, QUANTITY, FUNCTION AND LABELING TO BE CONFIGURED VIA

PROGRAMMING TO MATCH SPACE.

LEGEND:

SEQUENCE OF OPERATIONS:

· ROOM MANAGER AND WALL STATION CAN BE CONFIGURED TO SWITCH/DIM LIGHTS

BASED ON OCCUPANCY AND/OR TOUCH SCREEN COMMANDS.

· OCCUPANCY SENSORS WILL TURN LIGHTS OFF IF VACANCY IS DETECTED WITHIN

CONFIGURED TIME PERIOD (TYPICAL MAX OF 20-30 MINUTES).

· TOUCH SCREEN CAN BE CONFIGURED WITH DESIRED FUNCTIONS SUCH AS

INDIVIDUAL ZONE/DIMMING CONTROL.

L

M

M

M

M

M

L

F

F F

SCALE: NONE

DUAL ROOM CONTROL - SINGLE ZONE PER ROOM

SINGLE ROOM MANAGER CAN OPERATE UP TO 2 ZONES/ROOMS

2 4

1 5

2 4

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

AUTO MODE

DAY MODE

NIGHT MODE

LIGHTS ON

LIGHTS OFF

4.125"

1.765"

1.8"

1.425"

PAGE NOTES:

STANDARD DECORA® WALL PLATE TO BE SUPPLIED

SEPARATELY BY CONTRACTOR. VERIFY COLOR WITH

CONTRACTING OFFICER REPRESENTATIVE (COR) PRIOR

TO ORDERING.

WALL PLATE MOUNTING SCREWS

COMMUNICATION / POWER TERMINATION (CONNECTOR)

AUDIBLE "BEEPER"

TOUCH - SCREEN DISPLAY

DEVICE MOUNTING SCREWS (INCLUDED)

THREADED MOUNTING HOLES FOR WALL PLATE

STANDARD 1 - GANG ELECTRICAL ENCLOSURE

END OF LINE SWITCH (EOL)

PRIMARY BRANCH WIRING (CAT 6E)

CABLE LEGEND

CAT 6E PRIMARY BRANCH

P P

P P

WIRING

KEY NOTES:

RED EOL BUTTON

EXTENDED = END OF LINE RESISTOR ENABLED

DEPRESSED = END OF LINE RESISTOR DISABLED

WHEN A NEW DEVICE IS ADDED TO A BRANCH

NETWORK AN ACTIVATE "SOFT" BUTTON WILL

APPEAR FOR ADDRESSING, PRESSING ANY

BUTTON (20) TIMES WITH-IN (30) SECONDS WILL

PRESENT DEVICE MENU OPTIONS INCLUDING -

RESET TO FACTORY DEFAULTS

NOTE MULTIPLE SW-TS-M DEVICES CAN BE

"GANGED" WITH EQUIVALENT ELECTRICAL

MOUNTING BOX

A

LIGHT SWITCH FOR MULTI - ROOMS & MULTI OCCUPANCY RESTROOMS

TYPICAL DETAILS FOR MULTI-

FUNCTION SWITCH

E-104

B

C

A

C

SCALE: NONE

SW-TS-M DEVICE MOUNTING

SCALE: NONE

FRONT SW-TS-M DEVICE

SCALE: NONE

BACK & SIDE OF SW-TS-M DEVICE

SCALE: NONE

SW-TS-M DEVICE DIMENSIONS

B5

NOTE: LABELED INPUT AND OUTPUT

PORTS ARE FOR CABLE

IDENTIFICATION ONLY - PORTS

ARE ELECTRICALLY IDENTICAL

& CAN BE INTERCHANGED.

**HARD CEILINGS WITH OCTAGON

BOX MUST HAVE CIRCLE MUD RING

(NOTE 5)**

4"

0.75"

JOB NO:

DATE:

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

PAGE NOTES:

MOUNTING SCREWS

SURFACE MOUNTED SMART MICRO AMBIENT

OCCUPANCY SENSOR (SMAOS) BACK COVER

SMART MICRO AMBIENT OCCUPANCY SENSOR

(SMAOS) FRONT COVER

4"X4" STANDARD ELECTRICAL JUNCTION BOX

STANDARD ELECTRICAL CIRCLE MUD RING

DRYWALL OR OTHER PERMANENT HARD

SURFACE

FRONT COVER HARD RELEASE FOR SURFACE

MOUNTED SMART MICRO AMBIENT OCCUPANCY

SENSOR (SMAOS) DEVICE (USE FLAT BLADE

SCREW DRIVER TO RELEASE CLIP)

ARROWS ARE FOR USE WITH AISLE

CONFIGURATION OF SMART MICRO AMBIENT

OCCUPANCY SENSOR (SMAOS) ALIGN ARROWS

WITH THE LONG DIMENSION OF THE AISLE.

PIR FRESNEL LENS

OCCUPANCY SENSOR FOR MULTI - ROOMS & MULTI OCCUPANCY RESTROOMS

TYPICAL DETAILS FOR SMART

OCCUPANCY SENSOR

E-105

SCALE: NONE

SMAOS FLUSH MOUNTING

SCALE: NONE

SMAOS DEVICE DIMENSIONS

SIDE VIEW SURFACE MOUNT

SCALE: NONE

SMAOS SURFACE MOUNTING

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

LOAD

120/277 VAC BLACK

SWITCHED HOT

NEUTRAL

GROUND

WHITE

LIGHT SWITCH FOR ROOMS WITH WALL MOUNTED OCCUPANCY SENSORS

MODEL # SW-O-D

PAGE NOTES:

OCCUPANCY SENSOR SWITCH WILL REPLACE EXISTING ROOM SWITCH

AS DESIGNATED IN THE ROOM LISTS.

NEW OCCUPANCY SENSOR SWITCHES WILL BE INSTALLED AT 4' ABOVE

FINISHED FLOOR.

TYPICAL DETAILS FOR

OCCUPANCY SENSOR SWITCH

E-106

NEUTRAL

SCALE: NONE

OCCUPANCY SENSOR SWITCH WIRING DIAGRAM

12.1

11.8

X5

X1

W

Y2

12.3 12.8 13.1 13.2

13.4

12.6

13.6

W4

W1

Y1

X7

X4

X3

X6

X8

X1

X9

11.7 11.9

12.2 13.27

13.3

ZONE 1

ZONE 2

ZONE 3

ZONE 4

LRM

LRM

LRM

LRM

JOB NO:

DATE:

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

LIGHT CONTROLS DEVICES

WS-TS-C

LRM-2P-120/347-0/10

SMART SENSOR DUAL TECHNOLOGY LOW (< 20') SURFACE MOUNT

SMAOS-D-360-L-S-W

COLOR TOUCHSCREEN WALL STATION

SYMBOL DESCRIPTION

EQUIPMENT

MODEL NUMBER

MORNING/DAYTIME:

· SYSTEM WILL OPERATE BASED ON OWNER-SELECTED TIME SCHEDULE.

· AT SPECIFIED TIME IN THE MORNING, LIGHTS WILL TURN ON TO 50% FOR "OPENING" SHIFT.

· AT SPECIFIED TIME LATER IN THE MORNING, LIGHTS WILL TURN ON TO 100% FOR CUSTOMERS.

· DURING THE DAY, NO MOVEMENT DETECTED BY ANY SENSOR ON THE SYSTEM AFTER OWNER-DETERMINED PERIOD OF TIME

WILL REDUCE LIGHT LEVEL TO 50%.

· SENSORS LOCATED NEAR WINDOWS WILL ALSO FUNCTION AS DAYLIGHT SENSORS AND WILL DIM THE RESPECTIVE DAYLIGHT

ZONE TO MAINTAIN A SPECIFIED LIGHT LEVEL. CAN SHUT LIGHTS OFF IF SUFFICIENT DAYLIGHT IS DETECTED IF DESIRED.

· WALL STATIONS WILL PROVIDE MANUAL ZONE CONTROL. CAN BE PIN CODE PROTECTED TO PREVENT UNAUTHORIZED USE.

VICINITY MAP

SCALE: N.T.S.

4'-6"

15'

4'-6"

23'

4'-6"

15'

15'

4'-6"

5'-7"

11'-8

20'-2

3'-5

21'-11

6'-5

6'-5

10'-7"

2'-4

18'-11

PASSIVE BRANCH BOOSTER & SPLITTER MODULE

MASTER INTERFACE SERIES 2

MSTR-DVOLT-S2

SBB1

MSTR

SBB1

CAT 6E CABLE (TYPICAL)

WS

SMAOS

SMAOS

WS

SMAOS

SMAOS

WS

SMAOS

SMAOS

WS

SMAOS

LRM

SMAOS

ZONE 1

ZONE 2

ZONE 3

ZONE 4

SMAOS

SMAOS SMAOS SMAOS

SMAOS SMAOS SMAOS

26'

22'

21'

26'

LOCAL (RELAY) MODULE - 2 POLE (2) 0-10V CHANNELS (2) DIGITAL INPUT PORTS (3) SMART PORTS

CANTEEN LIGHTING CONTROLS

E-201

LOCATE ABOVE ACCESSIBLE CEILING

(TYP 4)

LRM

LRM

LRM

COORDINATE WITH

CONTRACTING OFFICER

REPRESENTATIVE (COR)

FOR LOCATION

2'X2' LIGHT FIXTURE

DOWNLIGHT FIXTURE

CAMERA

RETURN AIR REGISTER, REFER TO MEP

SUPPLY AIR REGISTER, REFER TO MEP

EXISTING GYPSUM BOARD /

FURRDOWN

LEGEND:

EXIT SIGN

WALL WASHER FIXTURE

EXISTING 2'X2' ACOUSTICAL

PANELS

MAIN HOSPITAL

LRM

MSTR

EVENING/AFTER HOURS:

· AT SPECIFIED TIME IN THE EVENING, LIGHTS WILL DIM TO 20% TO MAINTAIN A LOW LIGHT LEVEL FOR SAFETY.

· MOTION DETECTION BY ANY SENSOR WILL RAISE LIGHT LEVEL TO 50% FOR OWNER-DETERMINED PERIOD OF TIME.

· WALL STATIONS WILL PROVIDE MANUAL ZONE CONTROL. CAN BE PIN CODE PROTECTED TO PREVENT UNAUTHORIZED USE.

· FUNCTION OF WALL STATION CAN BE CHANGED VIA TIME SCHEDULE.

· EXAMPLE: DURING THE DAY, WALL STATION PROVIDES ZONE CONTROL. DURING THE EVENING THE WALL STATION CAN REVERT

TO A "SIMPLE" LAYOUT TO ALLOW EASE OF OPERATION BY CUSTODIAL STAFF.

SCALE: NONE

SEQUENCE OF OPERATIONS

SCALE: NONE

LIGHTING CONTROLS DEVICE SCHEDULE

1/4" = 1'-0"

2' 4' 8'

SCALE:

TYPICAL WIRING DIAGRAM EXAMPLE

1/4" = 1'-0"

2' 4' 8'

SCALE:

CANTEEN

LIGHTING CONTROLS

15.7

12.1

X5

X1

W

Y2

12.3 12.8 13.1 13.2 13.4 14.1 14.912.6 15.314.413.6

VV

V3

W4

W1

Y1

X7

X4

X3

X6

X8

X1

X9

12.2 15.4

V4

13.27 13.3

ZONE 3

ZONE 4

ZONE 1

ZONE 2

JOB NO:

DATE:

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

E-202

CANTEEN REFLECTED CEILING

LIGHTING PLAN

VICINITY MAP

SCALE: N.T.S.

NEW 2'X2' LIGHT FIXTURE

NEW DOWNLIGHT FIXTURE

EXISTING CAMERA TO REMAIN

EXISTING RETURN AIR REGISTER

EXISTING SUPPLY AIR REGISTER

EXISTING 2'X2' ACOUSTICAL

CEILING

PAGE NOTES:

REPLACE ALL 2'x2' LIGHT FIXTURES

WITH 2'x2' FIXTURES LISTED ON LIGHT

FIXTURE SCHEDULE, SHEET G002.

REPLACE ALL INDICATED DOWN

LIGHTS WITH DOWN LIGHTS LISTED

ON LIGHT FIXTURE SCHEDULE SHEET

G002.

CAPTURE EXISTING CIRCUITING AT

HOMERUN ABOVE CEILING. CONNECT

TO NEW FIXTURES TO PROVIDE

CONTROL ZONES AS INDICATED.

LEGEND:

2'X2' LIGHT FIXTURE CONNECTED

UNSWITCHED TO EMERGENCY

CIRCUIT.

EXIT SIGN - EXISTING TO REMAIN,

MAINTAIN CIRCUITING

WALL WASHER FIXTURE - EXISTING

TO REMAIN, MAINTAIN CIRCUITING

SMART SENSOR - OCCUPANCY /

AMBIENT LIGHT - CEILING MOUNTED

3/16" = 1'-0"SCALE:

2.5' 5' 10'0

CANTEEN REFLECTED CEILING PLAN

A A A A

A

A A A A

A A A A A A

A A A A A A A A

A A A

AA

A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

B B B B B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

(TYP)

(TYP)

MAIN HOSPITAL

COLOR TOUCHSCREEN WALL

STATION

AutoCAD SHX Text S-7

AutoCAD SHX Text Y100.0

AutoCAD SHX Text Y101.3

AutoCAD SHX Text Y100.1

AutoCAD SHX Text Y101.2

AutoCAD SHX Text Y101

AutoCAD SHX Text Y101.13

AutoCAD SHX Text Y101.8

AutoCAD SHX Text Y101.11

AutoCAD SHX Text Y101.4

AutoCAD SHX Text Y102

AutoCAD SHX Text Y101.10

AutoCAD SHX Text Y101.10

AutoCAD SHX Text Y102.8

AutoCAD SHX Text Y101.8

AutoCAD SHX Text Y102.7

AutoCAD SHX Text Y101.4A

AutoCAD SHX Text Y102.4

AutoCAD SHX Text Y102.5

AutoCAD SHX Text Y101.4B

AutoCAD SHX Text Y102.3

AutoCAD SHX Text Y102.6

AutoCAD SHX Text

ELEVATOR

AutoCAD SHX Text

VENDING

AutoCAD SHX Text

STOCK

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

CONCESSION

AutoCAD SHX Text H.A.C.

AutoCAD SHX Text

CANTEEN

AutoCAD SHX Text

DINING ROOM

AutoCAD SHX Text

FOOD

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

FOOD

AutoCAD SHX Text

PREP

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text

FOOD

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

RETAIL STORAGE

AutoCAD SHX Text

STAFF

AutoCAD SHX Text

DINING ROOM

AutoCAD SHX Text

ECOLAB

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

ELECTRICAL ROOM

AutoCAD SHX Text

IDF

AutoCAD SHX Text

WOMEN TR

AutoCAD SHX Text

OFFICE 2

AutoCAD SHX Text

OFFICE 3

AutoCAD SHX Text

MEN TR

AutoCAD SHX Text

OFFICE 1

AutoCAD SHX Text

OFFICE 4

AutoCAD SHX Text

STAIR

AutoCAD SHX Text C-16

UP

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

PAGE NOTES:

120 / 277 VAC POWER SUPPLY CONNECTOR

120 / 277 VAC TO 27 VDC CLASS II POWER SUPPLY

POWER SUPPLY INDICATORS

PRIMARY BRANCH TERMINAL

LOCATION FOR BATTERY (CONTRACTOR SUPPLIED)

MAIN FUSE (BRANCH)

BATTERY TERMINAL

RJ 45 PORTS

TIME CLOCK BATTERY BACK UP

USB CONNECTIONS

ETHERNET (SWITCH)

TOUCH SCREEN DISPLAY

COIN TURN LATCH

PRIMARY BRANCH COMMUNICATION INDICATOR

27 VDC CLASS II POWER OUT

o w e r

S u p p l y

POWER

SOURCE

N O

R M

B A

T

BACKUP

BATTERY

FUSE

3.2A MAX

C L

A S

S

W

I R

I N

G

O

N L

Y

O

N

T

H

D

E

O

F

B

A R

R I E o w e r

S u p p l y

7.50" 4.75"

7.75"

4.25"

7.75"

4.25"

7.50" 4.75"

12.25"

12.00"

12.25"

12.00"

1.75"3.00"

1.75"3.00"7.50"

1.75"

1.75"

6.00"

6.00"

1.50" 5.00"

4.25"

LINE VOLTAGE

CONDUIT ENTRY

LOCATION

CONDUIT ENTRY

LOCATION

POWER

OUT

PRIMARY

BRANCH

FUNCTION & INDICATION:

PRIMARY COMM. STATUS INDICATOR (BLUE).

(BLINKING OR SOLID = ACTIVE AND PRIMARY COMM. IS OK)

(OFF = NO COMM.)

SYSTEM CURRENTLY SOURCE BY NORMAL OL BATTERY AS

INDICATED

TOUCH SCREEN DISPLAY- TOUCH SCREEN INTERFACE

E-203

TYPICAL DETAIL FOR MASTER

INTERFACE (1 OF 2)

B

LOW VOLTAGE

6 15 4

14 A

12 C

BATTERY LOCATION NO

CONDUIT PENETRATION

RECOMMENDED

BATTERY LOCATION

NO CONDUIT

PENETRATION

RECOMMENDED

BATTERY LOCATION NO

CONDUIT PENETRATION

RECOMMENDED

A

B

C

SCALE: NONE

FRONT OF MSTR-DVOLT INTERFACE

SCALE: NONE

INSIDE OF MSTR-DVOLT INTERFACE

SCALE: NONE

MSTR-DVOLT INTERFACE DIMENSIONS

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

G R

E E

N Y

E L

B R

O W

N

B L U

E

POWER

SUPPLY

LINE IN

P P

P P

P

P P P P

P P P

TO OTHER PRIMARY DEVICES (UP TO 100

MAXIMUM)

E E E E E E E E E E E E

E

COORDINATE NETWORK CONNECTION WITH

CONTRACTING OFFICER REPRESENTATIVE (COR)

E

BLUE

BLUE

BLACK (-)

RED (+)

BATTERY

CONNECTION

BLACK (-)

RED (+)

1 2 3 4 5 6 7 8

TAB SIDE DOWN

W H

T G

R N

G R

N

W H

T O

R N

B L

U

W H

T B

L U

O R

N

W H

T B

R N

B R

N

T568A

8P8C (RJ45)

67854321

A

8-POSITION

8-CONTACTS

STANDARD RJ45 MALE CONNECTOR

A

POWER

SOURCE

N O

R M

BACKUP

BATTERY

FUSE

3.2A MAX

C L

A S

W

R

I N

G

O

N L

Y

O

N

T

H

D

E

O

F

B

A R

R I E

R

POWER

OUT

PRIMARY

BRANCH

LRM

G R

O U

N D

L I N

E

N E

U T

R A

L

B

T

W

E

U P

P L

Y

SCALE: NONE

INSIDE OF MSTR DVOLT

SCALE: NONE

BATTERY BACK-UP WIRING

E-204

TYPICAL DETAIL FOR MASTER

INTERFACE (2 OF 2)

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS HOSPITAL

SAN ANTONIO, TEXAS

671-15-132

VARIES

Project Director

10/28/2020 JH AGRevisions: Date:

35% DD REVIEW SET 02/14/19

65% DD REVIEW SET 04/09/20

VAA19002

B. MILLER

10/28/2020

95% DD REVIEW SET 07/08/20

95% DD SET 07/31/20

100% CD SET 10/28/20

SBB1

SPLITTER BOOSTER

LOCAL RELAY MODULE

TOUCH SCREEN SWITCH

SBB1

SBB1

BRANCH PORTS OUT

BRANCH PORT IN

IN PWR IN

OUT A

OUT B

PWR OUT

SPLITTER

E-205

TYPICAL DETAIL SBB1 (1 OF 2)

LEGEND:

CABLE TYPE SCHEDULE

ID

DESCRIPTION TYPE NOTES

PRIMARY NETWORK CAT 6E

TOTAL PRIMARY BRANCH LENGTH NOT TO EXCEED

2000' WITHOUT A BRANCH BOOSTER.

BOOSTER CABLE 16 GAUGE / 2C

BOOSTER CABLE MUST NOT CROSS SEPARATE

MASTER INTERFACES

P

B

P

B

P

B

P

P

P

P

P

P

B

SCALE: NONE

SBB1 DEVICE WIRING

SCALE: NONE

TYPICAL SBB1 APPLICATION

BG:

PROJECT

MANAGER:

BATON ROUGE - NEW ORLEANS

MCA

Engineering & Construction

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i t h

100%

CONSTRUCTION DRAWINGS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Hernandez Consulting & Construction 3221 Tulane Ave New Orleans, LA 70119 504-305-8571 A/E firm POC

MCA:

Marrero, Couvillon & Associates, LLC 4354 S. Sherwood Forest Blvd., Suite D200 Baton Rouge, LA. 70816 225-408-8249 John L. Hamm, III

AUDIE L. MURPHY MEMORIAL

VETERANS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .