Questions Answers
Who is the current contractor and can we have the original bid price?
There is no current contract.
Can you please tell me if there will be a site visit scheduled?
Currently, no site visit is planned.
If one took place, can we please get a copy of the attendees?
A site visit was not previously held for this requirement
Please can you spell out the current required annual testings?
The most common tests are Monitoring System Certification Test and Annual Spill Bucket Test.
Annual Monitoring Equipment Certification and Spill Bucket testing will be performed on all systems in accordance with manufacturer's guidelines or standards.
There are four (4) USTs, however, you have only called for annual tests to be done on three (3). So you are indicating that no annual tests will be done on the fourth
UST?
One of our tanks is a split tank, which is one UST with two compartments.
Three (3) Year Secondary Containment Test (SB 989 Test) is required on each UST every three
(3) years. When was this test done on each of the tasks and where will we include this cost?
No, the three year secondary containment certification will be handled separately.
Is the annual test vacuum, or internal inspections?
No internal inspections should be required.
Is the ICC California UST System Operator license necessary if we have nation wide ICC instal/ retrofit license?
This testing will be conducted by individual that meets the following: a) Possess a current Tank Testers License or appropriate CSLB license; b) Obtain training and certification from the monitoring equipment manufacturer and be recertified at the time interval recommended by the manufacturer, or every 36 months, whichever is shorter; and c) Possess or work under the direct and personal supervision of an individual physically present at the work site who possesses a current "California UST Service Technician" certification issued by the ICC by July 1, 2005. Certification must be renewed every 24 months.
FA9301-16-R-0015
Attachment 4_Rev 2
Does this solicitation have Standard Form 1449 or only Attachment 2_Rev. 1?
Attachment 2_Rev 1.
What Tank Monitoring system (INCON, Veeder-Root or other) is currently used at the two sites?
See Attachment 5.
Does this solicitation cover the above finished grade equipment;
dispensers, hanging hardware and Point of Sale or just the below finished grade equipment; STP’s, Piping, Vapor Recovery and Tank Monitoring components?
No. This contract covers only those requirements of the designated UST Operator.
If the above finished grade equipment is covered, what mfg./model dispenser is installed and what is the quantity?
See above.
On the Monthly Inspection (DUSTO) there is no mention of the required annual training.
Should this be included in the Monthly CLIN Line item?
Yes.
On provided Q&A #8, shouldn’t the ICC UST System Operator be listed as a requirement to conduct the monthly DUSTO Inspections?
Yes, UST Operator provides the monthly inspections.
FA9301-16-R-0015
Attachment 4_Rev 2
Sheet1