The RFQ solicits quotes to provide a factory new RF anechoic chamber to specifications outlined in an attachment. Quotes are due by 12:00pm on 18 September 2023 and shall be submitted to the identified contracting officer. The anticipated delivery date for the chamber is to be determined. Evaluation will consider price and technical capability, with the government intending to make award without discussions to the offer representing the best value. The total evaluated price will be determined by summing the proposed prices for all contract line items listed in an attached price schedule.
The RFQ also provides responses to questions from potential offerors that clarify firmness of certain chamber specifications, absorber and walkway requirements, and intent for the contractor to furnish and install the chamber including ancillary components.
This document summarizes the key details of the request for quotation to procure an RF anechoic chamber, including response date, pricing and evaluation terms, clarifications provided to offerors, and anticipated delivery date.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Re-solicit Questions_Answers _R2.docx | DOCX document | |
| Attch 4_Compliance Matrix_23r12_R1.xlsx | XLSX spreadsheet | |
| Attch 1_Chamber Specifications_23r12_R1.docx | DOCX document | |
| Re-solicit Questions_Answers.docx | DOCX document | |
| Attch 1_Chamber Specifications_23r12.docx | DOCX document | |
| Attch 4_Compliance Matrix_23r12.xlsx | XLSX spreadsheet | |
| Attch 2_Offeror Representations and Certifications--23r12.docx | DOCX document | |
| Attch 3_Price Schedule_23r12.docx | DOCX document | |
| RF Anechoic Chamber_Questions_Answers_R2.docx | DOCX document | |
| Attch 1_Chamber Specifications_23r12 _R2.docx | DOCX document | |
| RF Anechoic Chamber_Questions_Answers_R1.docx | DOCX document | |
| RF Anechoic Chamber_ Questions_Answers.docx | DOCX document | |
| Attch 1_Chamber Specifications_23r12 _R1.docx | DOCX document | |
| Attch 3_Price Schedule_23r12.docx | DOCX document | |
| Attch 1_Chamber Specifications_23r12.docx | DOCX document | |
| Attch 2_Offeror Representations and Certifications--23r12.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA875123R0012 – RF Anechoic Chamber – Resolicit Q&A Q1: Do you have any more drawings etc? The verbiage says there's a sketch in section 4 - is that the one titled 'National (sic) Layout'?
A1: Yes, any references to a sketch throughout the specifications attachment are referring to the ‘Notional Layout’ that can be seen in Section 4 of the document. Note that it’s titled ‘Notional Layout’, and not ‘National Layout’. There are no additional drawings available aside from this one.
Q2: Can you please confirm what dates all RFI’s are due and when the final proposal is due?
A2: Per the solicitation: “Questions regarding the solicitation must be submitted no later than 10 calendar days prior to the quotation due date to enable the Government sufficient time to provide answers prior to solicitation closing.” The current solicitation closing is 12:00pm EST on Wednesday, 17 January 2024.
Q3: We assume the intent is for the chamber manufacturer to furnish AND install the chamber onsite, including ancillary components such as electrical outlets, lighting fixtures, etc. within the chamber. Please confirm.
A3: Yes, your understanding of our requirement here is correct.
Q4: Is the requirement that the chamber door be reversible firm?
A4: No, the chamber door need not necessarily be reversible. Specifications attachment has been updated accordingly, to remove this being a firm requirement.
Q5: Is the requirement that the chamber door have a phenolic lever handle firm?
A5: No, the lever handle on the chamber door need not necessarily be phenolic. Specifications attachment has been updated accordingly, to remove this being a firm requirement.
Q6: Is the requirement that the chamber door have an auto latch firm?
A6: No, chamber door need not necessarily have an auto latch. Specifications attachment has been updated accordingly, to remove this being a firm requirement.
Q7: Is the intent for absorbers to be positioned within the walkway area such that personnel may walk overtop of the absorbers? Or, is the floor free of absorbers in the walkway area?
A7: Absorbing material needs to cover the full floor with the ability to walk over the absorber in the necessary areas.
Q8: If personnel need to be able to walk above floor-mounted absorbers, what is the load requirement for the walkway?
A8: The manufacturer shall provide a suitable walking surface capable of accommodating a person above the absorbers.
Q9: Are the NPT Brass Feedthrough Waveguides intended to be 100 dB uncapped at 6.5 GHz? Are these intended to meet the 40 GHz shielding requirement only when capped?
A9: 100 dB/40 GHz rating only when capped.