This document contains a federal contract opportunity solicitation for storage aid systems and related questions and responses. The Air Force Materiel Command Lifecycle Management Center is soliciting proposals for the design, fabrication, installation, and testing of storage aid systems at Charlotte Air National Guard Base in North Carolina and Buckley Air Force Base in Colorado under solicitation number FA8604-21-R-B016. The 100% small business set-aside contract has a NAICS code of 333922 and requires completion within 240 days of award. Proposals are due by July 13, 2021 and will be evaluated using lowest price technically acceptable criteria. The questions and responses document provides clarification on dimensions, power supply, and cage construction requirements for the storage aid systems.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA860421RB005

Charlotte ANGB NC and Buckley AFB CO Questions/Answers Set 1 24 Jun 2021

Question 1: Due to the drawing provided I can’t tell how much room is available for the VLM’s.

Our dimensions do not fit the spec as described – we are 114.7”W VS the requested 110”W & 124.9”D VS the 122”D requested – will those dimensions be acceptable?

Response 1: Specified dimensions must be met to meet mission/space requirements therefore the proposed dimensions are not acceptable.

Question 2: Not seeing available power supply for either location – is there 480V 3 ph available for the VLM hookup?

Response 2: Equipment is being installed in a new building with sufficient power supply to power VLMs. Electrical hookup will not exceed 100 feet from equipment installation location.

Question 3: Cover PD – 3.1.10. – pilf cage States “free standing” meaning no attachment to a wall etc. Then states – 3 sides and a top cap. Drawing 805-2 shows 4 sides – OA dims of 6’ x 30’

– Please have engineer clarify what he is wanting – 3 side or 4 side.

Response 3: Cage shall have 3 sides and a top cap with the adjacent wall severing as the 4th side.