DEC2023 202312011131 ECN 108221 MCI AA0128 RPT_Redacted.pdf

PDF 3 MB Posted

Attached to
Hazardous & Non-Hazardous Clean Room Testing
Solicitation number
FA860124Q0111
Issued by

About this file

This document is a test report related to a federal contract opportunity. The report details the results of airflow velocity tests and other site installation assessment tests conducted on a piece of equipment. It includes details on the equipment, test methods, and test results.

The related federal contract opportunity is for Hazardous and Non-Hazardous Clean Room Testing services. The contract is a firm-fixed-price award to be made to the lowest priced, technically acceptable offeror. The 12-month contract period will require testing of 797 USP and 800 USP standards-compliant clean rooms at an 88th Medical Group facility that supports 55,000 beneficiaries and performs 20,000 sterile IV admixtures annually. Offerors must submit proposals by June 6, 2024 in accordance with the instructions provided.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Report No.: 102458839 FINAL AIRFLOW VELOCITY TESTS

Anemometer: Mfg. Model S/N Cal DueTSI 966 P23360080 February 15, 2024

Downflow Velocity

Number of Supply Readings Taken

Maximum Supply Velocity Allowable/Actual

Minimum Supply Velocity Allowable/Actual

Average Downflow Velocity

Acceptance Criteria

Diagram of Supply Velocity Profile Taken at inch(es)

45 4144 454144 43

46 4444 434542 41

37 4136 393739 41

Exhaust Volume

Velocity Conforms to:

Blower Speed Required:

Exhaust Configuration:

Exhaust Damper:

SITE INSTALLATION ASSESSMENT TESTS

Sash Alarm Verification

Airflow Alarm Verification

Type B Supply Blower Interlock Test

Exhaust Performance Test

Differential Pressure: Hood "W.C. Exhaust Duct: "W.C.

PASS FAIL NA

PASS FAIL NA

PASS FAIL NA

PASS FAIL NA

58 46

26 36

42 35 45-

NSF Std. 49 & Manufacturer's Specs

No Change

Hard Ducted

No Change

.01 NA

No Adjustments Required

No Adjustments Required

Hard Duct Negative above 8" sash height

Pass Average Velocity

& Airflow Uniformity

Fail Average Velocity

Pass Average Velocity

Fail Airflow Uniformity

All readings within the larger of ±25% of Avg. or ±16 FPM

(cfm1 + cfm2 + ... cfm5 / 5 = Qi) Average Intake Volume (Qi)

Acceptance Criteria

257.20

100 - 110 Pass Fail

689656678 677 662

Intake Area (Ai)

(Qi / Ai = Vi) Intake Velocity (calculated) (Vi)

2.56

Flowhood: Mfg. Model January 31, 2024S/N Cal DueTSI EBT721

1) ________ cfm 2) ________ cfm 3) ________ cfm 4) ________ cfm 5) ________ cfm

257260258 256 255

1) ________ cfm 2) ________ cfm 3) ________ cfm 4) ________ cfm 5) ________ cfm

90533004

(cfm1 + cfm2 + ... cfm5 / 5 = Qe) Average Exhaust Volume (Qe) cfm (INFORMATION ONLY)672.40

Note: Readings were taken with flowhood at intake with supply blower off and supply intake sealed. Exhaust volumes are for information only.

Intake Volume

Flowhood: Mfg. Model January 31, 2024S/N Cal DueTSI EBT721 90533004

Note: Readings were taken with flowhood at intake with supply blower on and intake side edge slots sealed.

(Blower must shut off with ~20% reduction of exhaust cfm.)

Pass-No Adjustment Req'd cfm sq.ft.

fpm fpm fpm fpm fpm fpm

B2DMINT Rev. 05MAR2016 R1.0Copyright © 2006 - All rights reserved

Test Report No.:

A smoke source shall be passed from one end of the cabinet to the other, along the centerline of the work surface at a height of 4 inches (10 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux (upward flow). No smoke shall escape from the cabinet.

102458839 AIRFLOW SMOKE PATTERN TESTS

1. DOWNFLOW TEST:

PASS FAIL

Comments: NA

A smoke source shall be passed from one end of the cabinet to the other, 1 inch (2.5 cm) behind the viewscreen, at a height of 6 inches (15 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux. No smoke shall escape from the cabinet.

PASS FAIL MEETS MANUFACTURER'S SPECIFICATIONS

3. WORK OPENING EDGE RETENTION TEST:

Comments: NA

A smoke source shall be passed along the entire perimeter of the work opening edges, approximately 1.5'' (3.8 cm) outside the cabinet. Particular attention should be paid to corners and vertical edges. No smoke shall reflux out of the cabinet once drawn in, nor shall smoke billow over the work surface or penetrate onto it.

PASS FAIL

Comments: NA

PASS FAIL

4. SASH/WINDOW SEAL TEST:

A smoke source shall be passed up the inside of the window 2'' (5 cm) from the sides and along the top of the cabinet interior work area. No smoke shall escape out of the cabinet.

Comments: NA

1-18 x 48 x 3.54 P/N: 41978

2-11.15 x 22.08 x 8 P/N: 42061

Supply HEPA Filter(s) Size:

Exhaust HEPA Filter(s) Size:

HEPA Filter(s) Replaced:

Prefilter(s) Replaced:

U.V. Lamp(s) Replaced:

REMARKS

No

No

NA

2. VIEW SCREEN RETENTION TEST:

MK41978

MK372G002

Pre Filter(s) Size:

B2DMINT Rev. 05MAR2016 R1.0Copyright © 2006 - All rights reserved