This document is a Test Report for airflow velocity tests conducted on a Bio clean room. The tests evaluated supply airflow, exhaust airflow, air velocity profiles, and various safety features of the clean room. The report includes detailed test results, diagrams, and concludes that the clean room meets manufacturer's specifications.

The related federal contract opportunity is a Request for Quote (RFQ) issued by the Department of the Air Force Materiel Command Lifecycle Management Center at Wright-Patterson Air Force Base for Hazardous and Non-Hazardous Clean Room Testing services. The contract is a 12-month firm-fixed-price award to be made on a Lowest Price Technically Acceptable (LPTA) basis to the offeror whose proposal conforms to the requirements outlined in the Performance Work Statement (PWS) and has the lowest evaluated price. Proposals are due by June 6, 2024.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Report No.: 102458846 FINAL AIRFLOW VELOCITY TESTS

Anemometer: Mfg. Model S/N Cal DueTSI 966 P23360080 February 15, 2024

Supply Filter

Number of Supply Readings Taken

Maximum Supply Velocity Allowable/Actual

Minimum Supply Velocity Allowable/Actual

Average Supply Velocity

Acceptance Criteria

Diagram of Supply Velocity Profile Taken at inch(es)

615860 62

616161 65

625963 60

Intake Volume

Velocity Conforms to:

Blower Speed Required:

Exhaust Configuration:

Internal Damper:

Exhaust Damper:

SITE INSTALLATION ASSESSMENT TESTS

Sash Alarm Test

Airflow or Pressure Alarm Test

Type B Supply Blower Interlock Test

Exhaust System Performance Test

Differential Pressure: Hood "W.C. Exhaust Duct: "W.C.

PASS FAIL NA

PASS FAIL NA

PASS FAIL NA

PASS FAIL NA

77 65

45 58

61 55 65-

NSF Std. 49 & Manufacturer's Specs

No Change

Internal

No Change

NA

NA NA

No Adjustments Required

No Adjustments Required

NA

above 10" sash height

Pass Average Velocity

& Airflow Uniformity

Fail Average Velocity

Pass Average Velocity

Fail Airflow Uniformity

All readings within the larger of ±25% of Avg. or ±16 FPM.

Average Intake Velocity

Acceptance Criteria

109 100 - 110 Pass Fail

261257258 264 262

(cfm1 + cfm2 + ... cfm5 / 5 = Qi) Average Exhaust Volume (Qi)

Intake Area (Ai)

(Qi / Ai = Vi) Intake Velocity (calculated) (Vi) cfm sq ft fpm

260.40

2.39

Flowhood: Mfg. Model January 31, 2024S/N Cal DueTSI EBT721

1) ________ cfm 2) ________ cfm 3) ________ cfm 4) ________ cfm 5) ________ cfm

Air Balance

90533004

Note: Readings were taken with flow hood at intake with supply blower on. Five individual readings were taken labelled 1-5 above. Indicated below is the average of these readings.

fpm fpm fpmfpm fpmfpm

Actual Downflow setpoint 60 fpm, lower limit 45 fpm, upper limit 77

Inflow setpoint 108 100 fpm, upper limit 110fpm, lower limit fpm fpm

A-FH Rev. 05MAR2016 R1.0Copyright © 2006 - All rights reserved

Test Report No.:

A smoke source shall be passed from one end of the cabinet to the other, along the centerline of the work surface at a height of 4 inches (10 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux (upward flow). No smoke shall escape from the cabinet.

102458846 AIRFLOW SMOKE PATTERN TESTS

1. DOWNFLOW TEST:

PASS FAIL

Comments: NA

A smoke source shall be passed from one end of the cabinet to the other, 1 inch (2.5 cm) behind the viewscreen, at a height of 6 inches (15 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux. No smoke shall escape from the cabinet.

PASS FAIL MEETS MANUFACTURER'S SPECIFICATIONS

3. WORK OPENING EDGE RETENTION TEST:

Comments: NA

A smoke source shall be passed along the entire perimeter of the work opening edges, approximately 1.5'' (3.8 cm) outside the cabinet. Particular attention should be paid to corners and vertical edges. No smoke shall reflux out of the cabinet once drawn in, nor shall smoke billow over the work surface or penetrate onto it.

PASS FAIL

Comments: NA

PASS FAIL

4. SASH/WINDOW SEAL TEST:

A smoke source shall be passed up the inside of the window 2'' (5 cm) from the sides and along the top of the cabinet interior work area. No smoke shall escape out of the cabinet.

Comments: NA

1-21 x 32 x 3 DG MF

1-20 x 14 x 11-1/2 DG MF 99.99

NA

Supply HEPA Filter(s) Size:

Exhaust HEPA Filter(s) Size:

HEPA Filter(s) Replaced:

Prefilter(s) Replaced:

U.V. Lamp(s) Replaced:

REMARKS

No

No

NA

2. VIEW SCREEN RETENTION TEST:

P/N: A-980979-04

P/N: A-980957-21

Pre Filter(s) Size:

A-FH Rev. 05MAR2016 R1.0Copyright © 2006 - All rights reserved

File details come from the government source that posted it. Updated .