DEC2023 202312011129 ECN 108219 MCI AA0129 Bio_Redacted.pdf
PDF 3 MB Posted
- Attached to
- Hazardous & Non-Hazardous Clean Room Testing
- Solicitation number
- FA860124Q0111
About this file
This document is a Test Report for airflow velocity tests conducted on a Bio clean room. The tests evaluated supply airflow, exhaust airflow, air velocity profiles, and various safety features of the clean room. The report includes detailed test results, diagrams, and concludes that the clean room meets manufacturer's specifications.
The related federal contract opportunity is a Request for Quote (RFQ) issued by the Department of the Air Force Materiel Command Lifecycle Management Center at Wright-Patterson Air Force Base for Hazardous and Non-Hazardous Clean Room Testing services. The contract is a 12-month firm-fixed-price award to be made on a Lowest Price Technically Acceptable (LPTA) basis to the offeror whose proposal conforms to the requirements outlined in the Performance Work Statement (PWS) and has the lowest evaluated price. Proposals are due by June 6, 2024.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Test Report No.: 102458846 FINAL AIRFLOW VELOCITY TESTS
Anemometer: Mfg. Model S/N Cal DueTSI 966 P23360080 February 15, 2024
Supply Filter
Number of Supply Readings Taken
Maximum Supply Velocity Allowable/Actual
Minimum Supply Velocity Allowable/Actual
Average Supply Velocity
Acceptance Criteria
Diagram of Supply Velocity Profile Taken at inch(es)
615860 62
616161 65
625963 60
Intake Volume
Velocity Conforms to:
Blower Speed Required:
Exhaust Configuration:
Internal Damper:
Exhaust Damper:
SITE INSTALLATION ASSESSMENT TESTS
Sash Alarm Test
Airflow or Pressure Alarm Test
Type B Supply Blower Interlock Test
Exhaust System Performance Test
Differential Pressure: Hood "W.C. Exhaust Duct: "W.C.
PASS FAIL NA
PASS FAIL NA
PASS FAIL NA
PASS FAIL NA
77 65
45 58
61 55 65-
NSF Std. 49 & Manufacturer's Specs
No Change
Internal
No Change
NA
NA NA
No Adjustments Required
No Adjustments Required
NA
above 10" sash height
Pass Average Velocity
& Airflow Uniformity
Fail Average Velocity
Pass Average Velocity
Fail Airflow Uniformity
All readings within the larger of ±25% of Avg. or ±16 FPM.
Average Intake Velocity
Acceptance Criteria
109 100 - 110 Pass Fail
261257258 264 262
(cfm1 + cfm2 + ... cfm5 / 5 = Qi) Average Exhaust Volume (Qi)
Intake Area (Ai)
(Qi / Ai = Vi) Intake Velocity (calculated) (Vi) cfm sq ft fpm
260.40
2.39
Flowhood: Mfg. Model January 31, 2024S/N Cal DueTSI EBT721
1) ________ cfm 2) ________ cfm 3) ________ cfm 4) ________ cfm 5) ________ cfm
Air Balance
90533004
Note: Readings were taken with flow hood at intake with supply blower on. Five individual readings were taken labelled 1-5 above. Indicated below is the average of these readings.
fpm fpm fpmfpm fpmfpm
Actual Downflow setpoint 60 fpm, lower limit 45 fpm, upper limit 77
Inflow setpoint 108 100 fpm, upper limit 110fpm, lower limit fpm fpm
A-FH Rev. 05MAR2016 R1.0Copyright © 2006 - All rights reserved
Test Report No.:
A smoke source shall be passed from one end of the cabinet to the other, along the centerline of the work surface at a height of 4 inches (10 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux (upward flow). No smoke shall escape from the cabinet.
102458846 AIRFLOW SMOKE PATTERN TESTS
1. DOWNFLOW TEST:
PASS FAIL
Comments: NA
A smoke source shall be passed from one end of the cabinet to the other, 1 inch (2.5 cm) behind the viewscreen, at a height of 6 inches (15 cm) above the top of the access opening. The smoke shall show smooth downward flow with no dead spots or reflux. No smoke shall escape from the cabinet.
PASS FAIL MEETS MANUFACTURER'S SPECIFICATIONS
3. WORK OPENING EDGE RETENTION TEST:
Comments: NA
A smoke source shall be passed along the entire perimeter of the work opening edges, approximately 1.5'' (3.8 cm) outside the cabinet. Particular attention should be paid to corners and vertical edges. No smoke shall reflux out of the cabinet once drawn in, nor shall smoke billow over the work surface or penetrate onto it.
PASS FAIL
Comments: NA
PASS FAIL
4. SASH/WINDOW SEAL TEST:
A smoke source shall be passed up the inside of the window 2'' (5 cm) from the sides and along the top of the cabinet interior work area. No smoke shall escape out of the cabinet.
Comments: NA
1-21 x 32 x 3 DG MF
1-20 x 14 x 11-1/2 DG MF 99.99
NA
Supply HEPA Filter(s) Size:
Exhaust HEPA Filter(s) Size:
HEPA Filter(s) Replaced:
Prefilter(s) Replaced:
U.V. Lamp(s) Replaced:
REMARKS
No
No
NA
2. VIEW SCREEN RETENTION TEST:
P/N: A-980979-04
P/N: A-980957-21
Pre Filter(s) Size: