Questions and Answers 26 December 2017

View the file

Other files for this federal contract opportunity

Other files attached to Waterless Fire Supression System Maintenance and Repair, newest first.
File Type Posted
Q&A_27_December_2017.docx DOCX document
SOW_Fire_Suppression_System_Maintenance-17-12-26.docx DOCX document
PWS_revised_1_year.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q&A 26 December 2017

Q1. How many Refrigeration maintenance calls should we account for and should we include R-11 gas as needed? (if so how many lbs)

A1. 1 call for the annual refrigeration inspection and 1 service call. Unless there is a major failure we should not need much refrigerant.

Q2. How many emergency repair calls and # of hrs each should we account for? Repair Parts as needed cannot be included because we have no way of knowing what may fail.

A2. 1 emergency call (20 hours) and 2 calls to replace batteries.

Q3. How many LBS of Carbon Dioxide recharge should be included? How many trips/fills?

A3. 2 calls to top off the main CO2 tank, approximately 8,500 lbs each.

Q4. Section 15b (repairs, modifications/upgrades) - Please provide more specific detailed information

A4. System to be replaced are 1 Chemetron Micro 1 EV Low Pressure CO2 panel in Bldg 18C, Battery vault B003. System to be modified due to changes to the Phoenix test rig is a Gemini Kidde-Fenwal WK-265134-000 High Pressure CO2 system; system needs to be converted to manual dump and the nozzle will have to be relocated. Isolation valve to be installed will be a 1-1/2 inch Low Pressure CO2 valve in Bldg 18C, Battery vault B003.