Site Visit Questions and Answers.pdf
PDF 86 KB Posted
- Attached to
- RECOVERY--PROJECT NUMBER ZHTV071983R, Replace Windows Administration Facility Building 20039 Federal contract opportunity
- Solicitation number
- FA8601-10-B-0002
About this file
Site Visit Questions and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Addendum 1 Drawing.pdf | ||
| Wage Decision 25Jun2010.pdf | ||
| Addendum 1.pdf | ||
| Amendment 2.pdf | ||
| Site Visit Attendance and Rules.pdf | ||
| Wage Decision June 2010.pdf | ||
| Amendment 1.pdf | ||
| Specifications.pdf | ||
| Safety Health Plan Requirement | — | |
| Submittal Specifications.pdf | ||
| ZHTV071983R Solicitation.pdf | ||
| Wage.pdf | ||
| Drawings.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation FA8601-10-B-0002
Replace Windows – South/East Side of Building 20039
Site Visit Questions
Q1. Note #10 E on our drawing mentions to re-point the brickwork on the SW Tower. The line drawing omits the SW Tower and only shows the NE Tower. Our Group was not shown the
SW Tower during the walk thru. Can we take a look at the SW Tower or can a picture be provided?
RESPONSE – This work was removed from the scope of work. No work is to occur on the SW tower. See revised sheet A-2 note 10 modified with addendum #1.
Q2. What factor is more relevant ie: AT/FP "or" Exact Match? Pertains to whether or not the previously installed windows meet current blast requirements despite past installation.
RESPONSE – The Exact Match applies to appearance only. Newly installed windows must meet AT/FP requirements in terms of performance. See revised sheet A-2 “Window Notes” modified with addendum 1.
Q3. Was load considered on Exact Match?
RESPONSE – The Exact Match applies to appearance only. Newly installed windows must meet AT/FP requirements in terms of performance. See revised sheet A-2 “Window Notes”
Q4. Requesting information on stand-off distance requirements for Administration Facility
Building 20039 window replacement. We need stand-off distance to calculate correct window configuration to meet loads imposed on window system.
RESPONSE– Use an 82 ft Stand-off distance. See revised sheet A-2 “Window Notes”
Q5. Is an Irrevocable Letter of Credit from a local bank for the contract amount enough to meet the surety requirements on this job?
RESPONSE- Must follow guidance provided in FAR 52.228-14 regarding a Letter of Credit.