Apprendix A_Equipment List_FA813224Q0042_Revised 27 Aug 2024.pdf

PDF 109 KB Posted

Attached to
Reverse Osmosis System Preventive and Remedial Maintenance
Solicitation number
FA813224Q0042
Issued by

About this file

This document appears to be an Equipment List titled "Appendix A_Equipment List_FA813224Q0042_Revised 27 Aug 2024" related to a federal contract opportunity for Reverse Osmosis System Preventive and Remedial Maintenance, Solicitation Number FA813224Q0042.

The Equipment List provides detailed information on various reverse osmosis and water treatment equipment, including manufacturer, model numbers, and required maintenance tasks such as replacing filters, media, membranes, and performing regular system checks and calibrations. The contract opportunity is being issued by the Department of the Air Force Materiel Command Air Force Sustainment Center. While this document does not directly state the required products or services, it provides the necessary context and details regarding the equipment that will be covered under the contract.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OC-Number NUMBER NAME Manufacturer Model No./Serial No. MAINTENANCE REQUIRED

- Check for proper function on all equipment, i.e. check each system for errors. Verify systems are operating to designed set points. Initiate RM as required.

OC23392 RAW WATER BOOSTER PUMP 1 MARLO INCORPORATED OF RACINE

BOOSTER PUMP SKID MTD / EP-170287-

001-3020 - (Standard pump/motor maintenance)

RAW WATER BOOSTER PUMP 2 - (Standard pump/motor maintenance)

OC23390 MMF-1 MULTIMEDIA FILTRATION SYSTEM MARLO INCORPORATED OF RACINE MZA-63G DUPLEX/PARALLEL MEDI / EP- 160275-001-1441

- Replace multimedia if required. Expected media life is 10-15 years (expected replacement 2028-2033).

OC23387 CCF-1 CARBON FILTRATION SYSTEM MARLO INCORPORATED OF RACINE ACA-48G DUPLEX PARALLEL CARB / EP- 160275-002-1442

- Replace carbon media if required. Expected carbon life is 2-5 years (expected replacement 2020-2023, based on

ORP).

OC23391 WS-1 WATER SOFTENER SYSTEM MARLO INCORPORATED OF RACINE

MRG-1200-3 DUPLEX ALT WATER S /

EP-160275-003-1443

- Replace 2 consumable bottles for hardness monitor as required (expected replacement every ~2 months). Use:

Hach SP 510 Hardness Monitor Buffer Solution for 20 mg/L Hardness, 500 mL container Hach SP 510 Hardness Monitor Indicator Solution for 5 to 100 mg/L Hardness, 500 mL container

- Hardness monitor 2-point standardization whenever reagent is replaced or when optical system component is replaced.

Use:

Hach TitraVer (EDTA) Hardness Titrant 0.200N, 0.100M, 29 mL container Hach Magnesium Sulfate Solution 10,000 ±1000 mg/L, 29 mL container

- Replace water softener resin if required. Expected resin life is very long, 15+ years (expected replacement 2033 or later).

- Replace hardness monitor pump tubes every 3 months

BRINE TANK

- Clean out brine tank to maintain cleanliness. Minimum yearly.

- Check function on automatic water fill equipment for proper function.

- Provide salt (A-A-694, Type II, Form 1, 40 lb bag) in brine tank to support water softener regenerations.

OC23385 RO-1 REVERSE OSMOSIS SYSTEM 1 MARLO INCORPORATED OF RACINE

MRO-72K-8H SINGLE PASS RO SKID /

EP-160275-004-1113

- Fill antiscallant tank (use PWT SpectraGuard 111, 0.5 gallon container currently authorized)

- Replace 5 micron cartridge filter as required when differential pressure reaches 15 psi.

- Calibrate all gauges and meters based on manufacturer's recommendations. Frequency no less than every 3 months.

- Replace membranes when required. There are 4 membranes on the unit.

- Grease motor bearings quarterly

- Change metering pump cartridge valves yearly

- (Standard pump/motor maintenance)

OC23389 RO-2 REVERSE OSMOSIS SYSTEM 2 MARLO INCORPORATED OF RACINE

MRO-72K-8H SINGLE PASS RO SKID / EP-

160275-013-1120

- Fill antiscallant tank (use PWT SpectraGuard 111, 0.5 gallon container currently authorized)

- Replace 5 micron cartridge filter as required when differential pressure reaches 15 psi.

- Calibrate all gauges and meters based on manufacturer's recommendations. Frequency no less than every 3 months.

- Replace membranes when required. There are 4 membranes on the unit.

- Grease motor bearings quarterly

- Change metering pump cartridge valves yearly

- (Standard pump/motor maintenance)

RO WATER STORAGE TANK - Inspect level sensor and high-high level sensor

OC23386 P-101 RO SUPPLY PUMP 1 MARLO INCORPORATED OF RACINE

RECIRCULATION PUMP SKID WITH / EP-

160275-006-1502 - (Standard pump/motor maintenance)

P-102 RO SUPPLY PUMP 2 - (Standard pump/motor maintenance)

UV FILTER Viqua K Plus/17051610

- Replace UV lamp when required (minimum annually)

- Inspect and clean or replace UV sleeve as required

- Inspect flow meter sensor periodically

OC23388 CIP-1 CLEAN IN PLACE SYSTEM MARLO INCORPORATED OF RACINE MEMBRANE CLEAN-IN-PLACE (CIP) / EP- 160275-005-1491

- Run clean in place cycle as required to maintain RO membranes. Use PWT Lavasol 1, 5 gallon containers currently authorized

- Replace filter as required

- (Standard pump/motor maintenance)

Sodium Bisulfite Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with SBS (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance Antiscalant Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with Anticalant (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance

ALL EQUIPMENT

NUMBER NAME Manufacturer Model No./Serial No. MAINTENANCE REQUIRED Side A Filter Shelco Microguardian 12F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Side A Pump Grundfos A91129158-P21008003 Standard Pump/Motor Maintenance Side B Filter Shelco Microguardian 12F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Side B Pump Grundfos A91129158-P21008003 Standard Pump/Motor Maintenance

Sodium Bisulfite Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with SBS (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance

Antiscalant Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with Anticalant (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance

Cleaner Tank After use of cleaning out the skid, ensure tank is fully drained. Ensure sensor operates, replace as needed.

Cleaner Tank Filter Shelco Microguardian 7F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Cleaner Tank Pump Leeson Electric Corporation C184T34FK15D/131583.00 Standard Pump/Motor Maintenance

P-3 Re-Pressure Skid Pump 1 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-4 Re-Pressure Skid Pump 2 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-5 Distribution Skid Pump 1 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-6 Distribution Skid Pump 2 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance

Product Water Holding Tanks Ensure level sensor is working properly. Replace as needed.

UltraViolet Lamp Aquafine SL-1/FS 0410 061

Replace UV lamps as needed, minimum of once a year. Clean quartz sleeves as needed, and replace once a year. Clean sensor probe window and replace probe once a year. Replace ballast as needed, though it should be infrequent.

OC20140 Main Line Reverse Osmosis System Hausers Water Systems

Ensure membranes are clear of fouling and there are no leaks on the system as a whole. Clean membranes as needed, minimum once a year. There are 16 membranes on the unit. Calibrate, clean, or replace any electrodes/sensors as needed.

AC Units for Control Panels (3) Industrial Cooling Equipment HC12012604XCX Clean out filters as needed, minimum of once a year.

NUMBER NAME Manufacturer Model No./Serial No. MAINTENANCE REQUIRED Side A Filter Shelco Microguardian 12F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Side A Pump Grundfos A91129158-P21008003 Standard Pump/Motor Maintenance Side B Filter Shelco Microguardian 12F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Side B Pump Grundfos A91129158-P21008003 Standard Pump/Motor Maintenance

Sodium Bisulfite Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with SBS (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance

Antiscalant Chem Tanks (2) Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year.

Pumps Associated with Anticalant (2) Pulsatron LB64SA-VTC1-XX2 Standard Pump/Motor Maintenance

Cleaner Tank After use of cleaning out the skid, ensure tank is fully drained. Ensure sensor operates, replace as needed.

Cleaner Tank Filter Shelco Microguardian 7F0S4/112739 Ensure filter is not clogged, replace cartridges as needed.

Cleaner Tank Pump Leeson Electric Corporation C184T34FK15D/131583.00 Standard Pump/Motor Maintenance

P-3 Re-Pressure Skid Pump 1 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-4 Re-Pressure Skid Pump 2 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-5 Distribution Skid Pump 1 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance P-6 Distribution Skid Pump 2 Leeson Electric Corporation C215T34FK10AA Standard Pump/Motor Maintenance

Product Water Holding Tanks Ensure level sensor is working properly. Replace as needed.

UltraViolet Lamp Aquafine SL-1/FS 0410 061

Replace UV lamps as needed, minimum of once a year. Clean quartz sleeves as needed, and replace once a year. Clean sensor probe window and replace probe once a year. Replace ballast as needed, though it should be infrequent.

OC20140 Main Line Reverse Osmosis System Hausers Water Systems

Ensure membranes are clear of fouling and there are no leaks on the system as a whole. Clean membranes as needed, minimum once a year. There are 16 membranes on the unit. Calibrate, clean, or replace any electrodes/sensors as needed.

AC Units for Control Panels (3) Industrial Cooling Equipment HC12012604XCX Clean out filters as needed, minimum of once a year.

Plating RO_Appendix A-1(Equipment List) Serv 19-008-R-0045 Reverse Osmosis
Plating RO
Main Line RO_Appendix A-1(Equipment List) Serv 19-008-R-0045 Reverse Osmosis
Main Line RO
O95 RO_Appendix A-1(Equipment List) Serv 19-008-R-0045 Reverse Osmosis
Main Line RO