A20-002 CLEMCO Wet Duster Collector B3705 - Item Description - Rev.pdf
PDF 249 KB Posted
- Solicitation number
- FA8125-20-Q-0028
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12 QandA 28Feb2020.docx | DOCX document | |
| A20-002 CLEMCO Wet Duster Collector B3705 - Item Description.docx | DOCX document | |
| A20-002 CLEMCO Wet Duster Collector B3705 - SOW.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 05.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 04b.docx | DOCX document | |
| Vendor Q&A_13Feb.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 04.docx | DOCX document | |
| A20-002 CLEMCO Wet Duster Collector B3705 - SOW.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 03.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 02.docx | DOCX document | |
| 12 FA8125-20-Q-0028 AM 01.docx | DOCX document | |
| 12 FA8125-20-Q-0028 Rev SOW.pdf | ||
| 12 FA8125-20-Q-0028 FINAL RFQ.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
OKLAHOMA CITY AIR LOGISTICS COMPLEX
TINKER AIR FORCE BASE OKLAHOMA
8 February 2020
MEMORANDUM FOR RECORD
SUBJECT: Item Description, A20-002 CLEMCO Wet Duster Collector B3705
1. The 76 AMXG is requesting utilization of funds for one (1) each Wet Dust Collector for a blast barn in Building 3705.
2. The requested equipment specifications are outlined below.
A. One (1) each Wet Dust Collector with the minimum listed specification:
a. The item shall have a minimum of 10 horsepower.
b. The item shall meet the electrical requirements of 460V 3PH
60HZ 18A.
c. Item shall have Direct Drive, Airfoil (or Backward incline)
Design and Non-Overloading.
d. Item shall have a minimum air volume of 4400 CFM.
e. Item shall have a Magnetic Motor Starter with Overload protection and a push button start/stop.
f. Item shall have a PLC Controlled Water Level with High and Low Water Indicator Lights.
g. Item shall have a Magnehelic Gauge.
h. Item shall include and utilize MERV 11 Legacy Pre-Filters with a 60% Efficiency Rating.
i. Item shall include and utilize HEPA Afterfilters with a
99.97% Efficiency Rating.
j. Item shall include a High Temperature Shutdown Switch.
k. Item shall be constructed of Heavy Welded Galvanized
Steel, or #304 Stainless Steel, with a Dura-Plate 239 Coating
Throughout. Parts that do not touch water can be powder coated mild steel.
OC-ALC OBCA 2
SUBJECT: Item Description, A20-002 CLEMCO Wet Duster Collector B3705
l. Item shall include Fork Lift Pockets.
m. Item shall be a maximum of ten (10) ft. tall and a maximum of (5) ft. wide.
n. Item shall include a safety powered vent fan that runs all times that the primary blower is off which includes controls.
o. Item shall have an aluminum blower wheel (or a backward inclined, spark-resistant blower wheel) and cone for added spark resistance with corrosion control for humid environments.
p. Item shall meet or exceed the minimum requirements for
NFPA484.
q. Contractor shall provide installation, training, and performance verification In Accordance With (IAW) the Statement of Work (SOW).
r. Contractor shall warranty the Wet Dust Collector for a period of no less than one (1) year.
3. Point of contact for this memorandum is Monica J. Callaway at (405) 622-7847 or e-mail at monica.callaway@us.af.mil.