A20-002 CLEMCO Wet Duster Collector B3705 - Item Description.docx

DOCX document 42 KB Posted

Attached to
Wet Dust Collector Combined Synopsis / Solicitation Federal contract opportunity
Solicitation number
FA8125-20-Q-0028
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

View the file

Other files for this federal contract opportunity

Other files attached to Wet Dust Collector Combined Synopsis / Solicitation, newest first.
File Type Posted
A20-002 CLEMCO Wet Duster Collector B3705 - SOW.docx DOCX document
12 QandA 28Feb2020.docx DOCX document
12 FA8125-20-Q-0028 AM 05.docx DOCX document
12 FA8125-20-Q-0028 AM 04b.docx DOCX document
Vendor Q&A_13Feb.docx DOCX document
A20-002 CLEMCO Wet Duster Collector B3705 - Item Description - Rev.pdf PDF
12 FA8125-20-Q-0028 AM 04.docx DOCX document
A20-002 CLEMCO Wet Duster Collector B3705 - SOW.docx DOCX document
12 FA8125-20-Q-0028 AM 03.docx DOCX document
12 FA8125-20-Q-0028 AM 02.docx DOCX document
12 FA8125-20-Q-0028 AM 01.docx DOCX document
12 FA8125-20-Q-0028 FINAL RFQ.docx DOCX document
12 FA8125-20-Q-0028 Rev SOW.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

OKLAHOMA CITY AIR LOGISTICS COMPLEX

TINKER AIR FORCE BASE OKLAHOMA

OC-ALC OBCA 2

SUBJECT: Item Description, A20-002 CLEMCO Wet Duster Collector B3705

28 February 2020

MEMORANDUM FOR RECORD

SUBJECT: Item Description, A20-002 CLEMCO Wet Duster Collector B3705

1. The 76 AMXG is requesting utilization of funds for one (1) each Wet Dust Collector for a blast barn in Building 3705.

2. The requested equipment specifications are outlined below.

A. One (1) each Wet Dust Collector with the minimum listed specification:

a. The item shall have a minimum of 10 horsepower.

b. The item shall meet the electrical requirements of 460V 3PH 60HZ 18A.

c. Item shall have Direct Drive, Airfoil (or Backward incline) Design and Non-Overloading.

d. Item shall have a minimum air volume of 6500 CFM.

e. Item shall have a Magnetic Motor Starter with Overload protection and a push button start/stop.

f. Item shall have a PLC Controlled Water Level with High and Low Water Indicator Lights.

g. Item shall have a Magnehelic Gauge.

h. Item shall include and utilize MERV 11 Legacy Pre-Filters with a 60% Efficiency Rating.

i. Item shall include and utilize HEPA Afterfilters with a 99.97% Efficiency Rating.

j. Item shall include a High Temperature Shutdown Switch.

k. Item shall be constructed of Heavy Welded Galvanized Steel, or #304 Stainless Steel, with a Dura-Plate 239 Coating Throughout. Parts that do not touch water can be powder coated mild steel.

l. Item shall include Fork Lift Pockets.

m. Item shall be a maximum of ten (10) ft. tall, a maximum of (5) ft. wide, and a maximum of ten (10) ft. length.

n. Item shall include a safety powered vent fan that runs all times that the primary blower is off which includes controls.

o. Item shall have an aluminum blower wheel (or a backward inclined, spark-resistant blower wheel) and cone for added spark resistance with corrosion control for humid environments.

p. Item shall meet the minimum requirements for NFPA484.

q. Contractor shall remove from location the old Dust Collector, the old HEPA Box, the old Blast Tank System, and the old Reclaim System on the Blast Tank.

r. Contractor shall provide installation of the new Wet Dust Collector, training, and performance verification In Accordance With (IAW) the Statement of Work (SOW).

s. Contractor shall warranty the Wet Dust Collector for a period of no less than one (1) year.