EP-090134-03-03.pdf

PDF 438 KB Posted

Attached to
Repair of PMXG Reverse Osmosis System Federal contract opportunity
Solicitation number
FA8125-15-R-0010
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

View the file

Other files for this federal contract opportunity

Other files attached to Repair of PMXG Reverse Osmosis System, newest first.
File Type Posted
2263-201.pdf PDF
PLOT_PLAN.pdf PDF
2263-203.pdf PDF
EP-090134-03-01_Sheet_1.pdf PDF
EP-090134-03-01_Sheet_2.pdf PDF
tinker_map.JPG JPG image
FA8125-15-R-0010 _Solicitation_13_April_2015.pdf PDF
Appendix_A2-RO_PMXG_Maintenance_Contract.xls XLS spreadsheet
Appendix_A1-RO_PMXG_Maintenance_Contract.xlsx XLSX spreadsheet
Wage_Determination_Dated_Version_19_Dated_(December_22_2014).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A A

B B

C C

D D

58"

52"

69 1/4"

Table

ITEM DESCRIPTION LOCATION MAX. FLOW SIZE CONNECTION MATERIAL

H REPRESSURE PUMP SUCTION REPRESS PUMP SKID 300 GPM 6" 150# FLANGE SCH 80 PVC

J PERMEATE OUTLET REPRESS PUMP SKID 300 GPM 4" 150# FLANGE SCH 80 PVC

K PERMEATE FLUSH TO RO REPRESS PUMP SKID 50 GPM 2" 150# FLANGE SCH 80 PVC

L UV RECIRC FEED TO TANK REPRESS PUMP SKID 10 GPM 1" 150# FLANGE SCH 80 PVC

DATE

FRAC.

DRN.

APP'D.

DEC.

DRAWING NO.

SCALE

FILE ID.

SHEET

REV.

OF

REPRESSURIZATION PUMP SKID

GENERAL DIMENSIONAL DRAWING

REVISIONS

NO. BY REMARKS

INCORPORATED

DATE

TINKER AIR FORCE BASE EP-090134-03-03

1 1 AGG

7/10/2009 1

1 2/4/10 AGG MODIFIED SKID & SIZE OF PANEL

TO RO MCP 460V/60Hz/3Ph

H 9 1/2"12 1/4"

J

K

L

AQUAFINE SL-1

UV STERILIZER

AQUAFINE

UV INTENSITY

METER

EBARA 15 HP, 400V/60Hz/3Ph

304SS PUMPS

300 GPM @ 60 PSI

MODEL 3U 50-160-1

POWDER COATED

STRUCTURAL STEEL SKID

NOTE: ALL PIPING SCH 80 PVC EXCEPT BUTTERFLY ISOLATION VALVES

AND 316SS UV LIGHT TRAPS.

53 1/8" 59 3/4"

DISCHARGE

PRESSURE

TRANSMITTER

DISCHARGE

CHECK

VALVE

ISOLATION

VALVES

Model

File details come from the government source that posted it. Updated .