EP-090134-03-01_Sheet_1.pdf

PDF 2 MB Posted

Attached to
Repair of PMXG Reverse Osmosis System Federal contract opportunity
Solicitation number
FA8125-15-R-0010
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

View the file

Other files for this federal contract opportunity

Other files attached to Repair of PMXG Reverse Osmosis System, newest first.
File Type Posted
2263-201.pdf PDF
PLOT_PLAN.pdf PDF
2263-203.pdf PDF
EP-090134-03-01_Sheet_2.pdf PDF
EP-090134-03-03.pdf PDF
tinker_map.JPG JPG image
FA8125-15-R-0010 _Solicitation_13_April_2015.pdf PDF
Wage_Determination_Dated_Version_19_Dated_(December_22_2014).pdf PDF
Appendix_A2-RO_PMXG_Maintenance_Contract.xls XLS spreadsheet
Appendix_A1-RO_PMXG_Maintenance_Contract.xlsx XLSX spreadsheet

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A A

B B

C C

D D

CONNECTION SCHEDULE

ITEM DESCRIPTION LOCATION MAX. FLOW SIZE CONNECTION MATERIAL

A RO INLET @ 30 PSI MINIMUM R.O. SKID 534 GPM 6" 150# FLANGE RF SCH 80 PVC

B PERMEATE OUTLET R.O. SKID 400 GPM 6" 150# FLANGE RF SCH 80 PVC

C CONCENTRATE OUTLET R.O. SKID 134 GPM 3" 150# FLANGE RF SCH 80 PVC

D PERMEATE FLUSH INLET R.O. SKID 50 GPM 2" 150# FLANGE RF SCH 80 PVC

E INSTRUMENT AIR @ 80 PSI R.O. SKID 1 SCFM 1/4" FNPT BRASS

TEMPERATURE

GAUGE

CONCENTRATE

FLOW SENSOR

MEMBRANE

FEED PRESSURE

304SS 5 MICRON

PREFILTER

SHELCO 12FOS4

PERMEATE

CONDUCTIVITY

SENSOR

MEMBRANE

CONCENTRATE

PRESSURE

MEMBRANE

CONCENTRATE

THROTTLE VALVE

ANTI-SCALANT

FEEDER

150 GAL.

SBS

FEEDER

150 GAL.

ORP SENSOR

CIP

ROTAMETER

CODELINE FRP

MEMBRANE VESSELS

300 PSI

6 MEMBRANES PER VESSEL

10 HP

CIP PUMP

CIP FILTER

SHELCO 7FOS4

ANTI-SCALANT

INJECTION

FITTING

SBS

INJECTION

FITTING

VACUUM BREAKER

(PIPE TO FLOOR DRAIN)

460V/60Hz/3Ph

VFD

MOTOR

STARTER

A BC

D

DATE

FRAC.

DRN.

APP'D.

DEC.

DRAWING NO.

SCALE

FILE ID.

SHEET

REV.

OF

MRO-576K-8H DUAL TRAIN RO SYSTEM

GENERAL ARRANGEMENT

REVISIONS

NO. BY REMARKS

INCORPORATED

DATE

TINKER AIR FORCE BASE EP-090134-03-01

2 1 AGG

7/10/2009

PERMEATE

FLUSH VALVE

RAW WATER

CONDUCTIVITY

SENSOR

300 PSI

FRP MEMBRANE VESSELS

E

120V/60Hz/1Ph

TRAIN B

LOCAL

DISPLAY

PANEL

AUTO

FLUSH

VALVE

CONCENTRATE

THROTTLE VALVE

CAUSTIC

INJECTION

FITTING

CIP

SOLUTION

TANK

500 GAL.

CIP IMMERSION

HEATER 7500 W

PERMEATE

FLOW SENSOR

AUTO INLET

VALVE

Model

File details come from the government source that posted it. Updated .