QUESTIONS AND ANSWERS II
Question #1. What is the R-value building code requirement for the new insulation to be installed?
Answer to #1. R-Value Building Code for B1776, B1790, B1628, and B3356 is R-35.
Question #2. Will a 1/2" gypsum sheathing be required to be installed?
Answer to #2. Yes. A 1/2" Gypsum sheathing will be required to be installed on the flat roofs located at B1790, B1628, and B3356
Question #3. What is the physical address for Building 1776?
Answer to #3. 1776 Carswell Ave.
NAS JRB Fort Worth, TX 76127
Question #4. What will be done with the lighting protection during the reroof, are we to provide temporary lighting protection?
Answer to #4. The lightning protection system at B3356 will be removed before roofing demolition and replaced after the new roofing system is installed. A temporary lightning protection system will not be necessary during construction. The occupants of B3356 will shut down operations and evacuate if lightning is within 25 miles.
Question #5. Can you show on some type of site plan where the material storage is to be and also the area that will be for access to the buildings?
Answer to #5. See drawing attachments for Roofing Staging Areas