ZQEL 22-0006 Renovate B301
Solicitation number
FA665626B0003
Issued by

About this file

This document is a specification for construction/maintenance/repair work at Youngstown Air Reserve Station, 910th Airlift Wing, identified as federal contract ZQEL 22-0006.

The specification covers multiple trade sections including metal suspension systems (Section 09 22 26), gypsum board (Section 09 29 00), acoustical panel ceilings (Section 09 51 13), roll-down blinds (Section 11 21 23), diffusers/registers/grilles (Section 23 37 13), and basic electrical materials and methods (Sections 26 05 00 and 26 05 29). For metal suspension systems, contractors must provide hot-dipped galvanized main beams and cross tees complying with ASTM standards, with a ten-year manufacturer warranty against red rust. Acceptable manufacturers include Armstrong World Industries, USG Corp, and CertainTeed Corp. Gypsum board installation requires interior panels and tile backing panels with specified joint treatment materials and trim accessories. Acoustical panel ceilings must be Type III mineral-based panels in white, 3/4-inch thickness, 24-by-24-inch modular size, from manufacturers such as Armstrong, CertainTeed, Chicago Metallic, or USG, installed per ASTM C 636/C 636M standards with a 25-percent minimum recycled content requirement for suspension systems and proper hanger spacing not exceeding 48 inches on center.

Roll-down blinds specifications require manually operated chain-drive sunscreen and room-darkening roller shades with environmentally certified TPO shadecloth and welded hem pockets, utilizing stainless steel chain rated to 90-pound breaking strength and oil-impregnated permanently lubricated brake assemblies. Diffusers, registers, and grilles must be equivalent to Titus models (OMNI for ceiling diffusers, 300FS for supply grilles, 350FL for return/exhaust grilles) installed level and plumb. Electrical work requires EMT, FMC, and rigid galvanized steel conduit, stranded copper conductors with thermoplastic insulation rated 75 degrees Celsius minimum, and support systems complying with NECA 1 and NECA 101 standards. All materials must be delivered in original unopened packages and stored in fully enclosed, conditioned spaces. Field conditions require coordination with HVAC and electrical sections, and all work must comply with OSHA, NFPA, and NEMA standards.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

910th Airlift Wing USAFR ZQEL 22-0006 Youngstown Air Reserve Station Construct/Maintain/Repair Various Rooms

METAL SUSPENSION SYSTEMS 09 22 26 -1

SECTION 09 22 26

METAL SUSPENSION SYSTEMS

PART 1 - GENERAL

2.1 RELATED DOCUMENTS

A. Drawings and general conditions of Contract, including General and Supplementary Conditions and Divisions-1 Specification sections apply to work of this section.

2.2 SUMMARY

A. Section Includes

1. Suspension System Framing and Furring for Plaster and Gypsum Board Assemblies

2. Wire hangers, fasteners, main runners, cross tees, and wall angle moldings.

B. Related Selections

1. Section 09 20 00 - Gypsum Board

2. Section 09 50 01 Wood Panel Ceilings

3. Sections 23 - HVAC Air Distribution

4. Sections 26 - Electrical

2.3 REFERENCES

A. American Society for Testing and Materials (ASTM):

1. ASTM A 641 Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire.

2. ASTM A 653 Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) by the Hot-Dip Process.

3. ASTM A 1008 Standard Specification for Steel, Sheet, Cold Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability"

4. ASTM D 610 Standard Test Method for Evaluating Degree of Rusting on Painted Steel Surfaces

5. ASTM B 117 Standard Practice for Operating Salt Spray (Fog) Apparatus

6. ASTM C 635 Standard Specification for Metal Suspension Systems for Acousti-cal Tile and Lay-in Panel Ceilings.

7. ASTM C 636 Recommended Practice for Installation of Metal Ceiling

Suspension Systems for Acoustical Tile and Lay-in Panels.

910th Airlift Wing ZQEL 22-0006

GYPSUM BOARD 09 29 00 - 3

2. All work above the ceiling line should be completed prior to installing the drywall sheet goods. There should be no materials resting against or wrapped around the suspension system, hanger wires or ties.

2.6 DELIVERY, STORAGE AND HANDLING

2.7 Deliver materials to project site in original, unopened packages and store them in a ful-ly enclosed space where they will be protected against damage from moisture, direct sunlight, surface contamination, and other causes.

2.8 WARRANTY

A. Suspensions System: Submit a written limited warranty executed by the manufacturer, agreeing to repair or replace grid components that are supplied with a hot-dipped gal-vanized coating or aluminum base material. Failures include, but are not limited to:

1. The occurrence of 50% red rust as defined by ASTM D 610 test procedures as a result of defects in materials or factory workmanship.

B. Warranty Period:

1. Grid: Ten years from date of installation.

C. The Warranty shall not deprive the Owner of other rights the Owner may have under other provisions of the Contract Documents and will be in addition to and run concur-rent with other warranties made by the Contractor under the requirements of the Con-tract Documents.

PART 3 - PRODUCTS

3.1 MANUFACTURERS

A. Acceptable Manufacturers:

1. Armstrong World Industries, Inc.

2. USG Corp.

3. CertainTeed Corp.

3.2 COMPONENTS:

A. Main Beam: Shall be double-web construction (minimum 0.0179 inch prior to protective coating, ASTM C645), hot dipped galvanized (per ASTM A653).

B. Primary Cross Tees: Shall be double-web steel construction (minimum 0.0179 inch pri-or to protective coating, ASTM C645), hot dipped galvanized (minimum G40 or G90 per ASTM A653)

GYPSUM BOARD 09 29 00 - 5

PART 4 - EXECUTION

4.1 INSTALLATION - GENERAL

A. Install suspension system and panels in accordance with the manufacturer's instruc-tions, in compliance with ASTM installation standard, and with applicable codes as re-quired by the authorities having jurisdiction.

B. The Armstrong Drywall Grid System can be installed in interior or exterior applications.

C. To secure to metal clips, concrete inserts, steel bar joist or steel deck, use power actu-ated fastener, or insert. Coordinate placement for hanger wire spaced as required for expected ceiling loads and layout.

D. Install hanger wire as required with necessary on center spacing to support expected ceiling load requirements, following local practices, codes and regulations. Provide ad-ditional wires at light fixtures, grilles, and access doors where necessary. A pigtail knot shall be used with three tight wraps at top and bottom fastening locations.

E. Add additional wire as needed when using compatible clips and accessories.

F. Control Joints: Roll formed zinc alloy, aluminum, or plastic as required for expansion and contraction as shown on drawings.

G. Expansion Joints: Roll formed zinc alloy, aluminum, or plastic as required for expan-sion and contraction as shown on drawings.

H. Main beams shall be suspended from the overhead construction with hanger wire, spaced as required for expected ceiling loads, along the length of the main beams.

I. Install cross tees at on center spacing as specified by the drywall manufacturer.

Typical drywall cross tee spacing:

1. 16 inches on center with 5/8 or 1/2 inch gypsum board

2. 24 inches on center with 5/8 inch gypsum board

J. Other items such as wood, sheet metal, or plastic panels should be screwed to comply with deflection limit equivalent to that of the ceiling installation.

K. Use channel molding or angle molding to interface with Drywall Grid System to provide perimeter attachment or to obtain drop soffits, verticals, slopes, etc.

L. To suspend a second ceiling beneath a new or existing drywall ceiling, without breach-ing the integrity of the upper ceiling, use the Drywall Clip. To form a transition from a

Construct/Maintain/Repair Various Rooms

GYPSUM BOARD 09 29 00 - 7

SECTION 09 29 00

GYPSUM BOARD

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Interior gypsum board.

2. Tile backing panels.

B. Related Requirements:

1. Division 09 Section "Non-Structural Metal Framing" for non-structural framing and suspension systems that support gypsum board panels.

2. Division 09 Section "Tiling" for cementitious backer units installed as substrates for ceramic tile.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Recycled Content:

1. Product Data: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.

1.4 DELIVERY, STORAGE AND HANDLING

A. Store materials inside under cover and keep them dry and protected against weather, condensation, direct sunlight, construction traffic, and other potential causes of damage. Stack panels flat and supported on risers on a flat platform to prevent sagging.

1.5 FIELD CONDITIONS

GYPSUM BOARD 09 29 00 - 9

b. National Gypsum Company, Permabase Cement Board.

c. USG Corporation; DUROCK Cement Board.

2. Thickness: 5/8 inch (15.9 mm).

3. Mold Resistance: ASTM D 3273, score of 10.

2.4 TRIM ACCESSORIES

A. Interior Trim: ASTM C 1047.

1. Material: Galvanized or aluminum-coated steel sheet, rolled zinc, plastic, or paper-faced galvanized steel sheet.

2. Shapes:

a. Cornerbead.

b. Expansion (control) joint.

2.5 JOINT TREATMENT MATERIALS

A. General: Comply with ASTM C 475/C 475M.

B. Joint Tape:

1. Interior Gypsum Board: Paper.

2. Tile Backing Panels: As recommended by panel manufacturer.

C. Joint Compound for Interior Gypsum Board: For each coat use formulation that is compatible with other compounds applied on previous or for successive coats.

1. Prefilling: At open joints or beveled panel edges, and damaged surface areas, use settingtype taping compound.

2. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim flanges, use drying-type, all-purpose compound.

a. Use setting-type compound for installing paper-faced metal trim accessories.

3. Fill Coat: For second coat, use drying-type compound.

4. Finish Coat: For third coat, use drying-type compound.

D. Joint Compound for Tile Backing Panels:

1. Cementitious Backer Units: As recommended by backer unit manufacturer.

2.6 AUXILIARY MATERIALS

A. General: Provide auxiliary materials that comply with referenced installation standards and manufacturer's written recommendations.

GYPSUM BOARD 09 29 00 - 11

3. Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4-to 3/8-inch- (6.4- to 9.5-mm-) wide joints to install sealant.

F. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments, except floors. Provide 1/4- to 1/2-inch- (6.4- to 12.7-mm-) wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant.

G. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first.

H. Install sound attenuation blankets before installing gypsum panels unless blankets are readily installed after panels have been installed on one side.

3.3 APPLYING INTERIOR GYPSUM BOARD

A. Single-Layer Application:

1. On partitions/walls, apply gypsum panels vertically (parallel to framing) unless otherwise indicated or required by fire-resistance-rated assembly, and minimize end joints.

a. Stagger abutting end joints not less than one framing member in alternate courses of panels.

2. Fastening Methods: Apply gypsum panels to supports with steel drill screws.

3.4 APPLYING TILE BACKING PANELS

A. Cementitious Backer Units: ANSI A108.11, at showers, and locations indicated to receive tile.

B. Where tile backing panels abut other types of panels in same plane, shim surfaces to produce a uniform plane across panel surfaces.

3.5 INSTALLING TRIM ACCESSORIES

A. General: For trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions. B. Control Joints:

Install control joints at locations indicated on Drawings.

C. Interior Trim: Install in the following locations:

1. Cornerbead: Use at outside corners.

Construct/Maintain/Repair Various Rooms

ACOUSTICAL PANEL CEILINGS 09 51 13 - 1

SECTION 09 51 13

ACOUSTICAL PANEL CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes acoustical panels and exposed suspension systems for ceilings.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Recycled Content:

1. Product Data: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating costs for each product having recycled content.

C. Samples: For each exposed product and for each color and texture specified, 6 inches (150 mm) in size.

1.4 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Acoustical Ceiling Panels: Full-size panels equal to 7 percent of quantity installed.

2. Suspension-System Components: Quantity of each exposed component equal to 2 percent of quantity installed.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

Construct/Maintain/Repair Various Rooms

ACOUSTICAL PANEL CEILINGS 09 51 13 - 3

1. Where appearance characteristics of acoustical panels are indicated by referencing pattern designations in ASTM E 1264 and not manufacturers' proprietary product designations, provide products selected by Architect from each manufacturer's full range that comply with requirements indicated for type, pattern, color, light reflectance, acoustical performance, edge detail, and size.

2.3 ACOUSTICAL PANELS

A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. Chicago Metallic Corporation.

4. USG Interiors, Inc.; Subsidiary of USG Corporation.

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type III, mineral base with painted finish; Form 2, water felted. C.

Color: White.

D. Edge/Joint Detail: Reveal sized to fit flange of exposed suspension-system members.

E. Thickness: 3/4 inch (19 mm).

F. Modular Size: 24 by 24 inches (610 by 610 mm).

2.4 METAL SUSPENSION SYSTEMS, GENERAL

A. Recycled Content: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.

B. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.

C. Attachment Devices: Size for five times the design load indicated in ASTM C 635/C 635M, Table

1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements. D. Wire

Hangers, Braces, and Ties: Provide wires complying with the following requirements:

1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.

Construct/Maintain/Repair Various Rooms

ACOUSTICAL PANEL CEILINGS 09 51 13 - 5

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.

6. Space hangers not more than 48 inches (1200 mm) o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches (200 mm) from ends of each member.

7. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or postinstalled anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.

1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.

2. Screw attach moldings to substrate at intervals not more than 16 inches (400 mm) o.c. and not more than 3 inches (75 mm) from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet (3.2 mm in 3.6 m). Miter corners accurately and connect securely.

3. Do not use exposed fasteners, including pop rivets, on moldings and trim.

Construct/Maintain/Repair Various Rooms

ROLL-DOWN BLINDS 11 21 23 - 1

SECTION 11 21 23

ROLL-DOWN BLINDS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes:

1. Manually operated sunscreen roller shades.

2. Manually operated double-roller sunscreen and room-darkening shades.

1.3 RELATED SECTIONS

A. Section 06 10 00 - Rough Carpentry: Wood blocking for mounting roller shades and accessories.

1.4 REFERENCES

A. ASTM G 21 - Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi.

B. NFPA 701-99 - Fire Tests for Flame-Resistant Textiles and Films.

1.5 SUBMITTALS

A. Product Data: Manufacturer's data sheets on each product to be used, including:

1. Preparation instructions and recommendations.

2. Styles, material descriptions, dimensions of individual components, profiles, features, finishes and operating instructions.

3. Storage and handling requirements and recommendations.

4. Mounting details and installation methods.

B. Shop Drawings: Plans, elevations, sections, product details, installation details, operational clearances, and relationship to adjacent work.

Construct/Maintain/Repair Various Rooms

ROLL-DOWN BLINDS 11 21 23 - 3

B. Roller Shade Installation: One year from date of Substantial Completion, not including scaffolding, lifts or other means to reach inaccessible areas.

PART 2 - PRODUCTS

2.1 APPLICATIONS/SCOPE

A. Roller Shade Schedule:

1. Shade Type SR.1: Manual operating, chain drive, sunscreen roller shades in all exterior windows of rooms and spaces shown on the Drawings.

2. Shade Types DR.1 and DR.2: Manual operating interior, chain drive "double" solar and room darkening blackout roller shades, operating independently of each other, in all exterior windows of rooms and spaces shown on Drawings, and related mounting systems and accessories.

2.2 SHADE CLOTH

A. Environmentally Certified Shadecloth: Fabricated from TPO for both core yarn and jacket, single thickness, non-raveling 0.030 inch (0.762 mm) thick fabric.

1. Weave: 5 percent open, 2x2 basket weave pattern.

2. Color: Selected from manufacturer's standard colors.

B. Room darkening (PVC Free) Shadecloth with opaque acrylic backing: .008 inches thick (.19 mm) blackout material and weighing .94 lbs. per square yard, comprising of 53% fiberglass, 45% acrylic, 2% poly finish.

1. Color: Selected from manufacturer’s standard colors.

2.3 SHADE BAND

A. Shade Bands: Construction of shade band includes the fabric, the hem weight, hem-pocket, shade roller tube, and the attachment of the shade band to the roller tube. Sewn hems and open hem pockets are not acceptable.

1. Hem Pockets and Hem Weights: Fabric hem pocket with RF-welded seams (including welded ends) and concealed hem weights. Hem weights shall be of appropriate size and weight for shade band. Hem weight shall be continuous inside a sealed hem pocket. Hem pocket construction and hem weights shall be similar, for all shades within one room.

2. Shade band and Shade Roller Attachment:

a. Use extruded aluminum shade roller tube of a diameter and wall thickness required to support shade fabric without excessive deflection. Roller tubes less than 1.55 inch

Construct/Maintain/Repair Various Rooms

ROLL-DOWN BLINDS 11 21 23 - 5

2.5 COMPONENTS

A. Access and Material Requirements:

1. Provide shade hardware allowing for the removal of shade roller tube from brackets without removing hardware from opening and without requiring end or center supports to be removed.

2. Provide shade hardware that allows for removal and re-mounting of the shade bands without having to remove the shade tube, drive or operating support brackets.

B. Manual Operated Chain Drive Hardware and Brackets:

1. Provide for universal, regular and offset drive capacity, allowing drive chain to fall at front, rear or non-offset for all shade drive end brackets. Universal offset shall be adjustable for future change.

2. Provide hardware capable for installation of a removable fascia, for both regular and/or reverse roll, which shall be installed without exposed fastening devices of any kind.

3. Provide positive mechanical engagement of drive mechanism to shade roller tube. Friction fit connectors for drive mechanism connection to shade roller tube are not acceptable.

4. Provide shade hardware constructed of minimum 1/8-inch (3.18 mm) thick plated steel or heavier as required to support 150 percent of the full weight of each shade.

5. Drive Bracket / Brake Assembly:

a. Drive Bracket shall be fully integrated with all accessories, including, but not limited to: fascia, and room darkening side / sill channels.

b. Drive sprocket and brake assembly shall rotate and be supported on a welded 3/8 inch (9.525 mm) steel pin.

c. The brake shall be an over -unning clutch design which disengages to 90 percent during the raising and lowering of a shade. The brake shall withstand a pull force of 50 lbs. (22 kg) in the stopped position.

d. The braking mechanism shall be applied to an oil-impregnated hub on to which the brake system is mounted. The oil impregnated hub design includes an articulated brake assembly, which assures a smooth, non-jerky operation in raising and lowering the shades. The assembly shall be permanently lubricated. Products that require externally applied lubrication and or not permanently lubricated are not acceptable.

e. The entire assembly shall be fully mounted on the steel support bracket, and fully independent of the shade tube assembly, which may be removed and reinstalled without effecting the roller shade limit adjustments.

C. Drive Chain: #10 qualified stainless steel chain rated to 90 lb. (41 kg) minimum breaking strength.

Nickel plate chain shall not be accepted.

Construct/Maintain/Repair Various Rooms

ROLL-DOWN BLINDS 11 21 23 - 7

C. Clean roller shade surfaces after installation, according to manufacturer's written instructions.

D. Engage Installer to train Owner's maintenance personnel to adjust, operate and maintain roller shade systems.

3.4 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION 12 49 40

Construct/Maintain/Repair Various Rooms

DIFFUSERS, REGISTERS, AND GRILLES 23 37 13-2

3. Tuttle & Bailey

SUPPLY AIR DIFFUSERS & GRILLES

Rectangular Architectural Ceiling Diffusers (CD-1):

Rectangular, round neck, stamped, architectural square panel type diffuser to discharge air in 360-degree pattern with sectorizing baffles where indicated.

Material: Steel.

Finish: Baked enamel, off-white.

Mounting: To match ceiling construstion.

Dampers: Radial opposed blade.

Shall be equivalent to Titus Model OMNI.

REGISTERS AND GRILLES

Rectangular Supply Grille (SR-1):

Double deflection with individually adjustable 3/4" aluminum airfoil blades on 3/4" centers and 1-1/4" border. Front blades parallel to short dimension.

Border Material - Steel.

Finish: Baked enamel, off-white.

Damper Type: Adjustable opposed blade.

Shall be equivalent to Titus Model 300FS.

Rectangular Return and Exhaust Grille (RG-1,ER-1, TG-1):

Single 35 degree fixed deflection and 1-1/4" border.

Border Material - Steel.

Finish: Baked enamel, off-white.

Damper Type: Adjustable opposed blade.

Shall be equivalent to Titus Model 350FL.

Verification of Performance: Rate diffusers, registers, and grilles according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets."

PART 3 - EXECUTION

INSTALLATION

Install diffusers, registers, and grilles level and plumb.

Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design

Construct/Maintain/Repair Various Rooms

DIFFUSERS, REGISTERS, AND GRILLES 23 37 13-2

THIS PAGE IS INTENTIONALLY BLANK

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 1

SECTION 26 05 00

BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 – GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

B. The construction, installation, workmanship, equipment and materials shall be in accordance with the latest issues of the following standards and regulations insofar as they apply:

Occupational Safety and Health Act (OSHA) National Fire Protection Association (NFPA)

National Electric Manufacturers Association (NEMA)

1.02 SUMMARY

A. This Section includes the following:

1. Raceways.

2. Building wire and connectors.

3. Supporting devices for electrical components.

4. Electrical identification.

5. Electrical demolition.

6. Touchup painting.

1.03 DEFINITIONS

A. EMT: Electrical metallic tubing.

B. FMC: Flexible metal conduit.

C. RGSC: Intermediate metal conduit.

D. LFMC: Liquid-tight flexible metal conduit.

E. RNC: Rigid nonmetallic conduit.

F. RGSC: Rigid galvanized steel conduit.

G. "Provide" is defined as "furnish new, install, and make operational".

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 3

PART 2 – PRODUCTS

2.01 RACEWAYS

A. EMT: ANSI C80.3, zinc-coated steel, with compression fittings.

B. FMC: Flexible metal conduit.

C. RGSC: ANSI C80.6, zinc-coated steel, with threaded fittings.

D. LFMC: Zinc-coated steel with sunlight-resistant and mineral-oil-resistant plastic jacket.

E. RNC: NEMA TC 2, Schedule 40 PVC, with NEMA TC3 fittings.

F. RGSC: ANCI C80.1, galvanized steel

G. Raceway Fittings: Specifically designed for the raceway type with which used.

2.02 CONDUCTORS

A. Conductors, No. 10 AWG and Smaller: Stranded copper.

B. Conductors, Larger Than No. 10 AWG: Stranded copper.

C. Insulation: Thermoplastic, rated at 75 deg C minimum.

D. Wire Connectors and Splices: Units of size, ampacity rating, material, type, and class suitable for service indicated.

2.03 SUPPORTING DEVICES

A. Material: Cold-formed steel, with corrosion-resistant coating acceptable to authorities having jurisdiction.

B. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel.

C. Slotted-Steel Channel Supports: Flange edges turned toward web, and 9/16-inch (14-mm) diameter slotted holes at a maximum of 2-inches (50-mm) on center, in webs.

D. Raceway and Cable Supports: Manufactured clevis hangers, riser clamps, straps, threaded C-clamps with retainers, ceiling trapeze hangers, wall brackets, and spring-steel clamps or click-type hangers.

E. Pipe Sleeves: ASTM A 53, Type E, Grade A, Schedule 40, galvanized steel, plain ends.

F. Cable Supports for Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug for non-armored electrical cables in riser conduits. Plugs

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 5

G. Interior Warning and Caution Signs: Comply with 29 CFR, Chapter XVII, Part 1910.145.

Preprinted, aluminum, baked-enamel-finish signs, punched or drilled for mechanical fasteners, with colors, legend, and size appropriate to the application.

H. Fasteners for Nameplates and Signs: Self-tapping, stainless steel screws or No. 10/32 stainless steel machine screws with nuts and flat and lock washers.

2.05 TOUCHUP PAINT

A. For Equipment: The Equipment Manufacturer's paint selected to match installed equipment finish.

B. Galvanized Surfaces: Zinc-rich paint recommended by the Item Manufacturer.

PART 3 – EXECUTION

3.01 ELECTRICAL EQUIPMENT INSTALLATION

A. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide the maximum possible headroom.

B. Materials and Components: Install level, plumb, and parallel and perpendicular to other building systems and components, unless otherwise indicated.

C. Equipment: Install to facilitate service, maintenance, and repair or replacement of components. Connect for ease of disconnecting, with minimum interference with other installations.

D. Right of Way: Give to raceways and piping systems installed at a required slope.

3.02 RACEWAY APPLICATION

A. Use the following raceways for outdoor installations:

1. Exposed: RGSC.

2. Concealed: RGSC.

3. Underground, Single Run: Encased PVC, Schedule 40.

4. Underground, Grouped: Encased PVC, Schedule 40.

5. Connection to Vibrating Equipment: LFMC.

6. Boxes and Enclosures: NEMA 250, Type 3R or Type 4.

7. RGSC: As required by NFPA 70.

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 7

5. Make bends in exposed parallel or banked runs from same centerline to make bends parallel. Use factory elbows only where elbows can be installed parallel;

otherwise, provide field bends for exposed parallel raceways.

G. Install pull wires in empty raceways. Use No. 14 AWG zinc-coated steel or monofilament plastic line with not less than 200-pound (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end of the pull wire.

H. Install telephone and signal system raceways, 2-inch trade size and smaller, in maximum lengths of 150 feet (45 m) and with a maximum of two 90-degree bends or equivalent.

Separate lengths with pull or junction boxes where necessary to comply with these requirements, in addition to requirements above.

I. Connect motors and equipment subject to vibration, noise transmission, or movement with a maximum of 72-inch (1830-mm) flexible conduit. Install LFMC in wet or damp locations.

Install separate ground conductor across flexible connections.

J. Set floor boxes level and trim after installation to fit flush to finished floor surface.

3.04 WIRING METHODS FOR POWER, LIGHTING, AND CONTROL CIRCUITS

A. Feeders: Type THHN/THWN insulated conductors in raceway

B. Underground Feeders and Branch Circuits: Type THWN or single-wire, Type UF insulated conductors in raceway.

C. Branch Circuits: Type THHN/THWN insulated conductors in raceway.

D. Remote-Control Signaling and Power-Limited Circuits: Type THHN/THWN insulated conductors in raceway for Classes 1, 2, and 3, unless otherwise indicated.

3.05 WIRING INSTALLATION

A. Install splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than un-spliced conductors. B.

Install wiring at outlets with at least 12 inches (300 mm) of slack conductor at each outlet.

C. Connect outlet and component connections to wiring systems and to ground. Tighten electrical connectors and terminals, according to the Equipment Manufacturer's published torque-tightening values. If the Equipment Manufacturer's torque values are not indicated, use those specified in UL 486A.

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 9

J. Separately support cast boxes that are threaded to raceways and used for fixture support.

Support sheet metal boxes directly from the building structure or by bar hangers. If bar hangers are used, attach bar to raceways on opposite sides of the box and support the raceway with an approved fastener not more than 24 inches (610 mm) from the box.

K. Install metal channel racks for mounting cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices unless components are mounted directly to structural elements of adequate strength.

L. Install sleeves for cable and raceway penetrations of concrete slabs and walls unless core-drilled holes are used. Install sleeves for cable and raceway penetrations of masonry and fire-resistance-rated gypsum walls and of all other fire-resistance-rated floor and wall assemblies. Install sleeves during erection of concrete and masonry walls.

M. Securely fasten electrical items and their supports to the building structure, unless otherwise indicated. Perform fastening according to the following unless other fastening methods are indicated:

1. Wood: Fasten with wood screws or screw-type nails.

2. Masonry: Toggle bolts on hollow masonry units and expansion bolts on solid masonry units.

3. Existing Concrete: Expansion bolts.

4. Instead of expansion bolts, threaded studs driven by a powder charge and provided with lock washers may be used in existing concrete.

5. Steel: Welded threaded studs or spring-tension clamps on steel.

a. Field Welding: Comply with AWS D1.1.

6. Welding to steel structure may be used only for threaded studs, not for conduits, pipe straps, or other items.

7. Light Steel: Sheet metal screws.

8. Fasteners: Select so the load applied to each fastener does not exceed 25 percent of its proof-test load.

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 11

H. Install warning, caution, and instruction signs where required to comply with 29 CFR, Chapter XVII, Part 1910.145, and where needed to ensure safe operation and maintenance of electrical systems and of items to which they connect. Install engraved plastic-laminated instruction signs with approved legend where instructions are needed for system or equipment operation. Install metal-backed butyrate signs for outdoor items.

J. Install engraved-laminated emergency-operating signs with white letters on red background with minimum 3/8-inch (9-mm) high lettering for emergency instructions on power transfer, load shedding, and other emergency operations.

3.09 FIRESTOPPING

A. Apply firestopping to cable and raceway penetrations of fire-resistance-rated floor and wall assemblies to achieve fire-resistance rating of the assembly. Firestopping materials and installation requirements are specified in Division 7 Section "Firestopping."

3.10 DEMOLITION

A. Protect existing electrical equipment and installations indicated to remain. If damaged or disturbed in the course of the Work, remove damaged portions and install new products of equal capacity, quality, and functionality.

B. Accessible Work: Remove exposed electrical equipment and installations, indicated to be demolished, in their entirety.

C. Abandoned Work: Cut and remove buried raceway and wiring, indicated to be abandoned in place, 2-inches (50-mm) below the surface of adjacent construction. Cap raceways and patch surface to match existing finish.

D. Remove demolished material from Project site and dispose of in accordance with all applicable laws.

E. Remove, store, clean, reinstall, reconnect, and make operational components indicated for relocation.

3.11 CUTTING AND PATCHING

A. Cut, channel, chase, and drill floors, walls, partitions, ceilings, and other surfaces required to permit electrical installations. Perform cutting by skilled mechanics of trades involved.

B. Repair and refinish disturbed finish materials and other surfaces to match adjacent undisturbed surfaces. Install new fireproofing where existing firestopping has been disturbed. Repair and refinish materials and other surfaces by skilled mechanics of trades involved.

Construct/Maintain/Repair Various Rooms

BASIC ELECTRICAL MATERIALS AND METHODS 16 05 00 – 13

A. Daily type use extension cords, work lights, etc. will be provided by other trades.

B. This Contractor shall furnish temporary power to a maximum of 60 amps. Additional temporary power requirements above 60 amps shall be negotiated with the requesting contractor.

C. Contracting Officer will assume the cost of the electrical energy used.

D. The temporary power system shall remain in place until the permanent power system is in operation. This Contractor shall then remove all materials and equipment previously installed.

END OF SECTION

Construct/Maintain/Repair Various Rooms

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 26 05 29-1

SECTION 26 05 29

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.02 DEFINITIONS

A. EMT: Electrical metallic tubing.

B. RMC: Rigid metal conduit.

1.03 PERFORMANCE REQUIREMENTS

A. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

1.04 QUALITY ASSURANCE

A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

B. Comply with NFPA 70.

1.05 COORDINATION

A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements as specified.

PART 2 - PRODUCTS

2.01 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

Construct/Maintain/Repair Various Rooms

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 26 05 29-3

3. MKT Fastening, LLC.

4. Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.

J. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS Type 18; complying with MFMA-4 or MSS SP-58.

K. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

L. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A 325.

M. Toggle Bolts: All-steel springhead type.

N. Hanger Rods: Threaded steel.

2.02 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.

PART 3 - EXECUTION

3.01 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for EMT, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch in diameter.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with two-bolt conduit clamps.

3.02 SUPPORT INSTALLATION

Construct/Maintain/Repair Various Rooms

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 26 05 29-5

3.05 PAINTING

A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field- painted surfaces.

1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.

B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION 26 05 29