Questions and Answers.docx

DOCX document 17 KB Posted

Attached to
Fire Department Air Duct Cleaning
Solicitation number
FA665625Q0004
Issued by

About this file

This is a Questions and Answers document for air duct cleaning services at Building 402, which is 23,698 square feet. The document clarifies technical specifications including equipment details: four packaged RTUs (5-18 tons), one fan coil unit (3 ton), two exhaust systems (8000 CFM each), two DX condensers (3 and 1.5 ton), and one modular indoor AHU (3000 CFM, 7.5 ton).

Key clarifications include: no wall cutting is required, no testing or air monitoring is needed, repairs and replacements are not in scope but must be documented for the base BOS contractor, prevailing wage rates apply, all interior ductwork and VAV boxes must be cleaned, filters are not to be supplied by the contractor, and exhaust systems do not require cleaning. The work is being solicited by the Department of the Air Force Reserve Command under solicitation number FA665625Q0004, with quotes due by February 26, 2025 at 10:00 AM EST. A site visit is scheduled for February 10, 2025.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers B402 Air Duct Cleaning

What is the square footage of the facility requiring duct cleaning.

23,698 square feet Please provide CFM or tonnage of each air handler unit.

Packaged units RTU-1 = 5 Ton RTU-2 = 5 Ton RTU-3 = 18Ton RTU-4 = 5 Ton

Fan Coil Unit FCU-1 = 3 Ton

Exhaust Systems

VEF-1 8000 CFM

VEF-2 8000 CFM

DX Condenser DX-1 = 3 Ton DX-2 = 1.5 Ton

Modular Indoor AHU AHU 3000 CFM, 7.5 Ton

Please confirm that hard surfaces (e.g. walls and /or ceilings) are not required to be cut into in order to facilitate cleaning.

No walls to cut

Please confirm that testing and/or air monitoring is not required.

No testing required Please confirm that repairs and/or replacements are not part of the scope of work No repairs or maintenance just needs to be annotated and we will push it to the on-base BOS contractor.

Please advise if we are to pay the Sheet metal Maintenance wage to clean duct work? Are Prevailing Wage Rates required to be used on this project?

Yes – wage determination posted previously on sam.gov

Any idea on total square footage of ductwork?

No

Please confirm we are cleaning all units and VAV boxes?

All interior duct work

Is the facility supplying new filters for units? If not, what are the sizes for us to supply?

The facility is not supplying filters and the contractor does not need to supply filters. This is handled by the on-base BOS contractor.

Are Exhaust Systems Required to be cleaned?

No