This document appears to be Attachment 3 Drawings related to Solicitation Number FA665624B0001 for the Renovate Hangar B295 project. The solicitation is a 100% HUBZone Small Business set-aside, with a Firm-Fixed Price contract for the work. The project consists of removing the concrete mezzanine, relocating HVAC, piping and electrical systems, constructing new stairs and a catwalk, and building concrete pads and masonry walls for equipment. The period of performance is 240 calendar days. The magnitude of the project is between $500,000 and $1,000,000. Interested parties must register on the Interested Vendors List and be listed and active in the SAM database for NAICS code 236220. Proposals are due by 29 May 2024 at 10:00am EDT. A site visit is anticipated on 10 May 2024.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAIN GATE
DYNOTEC
100% FINAL SUBMISSION
2931 E Dublin-Granville Rd Suite 200
Columbus, OH 43231 Main: 614.880.7320 | Fax: 614.880.7324
PREPARED FOR:
DEPARTMENT OF THE U.S. AIR FORCE
HEADQUARTERS, 910TH AIRLIFT WING (AFRC)
YOUNGSTOWN AIR RESERVE STATION
VIENNA OH 44473-5937
PROJECT NO. ZQEL 24-0005
RENOVATE HANGAR B295 FOR C130J CONVERSION
PREPARED BY:
ARCHITECT & STRUCTURAL ENGINEER
VICINTY MAP PARTIAL BASE PLAN
N N
PROJECT LOCATION
BASE CONTRACTING
BASE CIVIL ENGINEER
BASE LOCATION
GOVERNMENT SIGNATURE BLOCK
CHIEF, ENGINEERING DIVISION DATE
CHIEF, DESIGN BRANCH
PROJECT ENGINEER
DATE
DATE
APPROVED BY
REVIEWED BY
CONCRETE
BRICK
CONCRETE MASONRY
(VARIES REFER TO PARTITION SCHEDULE)
STONE
STEEL OR METAL
WOOD, FINISH
WOOD, FRAMING
WOOD, BLOCKING, INTERRUPTED MEMBER
PLYWOOD, EDGE
GLASS
ACOUSTIC TILE
GYPSUM BOARD
BATT INSULATION
RIGID INSULATION / E.I.F.S.
CERAMIC TILE
EXISTING CONSTRUCTION TO REMAIN
NOTE: MATERIALS SHOWN ARE FOR WALL SECTIONS AND/OR LARGE SCALE
DETAILS ONLY. PATTERNS FOR SMALLER SCALE PLANS AND/OR ELEVATIONS
MAY VARY. REFER TO INDIVIDUAL LEGENDS AND/OR SCHEDULES FOR
VARIATIONS.
DRAWING INDEXCODE INFORMATION
ISSUED FOR:
R E
C O
R D
O C
U M
E N
T S
B I D
D I N
G
C
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
S H
E E
T
GENERAL
● ● ● G001 COVER SHEET 01
● ● ● G002 DRAWING INDEX, LEGENDS, AND GENERAL NOTES 02
● ● ● G101 OVERALL FIRST FLOOR PLAN 03
STRUCTURAL
● ● ● S001 STRUCTURAL GENERAL NOTES 04
● ● ● S101 FIRST FLOOR PLAN 05
● ● ● S102 DEMO AND FOUNDATION PLANS 06
● S103 PARTIAL FLOOR PLANS 07
● S104 ROOF FRAMING PLAN 08
● ● ● S201 SECTIONS 09
● ● ● S301 ELEVATIONS 10
● S302 ELEVATIONS 11
● ● ● S401 STRUCTURAL DETAILS 12
● ● ● S402 STRUCTURAL DETAILS 13
ARCHITECTURAL
● ● ● A121 OVERALL ROOF PLAN 14
● ● ● A501 EXTERIOR DETAILS 15
FIRE PROTECTION
● ● ● F000 FIRE PROTECTION COVERSHEET 16
● ● ● F101 FIRE PROTECTION DEMOLITION PLAN 17
● ● ● F201 FIRE PROTECTION PLAN 18
ACOUS. ACOUSTIC
ATC ACOUSTIC TILE CEILING
A.D.A AMERICAN DISABILITIES ACT
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
AL. ALUMINUM
ALT. ALTERNATE
APPROX. APPROXIMATE
BLDG. BUILDING
BLK. BLOCK
BLKG. BLOCKING
B.M. BENCH MARK
BM. BEAM
B.N. BULL NOSE
BRG. BEARING
B.O. BOTTOM OF
BOT. BOTTOM
C.B CATCH BASIN
CERM. CERAMIC
C.I. CAST IRON
C.J. CONTROL JOINT
CLG. CEILING
C.L. CENTER LINE
CLR. CLEAR
C.M.U. CONCRETE MASONRY UNIT
COL. COLUMN
CONC CONCRETE
CONST. CONSTRUCTION
CNTR. CENTER
C.T. CERAMIC TILES
DEPT. DEPARTMENT
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DTL. DETAIL
D.S. DOWNSPOUT
EA. EACH
E.I.F.S EXTERIOR INSULATION FINISH SYSTEM
EL. ELEVATION
E.P. ELECTRICAL PANEL
EQ. EQUAL
E.W.C. ELECTRICAL WATER COOLER
EXP. J. EXPANSION JOINT
F.E. FIRE EXTINGUISHER
F.D. FLOOR DRAIN
EXIST. EXISTING
EXT. EXTERIOR
FT. FEET / FOOT
F.R.T. FIRE RETARDANT TREATED
FLOUR. FLOURESCENT
FTG. FOOTING
GA. GAUGE
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
G.W.B. GYPSUM WALL BOARD
H.B. HOSE BIBB
H.C. HANDICAP
HGT. HEIGHT
H. HIGH
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
INT. INTERIOR
I.D. INSIDE DIAMETER
LAM. LAMINATE
LAV. LAVITORY
LKR. LOCKER
L. LONG
L.L.V. LONG LEG VERTICAL
L.L.H. LONH LEG HORIZONTAL
MAX. MAXIMUM
MECH. MECHANICAL
MEMB. MEMBRANE
MET. METAL
MFR. MANUFACTURER
M.O. MASONRY OPENING
MTL. METAL
MCG. METAL CORNER GUARD
MISC. MISCELLANEOUS
MIN. MINIMUM
MTD. MOUNTED
N NORTH
NO. NUMBER
NOM. NOMINAL
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O/ OVER
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O/O OUT TO OUT
OPNG. OPENING
OPP. OPPOSITE
PNL. PANEL
PL. PLATE
P. LAM PLASTIC LAMINATE
PLAS. PLASTER
PLUMB. PLUMBING
PLYWD. PLYWOOD
P.J. PANEL JOINT
PR. PAIR
PT. POINT
PTN. PARTITION
PTD. PAINTED
R, RAD. RADIUS
R.D. ROOF DRAIN
REQ'D. REQUIRED
REINF. REINFORCING
REV. REVISION
R.T.U. ROOF TOP UNIT
RM. ROOM
R.O. ROUGH OPENING
R/W RRIGHT-OF-WAY
SHT. SHEET
SIM. SIMILAR
S.O.G. SLAB ON GRADE
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
ST.D STANDARD
STL. STEEL
SUSP. SUSENDED
TEMP. TEMPERED
THK. THICK
T.B.D. TO BE DETERMINED
T & G TONGUE & GROOVE
T.O. TOP OF
T.S. TUBE STEEL
TYP. TYPICAL
U.N.O. UNLESS NOTE OTHERWISE
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
V.C.T. VINYL COMPOSITE TILE
W.H. WATER HEATER
W.W.F. WELDED WIRE FABRIC
W.W.M. WELDED WIRE MESH
W. WIDE
W/ WITH
W/O WITHOUT
WD. WOOD
ABBREVIATIONS
EXISTING USE & OCCUPANCY: (OBC SECTION 304.1)
S1 - MODERATE HAZARD STORAGE
HEIGHT & AREA LIMITATIONS (OBC TABLE 504.3, 504.4,506.2)
HEIGHT ALLOWABLE EXISTING
SI USE, IIB CONSTRUCTION, S1
HEIGHT IN FEET 75'-0" 55'-10"
HEIGHT IN STORIES 3 1
AREA
ALLOWABLE
(GROSS AREA/FLOOR)
EXISTING
(GROSS AREA/FLOOR)
S1 USE, IIB CONSTRUCTION, S1
FIRST FLOOR 92,000 SF 22,929 SF
MEZZANINE 92,000 SF 195 SF
TOTAL: 184,000 SF 23,124 SF
EXISTING CONSTRUCTION TYPE: II B (OBC SECTION 602.2)
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS: (OBC TABLE 601)
EXISTING FIRE-RESISTANCE RATED BUILDING ELEMENTS WILL REMAIN UNCHANGED.
USE GROUP
SPRINKLERED
EXIT ENCLOSURES
/ PASSAGEWAYS
(ASTM E 84 OR UL
CORRIDORS (ASTM
E 84 OR UL 723)
ROOMS &
ENCLOSED
SPACES (ASTM E
84 OR UL 723)
SI
C
FLAME SPREAD
INDEX 76-200,
SMOKE
DEVELOPED INDEX
0-450
C
FLAME SPREAD
INDEX 76-200,
SMOKE
DEVELOPED INDEX
0-450
C
FLAME SPREAD
INDEX 76-200,
SMOKE
DEVELOPED INDEX
0-450
FUNCTION OF SPACE
FLOOR AREA /
OCCUPANT
(SF)
TOTAL FLOOR
AREA
(SF)
TOTAL
OCCUPANTS
OFFICES 100 GROSS 2,168 22
LOCKER ROOMS 50 GROSS 915 18
HANGAR 500 GROSS 19,085 38
MECHANICAL 300 GROSS 956 2
TOTALS: - 80
MINIMUM NUMBER OF EXITS FOR OCCUPANT LOAD: (OBC TABLE 1006.3.1)
REQUIRED: 1 - 500 OCCUPANTS = 2 EXITS
EXISTING: 7 EXITS (UNCHANGED)
EXIT ACCESS TRAVEL DISTANCE: (OBC TABLE 1017.2)
S OCCUPANCY
REQUIRED: 250'-00” MAXIMUM WITH SPRINKLERS
EXISTING: 70' - 0" (UNCHANGED)
CORRIDOR FIRE RESISTANCE RATING: (OBC TABLE 1020.1)
S OCCUPANCY w/ SPRINKLERS
REQUIRED: 0 HOUR
EXISTING: 0 HOUR (UNCHANGED)
MINIMUM CORRIDOR WIDTH: (OBC TABLE 1020.2)
S OCCUPANCY
REQUIRED: 44 INCHES MINIMUM
EXISTING: 48 INCHES (UNCHANGED)
STRUCTURAL DESIGN LOADS: (OBC SECTION 1603)
UNCHANGED
PLUMBING FIXTURES REQUIRED: (OBC TABLE 2902.1)
* SCOPE OF WORK DOES NOT INCREASE THE EXISTING AREA OR HEIGHT OF THE EXISTING BUILDING.
OCCUPANT LOAD (OBC TABLE 1004.1.2)
INTERIOR WALL AND CEILING FINISH REQUIREMENTS: (OBC TABLE 803.11)
BUILDING ELEMENT CONSTRUCTION TYPE IIB
REQUIRED RATING IN HOURS
PRIMARY STRUCTURAL FRAME 0
BEARING WALLS - EXTERIOR 0
BEARING WALLS - INTERIOR 0
NON-BEARING WALLS &
PARTITIONS-INTERIOR 0
FLOOR CONSTRUCTION 0
ROOF CONSTRUCTION 0
DYNOTEC
ISSUED FOR:
R E
C O
R
C
U M
E N
T S
B I D
D I N
G
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
N
S T
R U
C T
I O
N
D
O C
U M
E N
T S
S H
E E
T
PLUMBING
● ● ● P000 PLUMBING COVERSHEET 19
● ● ● P101 PLUMBING DEMOLITION PLAN 20
● ● ● P201 PLUMBING PLAN 21
● ● ● P400 PLUMBING DETAILS & SCHEDULES 22
MECHANICAL
● ● ● M000 HVAC COVERSHEET 23
● ● ● M101 VENTILATION DEMOLITION PLAN 24
● ● ● M201 VENTILATION PLAN 25
● ● ● M301 VENTILATION ROOF PLAN 26
● ● ● M400 HVAC DETAILS 27
● ● ● M401 HVAC DETAILS 28
● ● ● M600 HVAC SCHEDULES 29
ELECTRICAL
● ● ● E000 ELECTRICAL COVERSHEET 30
● ● ● E101 LIGHTING DEMOLITION PLAN 31
● ● ● E111 ELECTRICAL DEMOLITION PLAN 32
● ● ● E201 LIGHTING PLAN 33
● ● ● E211 ELECTRICAL PLAN 34
● ● ● E212 ELECTRICAL - ROOF PLAN 35
● ● ● E400 ELECTRICAL DETAILS 36
● E500 ELECTRICAL SINGLE LINE DIAGRAM 37
PROJECT DESCRIPTION
THE PROJECT INVOLVES AN INTERIOR ALTERATION FOR AN EXISTING SINGLE-STORY OFFICE/AIR CRAFT HANGAR BUILDING. AREA OF ALTERATION AREA IS APPROXIMATELY 650 SF. NO CHANGE IN USE OR
INCREASE IN EXISTING AREA IS PROPOSED.
APPLICABLE CODES
OHIO BUILDING CODE (OBC) - 2017
OHIO PLUMBING CODE (OPC) - 2017
OHIO MECHANICAL CODE (OMC) -2017
OHIO FIRE CODE (OFC) - 2017 W/ 2019 UPDATES
INTERNATIONAL ENERGY CONSERVATION CODE (IEC) - 2012, ASHRE 90.1 -2010
NATIONAL ELECTRIC CODE (NEC)-NFPA 70 - 2017
AMERICAN WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG)
NATIONAL FIRE ALARM & SIGNALING CODE (NFPA 72-16)
AUTOMATIC SPRINKLER SYSTEMS (NFPA 13 - 16)
AUTOMATIC SPRINKLER SYSTEM REQUIREMENTS: (OBC SECTION 903.3)
AUTOMATIC SPRINKLER SYSTEM IS PROVIDED IN ACCORDANCE WITH NFPA 13.
PORTABLE FIRE EXTINGUISHERS: (OBC TABLE 906.3(1))
PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED WITH A MINIMUM RATING OF 2-A AND IN QUANTITIES
OF 1 / 11,250 SF OF FLOOR AREA AND LOCATED A MAXIMUM OF 75'-0” TRAVEL DISTANCE.
(ORDINARY/MODERATE HAZARD)
WATER CLOSETS LAVATORIES
MALE
(1/50)
FEMALE
(1/50)
MALE
(1/80)
FEMALE
(1/80)
REQ' D PROV' D REQ' D PROV' D REQ' D PROV' D REQ' D PROV' D
1 4 1 2 1 3 1 2
DRINKING FOUNTAINS
(1/100)
SERVICE SINKS
(1/FLOOR)
REQUIRED PROVIDED REQUIRED PROVIDED
1 1 1 1
GENERAL NOTES
1. THE CONTRACT DOCUMENTS CONSIST OF THIS SET OF DRAWINGS, ADDENDA, CONSTRUCTION
CHANGE DIRECTIVES, CHANGE ORDERS, THE CONTRACT BETWEEN THE OWNER AND CONTRACTOR,
CONDITIONS OF THE CONTRACT AND ANY OTHER INFORMATION WRITTEN AND MUTUALLY AGREED
UPON BETWEEN THE OWNER AND CONTRACTOR.
2. THESE DRAWINGS ARE COMPLEMENTARY AND INTERRELATED; WORK OF ANY INDIVIDUAL TRADE IS
NOT NECESSARILY CONFINED TO SPECIFIC DOCUMENTS, CHAPTERS, OR LOCATIONS.
3. IT IS THE INTENT OF THE CONTRACT DOCUMENTS TO BE DESIGNED IN ACCORDANCE WITH ALL APPLICABLE CODES AND ORDINANCES IN EFFECT AT THE TIME THE PERMIT IS ISSUED. NOTIFY
CONTRACTING OFFICER IMMEDIATELY UPON DISCOVERY OF SUSPECTED DEVIATION.
4. IF DISCREPANCIES OR INCONSISTENCIES IN THE DOCUMENTS ARE DISCOVERED, NOTIFY THE
CONTRACTING OFFICER IMMEDIATELY USING A REQUEST FOR INTERPRETATION FORM AND
PROCEDURE INDICATED IN THE PROJECT MANUAL.
5. CONSTRUCTION TECHNIQUES, PROCEDURES, SEQUENCING, AND SCHEDULING ARE SOLELY THE
RESPONSIBILITY OF THE CONTRACTOR.
6. DO NOT SCALE DRAWINGS; USE DIMENSIONS ONLY. ALL DIMENSIONS MUST BE VERIFIED ON THE
JOB AND THE CONTRACTING OFFICER MUST BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK.
7. COORDINATE LOCATIONS AND/OR ELEVATIONS OF FLOOR DRAINS, REGISTERS, GRILLES, LOUVERS, DUCTS, UNIT HEATERS, PANELS, ETC. WITH THE MECHANICAL, PLUMBING, AND ELECTRICAL
CONTRACTORS AND THE ARCHITECTURAL DRAWINGS.
8. WHERE A DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL LIKE OR SIMILAR
CONDITIONS, EVEN THOUGH NOT SPECIFICALLY MARKED ON THE DRAWINGS.
9. ALL ABBREVIATIONS, MATERIALS AND SYMBOLS IN LEGENDS MAY OR MAY NOT BE USED.
10. FOLLOW THE MANUFACTURER'S INSTRUCTION SPECIFICATIONS FOR PREPARATION,
IMPLEMENTATION, AND CONSTRUCTION OF ALL MATERIALS AND SYSTEMS.
SYMBOLS
A A000
INTERIOR ELEVATION NO.
DWG. REF. NO.
DWG. REF. NO.
DETAIL NO.
WALL / BUILDING SECTION NO.
DWG. REF. NO.
COLUMN LINE
X A000
INSULATION MARK (REFER TO INSULATION SCHEDULE)
ROOM/SPACE NUMBER
PLAN NORTH ARROW
REVISION NUMBER
ARCHITECTURAL WOODWORK MARK (REFER TO ACCESSORY SCHEDULE)
DOOR MARK (REFER TO DOOR SCHEDULE)
N
CODED NOTE (REFER TO CODED NOTES ON EACH SHEET SERIES)09.01
AW-#
D-#
I-#
OFFICE
XXX
WINDOW MARK (REFER TO WINDOW SCHEDULE)W-#
EQUIPMENT MARK (REFER TO EQUIPMENT SCHEDULE)EQ-#
SPECIALTY MARK (REFER TO SPECIALTY SCHEDULE)SP-#
FURNITURE MARK (REFER TO FURNITURE SCHEDULE)F-#
MISCELLANEOUS METAL MARK (REFER TO MISC. METAL SCHEDULE)MM-#
ACCESSORY MARK (REFER TO ACCESSORY SCHEDULE)A-#
MATERIAL LEGEND
EXTERIOR ELEVATION NO.
DWG. REF. NO.
OVERALL FLOOR PLAN GENERAL NOTES
OVERALL FLOOR PLAN CODED NOTES
1. REFER TO PARTITION SCHEDULE FOR INTERIOR PARTITION TYPES.
2. REFER TO ROOM TREATMENT SCHEDULE OF ALL INTERIOR FINISHES.
3. REFER TO SHEET G002 FOR ALL ABBREVIATIONS AND SYMBOLS.
4. REFER TO SPECIALTY SCHEDULE FOR ALL ROOM SIGNAGE.
5. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN
CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO
CONTINUATION OF WORK.
6. ALL DIMENSIONS SHOWN ARE TO FACE OF MASONRY OR FRAMING UNLESS SPECIFICALLY NOTED
OTHERWISE.
7. ALL DIMENSIONS SHOWN LOCATING WINDOWS ARE TO CENTERLINE OF WINDOW OPENING, UNLESS
NOTED OTHERWISE.
8. ALL DIMENSIONS SHOWN LOCATING DOORS ARE TO ONE SIDE OF ROUGH OPENING, UNLESS
NOTED OTHERWISE. ALL DOORS NOT DIMENSIONED ARE LOCATED 4" FROM NEAREST INTERSECTING
PARTITION / WALL.
9. ALL CONCEALED BLOCKING SHALL BE FIRE-RETARDANT TREATED LUMBER.
10. WHERE NEW CONSTRUCTION INFILLS OPENINGS IN EXISTING CONSTRUCTION ALIGN FINISH FACES
OF NEW CONSTRUCTION WITH EXISTING CONSTRUCTION.
DIVISION 00 - PROCUREMENT & CONTRACTING REQUIREMENTS (REFER TO PROJECT MANUAL)
DIVISION 01 - GENERAL REQUIREMENTS (REFER TO PROJECT MANUAL)
DIVISION 02 - EXISTING CONDITIONS (REFER TO DEMOLITION PLANS)
DIVISION 03 - CONCRETE (NOT USED)
DIVISION 04 - MASONRY (NOT USED)
DIVISION 05 - METALS (REFER TO EXTERIOR DETAILS SHEET)
DIVISION 06 - WOOD, PLASTICS, & COMPOSITES (REFER TO EXTERIOR DETAILS SHEET)
DIVISION 07 - THERMAL & MOISTURE PROTECTION (REFER TO EXTERIOR DETAILS SHEET)
DIVISION 08 - OPENINGS (NOT USED)
DIVISION 09 - FINISHES (NOT USED)
DIVISION 10 - SPECIALITIES (NOT USED)
DIVISION 11 - EQUIPMENT (NOT USED)
DIVISION 12 - FURNISHINGS (NOT USED)
DIVISION 13 - SPECIAL CONSTRUCTION
DIVISION 14 - CONVEYING EQUIPMENT (NOT USED)
DIVISION 21 - FIRE SUPPRESSION (REFER TO FIRE PROTECTION SHEETS)
DIVISION 22 - PLUMBING (REFER TO PLUMBING SHEETS)
DIVISION 23 - HVAC (REFER TO HVAC SHEETS)
DIVISION 26 - ELECTRICAL (REFER TO ELECTRICAL SHEETS)
DIVISION 32 - EXTERIOR IMPROVEMENTS (NOT USED)
00.00
HANGAR BAY
MECHANICAL ROOM
STORAGE
OFFICE
OFFICE
TOOL ROOM
BREAK ROOM
TRAINING
UTILITY
MEN
WOMEN
1 2 2.1 3 3.3 4 5 5.1 5.5 5.8 6 7 8 9 X
H
G
F
E
D
C
B
A
DYNOTEC
N
SCALE: 1/8" = 1'-0"
OVERALL FIRST FLOOR PLAN
GENERAL NOTES
1. DESIGN AND CONSTRUCTION SHALL COMPLY WITH THESE GENERAL NOTES, THE SPECIFICATIONS, AND THE 2017 OHIO BUILDING CODE (OBC) WITH 2018 UPDATES BASED ON THE 2015 INTERNATIONAL BUILDING
CODE, ASCE-7-2016, AISC-15TH EDITION, AND ACI 301-16.
2. IF MATERIALS, QUANTITIES, STRENGTHS, OR SIZES INDICATED BY THE DRAWINGS OR SPECIFICATIONS ARE NOT IN AGREEMENTS WITH THESE NOTES, THE BETTER QUALITY AND/OR GREATER QUANTITY, STRENGTH, OR
SIZE INDICATED, SPECIFIED OR NOTED SHALL BE PROVIDED.
3. COORDINATE WITH ALL DRAWINGS FOR PERTINENT INFORMATION RELATED TO STRUCTURAL WORK. ANY CONTRACTOR-PROPOSED CHANGES TO THE STRUCTURAL SYSTEM SHALL BE REDESIGNED BY A REGISTERED PROFESSIONAL ENGINEER HIRED BY THE CONTRACTOR AT NO COST TO THE OWNER. THE PROPOSED CHANGE SHALL THEN BE SUBMITTED TO THE OWNER. SUBMITTAL SHALL BE APPROVED IN WRITING BEFORE BEGINNING
CONSTRUCTION OF ANY PROPOSED CHANGES.
REINFORCED CONCRETE
1. MATERIALS:
a. SPECIFICATIONS: IN GENERAL, COMPLY WITH ACI 301, "SPECIFICATIONS FOR STRUCTURAL
CONCRETE."
b. ALL STRUCTURAL CONCRETE TO HAVE A MINIMUM F'C=4,000 PSI WITH ENTRAINED AIR.
c. ALL DEFORMED REINFORCING BARS: ASTM A615, GRADE 60.
d. WELDED WIRE REINFORCEMENT SHALL CONFORM TO ASTM A1064 DELIVERED IN FLAT SHEETS.
e. ANCHOR BOLTS SHALL CONFORM TO ASTM A36, A449 OR F1554 GR 55 AS NOTED.
f. EMBEDDED PLATES & FRAMES, OF ANCHOR PLATES SHALL CONFORM TO ASTM A36.
2. PROVIDE AT LEAST ONE COPY OF THE ACI FIELD REFERENCE MANUAL, SP-(15), IN THE FIELD OFFICE AT
ALL TIMES.
3. ALL REINFORCING DETAILS SHALL CONFORM TO ACI 315-LATEST EDITION, "DETAILS AND DETAILING OF
CONCRETE REINFORCEMENT," UNLESS DETAILED OTHERWISE ON THE STRUCTURAL DRAWINGS.
4. LAP ALL REINFORCING BARS IN ACCORDANCE WITH TABLE TO THE RIGHT, UNLESS OTHERWISE NOTED
ON THE DRAWINGS.
5. PROVIDE 3/4"X45° CHAMFER ON ALL EXPOSED CORNERS, UNLESS NOTED OTHERWISE.
6. SETTING OF ALL WELD PLATES, ANCHOR BOLTS, SLEEVES, AND INSERTS SHALL BE VERIFIED WITH ALL
AFFECTED PARTIES PRIOR TO PLACING CONCRETE.
7. CONTRACTOR SHALL PROVIDE SPACERS, CHAIRS, BOLSTERS, ETC. NECESSARY TO SUPPORT
REINFORCING STEEL. SUPPORT ITEMS WHICH BEAR ON EXPOSED CONCRETE SURFACES SHALL HAVE ENDS WHICH ARE PLASTIC TIPPED OR STAINLESS STEEL. CONCRETE CUBES SHALL BE USED FOR THE SUPPORT OF
REINFORCING ON GRADE.
8. TYPICAL REINFORCEMENT BAR CLEARANCE:
LOCATION CLEARANCE
BEAMS 2"
INTERIOR WALLS AND SLABS (NOT CAST AGAINST EARTH) 2"
BEAM STIRRUPS 1 12"
CONCRETE CAST AGAINST EARTH 3"
SLABS ON GRADE (BOTTOM REINFORCEMENT) 3"
9. WELDING OF REINFORCING STEEL IS NOT PERMITTED.
10. CALCIUM CHLORIDE SHALL NOT BE PERMITTED NOR SHALL ANY ADMIXTURE CONTAINING CALCIUM CHLORIDE BE PERMITTED THAT RESULTS IN A TOTAL CONCRETE MIX IN WHICH THE PRESENCE OF CHLORIDE
IONS EXCEED 0.15%, EXPRESSED AS A PERCENT BY WEIGHT OF CEMENT.
11. ALL CONCRETE SHALL CONTAIN A WATER REDUCING ADMIXTURE CONFORMING TO ASTM C494, TYPE A, F, OR G.
12. REINFORCEMENT LAP SPLICE, EMBEDMENT LENGTH AND STANDARD HOOKS TABLE IS BASED ON A MINIMUM CONCRETE COMPRESSIVE STRENGTH OF 4000 PSI AND 60000 PSI REINFORCEMENT (WITH NO
EPOXY COATING).
13. ALL LAP SPLICES SHALL BE CLASS B SPLICES.
14. WHEN LAPPING TWO DIFFERENT BAR SIZES, USE THE GREATER OF THE LAP LENGTH OF THE SMALLER
BAR OR THE DEVELOPMENT LENGTH OF THE LARGER BAR.
15. A TOP BAR IS ANY HORIZONTAL BAR WITH MORE THAN 12" OF FRESH CONCRETE PLACED BELOW IT.
16. STAGGER LAPS OF ADJACENT BAR ROWS BY A MINIMUM OF 24" OR THE LAP SPLICE LENGTH, WHICHEVER IS GREATER
CONCRETE MASONRY UNIT
1. DESIGN COMPRESSIVE STRENGTH, FM, OF THE FINISHED ASSEMBLY AND MATERIAL PROPERTIES SHALL BE PER THE TABLE BELOW. 2000 PSI WILL BE REQUIRED UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
2. MORTAR: ASTM C270, TYPE S, HYDRATED.
3. GROUT: ASTM C476 COARSE GROUT. USE OF WATER REDUCERS OR SUPERPLASTICIZERS IS NOT PERMITTED.
4. 4. CONCRETE MASONRY UNITS: ASTM C90, MEDIUM WEIGHT, LINEAR SHRINKAGE SHALL NOT EXCEED 0.065
PERCENT. CONCRETE MASONRY UNITS: ASTM C90, MEDIUM WEIGHT, LINEAR SHRINKAGE
6. VERTICAL REINFORCEMENT SHALL BE #5 BARS EACH FACE WITH MATCHING CAST-IN-PLACE DOWELS AT 24 INCHES C/C UNLESS NOTED OTHERWISE ON THE DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT. THE FIRST TWO CELLS AT END WALLS SHALL BE GROUTED AND REINFORCED EACH WITH #5 BAR. THE FIRST TWO CELLS NEXT TO THE OPENINGS IN MASONRY WALLS SHALL BE GROUTED AND REINFORCED WITH 2 - #5 BAR EXTENDING 2'-0” ABOVE
THE TOP OF THE OPENING.
7. VERTICAL AND HORIZONTAL REINFORCEMENT SHALL BE AS NOTED ON THE DRAWINGS WITH CELLS GROUTED.
8. FOR CONCRETE MASONRY, THE REINFORCING STEEL SHALL BE LAPPED IN ACCORDANCE WITH THE FOLLOWING:
#4 -26 INCHES, #5 -32 INCHES, #6 -56 INCHES.
9. MASONRY WALLS SHALL HAVE GALVANIZED HORIZONTAL REINFORCING- TRUSS TYPE, #9 GAUGE SIDE AND
CROSS RODS, SPACED 8" O.C.
10. PROVIDE CONCRETE LINTELS OVER OPENINGS IN MASONRY WALLS UNLESS NOTED OTHERWISE ON DRAWINGS.
11. HORIZONTAL REINFORCEMENT SHALL BE CONNECTED TO EXISTING WALLS AT EACH END OF LINTEL BEAM
AND BOND BEAMS.
STRUCTURAL STEEL
1. MATERIALS (UNLESS OTHERWISE NOTED ON DWGS):
a. HOT ROLLED STRUCTURAL STEEL:
W-SHAPES AND WT-SHAPES…………ASTM A992 GRADE 50 (50 KSI)
CHANNELS……………………………………ASTM A572 GRADE 50 (50 KSI)
HOLLOW STRUCTURAL SECTIONS
SECTIONS (HSS)………………………………….… A501 GRADE B, (50 KSI)
ANGLES, PLATES AND BARS………………ASTM A36
b. HIGH STRENGTH BOLTS: ASTM A325 OR A490.
c. ELECTRODES: SERIES E-70XX
d. EXPANSION BOLTS: HILTI "KWK BOLTS 3"
e. ADHESIVE ANCHORS: HILTI "HIT-HY 150 MAX-SD ADHESIVE"
2. SPECIFICATIONS: WELDING PERSONNEL AND PROCEDURES ARE TO BE QUALIFIED PER AWS D1.1 UNLESS SPECIFICALLY SHOWN OTHERWISE. DESIGN, FABRICATION AND ERECTION ARE TO BE GOVERNED BY THE LATEST
REVISIONS OF:
a. AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
b. AISC CODE OF STANDARD PRACTICE.
c. AWS STRUCTURAL WELDING CODE.
d. SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS.
3. CONNECTIONS:
a. USE ¾" DIAMETER HIGH STRENGTH BOLTS (A325N), EXCEPT AS NOTED, IN BEARING TYPE CONNECTION.
b. ALL BOLTED CONNECTIONS FOR THE COLUMNS, BEAMS, BRACES AND PLATES THAT ARE A PART OF THE
STRUCTURAL LATERAL LOAD CARRYING SYSTEM ARE TO BE "PRETENSIONED" AND SHALL BE TIGHTENED TO
THE "PRETENSIONED" CRITERIA.
c. ORDINARY BEARING CONNECTIONS THAT ARE NOT "PRETENSIONED" MAY BE TIGHTENED USING THE
"TURN-OF-NUT" METHOD.
d. FIELD CONNECTIONS ARE TO BE BOLTED UNLESS OTHERWISE SPECIFIED; SHOP CONNECTIONS ARE TO BE WELDED OR BOLTED. CONNECTIONS ARE TO BE DESIGNED BY THE FABRICATOR TO DEVELOP FULL
STRENGTH OF MEMBER.
5. COARSE GROUT FOR REINFORCED MASONRY CONSTRUCTION SHALL CONFORM TO ASTM C-476 WITH A
MAXIMUM AGGREGATE SIZE OF 3/8” AND A MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI.
5. MISCELLANEOUS:
a. NO HOLES OTHER THAN THOSE SPECIFICALLY DETAILED SHALL BE ALLOWED THROUGH
STRUCTURAL STEEL MEMBERS. NO CUTTING OR BURNING OF STRUCTURAL STEEL IS
PERMITTED WITHOUT THE APPROVAL OF THE ENGINEER.
b. PROVIDE NON-METALLIC, NON-SHRINK GROUT UNDER ALL COLUMN BASE PLATES.
c. PROVIDE PLATE WASHERS AS NOTED ON DRAWINGS FOR ALL ANCHOR RODS AND PROVIDE
HEAVY WASHERS AT ALL CONNECTIONS THAT HAVE OVERSIZED OR SLOTTED HOLES.
d. FINISH ENDS OF ALL COLUMNS, STIFFENERS AND ALL OTHER MEMBERS IN DIRECT BEARING.
COLUMN BASES SHALL BE MILLED FOR ALL BEARING SURFACES INCLUDING AT THE BASE
PLATE CONNECTION, COLUMN BASE PLATE 2" OR LESS IN THICKNESS SHALL BE USED
WITHOUT MILLING. COLUMN BASE PLATES GREATER THAN 2" SHALL BE MILLED FOR ALL
BEARING SURFACES.
e. AFTER ERECTION, CONTRACTOR SHALL "TOUCH UP" WITH PAINT ALL ABRADED AREAS.
f. VERIFY THE EXACT SIZE AND LOCATION OF ALL OPENING AND EXISTING STRUCTURES PRIOR TO
FABRICATION OF STEEL FRAMING MEMBERS.
g. ALL STEEL BEAMS SHALL BE FABRICATED WITH THE NATURAL CAMBER (WITHIN THE MILL
TOLERANCE) LOCATED ABOVE THE HORIZONTAL CENTERLINE BETWEEN THE END CONNECTIONS.
REINFORCEMENT LAP SPLICE, EMBEDMENT LENGTH AND STANDARD HOOKS
BAR SIZE
MIN LAP
LENGTHS FOR
MIN EMBEDMENT
LENGTHS MIN STD. HOOKS
SLABS AND WALLS** FOR SLABS AND WALLS
** WITH STD
HOOKS
90° 135°
CLASS B
A OR G A OR G H
TOP*** OTHERS TOP*** OTHERS
#3 16 16 12 12 5 6 4 2.5
#4 20 16 15 12 7 8 4.5 3
#5 25 19 19 15 9 10 5.5 3.75
#6 29 23 23 18 10 12 8 4.5
#7 43 33 33 25 12 14 9 5.25
#8 49 37 37 29 14 16 10.5 6
#9 60 46 46 36 15 19 - -
#10 74 57 57 44 17 22 - -
#11 89 69 68 53 19 24 - -
LAP SPLICE AND EMBEDMENT LENGTH TABLE FOR CAST-IN-PLACE CONCRETE
STRAIGHT BAR
EMBEDMENT
LENGTH
STRAIGHT
90° HOOK
135° HOOK
EMBEDMENT
LENGTH WITH
STD HOOK
HOOK
H O
O K
A O
R G
A OR
G
H
LAP SPLICES SHALL BE CLASS B SPLICES.
1) THE MINIMUM LAP LENGTH FOR SLABS, WALLS AND STRAIGHT EMBEDMENTS ARE BASED ON
A 6 INCH BAR SPACING AND A 2 INCH BAR COVER. IF THE LAP CONDITION DOES NOT CONFIRM
TO THESE REQUIREMENTS, THEN USE BEAM LAP LENGTHS, OR COMPLY WITH LAP
REQUIREMENTS
OF ACI 318 WITH APPROVAL BY CONTRACTING OFFICER.
2) TOP BARS ARE REFINED AS ALL HORIZONTAL BARS WITH 12" OR MORE FRESH CONCRETE
BENEATH. WHERE SPLICES ARE REQUIRED BETWEEN BARS OF DIFFERENT SIZES, THE LAP
LENGTH SHALL BE NO LESS THAN THE EMBEDMENT LENGTH OF THE LARGER BAR OR THE LAP
LENGTH OF THE SMALLER BAR, WHICHEVER IS GREATER.
DESIGN COMPRESSIVE
STRENGTH
f'm (psi)
2,000
UNIT STRENGTH
(psi)
2,000
GROUT STRENGTH
(psi)
MIN. (MAX.)
2,000
MORTAR
PROPERTIES
TYPE S
e. FULL PENETRATION FIELD WELDS IN MATERIALS OVER 5/8" THICK SHALL BE SUBJECTED TO
NON-DESTRUCTIVE TESTING BY AN INDEPENDENT LABORATORY.
f. WELDING ELECTRODES SHALL BE E-70XX OR BETTER, FOR WELDING SYMBOLS WITH NO
LENGTH DIMENSION GIVEN, THE WELDING SHALL BE CONTINUOUS BETWEEN ABRUPT
CHANGES IN DIRECTION, WELDS NOT OTHERWISE NOTED SHALL BE 14" SIZE.
g. ALL CONNECTIONS IN THE CONCOURSE AREA SHALL BE GROUND FLUSH TO SURROUNDING
MATERIAL AND ABRASIVE BUFFED.
h. ALL BEAM CONNECTIONS NOT DETAILED ON THE DRAWINGS SHALL BE DETAILED BY THE
CONTRACTOR, USING A MINIMUM OF (2) A325 BOLTS.
1. NON-COMPOSITE BEAMS SHALL BE DESIGNED TO DEVELOP 55% OF THE TOTAL
LOAD CAPACITY DERIVED FROM THE MAXIMUM TOTAL UNIFORM LOAD TABLES, PART 3,
THIRTEENTH EDITION OF AISC STEEL CONSTRUCTION MANUAL, UNLESS THE REACTION "R"
IS SHOWN ON THE DRAWINGS.
2. MOMENT CONNECTIONS INDICATED ON THE DRAWINGS SHALL BE DESIGNED FOR THE
MOMENTS NOTED. IF NO DESIGN MOMENTS ARE INDICATED, THEN THE FULL CAPACITY
OF THE SECTION SHALL BE DEVELOPED.
4. PAINT:
a. ALL STRUCTURAL STEEL AND MISCELLANEOUS STEEL SHALL BE SHOP PAINTED PER PROJECT
PAINTING SPECIFICATIONS, 09900.
N
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN
EQ-
2 2.1 3 3.1 4 5 5.1 5.8 6 7 8 9 10
H
F.4
F.1
F
E
D
C
B
A
DYNOTEC
PROP 4'-0" x 6'-0" EQUIPMENT PAD
PROP. 4'-0" CATWALK
PROP. STAIRS
G
28'-11"± 14'-3"± 5'-0"± 5'-0"± 17'-6"± 21'-4"± 11'-8"± 14'-0"± 11'-8"± 21'-4"± 21'-0"± 20'-9"±
'-1
'-4
'-4
'-4
'-4
'6
'-0
'-3
28'-11"±
MEZZANINE
AREA
S103
S102
S102
'-1
10'-3 5/8"
12'-3" 12'-4"
'-8
S103
S103
MECHANICAL
ROOM
STRUCTURAL DEMO PLAN1
S102
5.1 5.8 6
H
G
FOUNDATION PLAN2
S102
5.1 5.8 6
H
G
'-3
11'-8" 14'-0" 11'-8"
'-3
" MEZZANINE
AREA
EXIST. W8 EXIST. W8EXIST. W8 EXIST. W12EXIST. W8
EX
IS
T.
W
EX
IS
T.
W x5
EXIST. W12 COLUMN EXIST. W12 COLUMN
EX
IS
T.
R
O O
F
TR
U S S
ES
EX
IS
T.
R
O O
F
TR
U S S
ES
EX
IS
T.
W
EX
IS
T.
W x5
LEGEND:
EXISTING STEEL MEMBERS TO BE REMOVED
11'-8" 14'-0" 11'-8"
EXIST. W8 EXIST. W18EXIST. W8 EXIST. W12EXIST. W18
EX
IS
T.
W
EX
IS
T.
W x5
EXIST. W12 COLUMN EXIST. W12 COLUMN
EX
IS
T.
R
O O
F
TR
U S S
ES
EX
IS
T.
R
O O
F
TR
U S S
ES
EX
IS
T.
W
EX
IS
T.
W x5
'-4
/8
8'-4" 14'-0" 11'-8"
'-1
/8
HSS6x6x12" (TYP.)
S402
TYP
S402
NOTE: NEW LOCATION FOR
NOSE CONE
EX. 9" REINFORCED
CONCRETE SLAB
EX
IS
T.
W
EX
IS
T.
W
EX
IS
T.
W
EX
IS
T.
W
EXIST. W12
EXIST. W12
EXIST. W12
EXIST. W12
EXIST. W12
EXIST. W12
EXIST. W24EXIST. W24 EXIST. W24
3'-4"
SCALE: 38" = 1'-0"
SCALE: 38" = 1'-0"
NOTE: REMOVE THE EXISTING MEZZANINE SLAB
MECHANICAL ROOM3MEZZANINE AREA1
S103
5.1 5.8 6 43.1
F.4
F.1
H
G
MEZZANINE AREA FRAMING PLAN2
5.1 5.8 6
H
G
F
29'-7 3/4"4'-0"
'-0
1"x4" GRATING
REMOVABLE RAILING 11
2" SCH 40 STEEL RAIL
'-9
'-0
'-8
4'-0" 10'-4"±
EQUIPMENT ISOLATION PAD
'-3
11'-8" 14'-0" 11'-8"
C12x20.7 C12x20.7 C12x20.7
C12x20.7 C12x20.7
C x2
.7
C x2
.7
EX
IS
T.
W
HSS 6x6x12" (TYP.)
EXIST. W8 EXIST. W8EXIST. W8 EXIST. W12EXIST. W8
EX
IS
T.
W x5
EXIST. W10 COLUMN (TYP. U.N.O.)
EXIST. W12 COLUMN EXIST. W12 COLUMN
EX
IS
T.
R
O O
F
TR
U S S
ES
EX
IS
T.
R
O O
F
TR
U S S
ES
C12x20.7
W x9
'-0
DOWN
D O
W N
11'-11" GARAGE DOOR OPENING
A
S201
S401
S401
MECHANICAL
ROOM
MEZZANINE
AREA
MEZZANINE
AREA
'-3
2'-0"±
S402
S302
S301
S302
C x2
.7
C12x20.7
S103
S103
B S201
S401
S401
S401
TYP
W x9
W x9
W x9
W x9
W x9
W x9
W x9
W 6x9
W 6x9
3 TYP
TYP
S401
S401
S401
TYP
TYP
TYP
S401
TYP
NOTE:
1) COORDINATE WITH EQUIPMENT SUPPLIER PRIOR TO PLACING
EQUIPMENT PAD, COORDINATE PIPE, OPENINGS WITH OTHER DISCIPLINE
DRAWINGS.
2) ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL
DRAWINGS SHALL BE VERIFIED BY THE CONTRACTOR AND SHALL
CONFORM TO THOSE SHOWN ON ALL OTHER DRAWINGS.
EX
IS
T.
W
W 6x9
W 6x9
W 6x9
W x9
W x9
COORDINATE THE EXACT
POSITIONS OF THE
TRANSFORMERS WITH MEP.
COORDINATE THE EXACT
POSOTION OF THE
TRANSFORMERS WITH MEP.
S402
SCALE: 38" = 1'-0"
543.132.12
H
G
F.4
F.1
F
14'-3"± 6'-6"± 3'-6"± 17'-6"± 21'-4"±
'-0
'-3
'-6
EXIST. W14x22 EXIST. W14x22 EXIST. W18x35
EXIST. W18x35
EX
IS
T.
W x4
EX
IS
T.
W x4
EX
IS
T.
W x6
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
'-8
1 2
'-1
1 2
'-8
1 2
'-0
'-6
'-0
'-0
'-6
'-6
'-8
EX
IS
T.
K1
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
EX
IS
T.
K1
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
EX
IS
T.
K1
'-8
/2
EX
IS
T.
W x6
S401
HVAC ROOF TOP UNIT
(SEE MEP FOR DETAILS)
2'-7 1/4"
'-6
/4
5.1 5.5 5.8 6 7 8 9
11'-8" 7'-0" 7'-0" 11'-8" 21'-4" 21'-0" 20'-9"
S401
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
EXIST. W8x24
EXIST. 16K2
EXIST. 20K4
EXIST. 20K3
EXIST. 20K3
EXIST. 20K3
EXIST. 18K3
EXIST. 16K2
ROOF FRAMING PLAN1
S104
EX
IS
T.
K1
EX
IS
T.
K1
EXIST. W14x22 EXIST. W14x22 EXIST. W18x35
EX
IS
T.
W x4
EX
IS
T.
W x6
EX
IS
T.
W x6
EX
IS
T.
W x4
HVAC ROOF TOP UNIT
(SEE MEP FOR DETAILS)
'-8
/2
8'-10"
SCALE: 3/16" = 1'-0"
SECTIONA
S201
ELEV. 1160'-5"
ELEV. 1153'-9"
ELEV. 1145'-9"±
H
EXIST. W12 COLUMN BEYOND
PROP. 11
2" SCH 40
STEEL PIPE RAILING
EXTERIOR
RAIL MOUNT
1"x4" GRATING
W 6X9 (TYP.)
C12x20 (TYP.)
EXIST. W14
EXIST. C12x20.7
EXIST. CMU WALL
EXIST. C12x20.7
EXIST. BRICK FACING
EXIST. SAG RODS
WALL PANELS (SEE
ARCH. DWGS.)
EXIST. HANGAR FLOOR
'-9
'-8 " C
LE
A R A N C
E
4'-0"
SECTIONB
S201
ELEV. 1145'-9"±
EXIST. W12 COLUMN BEYOND
EXTERIOR
RAIL MOUNT
1"x4" GRATINGEXIST. W14
EXIST. CMU WALL
EXIST. HANGAR FLOOR
'-9
'-8 " C
LE
A R A N C
E
4'-0"
EXIST. TRUSS
PROP. 11
2" SCH 40
STEEL PIPE RAILING
EXTEND GRATING TO WALL
BETWEEN COLUMNS
EXTEND GRATING TO WALL
BETWEEN COLUMNS
TRANSFORMER MOUNTING
TRAPEZE (SEE MEP DWGS.)
TRANSFORMER MOUNTING
TRAPEZE (SEE MEP DWGS.)
'-0
C
LE
A R A N C
E A T
TR
A N S
FO
R M
ER
L
O C
A
TI
O N S
'-0
C
LE
A R A N C
E A T
TR
A N S
FO
R M
ER
L
O C
A
TI
O N S
4" KICK PLATE 4" KICK PLATE
NOTES:
1. SEE SHEETSS401 THROUGH S402 FOR BEAM AND COLUMN CONNECTION
DETAILS.
SCALE:
DETAIL
3" = 1'-0"
S201
ROD FOR
TRANSFORMER
SUPPORT BY MEP.
W 6X9
BEAM
4" THK. STIFFENER PLATE
NOTE: PROVIDE STIFFENER
PLATES WHEREVER, THE
TRANSFORMER SUPPORTS ARE
PRESENT.
ELEV. TRUSS
VARIES
COORDINATE WITH MEP FOR
EXACT POSITION OF THE
TRANSFORMERS (TYP.)
W 6X9 (TYP.)
PROVIDE STIFFENER
PLATES AT ALL
TRANSFORMER
LOCATIONS. SEE
DETAIL 1, TYP.
SCALE: 1" = 1'-0" SCALE: 1" = 1'-0"
NOTES:
1. SEE SHEETS S401 THROUGH S402 FOR STAIR AND STAIR CONNECTION DETAILS.
2. SEE SHEETSS401 THROUGH S402 FOR BEAM AND COLUMN CONNECTION
DETAILS.
SCALE:
NORTH ELEVATION
3/4" = 1'-0"
S301
TOP OF CATWALK ELEV. 1160'-5"
TOP OF GARAGE DOOR ELEV. 1153'-9"
EXIST. FLOOR ELEV. 1145'-9"±
TOP OF MANDOOR ELEV. 1152'-9"
TOP OF LANDING ELEV. 1155'-6"
9 1/2"± CLEARANCE (TYP.)
'-6
/8
C
LE
A R A N C
E
EXIST. GARAGE DOOR
EXIST.
MANDOOR
TYP5
S402
REMOVABLE RAILING SECTIONS
TYP1
S401
2" SCH 40 STEEL PIPE RAILING
C12x20.7
C12x20.7
C12x20.7
W6X9 (TYP.)
STAIR TREAD
(TYP.)
S401
1"x4" GRATING
1"x4" GRATING
2 EQ. SPA. @ 4'-0" MAX. 5" 4'-0" 5" 4'-0" 5" 2 EQ. SPA. @ 4'-0" MAX. 3 EQ. SPA. @ 4'-0" MAX. 3'-3"
HSS6x6x12" (TYP.)
S402
TYP
S402
4'-8 1/8" 4'-8" 4'-8"
COORDINATE WITH MEP FOR
EXACT POSITION OF THE
TRANSFORMERS (TYP.)
SCALE:
WEST ELEVATION
3/4" = 1'-0"
S302
NOTES:
1. SEE SHEETS S401 THROUGH S402 FOR STAIR AND STAIR CONNECTION DETAILS.
5/8'' DIA CONC ANCHORS, 6'' FROM
EACH END MAX 12'' OC
SELF-TAPPING TEK SCREW, 1''
LONG IN 1/4'' DIA HOLE AT 6''
OC
10 GAGE STL PLATE
3/16'' STL BENT PL
/4 M
A X.
/4 M
A X.
14 GAGE STL PLATE
3/16'' STL BENT PL
5/8'' DIA CONC ANCHORS, 6'' FROM
EACH END MAX 12'' OC
SELF-TAPPING TEK SCREW, 1''
LONG IN 1/4'' DIA HOLE AT 6''
OC
/8
M
A X.
1/2" = 1'-0"
PARTIAL RISER
PLATE3
1/2" = 1'-0"
FULL RISER PLATE4
S302
S302
SCALE:
EAST ELEVATION
3/4" = 1'-0"
S302
S402
S302
S302
S402
TYP2
S401
TOP OF CATWALK ELEV. 1160'-5"
EXIST. FLOOR ELEV. 1145'-9"± EXIST. FLOOR ELEV. 1145'-9"±
TOP OF LANDING ELEV. 1155'-6"
H
2" SCH 40 STEEL PIPE RAILING
2" SCH 40 STEEL PIPE RAILING
1"x4" GRATING
1"x4" GRATING
TRANSFORMER AND MOUNTING
TRAPEZE, APPROX. LOCATION
(SEE MEP DWGS.) (TYP.)
TYP5
S402
TYP5
S402HSS6x6x12" (TYP.)
S402
HSS6x6x12" (TYP.)
S402
C 12x20.7
C12x20.7
C12x20.7
HSS 6X6X1
2" (TYP.)
W 6X9(TYP.)
TYP2
S401
STAIR TREAD
(TYP.)
3 SPA. @ 4'-0" MAX.
2'-0" 5" 8'-2" 2'-6"
S402
S402
EX. FLOOR
EX. FLOOR
3/16"
3/16"
4"
8" STL BOT PLATE
W/ 11/16x2 12" SLOTTED HOLES
NON-SHRINK
GROUT
3/16"
3/16"
3/16"
4"
2 REMOVABLE RAIL SECTIONS
2''
EQ-
2''
NOTES:
1. PROVIDE 4'' STIFFENED KICK PLATE ATTACHED TO REMOVABLE RAILING.
2. FABRICATE REMOVABLE RAILING IN MAXIMUM 4'-0'' SECTION WITH 2 POSTS EACH SECTION.
3. THE GUARDRAILS SHALL NOT BE LESS THAN 42 INCHES IN HEIGHT WHEN MEASURED VERTICALLY.
1.
2.
3.
4.
5.
GALVANIZED STEEL GRATING TREADS UNLESS
OTHERWISE NOTED ON PLANS.
HOT DIP GALVANIZE ALL MEMBERS AND FASTENERS
AFTER FABRICATION.
FIELD VERIFY DIMENSIONS AND ELEVATIONS
PRIOR TO FABRICATION.
PROVIDE PROTECTION FOR DISSIMILAR METALS
AS SPECIFIED.
AMERICAN STANDARD C12x20.7 STRINGERS TYPICAL
EXCEPT WHERE OTHERWISE NOTED ON PLANS.
NOTES:
RAILING - REMOVABLE TWO RAIL - STEEL1
S401
3'-0" MIN
2"
3'-0" MIN
" T
O E
PL
A
TE
1/2" GAP IN TOE PLATE (TYP.)2 SIDES
TYP
HSS COL. & C 12 BEAM
CONNECTION DETAIL-TYP.
W 12 COL.,C 12 BEAMS & W 8 BEAM CONNECTION
DETAIL-TYP.
C 12
S401
S401
2" TYP. 1 34" MIN.
1 4
" M
IN
4" DIA. BOLTS WITH 3"
C/C SPACING
HSS 6X6X1
2"
COLUMN
4" THK. CAP
PLATE
4" THK. PLATE
TYP.
4"
HSS COL. & W 6 BEAM
CONNECTION DETAIL-TYP.
S401
2" TYP. 1 34" MIN.
W 6
HSS 6X6X1
2"
COLUMN
4" THK. CAP
PLATE
1 4
" M
IN
2 NO. OF 34"
DIA. BOLTS
TYP.
4"
4" THK.
PLATE
W 10 COL FLANGE. & C 12 BEAM
CONNECTION DETAIL-TYP.
S401
2" TYP. 1 34" MIN.
1 4
" M
IN
C 12
EX. WF 10
COLUMN
4" DIA. BOLTS WITH 3"
C/C SPACING
TYP.
4"
CL
CL
CL
CL
C 12 & W 6
CONNECTION-TYP.
S401
W 6
2" TYP.
1 34" MIN.
1 4
" M
IN
2 NO. OF 34" DIA.
BOLTS
C 12
CHANNEL
4" THK. PALTE
TYP.
4"W 6
EX. W 12 COL.
3 NO. OF 34" DIA. BOLTS WITH 3"
C/C SPACING
C12 C12
L 4X3X1 4"
TYP.
1/4"
1 34" MIN.
1 2 " T
YP
W 12 COL.,C 12 BEAMS
CONNECTION DETAIL-TYP.
S401
EX. W 12 COL.
3 NO. OF 34" DIA. BOLTS WITH 3"
C/C SPACING
1 34" MIN.
W 12 COL.,C 12 & W 6 BEAMS
CONNECTION DETAIL-TYP.
S401
CL
W 6
L 6X4X3 8"
4" DIA. BOLTS
EX. W 12 COL.
1 2 " T
YP
1 34" MIN.
C 12
HVAC ROOF PENETRATION
SUPPORT DETAIL - PLAN
S401
A S
DIM A
VARIES
(SEE PLAN)
D
IM
B
DIM C
EX. 12K1 STEEL
JOIST
L 4X3X1/4
EX. WF 21X62
BEAM
EX. WF 21X62
BEAM
CL BEAM CL BEAM
EX. 12K1 STEEL
JOIST
OPENING DIM A DIM B DIM C
2 3'-9"
SECTIONA
S401
CL JOIST CL JOIST
EX. 12K1 JOIST
3'-8 12"
L 4X3X1/4
NOTE: SEE THE TABLE FOR THE OPENING DIMENSIONS.
4" THK. PLATE
(TYP.)
4" DIA. BOLT
(TYP.)
TYP.1
4"
6'-11"
7'-3"
5'-3 18"
5'-2" 11'-1 78"
4" THK. PALTE
C 12
4" THK. PALTE
EX. W 14
BEAM
TYP.
4"
1 4
" M
IN
4"
NOT TO SCALE
SCALE: 1 1/2" = 1'-0"
SCALE: 1 1/2" = 1'-0"
SCALE: 1 1/2" = 1'-0"
SCALE: 3" = 1'-0" SCALE: 3" = 1'-0"
SCALE: 1" = 1'-0"
SCALE: 1 1/2" = 1'-0"
SCALE: 3" = 1'-0"
SCALE: 3" = 1'-0"
1'-0 '' MIN UNLESS OTHERWISE
NOTED ON PLANS
STRINGER
RISER PLATE SEE NOTE 8
SEE NOTE 8
GRATING TREAD
3'-0'' UNLESS OTHERWISE
NOTED ON PLANS
1/2''
CLR FROM WALL
UNO
COPE 3/16'' BENT PL TO CLEAR GROUT AND
STRINGER MOUNTING PL
3/16'' STL BENT PL
VARIES W/ STAIR
SLOPE
/4
M A X
2'' 1 1/2''
STAIRWAY
WIDTH
TREAD BEARING BARS
STEEL
TREAD
2'-3'' OR LESS
2'-9'' OR LESS
3/4'' x 3/16'' 1'' x 3/16'' 2
EQUIPMENT PAD DETAIL7
6" BEYOND EDGES OF EQUIPMENT
#4 @ 18" EW (MIN. 2 EW)
6" UNLESS SHOWN
OTHERWISE
ROUGHEN SURFACE TO 14" FULL AMPLITUDE
#4 ADHESIVE DOWELS @ 18"
O.C. AROUND PERIMETER OF
BASE WITH 4" EMBEDMENT
STAIR TREADS1
S402
PLAN - BOTTOM CLOSURE
PLATE
S402
S402
STEEL COLUMN, SEE PLAN FOR
SIZE AND LOCATION
EXIST. CONCRETE SLAB
(HANGAR FLOOR)
BASE PLATE AND BOLTS
EPOXIED INTO EXIST. SLAB
2" NON-SHRINK GROUT
COLUMN BASEPLATE8
S402
1'-0"
'-0
1 1/2"
1 1/2"
HSS 6X6X1
2"
4" THK. BASE
PLATE
WELD HSS TO
PLATE, TYP.5
16"
COLUMN BASEPLATE - PLAN9
S402
(4) 58" DIA.
ADHESIVE ANCHOR BOLTS
NOTE 8:
4"
31 2
" M
IN
8" MIN.
PLAN
RAIL POST, FIELD CUT TO FIT
TOP MOUNTED POST
BASE AS SPECIFIED
(4) SST CONC
ANCHORS AS
SPECIFIED
THE BASEPLATE SHALL SIT
SOLIDLY ON CONCRETE. THE
USE OF SHIMS, WEDGES,
GROUT, ETC. FOR RAILING POST
ALIGNMENT OR ANY OTHER
REASON WILL NOT BE
PERMITTED
ELEVATION
PLAN
ELEVATION
BOLT HEADS AT
STAIRWAY OR
PLATFORM SIDE
STEEL RAILING
POST
BEAM
SIDE MOUNTED
POST BRACKET
AS SPECIFIED
SST BOLTS,
AS SPECIFIED
STAIR STRINGER
PLAN
ELEVATION
STEEL RAILING POST
TOP MOUNTED
POST BRACKET AS
SPECIFIED
SST BOLTS,
AS SPECIFIED
STAIR STRINGER
RAIL MOUNTING PLATE (FLOOR)4
S402
RAIL MOUNT BEAM OR STRINGER)5
S402
RAIL MOUNT (STAIRS)3
S402
9"
8" ADHESIVE ANCHOR BOLTS
(EMBED 13" TYP.)
W 6 - W6 BEAM CONNECTION6
S402
EX. CONCRETE FLOOR
EX. REINF. CONCRETE FLOOR
W 6x9
W 6x9
1 34" MIN.
1 4
" M
IN
2 NO. OF 34" DIA.
BOLTS
4" THK. PALTE
TYP.
4"
SCALE: 34" = 1'-0"
SCALE: 34" = 1'-0"
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
SCALE: 3" = 1'-0"
SCALE: 1 1/2" = 1'-0"
NOT TO SCALE
NOT TO SCALE
ROOF PLAN GENERAL NOTES
ROOF PLAN CODED NOTES
1. REFER TO PARTITION SCHEDULE FOR INTERIOR PARTITION TYPES.
2. REFER TO ROOM TREATMENT SCHEDULE OF ALL INTERIOR FINISHES.
3. REFER TO SHEET G002 FOR ALL ABBREVIATIONS AND SYMBOLS.
4. REFER TO SPECIALTY SCHEDULE FOR ALL ROOM SIGNAGE.
5. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN
CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE CONTRACTING OFFICER
PRIOR TO CONTINUATION OF WORK.
6. ALL DIMENSIONS SHOWN ARE TO FACE OF MASONRY OR FRAMING UNLESS SPECIFICALLY NOTED
OTHERWISE.
7. ALL DIMENSIONS SHOWN LOCATING WINDOWS ARE TO CENTERLINE OF WINDOW OPENING, UNLESS
NOTED OTHERWISE.
8. ALL DIMENSIONS SHOWN LOCATING DOORS ARE TO ONE SIDE OF ROUGH OPENING, UNLESS
NOTED OTHERWISE. ALL DOORS NOT DIMENSIONED ARE LOCATED 4" FROM NEAREST INTERSECTING
PARTITION / WALL.
9. ALL CONCEALED BLOCKING SHALL BE FIRE-RETARDANT TREATED LUMBER.
10. WHERE NEW CONSTRUCTION INFILLS OPENINGS IN EXISTING CONSTRUCTION ALIGN FINISH FACES
OF NEW CONSTRUCTION WITH EXISTING CONSTRUCTION.
DIVISION 00 - PROCUREMENT & CONTRACTING REQUIREMENTS (REFER TO PROJECT MANUAL)
DIVISION 01 - GENERAL REQUIREMENTS (REFER TO PROJECT MANUAL)
DIVISION 02 - EXISTING CONDITIONS (REFER TO DEMOLITION PLANS)
02.01 - EXISTING METAL STANDING SEAM ROOF SYSTEM TO REMAIN, U.N.O.
DIVISION 03 - CONCRETE (NOT USED)
DIVISION 04 - MASONRY (NOT USED)
DIVISION 05 - METALS (REFER TO EXTERIOR DETAILS SHEET)
DIVISION 06 - WOOD, PLASTICS, & COMPOSITES (REFER TO EXTERIOR DETAILS SHEET)
DIVISION 07 - THERMAL & MOISTURE PROTECTION (REFER TO EXTERIOR DETAILS SHEET)
07.01 - NEW ROOF CRICKET SLOPE 1/8": 12" MINIMUM.
DIVISION 08 - OPENINGS (NOT USED)
DIVISION 09 - FINISHES (NOT USED)
DIVISION 10 - SPECIALITIES (NOT USED)
DIVISION 11 - EQUIPMENT (NOT USED)
DIVISION 12 - FURNISHINGS (NOT USED)
DIVISION 13 - SPECIAL CONSTRUCTION (NOT USED)
DIVISION 14 - CONVEYING EQUIPMENT (NOT USED)
DIVISION 21 - FIRE SUPPRESSION (REFER TO FIRE PROTECTION SHEETS)
DIVISION 22 - PLUMBING (REFER TO PLUMBING SHEETS)
DIVISION 23 - HVAC (REFER TO HVAC SHEETS)
23.01 - NEW ROOF TOP UNITS (REFER TO STRUCTURAL & MECHANICAL SHEETS)
DIVISION 26 - ELECTRICAL (REFER TO ELECTRICAL SHEETS)
DIVISION 32 - EXTERIOR IMPROVEMENTS (NOT USED)
00.00
S
LO
PE
:1
S
LO
PE
:1
S
LO
PE
:1
S
LO
PE
:1
S
LO
PE
:1
S
LO
PE
23.01
23.01
A
A
A
A
02.01
H
IG
H R
O O
F
IN
TE
R M
ED
IA
TE
R
O O
F
H
IG
H R
O O
F
H
IG
H R
O O
F
LO
W
R O
O F
LO
W
R O
O F
02.01 02.0102.0107.01
07.01
DYNOTEC
N
SCALE: 1/8" = 1'-0"
OVERALL ROOF PLAN
tpaulin Text Box tpaulin Line
EXTERIOR DETAILS GENERAL NOTES
EXTERIOR DETAILS CODED NOTES
DIVISION 00 - PROCUREMENT & CONTRACTING REQUIREMENTS (NOT USED)
DIVISION 01 - GENERAL REQUIREMENTS (NOT USED)
DIVISION 02 - EXISTING CONDITIONS (REFER TO DEMOLITION SHEETS)
02.01 - EXISTING CONSTRUCTION TO REMAIN UNDISTURBED, U.N.O.
02.02 - EXISTING ROOF DECK TO REMAIN UNDISTURBED, U.N.O.
02.03 - EXISTING INSULATION TO REMAIN UNDISTURBED, U.N.O.
02.04 - EXISTING STANDING SEAM METAL ROOF REMAIN UNDISTURBED, U.N.O.
DIVISION 03 - CONCRETE (NOT USED)
DIVISION 04 - MASONRY (NOT USED)
DIVISION 05 - METALS
05.01 - BEARING PLATE.
05.02 - ROOF CURB.
05.03 - BASERAIL.
05.04 - FLOOR PANEL.
DIVISION 06 - WOOD, PLASTICS, & COMPOSITES
06.01 - 2x PRESERVATIVE TREATED WOOD BLOCKING.
06.02 - CANT STRIP.
DIVISION 07 - THERMAL & MOISTURE PROTECTION
07.01 - PREFINISHED FLASHING.
07.02 - PREFINISHED METAL COUNTER - FLASHING.
07.03 - ICE SHIELD.
07.04 - RIGID INSULATION (SEE INSULATION SCHEDULE).
07.05 - GASKET.
DIVISION 08 - OPENINGS (NOT USED)
DIVISION 09 - FINISHES (NOT USED)
DIVISION 10 - SPECIALITIES (NOT USED)
DIVISION 11 - EQUIPMENT (NOT USED)
DIVISION 12 - FURNISHINGS (NOT USED)
DIVISION 13 - SPECIAL CONSTRUCTION (NOT USED)
DIVISION 14 - CONVEYING EQUIPMENT (NOT USED)
DIVISION 21 - FIRE SUPPRESSION (REFER TO FIRE PROTECTION SHEETS)
DIVISION 22 - PLUMBING (REFER TO PLUMBING SHEETS)
DIVISION 23 - HVAC (REFER TO HVAC SHEETS)
DIVISION 26 - ELECTRICAL (REFER TO ELECTRICAL SHEETS)
DIVISION 32 - SITE IMPROVEMENTS (NOT USED)
1. REFER TO WALL SECTIONS FOR EXTERIOR WALL CONSTRUCTION.
2. REFER TO WINDOW SCHEDULE FOR ALL EXTERIOR WINDOWS.
3. REFER TO DOOR SCHEDULE FOR ALL EXTERIOR DOORS.
4. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN
CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE CONTRACTING OFFICER
PRIOR TO CONTINUATION OF WORK.
5. ALL DIMENSIONS SHOWN ARE TO FACE OF MASONRY OR FRAMING UNLESS SPECIFICALLY NOTED
OTHERWISE.
6. WHERE NEW CONSTRUCTION INFILLS OPENINGS IN EXISTING CONSTRUCTION ALIGN FINISH FACES OF
NEW CONSTRUCTION WITH EXISTING CONSTRUCTION.
00.00
05.02
05.01
07.04
06.01
02.02
02.01
07.05
07.03
06.02
02.03
02.04
05.03
05.04
07.02
07.01
06.01
DYNOTEC
SCALE: 3"=1'-0"DETAILA
SCALE: 3"=1'-0"NOT USEDB
SCALE: 3"=1'-0"NOT USEDC
SCALE: 3"=1'-0"NOT USEDD
SCALE: 3"=1'-0"NOT USEDJ
SCALE: 3"=1'-0"NOT USEDK
SCALE: 3"=1'-0"NOT USEDL
SCALE: 3"=1'-0"NOT USEDM SCALE: 3"=1'-0"NOT USEDH
SCALE: 3"=1'-0"NOT USEDG
SCALE: 3"=1'-0"NOT USEDF
SCALE: 3"=1'-0"NOT USEDE
tpaulin Text Box tpaulin Line
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
FIRE PROTECTION - DRY SYSTEMFPD
SERVICE WATER - POTABLEW
AIR PRESSURE MAINTENANCE DEVICE
AIR SUPERVISORY SWITCH
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
OS&Y GATE VALVE
OS&Y GATE VALVE WITH MONITOR SWITCH
PRESSURE SWITCH
P
NO HATCH LIGHT HAZARD
ORDINARY GROUP 1
ORDINARY GROUP 2
EXTRA GROUP 1
EXTRA GROUP 2
SPRINKLER - WALL MOUNTED
SPRINKLER
SPRINKLER - CONCEALED
SPRINKLER
SPRINKLER
SPRINKLER
SPRINKLER
A
SPRINKLER
A
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
COMPRESSED AIR - FIRE PROTECTIONCAF
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
SHUTOFF VALVE NORMALLY OPEN
DEMOLITION
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
AUTOMATIC DRAIN VALVE
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
CHECK VALVE
FLOW SWITCH
F
ROUTE TO DRAIN
AREA BOUNDARY
BACKFLOW PREVENTER
FIRE PROTECTION ABBREVIATION KEY
AD ACCESS DOOR
BFP BACKFLOW PREVENTER
N.C. NORMALLY CLOSED
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
I.E. INVERT ELEVATION
SHORT CIRCUIT CURRENT RATINGSCCR
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SLEEVE & SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF
SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY
MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.
17. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
18. DO NOT EXCEED 25 LBS PER HANGER AND A MINIMUM SPACING OF 2'-0" ON CENTER WHEN
ATTACHING TO METAL ROOF DECKING (LIMITATION NOT REQUIRED WITH CONCRETE ON
METAL DECK). THIS 25 LBS. LOAD AND 2'-0" SPACING INCLUDE ADJACENT ELECTRICAL AND
ARCHITECTURAL ITEMS HANGING FROM DECK. IF THE HANGER RESTRICTIONS CANNOT BE
ACHIEVED, SUPPLEMENTAL FRAMING OFF STEEL FRAMING SHALL BE ADDED. ANCHORS
EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE
WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH THEIR WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
MECHANICAL PHASING NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR
CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT
THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE
ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP
ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE
CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS
REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID
TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND
IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL
TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE
BASIS OF DESIGN.
3. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS
WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
SPRINKLER HEADS SHALL BE ALIGNED WITH OTHER SPRINKLER HEADS, LIGHTING,
DIFFUSERS, AND ANY OTHER FEATURES IN THE CEILING.
4. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK
RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
5. PROVIDE COVERAGE ABOVE AND BELOW ALL EXPOSED DUCTWORK…