This document is a solicitation (Request for Quotation) issued by the Department of the Air Force Reserve Command for monthly maintenance and inspection of five RGF Ultrasorb water treatment units located at Homestead Air Reserve Base in Florida. The solicitation requires the contractor to provide all management, supervision, personnel, materials, and other services necessary to perform the monthly maintenance, inspection, and repairs of the units for a base year plus four 1-year option periods and a 6-month option extension.
The solicitation is a 100% Small Business Set-Aside under NAICS code 562219, with a firm-fixed-price contract type. Offers are due by 10:00 AM EST on March 27, 2024. The evaluation factors are price, technical capability, and past performance. Award will be made to the lowest priced, technically acceptable offeror with acceptable past performance. A site visit is scheduled for March 25, 2024. Any questions must be submitted by March 20, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions & Answers
For
Solicitation Notice #: FA664824Q0003
MONTHLY MAINTENANCE FOR RGF ULTRASORB® WATER TREATMENT UNITS
Number Offeror Question Government Answer 1 Due to the age of the of the units, we would like to request the maintenance reports for the previous three years of the contract -if not, at least the last 12 months if possible.
The Monthly Maintenance Reports from Jan 2023- Dec 2023 are provided. Please see Attachment 1 -Response to Question 1
2 Do you have any copies of past waste shipping documents available for review?
Yes. 2 combined redacted Manifests have been provided. Please see Attachment 2- Response to Question 2
3 We would like to know if this is a brand new contract OR if there is (was) an incumbent performing these services.
If not brand new, could you please provide the current / previous contract number?
This is a follow on Service contract.
The current/previous contract number is FA664820C0008 which is available to the public via www.fpds.gov
4 Any details shared during site visit that would assist those who could not attend?
Yes. The following details were shared during the site visit:
• RGF units located at the
Transportation and FANG Facilities are set up as above-ground oil/water separators and do not recycle the waste water.
• The unit at the Transportation Vehicle Washrack gets the most use and will require the most maintenance.
• The unit at the Fire Station is only partially in use – HARB keeps the oil/water separator portion active, but http://www.fpds.gov/ the full system is not operational – future facility repairs need to be accomplished before the system can be fully put back into use
• Non-hazardous waste disposal is the responsibility of the contractor and such waste must be disposed of properly. HARB CEV can help coordinate to escort waste haulers if necessary. All storage drums and materials are the responsibility of the contractor.
• CEV at HARB will like to obtain a sludge sample from the first monthly service; this will help ensure that the sand/sediment accumulated is non-hazardous material.
Attachment 1 -Response to Question 1:
Combined Monthly Reports
Jan 2023
Maintenance shop:
ST
• Flushed all OWS tank compartments.
• Flushed media.
• Cleaned floating debris from sump.
• Tested pumps, float switches and controls.
• Cleaned skimmer and bleed back lines.
• Checked Delta‐p on canister filters.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
SD
• Checked oil level in hydrocarbon accumulator tank.
• Flushed OWS tank.
• Flushed HCA filter.
• Checked sump pumps & float switches for proper operation.
• Added water treatment in OWS tank.
• Flushed media.
• Cleaned inside containment area.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 500 gallons.
Hush House:
SM
• Drained and cleaned interior of OWS tank.
• Cleared and cleaned clogged CCS drain pipe.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Flushed media.
• Added water treatment in series one tank.
• The 2000 gallon storage tank is currently empty.
FANG:
OWS 50
• No access due to aircraft activity.
Fire Department:
SM
• Vacuumed inside the containment area.
• The 500 gallon storage tank is currently holding approximately 100 gallons.
Feb 2023
Maintenance shop:
ST
• Drained and flushed OWS.
• Flushed media.
• Removed and cleaned bag filters.
• Tested pumps, float switches and controls.
• Cleaned skimmer and bleed back lines.
• Removed and cleaned debris from CFC check valve.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
SD
• Checked oil level in hydrocarbon accumulator.
• Flushed OWS tank.
• Flushed HCA filter.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
• Flushed media.
• Cleaned inside containment area.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 575 gallons.
Hush House:
SM
• Drained and cleaned interior of OWS tank.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump, breather and air lines.
• Flushed media.
• Cleaned sight tube.
• Added water treatment in series one tank.
• The 2000-gallon storage tank is currently empty.
FANG:
OWS 50
• Drained and cleaned interior of OWS.
• Flushed HCA filter.
• Tested both in ground sump pumps.
• Check oil content in hydrocarbon accumulator.
• Flushed media.
• Tested above ground sump pump.
• Added water conditioner.
Fire Department:
SM
March 2023
ST
• Found CFC pump inoperable due to plugged suction line. Removed debris and flushed line.
Equipment is functioning at this time, however, will replace CFC pump during next month's service visit.
• Flushed OWS.
• Checked delta‐p on bag filters.
• Tested pumps, float switches and controls.
• Cleaned skimmer and bleed back lines.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
SD
• Checked oil level in hydrocarbon accumulator.
• Flushed OWS tank.
• Flushed HCA filter.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
• Flushed media.
• Vacuumed inside containment area.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 600 gallons.
Hush House:
SM
• Flushed OWS tank.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump, breather and air lines.
• Flushed media.
• Cleaned sight tube.
• Added water treatment in series one tank.
• The 2000 gallon storage tank is currently holding 200 gallons.
FANG:
OWS 50
• Cleaned skimmer.
• Flushed HCA filter.
• Tested both in ground sump pumps.
• Checked oil content in hydrocarbon accumulator.
• Tested above ground sump pump.
• Added water conditioner.
Fire Department:
SM
• The 500 gallon storage tank is currently holding approximately 30 gallons.
April 2023
ST
• Replaced pump and shaft seals for CFC pump.
• Flushed OWS.
• Removed and cleaned bag filters.
• Tested pumps, float switches and controls.
• Cleaned skimmer and bleed back lines.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
SD
• Checked oil level in hydrocarbon accumulator.
• Drained and flushed OWS tank.
• Flushed HCA filter.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
• Flushed media.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 600 gallons.
Hush House:
SM
• Flushed OWS tank.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump, breather and air lines.
• Flushed media.
• Cleaned sight tube.
• Added water treatment in series one tank.
• The 2000 gallon storage tank is currently holding 200 gallons.
FANG:
OWS 50
• Tested both in ground sump pumps.
• Checked oil content in hydrocarbon accumulator.
• Tested above ground sump pump.
Fire Department:
• The 500 gallon storage tank is currently holding approximately 75 gallons.
May 2023
• Touched up paint.
• Cleaned debris from sump.
• Checked delta‐p on bag filters.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned Y‐strainer.
• Cleaned skimmer and bleed back lines.
• Flushed media.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
• OWS
• Checked oil level in hydrocarbon accumulator.
• Flushed OWS tank.
• Flushed HCA filter.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
• Flushed media.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 600 gallons.
Hush House:
SM
• Drained and flushed OWS tank.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump, breather and air lines.
• Flushed media.
• Cleaned sight tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
• The 2000 gallon storage tank is currently holding 275 gallons.
FANG:
OWS 50
• Drained and flushed OWS tank.
• Cleaned clogged skimmer return.
• Flushed HCA filter.
• Tested both in ground sump pumps.
• Checked oil content in hydrocarbon accumulator.
• Flushed media.
• Tested above ground sump pump.
Fire Department:
• Vacuumed inside containment area.
June 2023
ST
• Found supply pump inoperable. Added a sump pump and rerouted plumbing to bypass supply pump. Will
• replace pump during next service visit.
• Cleared bleed back return tubing to storage tank.
• Removed and cleaned bag filters.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned suction line on CFC pump.
• Cleaned skimmer.
• Flushed media.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Flushed OWS tank.
• Flushed HCA filter.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
• Flushed media.
Maintenance building 307:
• The 2000 gallon storage tank is currently holding 675 gallons.
Hush House:
SM
• Drained and flushed OWS tank.
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump, breather and air lines.
• Flushed media.
• Cleaned sight tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
• The 2000 gallon storage tank is currently holding 275 gallons.
FANG:
OWS 50
• Vacuumed inside containment area.
• Flushed HCA filter.
• Tested both in ground sump pumps.
• Cleaned skimmer.
• Checked oil content in hydrocarbon accumulator.
• Tested above ground sump pump.
Fire Department:
SM
• The 500 gallon storage tank is currently holding 100 gallons.
July 2023
ST
• Replaced process and CFC pumps.
• Cleared CFC bleed back line to series one.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Added water treatment in OWS tank.
Maintenance building 307:
• The 2,000 gallon storage tank is currently holding 1,050 gallons.
Hush House:
SM
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump. Raised aeration line in 500 storage tank.
• Cleaned sight tube.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 600 gallons.
FANG:
OWS 50
• Flushed HCA filter.
• Tested both in ground sump pumps.
• Cleaned skimmer.
• Removed 2 gal. of oil from accumulator and placed in used oil drum in the maintenance shop.
• Tested above ground sump pump.
Fire Department:
SM
August 2023
ST
• Drained and flushed series one tank and media.
• Checked delta‐p on filters.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Flushed HCA filter.
• Flushed OWS tank and added water treatment.
Maintenance building 307:
• The 2,000 gallon storage tank is currently holding 650 gallons.
Hush House:
SM
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump & inlet filter.
• Cleaned sight tube.
• Drained and cleaned interior of series one tank.
• Added water treatment in series one tank.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 600 gallons.
FANG:
OWS 50
• Tested both in ground sump pumps.
• Cleaned skimmer.
• Removed 3 gal. of jet fuel from accumulator and placed in waste fuel drum per Tony's direction.
• Removed 2 gal. of sludge from accumulator.
• Tested above ground sump pump.
Fire Department:
SM
Sept 2023
• Removed sludge from trench, placed in drum and had EMC Oil haul off.
• Flushed series one tank and media.
• Checked delta-p on filters.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Flushed HCA filter.
• Flushed OWS tank and added water treatment.
Maintenance building 307:
• The 2,000 gallon storage tank is currently holding 650 gallons.
Hush House:
SM
• Checked delta-p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump & inlet filter.
• Cleaned sight tube.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 650 gallons.
FANG:
OWS 50
• Removed 25 gal. of jet fuel from OWS & accumulator. Placed in designated waste fuel
• recovery tank.
• Removed 4 gal. of sludge from OWS & accumulator. Placed in drums and had EMC Oil haul
• off.
• Removed filters and media from OWS. Placed in drums and had EMC Oil haul off. Tony
• Cedeno has a copy of shipping papers.
• EMC Oil also pumped out approximately 250 gallons of jet fuel from inground pit.
• I spoke to FANG mechanics about excessive fuel. They said two jets had sticking pressure
• relief valves on the fuel tanks. Problem has been corrected.
• Flushed entire system of heavy sludge and jet fuel.
• Tested both inground sump pumps.
• Cleaned skimmer.
• Tested above ground sump pump.
Fire Department:
SM
• Vacuumed inside containment area.
• The 500 gallon storage tank is currently holding 400 gallons.
October 2023
• Cleaned floating debris from sump.
• Flushed series one tank and media.
• Checked delta-p on filters.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Added water conditioner.
• Vacuumed inside containment area.
Maintenance building 307:
• The 2,000 gallon storage tank is currently holding 0 gallons.
Hush House:
SM
• Checked delta-p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump & inlet filter.
• Cleaned sight tube.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 150 gallons.
FANG:
OWS 50
• Removed 15 gal. of jet fuel from sump. Placed in designated waste fuel recovery tank.
• Tested both inground sump pumps.
• Cleaned skimmer.
• Tested above ground sump pump.
Fire Department:
SM
• The 500 gallon storage tank is currently holding 375 gallons.
November 2023
ST
• Pumped out sludge from sump basin. Placed in storage room in 5 gallon buckets to dewater.
Will place in drum
• during next month's scheduled service.
• Flushed series one tank and media.
• Checked delta‐p on filters.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Vacuumed inside containment area.
Maintenance building 307:
• The 2,000 gallon storage tank is currently holding 0 gallons.
Hush House:
SM
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump & inlet filter.
• Cleaned sight tube.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 150 gallons.
FANG:
OWS 50
• Tested both inground sump pumps.
• Cleaned skimmer.
• Checked oil level in hydrocarbon accumulator.
• Tested above ground sump pump.
Fire Department:
SM
December, 2023
ST
• Found supply pump running hot and drawing excessive amperage. Will replace during next moth's service.
• Found metal pressure tank seeping at a rusty seem. Will replace during next month's service.
• Flushed series one tank and media.
• Checked delta‐p on filters, removed and cleaned.
• Vacuumed inside containment area.
• Tested pumps, float switches and controls.
• Cleaned skimmer.
• Flushed HCA filter.
• Cleaned site tube.
• Added water treatment in series one tank.
OWS
• Checked oil level in hydrocarbon accumulator.
• Tested sump pumps & float switches.
• Vacuumed inside containment area.
• Added water treatment in OWS tank.
Maintenance building 307:
• The 2,000 gallon storage tank is currently empty.
Hush House:
SM
• Checked delta‐p on canister filters.
• Tested pumps, float switches and controls.
• Checked air pump & inlet filter.
• Cleaned sight tube.
• Vacuumed inside containment area.
• The 2,000 gallon storage tank is currently holding 600 gallons.
FANG:
OWS 50
• Tested both inground sump pumps.
• Cleaned skimmer.
• Checked oil level in hydrocarbon accumulator.
• Tested above ground sump pump.
• Vacuumed inside containment area.
Fire Department:
SM
Attachment 2 - Response to Question 2