HARB Bldg 194 TAB.pdf

PDF 4 MB Posted

Attached to
Provide Clean-Dirty Rooms, Hangar 194
Solicitation number
FA664820R0007
Issued by

About this file

This solicitation requests proposals to provide clean and dirty rooms for paint and blast booths at Building 194 of Homestead Air Reserve Base in Florida. The project involves modifying the existing building layout to include separate clean and dirty rooms in compliance with Unified Facilities Criteria 4-211-02 regarding corrosion control facilities. All work must be completed in accordance with the solicitation and attached statement of work. Offerors should provide all labor, equipment, materials, supplies, transportation and supervision to fully complete the project. The solicitation is a firm fixed-price effort issued by the Department of the Air Force Reserve Command.

View the file

Other files

File Type Posted
1.00 Solicitation Amendment FA664820R00070001.pdf PDF
2.00 SOW dated 20200513.pdf PDF
34.00 RFI for KYJM 17-9005 rev 3.pdf PDF
S-1 Layout.pdf PDF
Elevations Outside.pdf PDF
083 - 084 S.3-1.1&2.1 Structural.pdf PDF
049 - A.3-3.2 - 194 - EXTERIOR ELEVATIONS.pdf PDF
Ground Floor Plumbing.pdf PDF
HARB HVAC Repair Modernize Controls Specifications V 1-8 July 2019.pdf PDF
UFC 4-211-02 Aircraft Corrosion Control and Paint Facilities.pdf PDF
Fire Protection.pdf PDF
048 - A.3-3.1 - 194 - EXTERIOR ELEVATIONS.pdf PDF
S-2 Layout.pdf PDF
194-M100.pdf PDF
Sanitary Sewer Rev.pdf PDF
Power Plan.pdf PDF
Elec.pdf PDF
047 - A.3-2.1 - 194 - EXTERIOR ELEVATIONS.pdf PDF
Floor Plan.pdf PDF
Elevations 2.pdf PDF
33.00 Sign In Site Visit.pdf PDF
21.10 AF66 Construction _KYJM 17_9005.pdf PDF
31.00 HARB Visitor Map 2020.pdf PDF
21.8 Wage Determination Highway.pdf PDF
21.3 HARB - Electrical Design Requirements_rev11_July 2019.pdf PDF
21.00 Solicitation - FA664820R0007.pdf PDF
32.00 DOD-GUIDANCE-ON-THE-USE-OF-CLOTH-FACE-COVERINGS.PDF PDF
21.2 AFRC Energy Policy 2013.pdf PDF
30.00 Site Visit Memo.pdf PDF
21.4 HARB First 400 Feet dtd Jan 27.pdf PDF
21.6 Wage Determination Building.pdf PDF
21.9 AF66 Design_KYJM 17_9005.pdf PDF
21.5 HARB HVAC Specs.pdf PDF
21.7 Wage Determination Heavy.pdf PDF
21.1 SOW revised 3_20200406.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Air Logic Services, Inc.

8973 SW 212 Lane

Miami, Florida 33189

PHONE: (305) 971 ‐ 9672 airlogicservices@aol.com FAX: (305) 971 ‐ 6649

BUILDING 194

HOMESTEAD AIR RESERVE BASE

HOMESTEAD, FLORIDA

HVAC TEST & BALANCE ‐ NOVEMBER 2012

8973 SW 212 LANE

MIAMI, FLORIDA 33189

CERTIFICATION #3443

HVAC CONTRACTOR:

EDD HELMS AIR CONDITIONING & ELECTRIC, INC.

17850 NE 5TH AVENUE

NORTH MIAMI BEACH, FLORIDA 33162

NEBB TAB FIRM:

AIR LOGIC SERVICES, INC.

MOBILE, ALABAMA

Air Logic Services, Inc.

CERTIFIED TEST, ADJUST, AND

BALANCE REPORT

NOVEMBER 15, 2012

PROJECT:

BUILDING 194

HOMESTEAD AIR RESERVE BASE

HOMESTEAD, FLORIDA

DESIGN ENGINEER:

BOYLE ENGINEERING CORPORATION

U.S. ARMY ENGINEER DISTRICT

SUBMITTED AND CERTIFIED BY:

CERTIFICATION #:

CERTIFICATION EXPIRATION DATE: MARCH 31, 2013

NOVEMBER 15, 2012

DATE ROBIN BLANK

Air Logic Services, Inc.

PROJECT:

BUILDING 194

HOMESTEAD AIR RESERVE BASE

HOMESTEAD, FLORIDA

THE DATA REPRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL

ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE

NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL

SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE

NOTED IN THE TEST‐ADJUST‐BALANCE REPORT PROJECT SUMMARY.

AIR LOGIC SERVICES, INC.

Project:

Address:

X INSTRUMENT CALIBRATION 45 ‐ 46

IX SUBMITTAL DATA 36 ‐ 44

VIII EQUIPMENT PICTURES 33 ‐ 35

VII AIR DISTRIBUTION SCHEDULE 24 ‐ 32

VI VAV TERMINAL / HEATER SCHEDULE 19 ‐ 23

V EXHAUST FANS 15 ‐ 18

IV AIR HANDLING UNITS / SPLIT DX UNIT 9 ‐ 14

III PUMPS 7 ‐ 8

II AIR COOLED CHILLER 5 ‐ 6

I COVER LETTER 4

I TABLE OF CONTENTS 3

I NEBB CERTIFICATION 2

I PROJECT INFORMATION 1

I COVER PAGE ‐

SECTION DESCRIPTION PAGES

Air Logic Services, Inc.

TABLE OF CONTENTS

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Edd Helms Air Conditioning & Electric

17850 NE 5th Avenue

North Miami Beach, Florida 33162

Attention: Mr. Tom Martin

Subject: HVAC Test and Balance

Reference: Building 194 @ Homestead Air Reserve Base

Homestead, Florida 33039

Mr. Martin, On Wednesday, November 14, 2012, we completed our test and balance procedures for the HVAC system installed and operating at the above referenced project. The following comments and field data are for your information and affirmative action.

GENERAL COMMENTS

1 Total airflow quantities measured by pitot tube traverse of the main supply, return, outside air, and exhaust air main ducts where available.

2 Individual airflow quantities measured with a digital flowhood manufactured by TSI.

3 There are no dampers installed in the return air systems, no balancing can be conducted.

4 Some clarification is necessary on the AHU CFM quantities. The totals of return and outside air quantities do not match total supply air design.

If we can be of further assistance in this matter, please contact us at your convenience.

November 15, 2012

Date Robin Blank

Air Logic Services, Inc.

8973 SW 212 Lane

Miami, Florida 33189

PHONE: (305) 971 ‐ 9672 airlogicservices@aol.com FAX: (305) 971 ‐ 6649

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR COOLED CHILLER

Location:

Type:

Serves:

Notes:

NOTE: Insufficient heat load to conduct performance test at this time.

Air Logic Services, Inc.

Air Cooled Chiller Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Chill Water GPM 119

Serial: REPM011296 AHU ‐ 1, 2, & 3

Make: York Outside (East)

Model: YCAL0070EC46XCASD Air Cooled

H20 Temp. On 55

Description: Design: Test 1 Actual: Test 2 Actual:

BTUH 595,000 0 0

Tons 50

H20 Temp. Off 45

H20 Delta T 10

Delta P 15

Compressor # 1

Return PSI ‐

Supply PSI ‐

Compressor # 2

Voltage 480 / 3 / 60

Voltage 480 / 3 / 60

Amps 21.8

Voltage 480 / 3 / 60

Amps 21.8

Amps 21.8

Compressor # 3

Amps 21.8

Condenser Fans

Compressor # 4

Voltage 480 / 3 / 60

Amps # 2 4

Amps # 3 4

Voltage 480

Amps # 1 4

Readings By: Date:

Amps # 4 4

Outside Air Temp 91 / 79

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

PUMPS

Pump #

Type:

Size:

Serves:

Notes:

Pump #

Type:

Size:

Serves:

Notes:

NOTE:

1 Does not reflect all loses due to port location.

Total Dynamic Head (ft.) 50 43.8

Dead Head (ft.) ‐ 60.5

Suction PSI ‐ 7.4

Discharge PSI ‐ 26.1

Frame 182T 182T

GPM 119 127

Volts 460 / 3 / 60 484 / 483 / 486

Amps 4.2 3.1 / 3.4 / 3.4

RPM 1760 1760

Motor RPM / SF: 3 3

Location: 2nd Fl Mechanical Room AHU ‐ 1, 2, & 3

Description: Design: Actual: Calculation / Factors

Model: F11507 End Suction

Serial: Fl Series IMP ‐ 7.5

Dead Head (ft.) ‐ 60.75

Make: Taco 2

Discharge PSI ‐ 26.4

Total Dynamic Head (ft.) 50 44.5

GPM 119 125

Suction PSI ‐ 7.1

Frame 182T 182T

Motor RPM / SF: 3 3

Volts 460 / 3 / 60 483 / 483 / 486

Design: Actual: Calculation / Factors

RPM 1760 1760

Amps 4.2 3.1 / 3.8 / 3.8

Readings By: CHRIS MASTRAPA Date: 10/11/2012

Air Logic Services, Inc.

Pumps Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Serial: Fl Series IMP ‐ 7.5

Location: 2nd Fl Mechanical Room AHU ‐ 1, 2, & 3

Make: Taco 1

Model: F11507 End Suction

Description:

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR HANDLING UNITS / SPLIT DX UNIT

Location:

Serves:

Type:

No. Fans:

Fan Type:

Notes:

Total BTUH 155,300 146,000 94%

Mixed Air Temp. NA 75.6 / 65.3

OA Temperature 91 / 79 81.6 / 65.5

Return Air Temp. 78 / 65 77.2 / 64.6

Leaving Air Temp. 53 / 52.1 56.4 /55 21.91

Circuit Setter Setting ‐ 0 2.5'

Entering Temp. (H20) 45 43

Leaving Temp. (H20) 55 51

H20 Coil ΔP (Ft.) 5.5 6

Circuit Setter Make ‐ Taco

Circuit Setter Size: NA 1 1/4"

GPM 35 36.5 104%

Entering PSI ‐ 20.5

Leaving PSI ‐ 23.1

External Static Press. 1.5" 2.48"

Total Static Press. NA 2.8"

Coil APD (In. H20) NA .1"

Pre‐CHW Coil Static: ‐ 1.77"

Fan Suction Static: ‐ 1.87"

Discharge Static: ‐ .93"

CFM 4,300 4,645 108%

OA CFM 1,200 1,270 106%

Pre‐Filter Static: ‐ 1.55"

Volts 460 / 3 / 60 477 / 473 / 475

Amps 6.4 4.0 / 432 / 4.5

Frame 184 T 184T

Description: Design: Actual: Calculation / Factors

Fan RPM 1086 1077 99%

Motor Size 5 5

Center Diameter: 10.7" Fan Sheave x Shaft: BK90X x 1 3/16

Belt Adjustment: Fixed / Center Belt: B41

Model: 39MN10D20VD22XGS 1

Serial: 4011943816 Forward Curve

Motor RPM: 1740 Motor Sheave x Shaft: BK57H x H 1 1/8

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR HANDLING UNIT # 1

Men's Lockers 118 (Ceiling)

Lockers, Electrical Shop, Office (North Wing 1st Floor)

Make: Carrier Horizontal Draw Thru

Location:

Serves:

Type:

No. Fans:

Fan Type:

Notes:

Leaving Air Temp. 51 / 50.8 58.5 / 55.7 Total BTUH 157,830 148,500 94%

Return Air Temp. 78 / 65 79.7 / 66

Mixed Air Temp. NA 80.5 / 68.5

Leaving Temp. (H20) 55.85 60

OA Temperature 91 / 79 83.9 / 79.9

Flow Station Setting ‐ 1 1/2"

Entering Temp. (H20) 45 49

H20 Coil ΔP (Ft.) 3.5 2.8"

Flow Station Make/Size ‐ TA

Entering PSI ‐ 22.6"

Leaving PSI ‐ 23.8"

Coil APD (In. H20) .69" .56"

GPM 29 27 93%

External Static Press. 1.5" 2.04"

Total Static Press. 2.762 2.78"

Fan Suction Static: ‐ 1.66"

Discharge Static: ‐ 1.12"

Pre‐Filter Static: ‐ .92"

Pre‐CHW Coil Static: ‐ 1.1"

CFM 3,830 3,590 94%

OA CFM 600 650 108%

Amps 4.1 3.2 / 3.1 / 3.3

Frame 182T 182T

Motor Size 3 3

Volts 460 / 3 / 60 486 / 486 / 489

Description: Design: Actual: Calculation / Factors

Fan RPM 1758 1751 100%

Center Diameter: 13 1/4 Fan Sheave x Shaft: 4 3/4 x H 1 7/16

Belt Adjustment: Fixed / Out Belt: A39

Serial: KIIG77862 Air Foil

Motor RPM / SF: 1760 Motor Sheave x Shaft: AK490 x 1 1/8

Make: Trane Horizontal Draw Thru

Model: CSAA0106AC00 1

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR HANDLING UNIT # 2

2nd Floor Mechanical Room

2nd Floor North

Location:

Serves:

Type:

No. Fans:

Fan Type:

Notes:

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR HANDLING UNIT # 3

1st & 2nd Floor Mechanical Room

1st & 2nd Floor South

Make: Trane Horizontal Draw Thru

Model: CSAA0176AC00 1

Serial: KIIG77868 Air Foil

Motor RPM / SF: 1750 Motor Sheave x Shaft: 5 x H 1 1/8

Center Diameter: 15 3/8" Fan Sheave x Shaft: 6 1/4 x B 1 11/16

Belt Adjustment: Fixed / Out Belt: BX45

Description: Design: Actual: Calculation / Factors

Fan RPM 1421 1372 97%

Motor Size 5 5

Volts 460 / 3 / 60 485 / 485 / 488

Amps 6.5 5.6 / 4.5 / 4.7

Frame 184T 184T

CFM 6770 6190 91%

OA CFM 350 715 204%

Pre‐Filter Static: ‐ .9"

Pre‐CHW Coil Static: ‐ 1.01"

Fan Suction Static: ‐ 1.4"

Discharge Static: ‐ 1.42"

External Static Press. 1.5 2.32"

Total Static Press. 2.81 2.82"

Coil APD (In. H20) .76" .39"

GPM 52 50 96%

Entering PSI ‐ 21.2

Leaving PSI ‐ 18.1

H20 Coil ΔP (Ft.) 8.72 7.16

Flow Station Make/Size TA / 2" TA / 2"

Flow Station Setting 3.5 2.5

Entering Temp. (H20) 45

Leaving Temp. (H20) 54.8

OA Temperature 91 / 79

Return Air Temp. 78 / 65

Mixed Air Temp. ‐

Leaving Air Temp. 52.6 / 52.1

Total BTUH 256.40 0%

Location:

Serves:

Type:

No. Fans:

Fan Type:

Notes:

NOTES:

1 Outside air capped off.

2 Filter is plugged.

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Split DX Air Handling Unit # 4

Make: Trane Vertical Draw Thru

1st Floor Composite Repair 119

1st Floor Composite Repair 119

Serial: Forward Curve

Model: AHX10V600DX101 1

20745613

Motor RPM / SF: 1725 Motor Sheave x Shaft: 3 5/8 x 1/2

Belt Adjustment: Min / Out Belt:

Center Diameter: 13 1/2" Fan Sheave x Shaft: 6 1/4 x 3/4

A39

Description: Design: Actual: Calculation / Factors

Fan RPM NA 1263

Motor Size .25 .25

Volts 208 206

Amps 2.6 2.1

CFM 550 540 98%

OA CFM 50 / 100 / 150 NA

Pre‐Filter Static: ‐ .05"

Pre‐CHW Coil Static: ‐ .06"

Fan Suction Static: ‐ .09"

Discharge Static: ‐ .1"

External Static Press. NA .15"

Total Static Press. NA .16"

Coil APD NA .03"

OA Temperature 91 / 79 81 / 70.9

Return Air Temp. 78 / 65 76.5 / 70.6 34.61

Mixed Air Temp.

Leaving Air Temp. 53 / 52.1 66 / 60.6 26.87

Total BTUH 17,000 18,808 111%

Make Trane Model:

Notes:

AHU ‐ 1:

1 Static pressure calibration: Computer ‐ .81", Actual ‐ .82".

AHU ‐ 2:

1 Outside air automated damper was used to balance outside air CFM.

2 Max CFM for VAV's add up to 3,765. Due to VAV 2‐1 max CFM was changed to 450 instead of 515 design CFM as per plans.

3 Static pressure calibration: Computer ‐ 1.49", Actual ‐ 1.51".

AHU ‐ 3:

1 Need 18 x 12 O/A damper to set CFM and measure BTUH.

2 Static pressure calibration: Computer ‐ 1.49", Actual ‐ 1.54".

Volts 208 206

Amps 0.83 .6

Condenser Fan HP 1/8 1/8

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Compressor # 1: Design: Actual:

Volts

Condenser Fan RPM 1650 Direct Drive

Suction: NA 75

Discharge: NA 220

Readings By: CHRIS MASTRAPA Date: 10/15/2012

AIR HANDLING UNIT NOTES

208 206

Amps NA 6.5

Air Logic Services, Inc.

Split DX Condensing Unit

XE1000 Serial: NA

Location: Outside (East) Refrigerant Type: R‐22

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

EXHAUST FANS

Location:

Type:

Area Served:

Notes:

NOTES:

1 Fan not powered, jumped by this office.

2 Fan is on high speed.

3 Fire damper is restrictive in discharge duct.

Location:

Type:

Area Served:

Notes:

NOTE:

1 Opposed blade damper is not installed.

Static .375" NA

CFM 630 735 117%

Volts 120 121

Amps 3.9 .7

Fan RPM 1,588 1715 108%

Motor Size 1/4 1/4

Description: Design: Actual: Calculation / Factors:

Model: CW090VG44 Centrifugal

Serial: 125151181106 Women's 116 , Men's 117

Exhaust Fan # 3 Make: Green Heck 1st Fl Side Wall

Static .25" .91"

CFM 580 375 65%

Amps 3.9 1.2

Description: Design: Actual: Calculation / Factors:

Fan RPM 963 1726 179%

Exhaust Fan # 2

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

Serial: 125150381106 Electrical Room 115

Make: Green Heck Electrical Room

Model: SQ100BG4X Centrifugal

Motor Size 1/4 1/4

Volts 120

Location:

Type:

Area Served:

Notes:

NOTES:

1 No access to fan. 2nd floor side wall mounted.

2 Fan needs to be slowed down.

3 Opposed blade damper needs to be installed in 2nd Floor Janitor's Room.

Location:

Type:

Area Served:

Notes:

NOTES:

1 No submittal data provided.

Static NA .15"

Motor Frame 48 48

CFM 225 240 107%

Volts 115 120

Amps 1.6 1

Fan RPM 1,140 Direct Drive

Motor Size 1/8 1/8

Description: Design: Actual: Calculation / Factors:

Model: DCRW082B Centrifugal

Serial: LII000000057817 Parts Cleaning 103

Exhaust Fan # 5 Make: Twin City Outside Wall

Static .375" NA

CFM 600 830 138%

Amps NA NA

Motor Frame NA NA

Motor Size 1/4 1/4

Volts 115 120

Description: Design: Actual: Calculation / Factors:

Fan RPM 1,400 NA

Serial: NA Men's 210, Women's 211, Jan. 210A

Make: Green Heck 2nd Fl Side Wall of Bldg.

Model: CW095VG Centrifugal

Exhaust Fan # 4

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

Location:

Type:

Area Served:

Notes:

NOTE:

1 No power.

Static .25" NA

Motor Frame NA NA

CFM 100 NA

Volts 115 NA

Amps 3.9 NA

Fan RPM 1,044 Direct Drive

Motor Size 1/4 1/4

Description: Design: Actual: Calculation / Factors:

Model: SQ80V64X Centrifugual

Serial: 125150391106 Lead / Acid Room 101

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

Exhaust Fan # 7 Make: Green Heck Lead / Acid Room 101

Readings By: CHRIS MASTRAPA Date: 10/16/2012

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

VAV TERMINALS / HEATERS

VAV # Address Size D.MAX A. MAX D. MIN A. MIN COEFF Notes

1 ‐ 1 1 8 620 420 145 150 7.61 1

1 ‐ 2 2 6 300 305 80 80 2.43

1 ‐ 3 3 8 580 590 115 125 2.5

1 ‐ 4 4 6 370 385 80 75 1.17 2

1 ‐ 5 5 8 840 850 165 175 2.09

1 ‐ 6 6 6 185 185 50 50 1.16

1 ‐ 7 7 6 285 285 70 65 1.44

1 ‐ 8 8 8 560 555 110 120 2.42

1 ‐ 9 9 6 370 370 80 80 2.48

1 ‐ 10 10 6 100 100 50 50 1.4

1 ‐ 11 11 6 160 165 50 50 1.28

NOTES:

1 100% open.

2 Max flow revised to reflect connected diffuser sum.

VAV # D. KW D. Volts D. Amps A. KW A. Volts A. Amps Fan Amps Notes

1 ‐ 1 1 277 3.6 1 284 4.2 ‐

1 ‐ 2 1 277 3.6 1 283 4.2 ‐

1 ‐ 3 1 277 3.6 1 286 4.0 ‐

1 ‐ 4 1 277 3.6 1 282 4.4 ‐

1 ‐ 5 1 277 3.6 1 283 4.1 ‐

1 ‐ 6 1 277 3.6 1 283 4.2 ‐

1 ‐ 7 1 277 3.6 1 284 4.1 ‐

1 ‐ 8 1 277 3.6 1 282 4.1 ‐

1 ‐ 9 1 277 3.6 1 283 4.3 ‐

1 ‐ 10 1 277 3.6 1 284 4.2 ‐

1 ‐ 11 1 277 3.6 1 282 4.0 ‐

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 1 VAV Terminal Schedule

Heater Schedule

Readings By: CHRIS MASTRAPA Date: 10/11/2012

VAV # Address Size D.MAX A. MAX D. MIN A. MIN COEFF Notes

2 ‐ 1 12 7 450 430 105 95 2.69 1

2 ‐ 2 13 6 380 370 105 110 2.93

2 ‐ 3 14 6 385 385 80 80 2.91

2 ‐ 4 15 6 330 320 80 85 3.31

2 ‐ 5 16 5 240 250 70 65 1.81

2‐ 6 17 5 240 245 70 75 1.7

2 ‐ 7 18 5 230 225 70 70 1.62

2 ‐ 8 19 4 185 195 50 50 1.35

2 ‐ 9 20 6 405 380 85 90 2.7

2 ‐ 10 21 5 185 190 65 65 1.98

2 ‐ 11 22 5 215 220 65 70 1.71

2 ‐ 12 23 7 520 545 105 100 2.47

NOTES:

1 Max flow revised to reflect connected diffuser sum.

VAV # D. KW D. Volts D. Amps A. KW A. Volts A. Amps Fan Amps Notes

2 ‐ 1 1 277 3.6 1 284 4.1 ‐

2 ‐ 2 1 277 3.6 1 283 3.9 ‐

2 ‐ 3 1 277 3.6 1 284 4.1 ‐

2 ‐ 4 1 277 3.6 1 282 4 ‐

2 ‐ 5 1 277 3.6 1 284 4.1 ‐

2‐ 6 1 277 3.6 1 285 3.9 ‐

2 ‐ 7 1 277 3.6 1 284 3.9 ‐

2 ‐ 8 1 277 3.6 1 284 4.1 ‐

2 ‐ 9 1 277 3.6 1 283 4 ‐

2 ‐ 10 1 277 3.6 1 283 4 ‐

2 ‐ 11 1 277 3.6 1 281 3.7 ‐

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 2 VAV Terminal Schedule

Heater Schedule

Readings By: CHRIS MASTRAPA Date: 10/12/2012

VAV # Address Size D.MAX A. MAX D. MIN A. MIN COEFF Notes

3 ‐ 1 24 10 1275 1240 255 265 1.89

3 ‐ 2 25 6 170 175 50 50 1.13

3 ‐ 3 26 6 400 390 85 90 1.78

3 ‐ 4 27 8 1090 1065 230 240 2.52

3 ‐ 5 28 6 210 215 65 70 1.57

3 ‐ 6 29 6 250 260 70 70 1.54

3 ‐ 7 30 6 285 300 70 75 1.61

3 ‐ 8 31 6 220 225 65 70 1.53

3 ‐ 9 32 6 285 280 70 75 1.56

3 ‐ 10 33 8 80 810 160 170 2.68

3 ‐ 11 34 6 185 185 50 50 1.24

3 ‐ 12 35 6 185 185 50 50 1.21

3 ‐ 13 36 8 580 565 115 120 2.73

3 ‐ 14 37 6 220 225 65 70 1.62

3 ‐ 15 38 6 130 130 50 50 1.17

3 ‐ 16 39 6 130 130 50 50 1.33

3 ‐ 17 40 6 145 150 50 50 1.32

3 ‐ 18 41 6 210 210 65 650 1.65

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 3 VAV Terminal Schedule

VAV # D. KW D. Volts D. Amps A. KW A. Volts A. Amps Fan Amps Notes

3 ‐ 1 1 277 3.6 1 283 5.6 ‐

3 ‐ 2 1 277 3.6 1 284 3.7 ‐

3 ‐ 3 1 277 3.6 1 282 3.9 ‐

3 ‐ 4 2 277 7.2 2 275 7.5 ‐

3 ‐ 5 1 277 3.6 1 283 3.8 ‐

3 ‐ 6 1 277 3.6 1 284 3.96 ‐

3 ‐ 7 1 277 3.6 1 281 3.7 ‐

3 ‐ 8 1 277 3.6 1 284 3.7 ‐

3 ‐ 9 1 277 3.6 1 282 3.8 ‐

3 ‐ 10 3 277 10.8 3 280 10.1 ‐

3 ‐ 11 1 277 3.6 1 281 4 ‐

3 ‐ 12 1 277 3.6 1 283 3.9 ‐

3 ‐ 13 1 277 3.6 1 281 3.9 ‐

3 ‐ 14 1 277 3.6 1 284 3.8 ‐

3 ‐ 15 1 277 3.6 1 283 3.7 ‐

3 ‐ 16 1 277 3.6 1 284 3.9 ‐

3 ‐ 17 1 277 3.6 1 282 3.7 ‐

3 ‐ 18 1 277 3.6 1 284 3.9 ‐

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AHU ‐ 3 Heater Schedule

Readings By: CHRIS MASTRAPA Date: 10/15/2012

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AIR DISTRIBUTION SCHEDULE

Size: % Notes:

10"Ø 61%

8"Ø 72%

8"Ø 85%

71%

10" 102%

102%

10" 103%

10" 100%

102%

8"Ø 103%

8"Ø 105%

104%

8"Ø 102%

8"Ø 105%

8"Ø 100%

8"Ø 98%

101%

8"Ø 100%

100%

8"Ø 104%

8"Ø 100%

102%TOTAL: 280 285

Office 106 140 145

Office 107 140 140

VAV 1 ‐ 7

Hyd. Shop Office 185 185

TOTAL: 185 185

VAV 1 ‐ 6

Electrical Shop 210 205

TOTAL: 840 850

Electrical Shop 210 220

Electrical Shop 210 210

VAV 1 ‐ 5

Electrical Shop 210 215

TOTAL: 370 385

Break Room 110 185 190

Break Room 110 185 195

VAV 1 ‐ 4

Computer (CSA) 112 290 290

TOTAL: 580 590

VAV 1 ‐ 3

Computer (CSA) 112 290 300

TOTAL: 300 305

NCOLC 113 300 305

TOTAL: 620 440

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 1 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

Mens 117 195 140

Women 116 170 145

VAV 1 ‐ 1

Mens Lockers 118 255 155

VAV 1 ‐ 2

Size: % Notes:

10"Ø 96%

10"Ø 102%

99%

8"Ø 97%

8"Ø 103%

100%

6"Ø 100%

100%

8"Ø 103%

103%

Size: % Notes:

10"Ø 77%

8"Ø 67%

8"Ø 32%

16"Ø 27%

8"Ø 107%

8"Ø 68%

10"Ø 57%

6"Ø 30%

51%

Hydraulic Test 105 305 175

Office 102 100 30

TOTAL: 2280 1165

Electrical Shop 109 840 230

Office 107 145 155

Shop Office 108 185 125

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 1 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

VAV 1 ‐ 8

Hyd. Shop 104 280 270

Hyd. Shop 104 280 285

TOTAL: 560 555

VAV 1 ‐ 9

Hydraulic Test Stand 185 180

Hydraulic Test Stand 185 190

TOTAL: 370 370

VAV 1 ‐ 10

Office 102 100 100

TOTAL: 100 100

VAV 1 ‐11

Parts Cleaning 103 160 165

TOTAL: 160 165

AHU ‐ 1 Air Distribution Schedule (Return)

Area Served: Design CFM: Actual CFM:

NCOIC 113 265 205

Break Room 110 300 200

Office 106 140 45

Readings By: CHRIS MASTRAPA Date: 10/11/2012

Size: % Notes:

10"Ø 96%

10"Ø 96%

96%

8"Ø 100%

8"Ø 95%

97%

8"Ø 106%

10" 96%

100%

8"Ø 100%

8"Ø 94%

97%

10"Ø 104%

104%

10"Ø 102%

102%

6"Ø 96%

6"Ø 100%

98%

8"Ø 95%

95%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 2 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

VAV 2 ‐ 1

Mens ‐ 210 225 215

Corridor ‐ 200 225 215

TOTAL: 450 430

VAV 2 ‐ 2

QA ‐ 208 190 190

QA ‐ 208 190 180

TOTAL: 380 370

VAV 2 ‐ 3

Break ‐ 209 160 170

Corridor 225 215

TOTAL: 385 385

VAV 2 ‐ 4

Admin 203 165 165

Admin 203 165 155

TOTAL: 330 320

VAV 2 ‐ 5

TODO 207 240 250

TOTAL: 240 250

VAV 2 ‐ 6

LG CC 202 240 245

TOTAL: 240 245

VAV 2 ‐ 7

QA Office 206 115 110

QA Office 206 115 115

TOTAL: 230 225

VAV 2 ‐ 8

Conference 185 175

TOTAL: 185 175

Size: % Notes:

8"Ø 117%

10"Ø 76%

94%

8"Ø 103%

103%

8"Ø 100%

100%

10"Ø 109%

6"Ø 95%

8"Ø 104%

105%

Size: % Notes:

8"Ø 72%

10"Ø 83%

8"Ø 48%

8"Ø 43%

8"Ø 62%

10"Ø 57%

8"Ø 114%

10"Ø 73%

8"Ø 23%

8"Ø 31%

8"Ø 26%

10"Ø 24%

52%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 2 Air Distribution Schedule (Supply) Area Served: Design CFM: Actual CFM:

VAV 2 ‐ 9

Analysis 205 175 205

Corridor 230 175

TOTAL: 405 380

TOTAL: 185 190

VAV 2 ‐ 10

Conference 201 185 190

VAV 2 ‐12

VAV 2 ‐ 11

Office 204 215 215

TOTAL: 215 215

TOTAL: 520 545

Locker 212 280 305

Corridor 110 105

Women 211 130 135

Area Served: Design CFM: Actual CFM:

Break 209 160 115

Admin 203 330 275

LG CC 202 240 115

Conference 201 185 80

Analysis 175 55

Conference 201 185 115

QA 208 380 215

Corridor 105 120

AHU ‐ 2 Air Distribution Schedule (Return)

Office 204 215 55

Corridor 230 55

TOTAL: 2775 1450

Todo 207 240 175

QA Office 206 330 75

Readings By: CHRIS MASTRAPA Date: 10/12/2012

Size: % Notes:

8"Ø 98%

8"Ø 95%

8"Ø 95%

8"Ø 95%

8"Ø 91%

8"Ø 110%

97%

8"Ø 103%

103%

8"Ø 95%

8"Ø 100%

98%

8"Ø 97%

8"Ø 97%

8"Ø 110%

8"Ø 95%

8"Ø 94%

8"Ø 94%

8 x 4 95%

8 x 4 106%

98%

8"Ø 102%

102%

10"Ø 104%

104%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

AHU ‐ 3 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

VAV 3 ‐ 1

Structural Repair 122 215 210

Structural Repair 122 215 205

Structural Repair 122 215 205

Structural Repair 122 215 205

Structural Repair 122 215 195

Office 123 200 220

TOTAL: 1275 1240

VAV 3 ‐ 2

Tool Room 8 Mob 121 170 175

TOTAL: 170 175

VAV 3 ‐ 3

Training Stencil 120 200 190

Training Stencil 120 200 200

TOTAL: 400 390

VAV 3 ‐ 4

Blast Booth Area 124 175 170

Blast Booth Area 124 175 170

Blast Booth Area 124 100 110

Blast Booth Area 124 100 95

Blast Booth Area 124 175 165

Blast Booth Area 124 175 165

Vestibule 126 100 95

Storage 125 90 95

TOTAL: 1090 1065

VAV 3 ‐ 5

Repeater (comm) 216 210 215

TOTAL: 210 215

VAV 3 ‐ 6

MS Commander 213 250 260

TOTAL: 250 260

Size: % Notes:

10"Ø 105%

105%

8"Ø 102%

102%

10"Ø 98%

98%

8"Ø 108%

8"Ø 97%

8"Ø 105%

8"Ø 100%

103%

8"Ø 100%

100%

8"Ø 100%

100%

10"Ø 102%

10"Ø 93%

97%

8"Ø 102%

102%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AHU ‐ 3 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

VAV 3 ‐ 7

Classroom 215 285 300

TOTAL: 285 300

VAV 3 ‐ 8

MS Super 214 220 225

TOTAL: 220 225

VAV 3 ‐ 9

Classroom 215 285 280

TOTAL: 285 280

VAV 3 ‐ 10

Corridor 200 200 215

Corridor 200 190 185

Corridor 200 200 210

Corridor 200 200 200

TOTAL: 790 810

VAV 3 ‐ 11

Mobility 217 185 185

TOTAL: 185 185

VAV 3 ‐ 12

Training 218 185 185

TOTAL: 185 185

VAV 3 ‐ 13

Orderly Room 219 290 295

Orderly Room 219 290 270

Analysis 220 220 225

TOTAL: 220 225

TOTAL: 580 565

VAV 3 ‐ 14

Size: % Notes:

8"Ø 100%

100%

8"Ø 100%

100%

8"Ø 103%

103%

6"Ø 105%

6"Ø 95%

100%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AHU ‐ 3 Air Distribution Schedule (Supply)

Area Served: Design CFM: Actual CFM:

VAV 3 ‐ 15

NCOLC 221 130 130

TOTAL: 130 130

VAV 3 ‐ 16

Office 222 130 130

TOTAL: 130 130

VAV 3 ‐ 17

Career Adv 145 150

TOTAL: 145 150

VAV 3 ‐ 18

Office 224 105 110

Office 225 105 100

TOTAL: 210 210

Size: % Notes:

14"Ø 89%

14"Ø 93%

83%

8"Ø 69%

10"Ø 70%

10"Ø 185%

6"Ø 68%

10"Ø 154%

10"Ø 103%

6"Ø 37%

6"Ø 61%

8"Ø 176%

8"Ø 124%

8"Ø 55%

8"Ø 59%

8"Ø 119%

10"Ø 110%

12"Ø 93%

8"Ø 28%

8"Ø 40%

10"Ø 118%

90%

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

AHU ‐ 3 Air Distribution Schedule (Return)

Area Served: Design CFM: Actual CFM:

Structural Repair 122 555 495

Structural Repair 122 560 520

Office 123 180 150

Tool Room 121A 130 90

Training / Breakroom 120 320 225

MS Commander 213 230 425

MS Supe 214 200 135

Classroom 215 185 285

Classroom 215 185 190

Repeater Comm 216 190 70

Mobility 217 165 100

Office 224 105 185

Training 218 105 130

Analysis 220 200 110

NCOIC 221 110 65

Office 225 105 125

Orderly Room 219 290 320

Corridor 600 560

TOTAL: 4940 4440

Readings By: CHRIS MASTRAPA Date: 10/15/2012

Orderly Room 219 290 80

Career Advance 223 125 50

Office 222 110 130

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

EQUIPMENT PICTURES

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

EQUIPMENT PICTURES:

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

EQUIPMENT PICTURES:

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

SUBMITTAL DATA

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base

Homestead, Florida

INSTRUMENT CALIBRATION

Cal. Date: Due Date:

NR NR

NR NR

NR NR

NR NR

NR NR

NR NR

NR NR

6/28/2012 6/28/2013

12/1/2011 12/1/2012

4/12/2012 4/12/2013

9/13/2012 9/13/2013

9/12/2012 9/12/2013

12/20/2011 12/20/2012

12/5/2011 12/5/2012

11/1/2012 11/1/2013

1/9/2012 1/9/2013

NR NR

NOTES:

1 NA ‐ Not Applicable.

2 NR ‐ Not Required.

Description: Model Number: Serial Number:

Air Logic Services, Inc.

Building 194 @ Homestead Air Reserve Base Homestead, Florida

2012 Instrument Calibration Form

Dwyer .25" Differential Gauge DW33501 NA

Dwyer .50" Differential Gauge DW33502 NA

Dwyer 3.0" Differential Gauge DW33505 NA

Dwyer Pitot Tube ‐ 18 Inch DW33103 NA

Dwyer Pitot Tube ‐ 48 Inch DW33106 NA

Dwyer Pitot Tube ‐ 36 Inch DW33105 NA

Dwyer Pitot Tube ‐ 12 Inch DW33109 NA

Alnor Hydronic Manometer HM670 71222048

Alnor Capture Hood EBT721 90910012

Alnor Rotating Vane Anemometer RVA801 A01959

Fluke Humidity Thermohygrometer 971 14671384

Fluke Electronic AC/DC Clamp Meter 322 16180720

Alnor Hydronic Temperature Probe 801291 71149052

Alnor Micromanometer 5825 T58250737004

United McGill Duct Pressure Blower NA 5892‐5

Hoto Digital Stroboscope ESL‐100 111273

Cole‐Parmer Contact Probe Type K 08516‐60 CP018437P

HARB Bldg 194 Data1
HARB Bldg 194 Data
HARB Bldg 194 Data1
HARB Bldg 194 Data
HARB Bldg 194 Data
HARB Bldg 194 Data
HARB Bldg 194 Data2
HARB Bldg 194 Data3
HARB Bldg 194 Data4
HARB Bldg 194 Data5

HARB 194 Submittals

File details come from the government source that posted it. Updated .