This is a Major Equipment List specification document for a 50-meter indoor gun range facility. The equipment inventory includes two Fresh Air Handling Units (Carrier 39HQ model) with 11.20 m³/s supply air flow and 674.14 kW cooling capacity, a Carrier 30XB 1500 chiller with 1344 kW cooling capacity using R-134a refrigerant, two KSB Etanorm chilled water pumps rated at 65 L/s flow rate and 15 kW motor power, two System Air exhaust fans (ASP1100 model) with 26,400 CFM capacity and 45 kW motors, a Cummins QSK-60-G4 diesel generator rated at 2000 kVA output, a Carey's DDC (Direct Digital Control) system for facility automation, and a Donalson Torit DFT 2-8 dust collector unit with a 10 HP motor. All equipment operates on 400V/415V three-phase 50 Hz power systems supplied with fresh water and cooled fluids as appropriate.
The equipment list indicates that most major systems require maintenance scheduled for March 2025, with the diesel generator requiring maintenance in February 2025, and the dust collector unit requiring repair with no specified timeline. This equipment specification supports the Air Force's requirement for initial repairs and preventative maintenance services for a 50-meter indoor gun range facility located on Al Udeid Air Base, Qatar, as outlined in Solicitation FA570226Q0011 issued by the Department of the Air Force Air Combat Command. A mandatory site visit is scheduled for February 12, 2026, at 0900 Arabic Standard Time for interested contractors to evaluate the facilities and equipment condition prior to proposal submission.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| 50-m Indoor Range - Major Equipment List | |||||
| Description | Specification | Equipment Condition Overview | Installation Period | ||
| 1 | Fresh Air Handling Unit | ||||
| (FAHU - 2 Units) | Make: Carrier |
Model: 39HQ 15.14 Supply Air Flow: 11.20 m3/s Cooling Capacity: 674.14 kW Power: 400V/3ph/50Hz Fluid: Water Fluid Flow rate: 26.75 L/s Heater Capacity: 72 kW (4 Stage)
| Motor Power: 18.50 kW (VFD) | Maintenance Required | March 2025 | |
| 2 | Chiller | Model: 30XB 1500 |
Make: Carrier Cooling Capacity: 1344 kW Fluid: Fresh Water Fluid Flow Rate: 64.1 L/s Compressor: Screw (2 Nos).
Power: 400V/3ph/50Hz
| Refrigerant Gas: R-134a | Maintenance Required | March 2025 | |
| 3 | Chilled Water Pump (2 Units) | Make: KSB |
Model: Etanorm 150-125-250 GB Fluid: Fresh Water Fluid Flow Rate: 65 L/s Head: 15m Power: 400V/3ph/50Hz
| Motor Power: 15 kW (VFD) | Maintenance Required | March 2025 | |
| 4 | Exhaust Fan (2 Units) | Model: ASP1100 |
Make: System Air Air flow rate: 26400 cfm Motor Power: 45kW
| Power: 415V/3ph/50Hz | Maintenance Required | March 2025 | |
| 5 | Diesel Generator | Model: QSK-60-G4 |
Make: Cummins Circuit Breaker: ABB Output Ratings: 415V-3ph-50Hz
| Power Rating: 2000 kVA | Maintenance Required | February 2025 |
| 7 | DDC System |
Make: Carey's
| Maintenance Required | March 2025 | |
| 8 | Dust Collector Unit | Make: Donalson Torit |
Model: DFT 2-8 Motor Power: 10 HP Repair Required N/A