The PWS provides a detailed inventory and technical specifications of the fire detection, alarm, suppression, and standpipe systems in over 200 buildings across the two air bases. Key systems include addressable fire alarm control panels, wet and dry sprinkler systems, deluge systems, foam suppression systems, fire pumps, and other components. The PWS serves as the technical requirements document for an upcoming Request for Quote (RFQ) for fire protection system maintenance and repair services at the two locations. The U.S. Air Force intends to award a firm-fixed price contract for these commercial services using FAR Part 12 and Simplified Acquisition Procedures under FAR Part 13.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX A
MAINTENANCE AND REPAIR
OF
FIRE PROTECTION SYSTEMS
AT
AVIANO AND GHEDI ABs, ITALY
FIRE PROTECTION SYSTEMS & EQUIPMENT
DESCRIPTION
Aviano Air Base, Italy 02 April 2024
DRAFT
Table of Contents
AVIANO AIR BASE
AREA “A-1”
1. Bldg # 110
2. Bldg # 113
3. Bldg # 116
4. Bldg # 147
5. Bldg # 149
6. Bldg # 170
7. Bldg # 172
8. Bldg # 175
9. Bldg # 176 Bowling
10. Bldg # 176 Bank
11. Bldg # 17811
12. Bldg # 179
AREA “A-2”
13. Bldg # 263
14. Bldg # 264
AREA “C”
15. Bldg # 407
16. Bldg # 410
17. Bldg # 411
18. Bldg # 416
19. Bldg # 421
20. Bldg # 422
21. Bldg # 424
22. Bldg # 428
23. Bldg # 430-1 (Bay # 1)
24. Bldg # 430
AREA “D”
25. Bldg # 554
AREA “E”
26. Bldg # 600
27. Bldg # 604
28. Bldg # 606
29. Bldg # 620
30. Bldg # 623
31. Bldg # 624
32. Bldg # 627
AREA “F”
33. Bldg # 898
34. Bldg # 904
35. Bldg # 9041
36. Bldg # 9042
37. Bldg # 907
38. Bldg # 909
39. Bldg # 9109
40. Bldg # 914
41. Bldg # 916
42. Bldg # 91601
43. Bldg # 919
44. Bldg # 921
45. Bldg # 925
46. Bldg # 933
47. Bldg # 936
48. Bldg # 939
49. Bldg # 9393
50. Bldg # 940
51. Bldg # 940 A
52. Bldg # 94003
53. Bldg # 941
54. Bldg # 944
55. Bldg # 94504
56. Bldg # 946
57. Bldg # 1000
58. Bldg # 1004
59. Bldg # 1010
60. Bldg # 1013
61. Bldg # 1014
62. Bldg # 1015
63. Bldg # 10161
64. Bldg # 1023
65. Bldg # 1029
66. Bldg # 10293
67. Bldg # 10295
68. Bldg # 10296
69. Bldg # 1032
70. Bldg # 1035
71. Bldg # 1036
72. Bldg # 1037
73. Bldg # 10372
74. Bldg # 1046
75. Bldg # 10461
76. Bldg # 10462
77. Bldg # 1048
78. Bldg # 1063
79. Bldg # 1078
80. Bldg # 10781
81. Bldg # 1097
82. Bldg # 1099
83. Bldg # 1100
84. Bldg # 1121
85. Bldg # 11225
86. Bldg # 1131
87. Bldg # 1133
88. Bldg # 11341
89. Bldg # 1135
90. Bldg # 1140
91. Bldg # 1163
92. Bldg # 1173
93. Bldg # 1174
94. Bldg # 1175
95. Bldg # 1204
96. Bldg # 12043
97. Bldg # 1226
98. Bldg # 1227
99. Bldg # 1229
100. Bldg # 1230
101. Bldg # 1234
102. Bldg # 1235 (and 1236)
103. Bldg # 1237
104. Bldg # 1243
105. Bldg # 1270
106. Bldg # 1302
107. Bldg # 1305
108. Bldg # 1307
109. Bldg # 1325
110. Bldg # 1333
111. Bldg # 1334
112. Bldg # 1335
113. Bldg # 1338
114. Bldg # 1342
115. Bldg # 1360 HQ
116. Bldg # 1360 CP
117. Bldg # 1360 WT
118. Bldg # 1362
119. Bldg # 1379
120. Bldg # 1380
121. Bldg # 1381
122. Bldg # 13807
123. Bldg # 13909
124. Bldg # 1391
125. Bldg # 1396
126. Bldg # 1403
127. Bldg # 1404
128. Bldg # 1405
129. Bldg # 1407
130. Bldg # 14071
131. Bldg # 14081
132. Bldg # 1409
133. Bldg # 14108
134. Bldg # 1411
135. Bldg # 1412
136. Bldg # 1413
137. Bldg # 1420
138. Bldg # 1422
139. Bldg # 1423
140. Bldg # 14231
141. Bldg # 1424
142. Bldg # 1425
143. Bldg # 1426
144. Bldg # 1427
145. Bldg # 1428
146. Bldg # 1430
147. Bldg # 1431
148. Bldg # 1433
149. Bldg # 1434
150. Bldg # 1435
151. Bldg # 1437
152. Bldg # 1442
153. Bldg # 1445
154. Bldg # 1445 Annex
155. Bldg # 1446
156. Bldg # 1448
157. Bldg # 1459
158. Bldg # 1460
159. Bldg # 14613
160. Bldg # 1462
161. Bldg # 1464
162. Bldg # 14650
163. Bldg # 1467
164. Bldg # 14671
165. Bldg # 1467 South
166. Bldg # 1472 South
167. Bldg # 1472 Central
168. Bldg # 1472 North
169. Bldg # 1473
170. Bldg # 1476
171. Bldg # 1478 MBF
172. Bldg # 1478 Post Office
173. Bldg # 1479
174. Bldg # 1480
175. Bldg # 1481
176. Bldg # 1482
177. Bldg # 1483
178. Bldg # 1484
179. Bldg # 1496
180. Bldg # 15023
181. Bldg # 7230
182. Bldg # 7300
183. Bldg # 73002
184. Bldg # 73003
185. Bldg # 7350 GAOF
186. Bldg # 7810
187. Bldg # 7850
AREA “G”
188. Bldg # 1500
189. Bldg # 1525
190. Bldg # 1568
191. Bldg # 15706
AREA “X” (Comina – Pordenone)
192. Bldg # 17110
193. Bldg # 17113
194. Bldg # 17114
195. Bldg # 17123
AREA “Y” (Aviano Industrial Area)
196. Bldg # 43
GHEDI AIR BASE
197. Bldg # 5100
198. Bldg # 5102
199. Bldg # 5293
200. Bldg # 5294
201. Bldg # 5301
202. Bldg # 5302
203. Bldg # 5303
204. Bldg # 5307
205. Bldg # 5308
206. Bldg # 5311
207. Bldg # 5315
AVIANO AIR BASE
AREA “A-1”
1. Bldg # 110
a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N addressable FACP, 6 heat detectors on ceiling, 65 smoke detectors above ceiling, 65 repeaters, 42 smoke detectors on ceiling, 7 manual stations, 9 input modules, 2 output modules controlling 32 strobe lights, 1 output module to shut gas solenoid valve in case of ALR activation, 1 output modules controlling 6 door holders, 1 output module releasing tripping coil, 1 output module controlling the MNS, 1 optic/acoustic warning device, 1 output module connected to the transmitter. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A.(EVAC) system. MONACO BT-X transmitter
b) The P.A. (EVAC) System consists of a TUTONDO METCUBE EN 54-16 certified Evacuation Control Panel, 1 emergency microphone TUPONDO METMC1A, 1 Table microphone base METMC8CP, 38 speakers, 11 optic warning devices.
c) The Wet Sprinkler System consists of 65 pendant sprinkler heads (12987AB - K84 - 1/2" – standard response), 1 wet line, backflow preventing device, 2 OS&Y gate valves 4” with supervised tamper switches, 2 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 1 PIV, 1 check valve, 2 inspector test valves, 1 flow switch and 2 floor inspector test valves. All switches are connected to the FACP.
d) The Suppression System on Hood consists of a Model “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 1,5 gall wet chemical extinguishing product, a nitrogen pressurized cartridge, 1 releasing device, 1 manual station, 1 fuse (360oF – 182oC) and 2 spray heads. System has 1 switch that is connected to the FACP.
2. Bldg # 113
a) The Automatic Fire Detection System consists of NOTIFIER AM-1000 addressable FACP, 3 heat detectors place over 6 meters, 2 manual pull stations, 2 optic/acoustic warning panels, and 1 output module to shut gas solenoid valve in case of ALR activation; sprinkler system is connected to FACP with 6 input modules for 2 tamper switches, 1 flow switch, 1 pressure switch, and 2 temperature supervisors. MONACO BT-X transmitter.
b) The Wet Sprinkler System consists of 26 pendant sprinkler heads, 1 PIV, 1 water meter 5”,(the pipes are 4”), 1 gate valves with tamper switches, 1 strainer, 1 backflow preventing device, 1 butterfly valve with tamper, 1 sprinkler alarm valve with 2 pressure gauges, trim & main drain valve, 1 retardant chamber with 1 pressure switch, 1 flow switch, 1 water bell (gong), 1 twin fire truck connection (with internal check valve), one check valve on and 1 ITV.
3. Bldg # 116
a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N addressable FACP, 1 remote panel LCD6000N, 3 additional power supply, 3 heat detectors on ceiling, 38 smoke detectors above ceiling, 38 repeaters, 5 smoke detectors on ceiling, 4 duct smoke detector, total of 7 detector over 4 Mt. 19 manual pull stations, 55 input modules signaling activation of smoke dampers, 2 input module signaling the status of the power supplies, 1 input module signaling activation of kitchen hood system, 3 input modules signaling activation of flow switches, 4 input modules signaling activation of tampers of sprinkler system. 6 output modules controlling the activation of warning devices, 2 output modules controlling the emergency procedure of the elevator, 4 output modules to shut off AHU, 1 output module controlling 5 magnetic door holders, 1 output module for the “supervisory” input of transmitter, 19 output modules signaling the point or zone exclusion of transmitter. 28 strobe lights warning devices, 26 optic/acoustic warning devices and 5 external optic/acoustic warning devices. MONACO BT-X transmitter.
b) The Wet Sprinkler System consists of 225 pendant sprinkler heads, 168 upright sprinkler heads, 1 tampered PIV, 2 tampered main gate valves (6”), 1 backflow preventing device AMES 2000 (6”) with 3 ball valves ¾”, 1 main drain (2”), 1 water pressure gauge with 1 three-way valve ¼”, 2 lines (ground and first floor), 2 tampered butterfly valves, 2 flow switches connected to the FACP, 2 inspector test valves equipped with total 4 ball valves 1” and 2 site glasses water flow, 1 F.D. truck twin connection, 1 check valve VIKING mod. G-1 (4”, 2004)
c) The Standpipe System consists of 6 standpipe valves connected to the wet sprinkler system.
d) The Suppression System on Hood consists of a Model “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 3 gall dry chemical extinguishing product, a nitrogen pressurized tank, 1 manual station, 1 fusible link, total of 4 spray nozzles (2 under hood and 2 inside hood), and 1 double through switch. Upon activation system interrupts power to cooking and exhaust equipment, other contact is connected to the FACP.
4. Bldg # 147
a) The Automatic Fire Detection System consists of a NOTIFIER AM2000 addressable FACP, 2 auxiliary power supply units, 1 remote panel, 29 smoke detectors on ceiling, 71 smoke detector above ceiling, 2 duct smoke detectors, 46 repeaters, 6 input modules, 9 output modules, 2 isolating modules, 7 manual stations and 8 siren/strobe lights.
Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transmitter.
b) The P.A. (EVAC) System consists of a BOSCH audio rack with a PLENA “Voice Alarm Controller” with microphone on board, additional external microphone station, PLENA “Voice Alarm Router”, and 3 PLENA “Booster Amplifier”, 1 external UPS Riello mod. VSD3000 ER expansion pack BB SDH 72-Ml. Throughout the facility there are total 30 speakers.
c) The Wet sprinkler system with 1 PIV, 1 twin Fire Dept. truck connection, and 1 water bell located outside sprinkler room; inside sprinkler room: 1 check valve 4", 3 butterfly valves 6" with tamper switches, 1 backflow preventer 6", 1 butterfly valve 4" with tamper, 1 wet line, 1 automatic sprinkler valve "VICTAULIC" 4" mod. S/751 300 PSI (Apr '05), 1 test valve 2", 2 water pressure gauges, 1 check valve ½", 1 retardant chamber "VICTAULIC" mod. S/752 ('05), 2 ball valves ½", 1 automatic drain valve ½" on trim, 2 pressure switches ("SYSTEM SENSOR" mod. EPS10-1 e "POTTER" PS40- 1A), 1 butterfly valve 2" with tamper, 1 water flow gauge; inside facility: 117 sprinkler heads SSU-1 155oF-68oC, 117 sprinkler heads SSP 155oF-68oC, 1 inspector test valve; all switches connected to the FACP.
d) The Dry Standpipe System consists of a fire department connection that feeds 5 20 Mt. UNI45 standpipe hoses and 1 tampered control valve 3" connected to the FACP.
5. Bldg # 149
a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 auxiliary power supply unit
FireClass BXM24U50, 1 remote panel LCD6000N, 38 smoke detectors on ceiling, 32 smoke detectors above false ceiling, 1 duct smoke detector above false ceiling, 33 repeaters, total of 33 detectors placed over 3 meters, 11 manual station, 30 alarm strobe lights controlled by 1 output module, 1 input module monitoring 1 CO detector, 3 output modules controlling 3 door holders, 2 output modules controlling the elevator, 1 output module controlling the ventilation, 2 output modules activating 2 fire dampers, 2 input and 1 output modules controlling the MNS, 2 output and 9 input modules controlling the sprinkler system, 1 output module connected to the transmitter. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transmitter.
b) The P.A. (EVAC) System consists of a BOSCH audio rack with a PLENA “Voice Alarm Controller” with microphone on board, additional external microphone station, PLENA “Voice Alarm Router”, and 3 PLENA “Booster Amplifier”.
Throughout the facility there are total 30 speakers.
c) The Water Based Fire Suppression System main supply line consists of 1 PIV with tamper switch, 1 backflow preventer 6” equipped with test header assembly, 2 OS&Y gate valves 6” with supervised tamper switches, 1 OS&Y gate valve 4” without tamper switch (normally closed), All switches connected to the FACP.
d) The Wet sprinkler system consists of 113 recessed pendent sprinkler heads, 21 standard pendent sprinkler heads, 1 butterfly valve 4” with supervised tamper switch, 1 wet system alarm valve 4” equipped with complete trim circuit, 1 vane type flow switch 4”, 1 electric alarm bell, 1 zone control valve assembly (at first floor) consisting of a butterfly valve with supervised tamper switch, 2 gauges, 1 vane type flow switch and a “test and drain” device, 1 twin Fire Dept.
Connection and 1 check valve 4”. All switches connected to the FACP.
e) The Standpipe System consists of 1 butterfly valve 2”1/2 with supervised tamper switch, 1 drain valve 2”, 2 check valves 2”1/2, 1 twin Fire Dept. Connection, 1 gauge, 1 vane type flow switch and 4 standpipe hoses. All switches connected to the FACP.
6. Bldg # 170
a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N Addressable FACP, 1 remote annunciator panel
NOTIFIER LCD 6000, 1 Auxiliary Power Supply Unit NOTIFIER HLSPS25, 2 heat detectors, 71 smoke detectors on ceiling, 50 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, 3 duct smoke detectors on roof, total of 9 detectors placed over 4 meters, 51 repeaters, 7 switches, 19 manual stations, 28 strobe lights,2 acoustic/optic warning devices, 7 monitored fire dumpers. MONACO BT-X transmitter
b) The P.A.(EVAC) System consists of a TUTONDO METCUBE EN 54-16 certified Evacuation Control Panel, 1 emergency microphone TUPONDO METMC1A, 1 Table microphone base METMC8CP, 28 normal speakers installed on ceiling and total 5 water-proof speakers installed on external walls.
c) The Water Based Fire Suppression System main supply line consists of 1 PIV without tamper switch, 1 OS&Y gate valves 4" with supervised tamper, 1 backflow preventer 6”, 1 Filter 4”, 1 check valve 4”.
d) The Wet Sprinkler System consists of 192 Sprinkler heads, 1 OS&Y gate valve 4” with tamper switch, 1 wet alarm valve Viking mod. J-1 4” equipped with complete trim circuit, 1 water gong, 1 pressure switch and 1 flow switch.
e) The Deluge Sprinkler System consists of 1 OS&Y gate valve 4” with tamper, 1 Viking mod. F-1 deluge valve 4”, 1 solenoid valve and 1 manual station, 1 water pressure switch 1 water flow switch. All switches are connected to the fire alarm station. No water bell.
f) The Suppression System on Hood consists of a KIDDE-FENWAL mod. IND-25 with a 12,5 kg tank with wet chemical extinguishing product, 1 releasing device, 1 manual station, 2 fuses (212oF – 100oC) and 8 spray nozzles. System has 1 switch that is connected to the FACP.
7. Bldg # 172
a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 54 smoke detectors above ceiling, 54 repeaters, 50 smoke detectors on ceiling, 6 duct smoke detectors, 1 heat detector on ceiling, 20 manual pull stations, 4 input modules, 7 output modules, 20 optic/acoustic devices. MONACO BT-X transmitter.
b) The Wet Sprinkler System consist of 16 Sprinkler heads, 1 butterfly valve 4” with supervised tamper, 1 wet system alarm valve mod. J-1 4” equipped with complete trim circuit, 1 drain valve 2”, 2 gauges, 1 water pressure switch, 1 mod. G-1 check valve 4”, 1 PIV without tamper switch and 1 twin fire dept. connection.
c) The Suppression System on Hood consists of a “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 3 gall wet chemical extinguishing product, a nitrogen pressurized tank, 1 releasing device, 1 manual station, 2 fuses (360oF – 182oC) and 5 spray nozzles. System has 1 switch that is connected to the FACP.
8. Bldg # 175
a) The Automatic Fire Detection System consists of a Notifier S-5000 conventional FACP, 20 heat detectors, 1 duct smoke detector, total of 4 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 3 switches, 4 manual stations,6 optic lights. MONACO BT-X transmitter.
9. Bldg # 176 Bowling
a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 30 heat detectors, 7 heat & smoke detectors (dual technology), 3 smoke detector on ceiling, 74 smoke detectors above ceiling, 3 duct smoke detectors, total of 11 detectors placed over 3 meters, total of 64 detectors placed over 4 meters, 77 repeaters, 3 input modules, 12 output modules, 8 manual stations, 10 switches, 1 optic warning device, and 14 optic/acoustic warning panels. MONACO BT-X transmitter.
b) The Suppression System on Hood consists of a “ANSUL R-102 WET CHEMICAL” placed above cooking equipment with 3 gall dry chemical extinguishing product, a nitrogen pressurized tank, 1 manual station, 2 fuses (360oF – 182oC) and 5 spray nozzles. System has 1 switch that is connected to the FACP.
10. Bldg # 176 Bank
a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 12 smoke detectors on ceiling, 11 heat/smoke detectors above ceiling, 11 led repeaters, 1 heat detector on ceiling, total of 12 devices placed over 3 meters, 3 manual pull stations, 1 switch, and 3 audio/visual warning panels. MONACO BT-X transmitter.
11. Bldg # 17811
a) The Automatic Fire Detection System consists of a conventional FACP, 8 smoke detectors, 5 manual stations and 6 optic/acoustic warning panels. MONACO BT-X transmitter.
12. Bldg # 179
a) The Automatic Fire Detection System consists of a Notifier AFP-400 addressable FACP, 1 remote panel LCD80, 1 additional power supply, 6 smoke detectors, 36 smoke detector above ceiling, 7 duct smoke detectors, total of 36 detectors placed over 4 meters, 36 repeaters, 5 input modules, 5 output modules, 17 manual stations, 4 optical warning devices, and 49 acoustic/optical warning devices. MONACO BT-X transmitter.
b) The Wet Sprinkler System consist of 261 pendant sprinkler heads, 100 upright sprinkler heads, 7 long probe dry pendant sprinkler heads, 1 tampered PIV, 1 tampered main gate valves (6”), 1 automatic sprinkler valve (6”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 inspector test valve, 2 water flow switches connected to the FACP, 1 F.D. truck twin connection, 1 check valve 2½ mod
IVR.
AREA “A-2”
13. Bldg # 263
a) The Automatic Fire Detection System consists of a FireClass J408 conventional FACP to which are connected the Fire
Pump Control Panels and the valve tamper switches (see Section 2). System is equipped with an external warning device. The FACP is connected to the Monaco unit in Bldg# 264.
b) The Fire Pump System consist of 2 fire pumps, 6 control valves supervised with tamper switch, 2 check valves, 4 gauges and 1 flowmeter. The tamper switched and the Fire Pump Control Panel are connected to the FACP.
14. Bldg # 264
a) The Automatic Fire Detection System consists of a NOTIFIER FireStar conventional FACP, 1 smoke detector on ceiling, 7 smoke detectors above ceiling, 7 repeaters, 1 switch, 3 manual stations and 5 bells. MONACO BT-X transmitter.
AREA “C”
15. Bldg # 407
a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 24 heat detectors, 81 smoke detectors on ceiling, 64 smoke detectors above ceiling, 1 duct smoke detector, total of
64 detectors placed over 3 meters, total of 20 detectors placed over 6 meters, 64 repeaters, 30 modules, 1 damper, 20 manual stations and 28 optic/acoustic warning devices. MONACO BT-X transmitter.
16. Bldg # 410
a) The Automatic Fire Detection System consists of a Notifier AM1000 addressable FACP, 23 heat detectors, 1 heat detector waterproof, 9 smoke detectors on ceiling, 2 smoke detectors on ceiling, 6 smoke detectors above ceiling, 19 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, total of 13 detectors placed over 4 meters, 6 repeaters, 19 repeaters, 20 manual stations and 18 optic/acoustic warning devices. MONACO BT-X transmitter.
17. Bldg # 411
a) The Automatic Fire Detection System consists of a System consists of a NOTIFIER AM-2020 addressable FACP, 1 heat detector, 2 smoke detectors on ceiling, total 3 detectors placed over 4 meters, 3 output modules, 2 manual stations and 1 bell waterproof. MONACO BT-X transmitter.
b) The Wet Sprinkler System consist of 2 fire pumps, 1 jockey pump, 6 control valves, 2 check valves, 4 gauges and 1 flowmeter. The Fire Pump Control Panels are connected to the MONACO BT-X transmitter.
18. Bldg # 416
a) The Automatic Fire Detection System consists of a NOTIFIER NFS8-2 plus conventional FACP, 8 heat detectors, 4 smoke detectors on ceiling, 5 smoke detectors on ceiling, 3 smoke detectors above ceiling, 11 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 8 manual station and 8 sirens/strobe lights. MONACO BT-X transmitter.
19. Bldg # 421
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 9 heat detectors, 1 heat detector waterproof, 3 smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 2 detectors placed over 4 meters, 3 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.
20. Bldg # 422
a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 2 siren/strobe lights, 1 alarm bell. MONACO BT-X transmitter.
21. Bldg # 424
a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 10 heat detectors, 1 heat detectors waterproof, 8 smoke detectors above ceiling, 2 duct smoke detectors, total of 8 detectors placed over 4 meters, 9 repeaters, 2 air dampers, 1 switch, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.
22. Bldg # 428
a) The Automatic Fire Detection System consists of a Notifier NFS4-2PLUS conventional FACP, 6 smoke detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, 2 repeaters, 2 manual stations and 2 siren/strobe lights. MONACO BT-X transmitter.
23. Bldg # 430-1 (Bay # 1)
a) The Automatic Fire Detection System (Bay # 1) consists of a Notifier AM1000 addressable FACP, 1 auxiliary power supply unit, 24 heat detectors, 1 smoke detector, 2 smoke detectors under floating floor, 1 smoke detector above false ceiling, 14 smoke detectors above false ceiling, 6 manual stations, 6 optic/acoustic warning devices controlled by 6 modules, 1 input module monitoring the auxiliary power supply unit, 1 switch controlled by 1 module. FACP is connected to MONACO BT-X transmitter in Bldg. # 430 fire system mechanical room West side of facility.
24. Bldg # 430
a) The Automatic Fire Detection System (Bay # 2, # 3, # 4, & # 5) consists of a System consists of a THERMOSTICK MAR-
1 conventional FACP, 6 heat detectors, 5 heat detectors waterproof, 19 smoke detectors on ceiling, 18 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 4 detectors placed over 6 meters, 18 repeaters, 10 switches, 15 manual stations and 16 siren/strobe lights. MONACO BT-X transmitter.
b) The Wet Sprinkler System consist of 538 sprinkler heads, 2 lines, 2 automatic alarm valves (CSC 8”, year1997), 2 retardant chambers, 5 pressure gauges, 1 main drain in pump room, 1 twin Fire Dept. connection, 2 water bells, 3 test valves inside bays with flow indicator (side glass), 2 test valve inside. 1 butterfly valve 6” with supervised tamper, PIV without tamper switch, 2 water flow switches, 2 gate valves with tamper switches inside mechanic room, 8 control valves with tamper switches not connected to the FACP on lines inside building and 2 water pressure switches connected to the FACP.
c) The Standpipe System consists of 7 standpipe hoses with nozzles, connected to the wet sprinkler system.
AREA “D”
25. Bldg # 554
a) The Automatic Fire Detection System consists of a BENTEL J424-8 conventional FACP, 16 heat detectors, 1 heat detector waterproof, 4 smoke detectors on ceiling, 11 smoke detectors above ceiling, 1 duct smoke detector, total of 20 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 4 manual stations, 1 manual station waterproof, 5 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO BT-X transmitter.
AREA “E”
26. Bldg # 600
a) The Automatic Fire Detection System consists of a NOTIFIER S-500 conventional FACP, 114 heat detectors, 7 heat detectors waterproof, 16 smoke detectors on ceiling, 109 smoke detectors above ceiling, total of 103 detectors placed over 3 meters, 103 repeaters, 17 manual stations and 25 alarm bells. MONACO BT-X transmitter.
27. Bldg # 604
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 13 heat detectors, 2 heat detectors waterproof, 2 smoke detectors on ceiling, 7 smoke detectors above ceiling, total of 15 detectors placed over 3 meters, 4 manual stations, 1 manual station waterproof, 4 siren/strobe lights, 1 bell and 1 bell waterproof.
MONACO BT-X transmitter.
28. Bldg # 606
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1/A conventional FACP, 24 heat detectors, 8 smoke detectors on ceiling, 19 smoke detectors above ceiling, 1 duct detector, total of 8 detectors placed over 4 meters, 19 repeaters, 1 switch, 10 manual stations, 4 alarm bells, and 3 optic/acoustic warning devices. MONACO BT- X transmitter.
29. Bldg # 620
a) The Automatic Fire Detection System consists of a Bentel J408 conventional FACP, 12 heat detectors, 1 smoke detector on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 1 switch, 5 manual stations and 2 alarm bells. MONACO BT-X transmitter.
30. Bldg # 623
a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000N addressable FACP, 1 auxiliary power supply unit Bentel BXM24U50, 14 heat detectors, 2 smoke detectors on ceiling, 4 smoke detectors above ceiling, 4 repeaters, 1 duct smoke detector, total of 4 detectors placed over 3 meters, 8 manual pull stations, and 8 optic/acoustic warning panels controlled by 8 modules, 1 input module monitoring the auxiliary power supply unit, 1 output module to send the signal to the Fire suppression control panel to actuate the extinguishing sequence. MONACO BT-X transmitter.
31. Bldg # 624
a) The Automatic Fire Detection System consists of a COE CLERICI conventional FACP, 4 heat detectors, 1 smoke detector on ceiling, 2 manual stations and 2 alarm bells. MONACO BT-X transmitter.
32. Bldg # 627
a) The Automatic Fire Detection System consists of a CERBERUS CZ-16 conventional FACP, 14 heat detectors, 7 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 4 alarm bells. MONACO BT-X transmitter.
AREA “F”
33. Bldg # 898
a) The Automatic Fire Detection System consists of a NOTIFIER NFS4-2PLUS conventional FACP, 1 heat detector, 6 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 3 manual stations and 2 optic/acoustic warning panels. MONACO BT-X transmitter.
34. Bldg # 904
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 100 heat detectors, 11 heat detectors waterproof, 1 smoke detector on ceiling, 17 smoke detectors on ceiling in the attic, 50 smoke detectors above ceiling, total of 50 detectors placed over 3 meters, 67 repeaters, 18 manual stations and 19 siren/strobe lights.
MONACO BT-X transmitter.
35. Bldg # 9041
a) The Automatic Fire Detection System consists of a System consists of a THERMOSTICK MAR-1A conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.
b) The Dry Chemical Suppression System consist of two 60-liter cylinders (Nitrogen at 200 atm.) each one has a solenoid valve including 1 manual station, one 500 kg of ABCE Polyvalent extinguishing powder, 2 lines (one for each bay) each one has a discharge solenoid valve, total of 8 spray nozzles, 1 switch connected to fire alarm panel. System is activated by automatic fire detection system.
36. Bldg # 9042
a) The Automatic Fire Detection System consists of a NOTIFIER AFP-200 addressable FACP, 20 heat detectors, 2 smoke detectors on ceiling, 11 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 13 detectors placed over 4 meters, 1 output module, 1 input module, 11 repeaters, 4 manual stations, 1 bell and 6 siren/strobe lights. MONACO BT-X transmitter.
37. Bldg # 907
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 40 heat detectors, 3 smoke detectors on ceiling, 23 smoke detectors above ceiling, 4 duct smoke detectors above false ceiling, total of 26 detectors placed over 3 meters, 23 repeaters, 1 switch, 9 manual stations, 10 strobe lights, and 1 alarm bell. MONACO BT-X transmitter.
b) The Standpipe System consists of 2 external standpipe hoses with nozzles.
38. Bldg # 909
a) The Automatic Fire Detection System consists of a NOTIFIER S-5000 conventional FACP, 2 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 1 switch, 3 repeaters, 1 manual station and 2 siren/strobe lights. MONACO BT-X transmitter.
39. Bldg # 9109
a) The Automatic Fire Detection System consists of a NOTIFIER AM6000N addressable FACP, 1 NOTIFIER ALI-25EN auxiliary power supply device, 2 NOTIFIER UDS-3 and 1 NOTIFIER UDS-4 controlling foam suppression systems, 5 heat detectors, 6 heat detectors explosion-proof, 69 smoke detectors, 18 smoke duct detectors, 9 smoke detectors above false ceiling, 9 repeaters, 1 CO detector, 12 flame detectors explosion-proof, total of 6 detectors placed over 3 meters, total of 16 detectors placed over 4 meters, total of 44 detectors placed in the bays’ attics, 13 manual stations, 2 manual stations water-proof, 25 manual stations explosion-proof, 26 input modules monitoring the suppression system components, 2 input module monitoring the auxiliary power supply devices, 8 output modules for releasing devices, 18 output modules controlling the warning devices (3 strobe/siren explosion-proof, 4 sirens water-proof with strobe lights, 6 sirens explosion-proof, 6 strobe lights explosion-proof and 5 strobe/siren). MONACO BT-X transmitter.
b) The Water Based Fire Suppression System consist of:
b.2) Wet sprinkler system with 124 pendant and 88 upright sprinkler heads, 1 GRINNEL check valve (4”) for Fire
Depart. truck connection, 1 TFP AV-1 wet alarm valve (4”), 1 TYCO OS&Y gate valve, 2 TFP AV-1 alarm valves (6”), 1 VICTAULIC FIRELOCK SERIES T05 butterfly valve (3”), 1 VICTAULIC series 751 with European trim (3”), 1 VICTAULIC FIRELOCK SERIES T05 butterfly valve (6”), 1 VICTAULIC series 751 with European trim (6”), 2 TYCO OS&Y gate valves, 3 POTTER OSYSU-1 tamper switches, 3 POTTER VSR-EU flow switches, 5 POTTER PS10-1A pressure switches (not connected to FACP), and 3 water bells (gongs).
b.3) Fire hydrants system consisting of 1 TFP AV-1 alarm valve (6”), 1 TYCO OS&Y gate valve (4”), 1 POTTER OSYSU-1 tamper switch, 1 POTTER VSR-EU flow switch, 1 POTTER PS10-1A pressure switch (not connected to FACP), and 1 water bell (gong).
c) The Heat & Smoke Evacuation System consists of 2 two areas (Painting Bay & Sanding Bay) provided with heat & smoke evacuators. Each system consists of 1 CAODUR MDE01 control panel and 4 heat & smoke evacuators. Total of 2 (two) control panels and 8 (eight) heat and smoke evacuators.
40. Bldg # 914
a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 3 heat detectors with water-protection, 6 heat detectors, 1 smoke detector on ceiling, 4 smoke detectors above ceiling, 1 duct smoke detector, total of 4 detectors placed over 3 meters, 4 repeaters, 4 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.
b) The Wet Sprinkler System consist of 9 pendant sprinkler heads, 1 side wall sprinkler head, 1 wet line with 1 control valve Ever Metal Industry 2 ½”, 1 automatic sprinkler alarm valve GEM 2 ½" (1994) 175 psi with trim circuit, 1 retarding chamber Mod. F211 175 psi, 2 water pressure gauges, 1 main drain valve 1 ¼”, 1 Fire Dept. Connection with 1 hose gate valve (2”) and 1 check valve (2½”), 1 non-return valve Mueller ¾”, 1 water bell and 1 pressure switch connected to main FACP.
41. Bldg # 916
a) The Automatic Fire Detection System consists of a NOTIFIER SFP-400 conventional FACP, 4 heat detectors waterproof, 1 switch, 4 manual stations, 1 trouble bell and 7 siren/strobe lights. MONACO BT-X transmitter.
42. Bldg # 91601
a) The Automatic Fire Detection System consists of a Notifier AM1000 addressable FACP, 12 input modules monitoring fire pumps supervised valves, 1 optic/acoustic warning device waterproof. MONACO BT-X transmitter.
b) The Fire pump system consists of 3 main electric pumps (Motor FELM 400/690V, 275/159.4A, 50Hz, 1485rpm, 160kW / Impeller GRUPPO ATURIA Spa, Q = 341 m3/h, H = 85.2 mH2O), 2 Jokey pumps GRUNDFOSS (Q = 3.1 m3/h, H = 55.9/73.9 m), 1 FireKing OS&Y valves 8”, 3 SAPAG butterfly valves 8” with tamper switches, 3 check valves VIKING 8” mod. G-1, 3 relief valves 3” OCV mod. 108 FC, 1 test meter GERARD ENG.CO K-2000-8, 1 test header line with 8 hose gate valves 2 ½” and it’s FireKing OS&Y valves 8”, 3 expansion vessels 500L. A.B.C. All 5 pumps have a dedicated electric control panel, pressure control switches, assorted valves, and gauges. Downstream the pumps there are 3 backflow preventers AMES 4000-SS backflow preventing devices 8”, 3 FireKing OS&Y valves 8” with tamper switches, 1 FireKing OS&Y valve 12” with tamper switch on the ground floor. All switches are connected to main FACP.
43. Bldg # 919
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 3 heat detectors, 12 smoke detectors on ceiling, 3 manual stations and 3 siren/strobe lights. MONACO BT-X transmitter.
44. Bldg # 921
a) The Automatic Fire Detection System consists of NOTIFIER AM2000N addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 1 NOTIFIER ALI-25EN auxiliary power supply device, 1 BENTER BXM24U50 power supply device, 56 heat detectors, 1 heat detector explosion-proof monitored by a module, 65 smoke detectors on ceiling in aircrafts servicing area, 18 smoke detectors above false ceiling, 9 duct smoke detectors, 18 repeaters, 3 linear (beam) smoke detectors, total of 27 detectors installed over 3 meters, total of 3 detectors installed over 6 meters, total of 65 detectors installed over 10 meters, 37 monitor modules, 22 output control modules (21 for warning devices, 1 for gas shut off valve, 2 for AHU shut down), 3 relay modules, 28 manual stations (7 for foam discharge), 30 door holders, 23 sirens with strobe lights, 7 optic/acoustic panels. MONACO BT-X transmitter.
b) The Water Based Fire Suppression System main supply line consist of a F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-1, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.
c) The Wet Sprinkler System Back Shops & Offices consists of 139 sprinkler heads, 1 wet system alarm valve Viking Mod.J1 (3”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (3”) with position micro-switch, 1 POTTER VSR-EU flow switch, 1 Potter PS10 pressure switch, 2 ELBI AF-24/16 expansion tanks.
d) The Wet Sprinkler System Bay Area Zone A consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 Potter VSR-EU flow switch, 1 Potter PS10 pressure switch.
e) The Wet Sprinkler System Bay Area Zone B consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 Potter VSR-EU flow switch, 1 Potter PS10 pressure switch.
45. Bldg # 925
a) The Automatic Fire Detection System consists of NOTIFIER AM-2000N addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BENTEL BXM24U50 auxiliary power supply devices, 90 heat detectors, 5 heat detectors explosion-proof, 27 smoke detectors, 5 duct smoke detectors, 27 smoke detectors above ceiling, 27 repeaters, total of 27 detectors installed over 3 meters, 90 detectors installed over 10 meters, 1 shut-off gas solenoid valve, 15 monitor modules, 2 relay modules for the sprinkler system, 3 relay modules controlling warning devices, 35 manual pull stations (9 for foam discharge), 28 sirens with strobe light, 7 optic/acoustic panels, and 2 bells explosion-proof. MONACO BT-X transmitter.
b) The Water Based Fire Suppression System main supply line consists of a F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-1, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.
c) The Wet Sprinkler System Back Shops & Offices consists of 79 upright and 88 pendent sprinkler heads, 1 VIKING J-1 alarm valve (3”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (3”) with position micro-switch, 1 POTTER PS10 pressure switch, 2 ELBI AF-24/16 expansion tanks, and 1 water bell (gong).
d) The Wet Sprinkler System Bay Area Zone A consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 vane type flow switch Potter VSR-EU, 1 Potter PS10 pressure switch.
e) The Wet Sprinkler System Bay Area Zone B consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 vane type flow switch Potter VSR-EU, 1 Potter PS10 pressure switch.
46. Bldg # 933
a) The Automatic Fire Detection System consists of NOTIFIER AM4000 addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BTE auxiliary power supply devices, 92 heat detectors, 66 smoke detectors, 3 duct smoke detectors, 88 smoke detectors above false ceiling, 88 repeaters, total of 89 detectors placed over 3 meters, total of 20 detectors installed over 4 meters, total of 72 detectors placed over 10 meters, 1 module controlling the shut-off gas solenoid valve, 32 modules controlling the water based suppression system, 2 modules controlling the temperature probes, 6 modules controlling the warning devices, 2 modules controlling the auxiliary power supply devices, 51 manual station (10 for foam discharge), 4 acoustic warning devices, 47 optic/acoustic warning devices. MONACO BT-X transmitter.
b) The Wet Sprinkler System in room 119 consists of 29 upright and 135 pendent sprinkler heads, 1 butterfly valve 3” with supervised tamper, a main FIRE KING OS&Y gate valve 3” with supervised tamper switch Potter OSYSU-2, 1 Fivalco YS-G-1251-U strainer 3”, 1 VIKING J-1 alarm valve (3”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 POTTER PS10 pressure switch, 2 vane type flow switches Viking VSR-EU, 1 water bell (gong) and a F.D.
truck connection with check valve.
c) The Water Based Fire Suppression System main supply line in room 212 consists of main supply line F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-2, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.
d) The Wet Sprinkler System Back Shop in room 212 consists of 4 upright and 95 pendent sprinkler heads, 1 VIKING J-1 alarm valve (4”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (4”) with position micro-switch, 1 POTTER PS10 pressure switch, 3 vane type flow switches Viking VSR-EU, 2 ELBI AF- 24/16 expansion tanks, and 1 water bell (gong).
e) The Wet Sprinkler System Bay Area Zone A in room 212 consists of 186 upright sprinkler heads, 1 VIKING J-1 wet alarm valve (6”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (6”) with position micro-switch, 1 POTTER PS10-1A pressure switch, and 1 water bell (gong).
f) The Wet Sprinkler System Bay Area Zone B in room 212 consists of 186 upright sprinkler heads, 1 VIKING J-1 wet alarm valve (6”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (6”) with position micro-switch, 1 POTTER PS10-1A pressure switch, and 1 water bell (gong).
g) The Wet Sprinkler System Warehouse in New addition consist of 131 pendant sprinkler heads, 1 OS&Y gate valve 6” with tamper switch, 1 wet alarm valve 6” RAPIDROP mod. B equipped with complete trim circuit, 1 Pressure switch, 1 flow switch.
h) The Wet Sprinkler System Office in New addition consist of 174 pendant sprinkler heads, 45 upright sprinkler heads, 1 OS&Y gate valve 4” with tamper switch, 1 wet alarm valve 4” RAPIDROP mod. D equipped with complete trim circuit, 1 Pressure switch, 1 flow switch.
47. Bldg # 936
a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 11 heat detectors, 3 heat detectors waterproof, 7 smoke detectors above ceiling, 1 duct smoke detector, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.
48. Bldg # 939
a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000N addressable FACP, 2 auxiliary power supply units NOTIFIER ALI50EN, 1 panel repeater NOTIFIER LCD- 6000N, 1 heat detector, 41 smoke detectors on ceiling, 50 smoke detectors above ceiling, 4 duct smoke detector, total of 50 detectors placed over 3 meters, 50 repeaters, 7 input and 7 output modules monitoring and controlling 7 smoke/fire dampers, 5 input modules monitoring the sprinkler system devices, 3 output modules to shutdown utilities, 2 output modules controlling 4 magnetic door holders, 4 input modules monitoring the auxiliary power supply units and the gas leak detection panel, 6 manual stations, 4 sounder bases and 36 optic/acoustic warning devices. MONACO BT-X transmitter.
b) The Wet Sprinkler System consists of 80 sprinkler heads (73 pendent and 7 upright sprinkler heads), 1 PIV with tamper switch, 3 OS&Y gate valves (4”) with tamper switch, 1 backflow preventer (4”), 1 alarm valve with complete trim circuit (drain valve, test valve, retardant chamber, etc.) 1 water gong, 1 check valve on FDC line, 1 pressure switch and 1 flow switch. All switches are connected to main FACP.
49. Bldg # 9393
a) Building under renovation.
50. Bldg # 940
a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000 addressable FACP, 1 auxiliary power supply unit, 66 heat detectors, 2 smoke detector, 39 smoke detectors above ceiling, 39 repeaters, 8 manual stations, 12 acoustic/optic warning devices, 8 input modules, 1 output module, and total of 39 detectors placed over 3 meters.
MONACO BT-X transmitter.
51. Bldg # 940 A
a) The Automatic Fire Detection System consists of a NOTIFIER AM-1000 addressable FACP, 1 auxiliary power supply unit, 27 heat detectors, 17 smoke detectors on ceiling, 2 duct smoke detectors above ceiling, total of 19 detectors placed over 3 meters, 19 repeaters, 1 input module, 4 output modules, 1 isolating module, 3 manual stations, and 3 acoustic/optic warning devices. MONACO BT-X transmitter.
52. Bldg # 94003
a) The Automatic Fire Detection System consists of a NOTIFIER S-5000 conventional FACP, 6 heat detectors, 6 smoke detectors, total of 12 detectors placed over 4 meters, 1 switch, 2 manual stations and 2 siren/strobe lights. MONACO BT-X transmitter.
53. Bldg # 941
a) The Automatic Fire Detection System consists of a Bentel J-424 conventional FACP, 31 heat detectors, 3 heat detectors waterproof, 31 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 33 detectors placed over 3 meters, 31 repeaters, 1 switch, 6 manual stations and 7 alarm bells. MONACO BT-X transmitter.
54. Bldg # 944
a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 5 heat detectors, 5 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 3 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 6 repeaters, 1 switch, 2 manual stations and 2 bells. MONACO BT-X transmitter.
55. Bldg # 94504
a) The Automatic Fire Detection System consists of a Notifier AM-2000N addressable FACP, 3 heat detectors, 3 smoke detectors, 10 relay modules, 2 control modules (shutdown ventilation in EG shelter & mezzanine), 1 output module for warning devices, 4 manual pull stations, and 3 optic/acoustic warning devices. MONACO BT-X transmitter.
56. Bldg # 946
a) The Automatic Fire Detection System consists of a Notifier AM-2000N addressable FACP, 1 Notifier ALI-25EN auxiliary power supply device, 20 heat detectors, 9 smoke detectors on ceiling, 25 smoke detectors above ceiling, 4 duct smoke detectors, 1 linear (beam) smoke detector, total of 25 devices placed over 3 meters, total of 1 device placed over 4 meters, 26 led repeaters, 9 output modules controlling the warning devices, 1 input and 2 output modules for beam smoke detector functioning, 4 input modules for sprinkler system, 1 output module for release device, 14 manual pull stations, and 22 siren/strobe lights. MONACO BT-X transceiver.
b) The Water Based Fire Suppression System consists of a main water supply line located outdoor at ground floor with 2 butterfly valves (6”), 1 strainer (6”), 1 drain ball valve (2”), 1 check valve, 1 water pressure gauge, 2 F.D. truck connection valves (2 ½”), 1 Backflow preventer 6” and 1 pressure relief valve (1”).
c) The Fire Pump System, in a room on the roof, consists of 1 WILO water pumping unit mod. GPVA UNI 2-5204 + P 1.85 equipped with 2 main electric and 1 Jokey pump providing Q=60-30 m3/h water flow, 6” line, 2” by-pass, 3 expansion tanks 24-liter capacity each. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.
d) The Wet Sprinkler System consists of 83 pendent sprinkler heads, 1 distribution line, 1 butterfly valve (6”) with tamper, 1 VICTAULIC automatic sprinkler valve (6”) w/trim, 1 retardant chamber, 1 pressure switch, and 1 water bell (gong).
At the distribution lines of the Wet Sprinkler System are connected:
d.1) A Dry Sprinkler System in the basement consisting of 26 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (4”) with complete trim circuit, 1 VICTAULIC butterfly valve (4”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).
d.2) A Dry Sprinkler System at the ground floor consisting of 28 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (4”) with complete trim circuit, 1 VICTAULIC butterfly valve (4”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).
d.3) A Dry Sprinkler System at the ground floor consisting of 11 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (2”½) with complete trim circuit, 1 VICTAULIC butterfly valve (2”½) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).
d.4) A Dry Sprinkler System at the ground floor consisting of 41 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (6”) with complete trim circuit, 1 VICTAULIC butterfly valve (6”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).
57. Bldg # 1000
a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 1 auxiliary power supply unit, 12 heat detectors explosion-proof, 4 heat detectors, 1 smoke detector on ceiling, 1 heat & smoke detector, total of 12 detectors placed over 4 meters, 3 output control modules, 17 input modules, 3 manual stations explosion-proof, 2 manual stations, 3 explosion-proof bells, and 2 optic/acoustic warning panels. MONACO BT-X transmitter.
b) The Fire Pump System consists of 1 DAB water pumping unit equipped with 1 diesel pump, 1 electric pump (not energized), 1 Jokey pump, 6” line. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.
c) The Wet sprinkler system with 49 pendant sprinkler heads and 2 inspector test valves, 2 gate valves (6”) w/tamper, 1 strainer, 2 gate valves (6”), 2 check valves (6”), 5 butterfly valves (4”), 1 flow meter (4”), 1 F.D. truck twin connection, 1 check valve (4”), 1 VIKING mod. B-1 pilot operated valve (6”), 1 VIKING mod. J-1 valve (6”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, and 1 water bell (gong).
58. Bldg # 1004
a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 1 heat detector, 15 smoke detectors, 11 smoke detectors above ceiling, total of 9 detectors placed over 3 meters, 11 repeaters, 4 output modules controlling the warning devices, 2 spare input modules, 2 relay modules to transmit signals to Monaco unit, 8 manual stations and 5 optic/acoustic warning panels. MONACO BT-X transmitter.
59. Bldg # 1010
a) The Automatic Fire Detection System consists of a NOTIFIER CFP 12-24 conventional FACP, 1 auxiliary power supply unit, 25 smoke detectors, 2 smoke detectors above ceiling, 6 duct smoke detectors above ceiling, 8 repeaters, 25 manual stations, 7 bells, 14 acoustic/optical warning devices, 1 switch stops HVAC equipment, total of 8 detectors placed over 3 meters. MONACO BT-X transmitter.
b) The Wet Sprinkler System consists of three circuits, new West area protected with 92 upright sprinkler heads, existing Central area protected with 47 pendant and 196 upright…