This document is a Performance Work Statement (PWS) that describes the fire protection systems and equipment at Aviano and Ghedi Air Bases in Italy that require maintenance and repair services.

The PWS provides a detailed inventory and technical specifications of the fire detection, alarm, suppression, and standpipe systems in over 200 buildings across the two air bases. Key systems include addressable fire alarm control panels, wet and dry sprinkler systems, deluge systems, foam suppression systems, fire pumps, and other components. The PWS serves as the technical requirements document for an upcoming Request for Quote (RFQ) for fire protection system maintenance and repair services at the two locations. The U.S. Air Force intends to award a firm-fixed price contract for these commercial services using FAR Part 12 and Simplified Acquisition Procedures under FAR Part 13.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX A

MAINTENANCE AND REPAIR

OF

FIRE PROTECTION SYSTEMS

AT

AVIANO AND GHEDI ABs, ITALY

FIRE PROTECTION SYSTEMS & EQUIPMENT

DESCRIPTION

Aviano Air Base, Italy 02 April 2024

DRAFT

Table of Contents

AVIANO AIR BASE

AREA “A-1”

1. Bldg # 110

2. Bldg # 113

3. Bldg # 116

4. Bldg # 147

5. Bldg # 149

6. Bldg # 170

7. Bldg # 172

8. Bldg # 175

9. Bldg # 176 Bowling

10. Bldg # 176 Bank

11. Bldg # 17811

12. Bldg # 179

AREA “A-2”

13. Bldg # 263

14. Bldg # 264

AREA “C”

15. Bldg # 407

16. Bldg # 410

17. Bldg # 411

18. Bldg # 416

19. Bldg # 421

20. Bldg # 422

21. Bldg # 424

22. Bldg # 428

23. Bldg # 430-1 (Bay # 1)

24. Bldg # 430

AREA “D”

25. Bldg # 554

AREA “E”

26. Bldg # 600

27. Bldg # 604

28. Bldg # 606

29. Bldg # 620

30. Bldg # 623

31. Bldg # 624

32. Bldg # 627

AREA “F”

33. Bldg # 898

34. Bldg # 904

35. Bldg # 9041

36. Bldg # 9042

37. Bldg # 907

38. Bldg # 909

39. Bldg # 9109

40. Bldg # 914

41. Bldg # 916

42. Bldg # 91601

43. Bldg # 919

44. Bldg # 921

45. Bldg # 925

46. Bldg # 933

47. Bldg # 936

48. Bldg # 939

49. Bldg # 9393

50. Bldg # 940

51. Bldg # 940 A

52. Bldg # 94003

53. Bldg # 941

54. Bldg # 944

55. Bldg # 94504

56. Bldg # 946

57. Bldg # 1000

58. Bldg # 1004

59. Bldg # 1010

60. Bldg # 1013

61. Bldg # 1014

62. Bldg # 1015

63. Bldg # 10161

64. Bldg # 1023

65. Bldg # 1029

66. Bldg # 10293

67. Bldg # 10295

68. Bldg # 10296

69. Bldg # 1032

70. Bldg # 1035

71. Bldg # 1036

72. Bldg # 1037

73. Bldg # 10372

74. Bldg # 1046

75. Bldg # 10461

76. Bldg # 10462

77. Bldg # 1048

78. Bldg # 1063

79. Bldg # 1078

80. Bldg # 10781

81. Bldg # 1097

82. Bldg # 1099

83. Bldg # 1100

84. Bldg # 1121

85. Bldg # 11225

86. Bldg # 1131

87. Bldg # 1133

88. Bldg # 11341

89. Bldg # 1135

90. Bldg # 1140

91. Bldg # 1163

92. Bldg # 1173

93. Bldg # 1174

94. Bldg # 1175

95. Bldg # 1204

96. Bldg # 12043

97. Bldg # 1226

98. Bldg # 1227

99. Bldg # 1229

100. Bldg # 1230

101. Bldg # 1234

102. Bldg # 1235 (and 1236)

103. Bldg # 1237

104. Bldg # 1243

105. Bldg # 1270

106. Bldg # 1302

107. Bldg # 1305

108. Bldg # 1307

109. Bldg # 1325

110. Bldg # 1333

111. Bldg # 1334

112. Bldg # 1335

113. Bldg # 1338

114. Bldg # 1342

115. Bldg # 1360 HQ

116. Bldg # 1360 CP

117. Bldg # 1360 WT

118. Bldg # 1362

119. Bldg # 1379

120. Bldg # 1380

121. Bldg # 1381

122. Bldg # 13807

123. Bldg # 13909

124. Bldg # 1391

125. Bldg # 1396

126. Bldg # 1403

127. Bldg # 1404

128. Bldg # 1405

129. Bldg # 1407

130. Bldg # 14071

131. Bldg # 14081

132. Bldg # 1409

133. Bldg # 14108

134. Bldg # 1411

135. Bldg # 1412

136. Bldg # 1413

137. Bldg # 1420

138. Bldg # 1422

139. Bldg # 1423

140. Bldg # 14231

141. Bldg # 1424

142. Bldg # 1425

143. Bldg # 1426

144. Bldg # 1427

145. Bldg # 1428

146. Bldg # 1430

147. Bldg # 1431

148. Bldg # 1433

149. Bldg # 1434

150. Bldg # 1435

151. Bldg # 1437

152. Bldg # 1442

153. Bldg # 1445

154. Bldg # 1445 Annex

155. Bldg # 1446

156. Bldg # 1448

157. Bldg # 1459

158. Bldg # 1460

159. Bldg # 14613

160. Bldg # 1462

161. Bldg # 1464

162. Bldg # 14650

163. Bldg # 1467

164. Bldg # 14671

165. Bldg # 1467 South

166. Bldg # 1472 South

167. Bldg # 1472 Central

168. Bldg # 1472 North

169. Bldg # 1473

170. Bldg # 1476

171. Bldg # 1478 MBF

172. Bldg # 1478 Post Office

173. Bldg # 1479

174. Bldg # 1480

175. Bldg # 1481

176. Bldg # 1482

177. Bldg # 1483

178. Bldg # 1484

179. Bldg # 1496

180. Bldg # 15023

181. Bldg # 7230

182. Bldg # 7300

183. Bldg # 73002

184. Bldg # 73003

185. Bldg # 7350 GAOF

186. Bldg # 7810

187. Bldg # 7850

AREA “G”

188. Bldg # 1500

189. Bldg # 1525

190. Bldg # 1568

191. Bldg # 15706

AREA “X” (Comina – Pordenone)

192. Bldg # 17110

193. Bldg # 17113

194. Bldg # 17114

195. Bldg # 17123

AREA “Y” (Aviano Industrial Area)

196. Bldg # 43

GHEDI AIR BASE

197. Bldg # 5100

198. Bldg # 5102

199. Bldg # 5293

200. Bldg # 5294

201. Bldg # 5301

202. Bldg # 5302

203. Bldg # 5303

204. Bldg # 5307

205. Bldg # 5308

206. Bldg # 5311

207. Bldg # 5315

AVIANO AIR BASE

AREA “A-1”

1. Bldg # 110

a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N addressable FACP, 6 heat detectors on ceiling, 65 smoke detectors above ceiling, 65 repeaters, 42 smoke detectors on ceiling, 7 manual stations, 9 input modules, 2 output modules controlling 32 strobe lights, 1 output module to shut gas solenoid valve in case of ALR activation, 1 output modules controlling 6 door holders, 1 output module releasing tripping coil, 1 output module controlling the MNS, 1 optic/acoustic warning device, 1 output module connected to the transmitter. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A.(EVAC) system. MONACO BT-X transmitter

b) The P.A. (EVAC) System consists of a TUTONDO METCUBE EN 54-16 certified Evacuation Control Panel, 1 emergency microphone TUPONDO METMC1A, 1 Table microphone base METMC8CP, 38 speakers, 11 optic warning devices.

c) The Wet Sprinkler System consists of 65 pendant sprinkler heads (12987AB - K84 - 1/2" – standard response), 1 wet line, backflow preventing device, 2 OS&Y gate valves 4” with supervised tamper switches, 2 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 1 PIV, 1 check valve, 2 inspector test valves, 1 flow switch and 2 floor inspector test valves. All switches are connected to the FACP.

d) The Suppression System on Hood consists of a Model “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 1,5 gall wet chemical extinguishing product, a nitrogen pressurized cartridge, 1 releasing device, 1 manual station, 1 fuse (360oF – 182oC) and 2 spray heads. System has 1 switch that is connected to the FACP.

2. Bldg # 113

a) The Automatic Fire Detection System consists of NOTIFIER AM-1000 addressable FACP, 3 heat detectors place over 6 meters, 2 manual pull stations, 2 optic/acoustic warning panels, and 1 output module to shut gas solenoid valve in case of ALR activation; sprinkler system is connected to FACP with 6 input modules for 2 tamper switches, 1 flow switch, 1 pressure switch, and 2 temperature supervisors. MONACO BT-X transmitter.

b) The Wet Sprinkler System consists of 26 pendant sprinkler heads, 1 PIV, 1 water meter 5”,(the pipes are 4”), 1 gate valves with tamper switches, 1 strainer, 1 backflow preventing device, 1 butterfly valve with tamper, 1 sprinkler alarm valve with 2 pressure gauges, trim & main drain valve, 1 retardant chamber with 1 pressure switch, 1 flow switch, 1 water bell (gong), 1 twin fire truck connection (with internal check valve), one check valve on and 1 ITV.

3. Bldg # 116

a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N addressable FACP, 1 remote panel LCD6000N, 3 additional power supply, 3 heat detectors on ceiling, 38 smoke detectors above ceiling, 38 repeaters, 5 smoke detectors on ceiling, 4 duct smoke detector, total of 7 detector over 4 Mt. 19 manual pull stations, 55 input modules signaling activation of smoke dampers, 2 input module signaling the status of the power supplies, 1 input module signaling activation of kitchen hood system, 3 input modules signaling activation of flow switches, 4 input modules signaling activation of tampers of sprinkler system. 6 output modules controlling the activation of warning devices, 2 output modules controlling the emergency procedure of the elevator, 4 output modules to shut off AHU, 1 output module controlling 5 magnetic door holders, 1 output module for the “supervisory” input of transmitter, 19 output modules signaling the point or zone exclusion of transmitter. 28 strobe lights warning devices, 26 optic/acoustic warning devices and 5 external optic/acoustic warning devices. MONACO BT-X transmitter.

b) The Wet Sprinkler System consists of 225 pendant sprinkler heads, 168 upright sprinkler heads, 1 tampered PIV, 2 tampered main gate valves (6”), 1 backflow preventing device AMES 2000 (6”) with 3 ball valves ¾”, 1 main drain (2”), 1 water pressure gauge with 1 three-way valve ¼”, 2 lines (ground and first floor), 2 tampered butterfly valves, 2 flow switches connected to the FACP, 2 inspector test valves equipped with total 4 ball valves 1” and 2 site glasses water flow, 1 F.D. truck twin connection, 1 check valve VIKING mod. G-1 (4”, 2004)

c) The Standpipe System consists of 6 standpipe valves connected to the wet sprinkler system.

d) The Suppression System on Hood consists of a Model “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 3 gall dry chemical extinguishing product, a nitrogen pressurized tank, 1 manual station, 1 fusible link, total of 4 spray nozzles (2 under hood and 2 inside hood), and 1 double through switch. Upon activation system interrupts power to cooking and exhaust equipment, other contact is connected to the FACP.

4. Bldg # 147

a) The Automatic Fire Detection System consists of a NOTIFIER AM2000 addressable FACP, 2 auxiliary power supply units, 1 remote panel, 29 smoke detectors on ceiling, 71 smoke detector above ceiling, 2 duct smoke detectors, 46 repeaters, 6 input modules, 9 output modules, 2 isolating modules, 7 manual stations and 8 siren/strobe lights.

Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transmitter.

b) The P.A. (EVAC) System consists of a BOSCH audio rack with a PLENA “Voice Alarm Controller” with microphone on board, additional external microphone station, PLENA “Voice Alarm Router”, and 3 PLENA “Booster Amplifier”, 1 external UPS Riello mod. VSD3000 ER expansion pack BB SDH 72-Ml. Throughout the facility there are total 30 speakers.

c) The Wet sprinkler system with 1 PIV, 1 twin Fire Dept. truck connection, and 1 water bell located outside sprinkler room; inside sprinkler room: 1 check valve 4", 3 butterfly valves 6" with tamper switches, 1 backflow preventer 6", 1 butterfly valve 4" with tamper, 1 wet line, 1 automatic sprinkler valve "VICTAULIC" 4" mod. S/751 300 PSI (Apr '05), 1 test valve 2", 2 water pressure gauges, 1 check valve ½", 1 retardant chamber "VICTAULIC" mod. S/752 ('05), 2 ball valves ½", 1 automatic drain valve ½" on trim, 2 pressure switches ("SYSTEM SENSOR" mod. EPS10-1 e "POTTER" PS40- 1A), 1 butterfly valve 2" with tamper, 1 water flow gauge; inside facility: 117 sprinkler heads SSU-1 155oF-68oC, 117 sprinkler heads SSP 155oF-68oC, 1 inspector test valve; all switches connected to the FACP.

d) The Dry Standpipe System consists of a fire department connection that feeds 5 20 Mt. UNI45 standpipe hoses and 1 tampered control valve 3" connected to the FACP.

5. Bldg # 149

a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 auxiliary power supply unit

FireClass BXM24U50, 1 remote panel LCD6000N, 38 smoke detectors on ceiling, 32 smoke detectors above false ceiling, 1 duct smoke detector above false ceiling, 33 repeaters, total of 33 detectors placed over 3 meters, 11 manual station, 30 alarm strobe lights controlled by 1 output module, 1 input module monitoring 1 CO detector, 3 output modules controlling 3 door holders, 2 output modules controlling the elevator, 1 output module controlling the ventilation, 2 output modules activating 2 fire dampers, 2 input and 1 output modules controlling the MNS, 2 output and 9 input modules controlling the sprinkler system, 1 output module connected to the transmitter. Warning system throughout facility rely also on recorded warning messages from speakers controlled by P.A. system (see description at end of Section). MONACO BT-X transmitter.

b) The P.A. (EVAC) System consists of a BOSCH audio rack with a PLENA “Voice Alarm Controller” with microphone on board, additional external microphone station, PLENA “Voice Alarm Router”, and 3 PLENA “Booster Amplifier”.

Throughout the facility there are total 30 speakers.

c) The Water Based Fire Suppression System main supply line consists of 1 PIV with tamper switch, 1 backflow preventer 6” equipped with test header assembly, 2 OS&Y gate valves 6” with supervised tamper switches, 1 OS&Y gate valve 4” without tamper switch (normally closed), All switches connected to the FACP.

d) The Wet sprinkler system consists of 113 recessed pendent sprinkler heads, 21 standard pendent sprinkler heads, 1 butterfly valve 4” with supervised tamper switch, 1 wet system alarm valve 4” equipped with complete trim circuit, 1 vane type flow switch 4”, 1 electric alarm bell, 1 zone control valve assembly (at first floor) consisting of a butterfly valve with supervised tamper switch, 2 gauges, 1 vane type flow switch and a “test and drain” device, 1 twin Fire Dept.

Connection and 1 check valve 4”. All switches connected to the FACP.

e) The Standpipe System consists of 1 butterfly valve 2”1/2 with supervised tamper switch, 1 drain valve 2”, 2 check valves 2”1/2, 1 twin Fire Dept. Connection, 1 gauge, 1 vane type flow switch and 4 standpipe hoses. All switches connected to the FACP.

6. Bldg # 170

a) The Automatic Fire Detection System consists of a NOTIFIER AM2000N Addressable FACP, 1 remote annunciator panel

NOTIFIER LCD 6000, 1 Auxiliary Power Supply Unit NOTIFIER HLSPS25, 2 heat detectors, 71 smoke detectors on ceiling, 50 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, 3 duct smoke detectors on roof, total of 9 detectors placed over 4 meters, 51 repeaters, 7 switches, 19 manual stations, 28 strobe lights,2 acoustic/optic warning devices, 7 monitored fire dumpers. MONACO BT-X transmitter

b) The P.A.(EVAC) System consists of a TUTONDO METCUBE EN 54-16 certified Evacuation Control Panel, 1 emergency microphone TUPONDO METMC1A, 1 Table microphone base METMC8CP, 28 normal speakers installed on ceiling and total 5 water-proof speakers installed on external walls.

c) The Water Based Fire Suppression System main supply line consists of 1 PIV without tamper switch, 1 OS&Y gate valves 4" with supervised tamper, 1 backflow preventer 6”, 1 Filter 4”, 1 check valve 4”.

d) The Wet Sprinkler System consists of 192 Sprinkler heads, 1 OS&Y gate valve 4” with tamper switch, 1 wet alarm valve Viking mod. J-1 4” equipped with complete trim circuit, 1 water gong, 1 pressure switch and 1 flow switch.

e) The Deluge Sprinkler System consists of 1 OS&Y gate valve 4” with tamper, 1 Viking mod. F-1 deluge valve 4”, 1 solenoid valve and 1 manual station, 1 water pressure switch 1 water flow switch. All switches are connected to the fire alarm station. No water bell.

f) The Suppression System on Hood consists of a KIDDE-FENWAL mod. IND-25 with a 12,5 kg tank with wet chemical extinguishing product, 1 releasing device, 1 manual station, 2 fuses (212oF – 100oC) and 8 spray nozzles. System has 1 switch that is connected to the FACP.

7. Bldg # 172

a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 54 smoke detectors above ceiling, 54 repeaters, 50 smoke detectors on ceiling, 6 duct smoke detectors, 1 heat detector on ceiling, 20 manual pull stations, 4 input modules, 7 output modules, 20 optic/acoustic devices. MONACO BT-X transmitter.

b) The Wet Sprinkler System consist of 16 Sprinkler heads, 1 butterfly valve 4” with supervised tamper, 1 wet system alarm valve mod. J-1 4” equipped with complete trim circuit, 1 drain valve 2”, 2 gauges, 1 water pressure switch, 1 mod. G-1 check valve 4”, 1 PIV without tamper switch and 1 twin fire dept. connection.

c) The Suppression System on Hood consists of a “ANSUL R-102 WET CHEMICAL” placed above electric cooking equipment with 3 gall wet chemical extinguishing product, a nitrogen pressurized tank, 1 releasing device, 1 manual station, 2 fuses (360oF – 182oC) and 5 spray nozzles. System has 1 switch that is connected to the FACP.

8. Bldg # 175

a) The Automatic Fire Detection System consists of a Notifier S-5000 conventional FACP, 20 heat detectors, 1 duct smoke detector, total of 4 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 3 switches, 4 manual stations,6 optic lights. MONACO BT-X transmitter.

9. Bldg # 176 Bowling

a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 30 heat detectors, 7 heat & smoke detectors (dual technology), 3 smoke detector on ceiling, 74 smoke detectors above ceiling, 3 duct smoke detectors, total of 11 detectors placed over 3 meters, total of 64 detectors placed over 4 meters, 77 repeaters, 3 input modules, 12 output modules, 8 manual stations, 10 switches, 1 optic warning device, and 14 optic/acoustic warning panels. MONACO BT-X transmitter.

b) The Suppression System on Hood consists of a “ANSUL R-102 WET CHEMICAL” placed above cooking equipment with 3 gall dry chemical extinguishing product, a nitrogen pressurized tank, 1 manual station, 2 fuses (360oF – 182oC) and 5 spray nozzles. System has 1 switch that is connected to the FACP.

10. Bldg # 176 Bank

a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 12 smoke detectors on ceiling, 11 heat/smoke detectors above ceiling, 11 led repeaters, 1 heat detector on ceiling, total of 12 devices placed over 3 meters, 3 manual pull stations, 1 switch, and 3 audio/visual warning panels. MONACO BT-X transmitter.

11. Bldg # 17811

a) The Automatic Fire Detection System consists of a conventional FACP, 8 smoke detectors, 5 manual stations and 6 optic/acoustic warning panels. MONACO BT-X transmitter.

12. Bldg # 179

a) The Automatic Fire Detection System consists of a Notifier AFP-400 addressable FACP, 1 remote panel LCD80, 1 additional power supply, 6 smoke detectors, 36 smoke detector above ceiling, 7 duct smoke detectors, total of 36 detectors placed over 4 meters, 36 repeaters, 5 input modules, 5 output modules, 17 manual stations, 4 optical warning devices, and 49 acoustic/optical warning devices. MONACO BT-X transmitter.

b) The Wet Sprinkler System consist of 261 pendant sprinkler heads, 100 upright sprinkler heads, 7 long probe dry pendant sprinkler heads, 1 tampered PIV, 1 tampered main gate valves (6”), 1 automatic sprinkler valve (6”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 inspector test valve, 2 water flow switches connected to the FACP, 1 F.D. truck twin connection, 1 check valve 2½ mod

IVR.

AREA “A-2”

13. Bldg # 263

a) The Automatic Fire Detection System consists of a FireClass J408 conventional FACP to which are connected the Fire

Pump Control Panels and the valve tamper switches (see Section 2). System is equipped with an external warning device. The FACP is connected to the Monaco unit in Bldg# 264.

b) The Fire Pump System consist of 2 fire pumps, 6 control valves supervised with tamper switch, 2 check valves, 4 gauges and 1 flowmeter. The tamper switched and the Fire Pump Control Panel are connected to the FACP.

14. Bldg # 264

a) The Automatic Fire Detection System consists of a NOTIFIER FireStar conventional FACP, 1 smoke detector on ceiling, 7 smoke detectors above ceiling, 7 repeaters, 1 switch, 3 manual stations and 5 bells. MONACO BT-X transmitter.

AREA “C”

15. Bldg # 407

a) The Automatic Fire Detection System consists of a Notifier AM2000N addressable FACP, 1 additional power supply, 24 heat detectors, 81 smoke detectors on ceiling, 64 smoke detectors above ceiling, 1 duct smoke detector, total of

64 detectors placed over 3 meters, total of 20 detectors placed over 6 meters, 64 repeaters, 30 modules, 1 damper, 20 manual stations and 28 optic/acoustic warning devices. MONACO BT-X transmitter.

16. Bldg # 410

a) The Automatic Fire Detection System consists of a Notifier AM1000 addressable FACP, 23 heat detectors, 1 heat detector waterproof, 9 smoke detectors on ceiling, 2 smoke detectors on ceiling, 6 smoke detectors above ceiling, 19 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, total of 13 detectors placed over 4 meters, 6 repeaters, 19 repeaters, 20 manual stations and 18 optic/acoustic warning devices. MONACO BT-X transmitter.

17. Bldg # 411

a) The Automatic Fire Detection System consists of a System consists of a NOTIFIER AM-2020 addressable FACP, 1 heat detector, 2 smoke detectors on ceiling, total 3 detectors placed over 4 meters, 3 output modules, 2 manual stations and 1 bell waterproof. MONACO BT-X transmitter.

b) The Wet Sprinkler System consist of 2 fire pumps, 1 jockey pump, 6 control valves, 2 check valves, 4 gauges and 1 flowmeter. The Fire Pump Control Panels are connected to the MONACO BT-X transmitter.

18. Bldg # 416

a) The Automatic Fire Detection System consists of a NOTIFIER NFS8-2 plus conventional FACP, 8 heat detectors, 4 smoke detectors on ceiling, 5 smoke detectors on ceiling, 3 smoke detectors above ceiling, 11 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 8 manual station and 8 sirens/strobe lights. MONACO BT-X transmitter.

19. Bldg # 421

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 9 heat detectors, 1 heat detector waterproof, 3 smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 2 detectors placed over 4 meters, 3 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.

20. Bldg # 422

a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 2 siren/strobe lights, 1 alarm bell. MONACO BT-X transmitter.

21. Bldg # 424

a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 10 heat detectors, 1 heat detectors waterproof, 8 smoke detectors above ceiling, 2 duct smoke detectors, total of 8 detectors placed over 4 meters, 9 repeaters, 2 air dampers, 1 switch, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.

22. Bldg # 428

a) The Automatic Fire Detection System consists of a Notifier NFS4-2PLUS conventional FACP, 6 smoke detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, 2 repeaters, 2 manual stations and 2 siren/strobe lights. MONACO BT-X transmitter.

23. Bldg # 430-1 (Bay # 1)

a) The Automatic Fire Detection System (Bay # 1) consists of a Notifier AM1000 addressable FACP, 1 auxiliary power supply unit, 24 heat detectors, 1 smoke detector, 2 smoke detectors under floating floor, 1 smoke detector above false ceiling, 14 smoke detectors above false ceiling, 6 manual stations, 6 optic/acoustic warning devices controlled by 6 modules, 1 input module monitoring the auxiliary power supply unit, 1 switch controlled by 1 module. FACP is connected to MONACO BT-X transmitter in Bldg. # 430 fire system mechanical room West side of facility.

24. Bldg # 430

a) The Automatic Fire Detection System (Bay # 2, # 3, # 4, & # 5) consists of a System consists of a THERMOSTICK MAR-

1 conventional FACP, 6 heat detectors, 5 heat detectors waterproof, 19 smoke detectors on ceiling, 18 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 4 detectors placed over 6 meters, 18 repeaters, 10 switches, 15 manual stations and 16 siren/strobe lights. MONACO BT-X transmitter.

b) The Wet Sprinkler System consist of 538 sprinkler heads, 2 lines, 2 automatic alarm valves (CSC 8”, year1997), 2 retardant chambers, 5 pressure gauges, 1 main drain in pump room, 1 twin Fire Dept. connection, 2 water bells, 3 test valves inside bays with flow indicator (side glass), 2 test valve inside. 1 butterfly valve 6” with supervised tamper, PIV without tamper switch, 2 water flow switches, 2 gate valves with tamper switches inside mechanic room, 8 control valves with tamper switches not connected to the FACP on lines inside building and 2 water pressure switches connected to the FACP.

c) The Standpipe System consists of 7 standpipe hoses with nozzles, connected to the wet sprinkler system.

AREA “D”

25. Bldg # 554

a) The Automatic Fire Detection System consists of a BENTEL J424-8 conventional FACP, 16 heat detectors, 1 heat detector waterproof, 4 smoke detectors on ceiling, 11 smoke detectors above ceiling, 1 duct smoke detector, total of 20 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 4 manual stations, 1 manual station waterproof, 5 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO BT-X transmitter.

AREA “E”

26. Bldg # 600

a) The Automatic Fire Detection System consists of a NOTIFIER S-500 conventional FACP, 114 heat detectors, 7 heat detectors waterproof, 16 smoke detectors on ceiling, 109 smoke detectors above ceiling, total of 103 detectors placed over 3 meters, 103 repeaters, 17 manual stations and 25 alarm bells. MONACO BT-X transmitter.

27. Bldg # 604

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 13 heat detectors, 2 heat detectors waterproof, 2 smoke detectors on ceiling, 7 smoke detectors above ceiling, total of 15 detectors placed over 3 meters, 4 manual stations, 1 manual station waterproof, 4 siren/strobe lights, 1 bell and 1 bell waterproof.

MONACO BT-X transmitter.

28. Bldg # 606

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1/A conventional FACP, 24 heat detectors, 8 smoke detectors on ceiling, 19 smoke detectors above ceiling, 1 duct detector, total of 8 detectors placed over 4 meters, 19 repeaters, 1 switch, 10 manual stations, 4 alarm bells, and 3 optic/acoustic warning devices. MONACO BT- X transmitter.

29. Bldg # 620

a) The Automatic Fire Detection System consists of a Bentel J408 conventional FACP, 12 heat detectors, 1 smoke detector on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 1 switch, 5 manual stations and 2 alarm bells. MONACO BT-X transmitter.

30. Bldg # 623

a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000N addressable FACP, 1 auxiliary power supply unit Bentel BXM24U50, 14 heat detectors, 2 smoke detectors on ceiling, 4 smoke detectors above ceiling, 4 repeaters, 1 duct smoke detector, total of 4 detectors placed over 3 meters, 8 manual pull stations, and 8 optic/acoustic warning panels controlled by 8 modules, 1 input module monitoring the auxiliary power supply unit, 1 output module to send the signal to the Fire suppression control panel to actuate the extinguishing sequence. MONACO BT-X transmitter.

31. Bldg # 624

a) The Automatic Fire Detection System consists of a COE CLERICI conventional FACP, 4 heat detectors, 1 smoke detector on ceiling, 2 manual stations and 2 alarm bells. MONACO BT-X transmitter.

32. Bldg # 627

a) The Automatic Fire Detection System consists of a CERBERUS CZ-16 conventional FACP, 14 heat detectors, 7 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 4 alarm bells. MONACO BT-X transmitter.

AREA “F”

33. Bldg # 898

a) The Automatic Fire Detection System consists of a NOTIFIER NFS4-2PLUS conventional FACP, 1 heat detector, 6 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 3 manual stations and 2 optic/acoustic warning panels. MONACO BT-X transmitter.

34. Bldg # 904

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 100 heat detectors, 11 heat detectors waterproof, 1 smoke detector on ceiling, 17 smoke detectors on ceiling in the attic, 50 smoke detectors above ceiling, total of 50 detectors placed over 3 meters, 67 repeaters, 18 manual stations and 19 siren/strobe lights.

MONACO BT-X transmitter.

35. Bldg # 9041

a) The Automatic Fire Detection System consists of a System consists of a THERMOSTICK MAR-1A conventional FACP, 16 heat detectors, 1 smoke detector on ceiling, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.

b) The Dry Chemical Suppression System consist of two 60-liter cylinders (Nitrogen at 200 atm.) each one has a solenoid valve including 1 manual station, one 500 kg of ABCE Polyvalent extinguishing powder, 2 lines (one for each bay) each one has a discharge solenoid valve, total of 8 spray nozzles, 1 switch connected to fire alarm panel. System is activated by automatic fire detection system.

36. Bldg # 9042

a) The Automatic Fire Detection System consists of a NOTIFIER AFP-200 addressable FACP, 20 heat detectors, 2 smoke detectors on ceiling, 11 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 13 detectors placed over 4 meters, 1 output module, 1 input module, 11 repeaters, 4 manual stations, 1 bell and 6 siren/strobe lights. MONACO BT-X transmitter.

37. Bldg # 907

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 40 heat detectors, 3 smoke detectors on ceiling, 23 smoke detectors above ceiling, 4 duct smoke detectors above false ceiling, total of 26 detectors placed over 3 meters, 23 repeaters, 1 switch, 9 manual stations, 10 strobe lights, and 1 alarm bell. MONACO BT-X transmitter.

b) The Standpipe System consists of 2 external standpipe hoses with nozzles.

38. Bldg # 909

a) The Automatic Fire Detection System consists of a NOTIFIER S-5000 conventional FACP, 2 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 1 switch, 3 repeaters, 1 manual station and 2 siren/strobe lights. MONACO BT-X transmitter.

39. Bldg # 9109

a) The Automatic Fire Detection System consists of a NOTIFIER AM6000N addressable FACP, 1 NOTIFIER ALI-25EN auxiliary power supply device, 2 NOTIFIER UDS-3 and 1 NOTIFIER UDS-4 controlling foam suppression systems, 5 heat detectors, 6 heat detectors explosion-proof, 69 smoke detectors, 18 smoke duct detectors, 9 smoke detectors above false ceiling, 9 repeaters, 1 CO detector, 12 flame detectors explosion-proof, total of 6 detectors placed over 3 meters, total of 16 detectors placed over 4 meters, total of 44 detectors placed in the bays’ attics, 13 manual stations, 2 manual stations water-proof, 25 manual stations explosion-proof, 26 input modules monitoring the suppression system components, 2 input module monitoring the auxiliary power supply devices, 8 output modules for releasing devices, 18 output modules controlling the warning devices (3 strobe/siren explosion-proof, 4 sirens water-proof with strobe lights, 6 sirens explosion-proof, 6 strobe lights explosion-proof and 5 strobe/siren). MONACO BT-X transmitter.

b) The Water Based Fire Suppression System consist of:

b.2) Wet sprinkler system with 124 pendant and 88 upright sprinkler heads, 1 GRINNEL check valve (4”) for Fire

Depart. truck connection, 1 TFP AV-1 wet alarm valve (4”), 1 TYCO OS&Y gate valve, 2 TFP AV-1 alarm valves (6”), 1 VICTAULIC FIRELOCK SERIES T05 butterfly valve (3”), 1 VICTAULIC series 751 with European trim (3”), 1 VICTAULIC FIRELOCK SERIES T05 butterfly valve (6”), 1 VICTAULIC series 751 with European trim (6”), 2 TYCO OS&Y gate valves, 3 POTTER OSYSU-1 tamper switches, 3 POTTER VSR-EU flow switches, 5 POTTER PS10-1A pressure switches (not connected to FACP), and 3 water bells (gongs).

b.3) Fire hydrants system consisting of 1 TFP AV-1 alarm valve (6”), 1 TYCO OS&Y gate valve (4”), 1 POTTER OSYSU-1 tamper switch, 1 POTTER VSR-EU flow switch, 1 POTTER PS10-1A pressure switch (not connected to FACP), and 1 water bell (gong).

c) The Heat & Smoke Evacuation System consists of 2 two areas (Painting Bay & Sanding Bay) provided with heat & smoke evacuators. Each system consists of 1 CAODUR MDE01 control panel and 4 heat & smoke evacuators. Total of 2 (two) control panels and 8 (eight) heat and smoke evacuators.

40. Bldg # 914

a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 3 heat detectors with water-protection, 6 heat detectors, 1 smoke detector on ceiling, 4 smoke detectors above ceiling, 1 duct smoke detector, total of 4 detectors placed over 3 meters, 4 repeaters, 4 manual stations and 5 siren/strobe lights. MONACO BT-X transmitter.

b) The Wet Sprinkler System consist of 9 pendant sprinkler heads, 1 side wall sprinkler head, 1 wet line with 1 control valve Ever Metal Industry 2 ½”, 1 automatic sprinkler alarm valve GEM 2 ½" (1994) 175 psi with trim circuit, 1 retarding chamber Mod. F211 175 psi, 2 water pressure gauges, 1 main drain valve 1 ¼”, 1 Fire Dept. Connection with 1 hose gate valve (2”) and 1 check valve (2½”), 1 non-return valve Mueller ¾”, 1 water bell and 1 pressure switch connected to main FACP.

41. Bldg # 916

a) The Automatic Fire Detection System consists of a NOTIFIER SFP-400 conventional FACP, 4 heat detectors waterproof, 1 switch, 4 manual stations, 1 trouble bell and 7 siren/strobe lights. MONACO BT-X transmitter.

42. Bldg # 91601

a) The Automatic Fire Detection System consists of a Notifier AM1000 addressable FACP, 12 input modules monitoring fire pumps supervised valves, 1 optic/acoustic warning device waterproof. MONACO BT-X transmitter.

b) The Fire pump system consists of 3 main electric pumps (Motor FELM 400/690V, 275/159.4A, 50Hz, 1485rpm, 160kW / Impeller GRUPPO ATURIA Spa, Q = 341 m3/h, H = 85.2 mH2O), 2 Jokey pumps GRUNDFOSS (Q = 3.1 m3/h, H = 55.9/73.9 m), 1 FireKing OS&Y valves 8”, 3 SAPAG butterfly valves 8” with tamper switches, 3 check valves VIKING 8” mod. G-1, 3 relief valves 3” OCV mod. 108 FC, 1 test meter GERARD ENG.CO K-2000-8, 1 test header line with 8 hose gate valves 2 ½” and it’s FireKing OS&Y valves 8”, 3 expansion vessels 500L. A.B.C. All 5 pumps have a dedicated electric control panel, pressure control switches, assorted valves, and gauges. Downstream the pumps there are 3 backflow preventers AMES 4000-SS backflow preventing devices 8”, 3 FireKing OS&Y valves 8” with tamper switches, 1 FireKing OS&Y valve 12” with tamper switch on the ground floor. All switches are connected to main FACP.

43. Bldg # 919

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 3 heat detectors, 12 smoke detectors on ceiling, 3 manual stations and 3 siren/strobe lights. MONACO BT-X transmitter.

44. Bldg # 921

a) The Automatic Fire Detection System consists of NOTIFIER AM2000N addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 1 NOTIFIER ALI-25EN auxiliary power supply device, 1 BENTER BXM24U50 power supply device, 56 heat detectors, 1 heat detector explosion-proof monitored by a module, 65 smoke detectors on ceiling in aircrafts servicing area, 18 smoke detectors above false ceiling, 9 duct smoke detectors, 18 repeaters, 3 linear (beam) smoke detectors, total of 27 detectors installed over 3 meters, total of 3 detectors installed over 6 meters, total of 65 detectors installed over 10 meters, 37 monitor modules, 22 output control modules (21 for warning devices, 1 for gas shut off valve, 2 for AHU shut down), 3 relay modules, 28 manual stations (7 for foam discharge), 30 door holders, 23 sirens with strobe lights, 7 optic/acoustic panels. MONACO BT-X transmitter.

b) The Water Based Fire Suppression System main supply line consist of a F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-1, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.

c) The Wet Sprinkler System Back Shops & Offices consists of 139 sprinkler heads, 1 wet system alarm valve Viking Mod.J1 (3”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (3”) with position micro-switch, 1 POTTER VSR-EU flow switch, 1 Potter PS10 pressure switch, 2 ELBI AF-24/16 expansion tanks.

d) The Wet Sprinkler System Bay Area Zone A consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 Potter VSR-EU flow switch, 1 Potter PS10 pressure switch.

e) The Wet Sprinkler System Bay Area Zone B consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 Potter VSR-EU flow switch, 1 Potter PS10 pressure switch.

45. Bldg # 925

a) The Automatic Fire Detection System consists of NOTIFIER AM-2000N addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BENTEL BXM24U50 auxiliary power supply devices, 90 heat detectors, 5 heat detectors explosion-proof, 27 smoke detectors, 5 duct smoke detectors, 27 smoke detectors above ceiling, 27 repeaters, total of 27 detectors installed over 3 meters, 90 detectors installed over 10 meters, 1 shut-off gas solenoid valve, 15 monitor modules, 2 relay modules for the sprinkler system, 3 relay modules controlling warning devices, 35 manual pull stations (9 for foam discharge), 28 sirens with strobe light, 7 optic/acoustic panels, and 2 bells explosion-proof. MONACO BT-X transmitter.

b) The Water Based Fire Suppression System main supply line consists of a F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-1, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.

c) The Wet Sprinkler System Back Shops & Offices consists of 79 upright and 88 pendent sprinkler heads, 1 VIKING J-1 alarm valve (3”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (3”) with position micro-switch, 1 POTTER PS10 pressure switch, 2 ELBI AF-24/16 expansion tanks, and 1 water bell (gong).

d) The Wet Sprinkler System Bay Area Zone A consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 vane type flow switch Potter VSR-EU, 1 Potter PS10 pressure switch.

e) The Wet Sprinkler System Bay Area Zone B consists of 224 upright sprinkler heads, 1 wet system alarm valve Viking mod. J1 (6”) equipped with complete trim circuit, 1 water bell (gong), 1 gauge downstream the alarm valve, 1 butterfly valve (6”) with position micro-switch, 1 vane type flow switch Potter VSR-EU, 1 Potter PS10 pressure switch.

46. Bldg # 933

a) The Automatic Fire Detection System consists of NOTIFIER AM4000 addressable FACP, 1 NOTIFIER UDS-3 fire suppression panel (managing DELUGE suppression systems), 3 BTE auxiliary power supply devices, 92 heat detectors, 66 smoke detectors, 3 duct smoke detectors, 88 smoke detectors above false ceiling, 88 repeaters, total of 89 detectors placed over 3 meters, total of 20 detectors installed over 4 meters, total of 72 detectors placed over 10 meters, 1 module controlling the shut-off gas solenoid valve, 32 modules controlling the water based suppression system, 2 modules controlling the temperature probes, 6 modules controlling the warning devices, 2 modules controlling the auxiliary power supply devices, 51 manual station (10 for foam discharge), 4 acoustic warning devices, 47 optic/acoustic warning devices. MONACO BT-X transmitter.

b) The Wet Sprinkler System in room 119 consists of 29 upright and 135 pendent sprinkler heads, 1 butterfly valve 3” with supervised tamper, a main FIRE KING OS&Y gate valve 3” with supervised tamper switch Potter OSYSU-2, 1 Fivalco YS-G-1251-U strainer 3”, 1 VIKING J-1 alarm valve (3”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 POTTER PS10 pressure switch, 2 vane type flow switches Viking VSR-EU, 1 water bell (gong) and a F.D.

truck connection with check valve.

c) The Water Based Fire Suppression System main supply line in room 212 consists of main supply line F.D. truck connection with check valve, a main FIRE KING OS&Y gate valve 10” with supervised tamper switch Potter OSYSU-2, 1 MUELLER low pressure loss basket strainer 10”, 1 ELBI AF_100/16 expansion tank.

d) The Wet Sprinkler System Back Shop in room 212 consists of 4 upright and 95 pendent sprinkler heads, 1 VIKING J-1 alarm valve (4”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (4”) with position micro-switch, 1 POTTER PS10 pressure switch, 3 vane type flow switches Viking VSR-EU, 2 ELBI AF- 24/16 expansion tanks, and 1 water bell (gong).

e) The Wet Sprinkler System Bay Area Zone A in room 212 consists of 186 upright sprinkler heads, 1 VIKING J-1 wet alarm valve (6”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (6”) with position micro-switch, 1 POTTER PS10-1A pressure switch, and 1 water bell (gong).

f) The Wet Sprinkler System Bay Area Zone B in room 212 consists of 186 upright sprinkler heads, 1 VIKING J-1 wet alarm valve (6”) equipped with complete trim circuit, 1 gauge downstream the alarm valve, 1 VIKING butterfly valve (6”) with position micro-switch, 1 POTTER PS10-1A pressure switch, and 1 water bell (gong).

g) The Wet Sprinkler System Warehouse in New addition consist of 131 pendant sprinkler heads, 1 OS&Y gate valve 6” with tamper switch, 1 wet alarm valve 6” RAPIDROP mod. B equipped with complete trim circuit, 1 Pressure switch, 1 flow switch.

h) The Wet Sprinkler System Office in New addition consist of 174 pendant sprinkler heads, 45 upright sprinkler heads, 1 OS&Y gate valve 4” with tamper switch, 1 wet alarm valve 4” RAPIDROP mod. D equipped with complete trim circuit, 1 Pressure switch, 1 flow switch.

47. Bldg # 936

a) The Automatic Fire Detection System consists of a THERMOSTICK MAR-1 conventional FACP, 11 heat detectors, 3 heat detectors waterproof, 7 smoke detectors above ceiling, 1 duct smoke detector, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 3 alarm bells. MONACO BT-X transmitter.

48. Bldg # 939

a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000N addressable FACP, 2 auxiliary power supply units NOTIFIER ALI50EN, 1 panel repeater NOTIFIER LCD- 6000N, 1 heat detector, 41 smoke detectors on ceiling, 50 smoke detectors above ceiling, 4 duct smoke detector, total of 50 detectors placed over 3 meters, 50 repeaters, 7 input and 7 output modules monitoring and controlling 7 smoke/fire dampers, 5 input modules monitoring the sprinkler system devices, 3 output modules to shutdown utilities, 2 output modules controlling 4 magnetic door holders, 4 input modules monitoring the auxiliary power supply units and the gas leak detection panel, 6 manual stations, 4 sounder bases and 36 optic/acoustic warning devices. MONACO BT-X transmitter.

b) The Wet Sprinkler System consists of 80 sprinkler heads (73 pendent and 7 upright sprinkler heads), 1 PIV with tamper switch, 3 OS&Y gate valves (4”) with tamper switch, 1 backflow preventer (4”), 1 alarm valve with complete trim circuit (drain valve, test valve, retardant chamber, etc.) 1 water gong, 1 check valve on FDC line, 1 pressure switch and 1 flow switch. All switches are connected to main FACP.

49. Bldg # 9393

a) Building under renovation.

50. Bldg # 940

a) The Automatic Fire Detection System consists of a NOTIFIER AM-2000 addressable FACP, 1 auxiliary power supply unit, 66 heat detectors, 2 smoke detector, 39 smoke detectors above ceiling, 39 repeaters, 8 manual stations, 12 acoustic/optic warning devices, 8 input modules, 1 output module, and total of 39 detectors placed over 3 meters.

MONACO BT-X transmitter.

51. Bldg # 940 A

a) The Automatic Fire Detection System consists of a NOTIFIER AM-1000 addressable FACP, 1 auxiliary power supply unit, 27 heat detectors, 17 smoke detectors on ceiling, 2 duct smoke detectors above ceiling, total of 19 detectors placed over 3 meters, 19 repeaters, 1 input module, 4 output modules, 1 isolating module, 3 manual stations, and 3 acoustic/optic warning devices. MONACO BT-X transmitter.

52. Bldg # 94003

a) The Automatic Fire Detection System consists of a NOTIFIER S-5000 conventional FACP, 6 heat detectors, 6 smoke detectors, total of 12 detectors placed over 4 meters, 1 switch, 2 manual stations and 2 siren/strobe lights. MONACO BT-X transmitter.

53. Bldg # 941

a) The Automatic Fire Detection System consists of a Bentel J-424 conventional FACP, 31 heat detectors, 3 heat detectors waterproof, 31 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 33 detectors placed over 3 meters, 31 repeaters, 1 switch, 6 manual stations and 7 alarm bells. MONACO BT-X transmitter.

54. Bldg # 944

a) The Automatic Fire Detection System consists of a BENTEL J-408 conventional FACP, 5 heat detectors, 5 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 3 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 6 repeaters, 1 switch, 2 manual stations and 2 bells. MONACO BT-X transmitter.

55. Bldg # 94504

a) The Automatic Fire Detection System consists of a Notifier AM-2000N addressable FACP, 3 heat detectors, 3 smoke detectors, 10 relay modules, 2 control modules (shutdown ventilation in EG shelter & mezzanine), 1 output module for warning devices, 4 manual pull stations, and 3 optic/acoustic warning devices. MONACO BT-X transmitter.

56. Bldg # 946

a) The Automatic Fire Detection System consists of a Notifier AM-2000N addressable FACP, 1 Notifier ALI-25EN auxiliary power supply device, 20 heat detectors, 9 smoke detectors on ceiling, 25 smoke detectors above ceiling, 4 duct smoke detectors, 1 linear (beam) smoke detector, total of 25 devices placed over 3 meters, total of 1 device placed over 4 meters, 26 led repeaters, 9 output modules controlling the warning devices, 1 input and 2 output modules for beam smoke detector functioning, 4 input modules for sprinkler system, 1 output module for release device, 14 manual pull stations, and 22 siren/strobe lights. MONACO BT-X transceiver.

b) The Water Based Fire Suppression System consists of a main water supply line located outdoor at ground floor with 2 butterfly valves (6”), 1 strainer (6”), 1 drain ball valve (2”), 1 check valve, 1 water pressure gauge, 2 F.D. truck connection valves (2 ½”), 1 Backflow preventer 6” and 1 pressure relief valve (1”).

c) The Fire Pump System, in a room on the roof, consists of 1 WILO water pumping unit mod. GPVA UNI 2-5204 + P 1.85 equipped with 2 main electric and 1 Jokey pump providing Q=60-30 m3/h water flow, 6” line, 2” by-pass, 3 expansion tanks 24-liter capacity each. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.

d) The Wet Sprinkler System consists of 83 pendent sprinkler heads, 1 distribution line, 1 butterfly valve (6”) with tamper, 1 VICTAULIC automatic sprinkler valve (6”) w/trim, 1 retardant chamber, 1 pressure switch, and 1 water bell (gong).

At the distribution lines of the Wet Sprinkler System are connected:

d.1) A Dry Sprinkler System in the basement consisting of 26 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (4”) with complete trim circuit, 1 VICTAULIC butterfly valve (4”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).

d.2) A Dry Sprinkler System at the ground floor consisting of 28 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (4”) with complete trim circuit, 1 VICTAULIC butterfly valve (4”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).

d.3) A Dry Sprinkler System at the ground floor consisting of 11 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (2”½) with complete trim circuit, 1 VICTAULIC butterfly valve (2”½) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).

d.4) A Dry Sprinkler System at the ground floor consisting of 41 pendant sprinkler heads, 1 VICTAULIC Fire Lock NXT automatic valve (6”) with complete trim circuit, 1 VICTAULIC butterfly valve (6”) with tamper switch (not connected to the FACP) and 1 alarm pressure switch (not connected to the FACP).

57. Bldg # 1000

a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 1 auxiliary power supply unit, 12 heat detectors explosion-proof, 4 heat detectors, 1 smoke detector on ceiling, 1 heat & smoke detector, total of 12 detectors placed over 4 meters, 3 output control modules, 17 input modules, 3 manual stations explosion-proof, 2 manual stations, 3 explosion-proof bells, and 2 optic/acoustic warning panels. MONACO BT-X transmitter.

b) The Fire Pump System consists of 1 DAB water pumping unit equipped with 1 diesel pump, 1 electric pump (not energized), 1 Jokey pump, 6” line. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.

c) The Wet sprinkler system with 49 pendant sprinkler heads and 2 inspector test valves, 2 gate valves (6”) w/tamper, 1 strainer, 2 gate valves (6”), 2 check valves (6”), 5 butterfly valves (4”), 1 flow meter (4”), 1 F.D. truck twin connection, 1 check valve (4”), 1 VIKING mod. B-1 pilot operated valve (6”), 1 VIKING mod. J-1 valve (6”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, and 1 water bell (gong).

58. Bldg # 1004

a) The Automatic Fire Detection System consists of a NOTIFIER AM1000 addressable FACP, 1 heat detector, 15 smoke detectors, 11 smoke detectors above ceiling, total of 9 detectors placed over 3 meters, 11 repeaters, 4 output modules controlling the warning devices, 2 spare input modules, 2 relay modules to transmit signals to Monaco unit, 8 manual stations and 5 optic/acoustic warning panels. MONACO BT-X transmitter.

59. Bldg # 1010

a) The Automatic Fire Detection System consists of a NOTIFIER CFP 12-24 conventional FACP, 1 auxiliary power supply unit, 25 smoke detectors, 2 smoke detectors above ceiling, 6 duct smoke detectors above ceiling, 8 repeaters, 25 manual stations, 7 bells, 14 acoustic/optical warning devices, 1 switch stops HVAC equipment, total of 8 detectors placed over 3 meters. MONACO BT-X transmitter.

b) The Wet Sprinkler System consists of three circuits, new West area protected with 92 upright sprinkler heads, existing Central area protected with 47 pendant and 196 upright…