This document contains multiple appendices for tank inventories and inspection checklists for RAF Lakenheath, RAF Feltwell, and RAF Mildenhall military bases. The tank inventories comprehensively list aboveground (AST) and underground (UST) storage tanks, including their locations, construction materials, contents (primarily diesel fuel), building numbers, and tank volumes. The appendices reveal that RAF Lakenheath has 124 ASTs and 2 USTs, RAF Feltwell has 10 ASTs, and RAF Mildenhall has 104 ASTs and 3 USTs.
The document also includes detailed monthly and annual inspection checklists for tank systems, which provide a structured approach to examining tank foundations, shell, piping, equipment, and containment areas. These checklists cover critical aspects such as checking for leaks, verifying equipment functionality, inspecting secondary containment areas, and assessing overall tank integrity. Additionally, the document contains forms for reporting pollution incidents and spill releases, which outline procedures for documenting and responding to potential environmental hazards at these military facilities.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Base Tank Identification Tank
Constru ction
Tank Contents BLDG
AST or
UST
Tank Volume
(GAL)
Monthly Inspection
Annual Inspection / Testing
LAK GENSPT-B1026-AST1 STEEL DIESEL FUEL 1026 AST 1395 NO NO
LAK GENSPT-B1084-AST1 STEEL DIESEL FUEL 1084 AST 950 NO NO
LAK GENSPT-B1085-AST1-
TOWER LIGHTS
STEEL DIESEL FUEL 1085 AST 610 NO NO
LAK GENSPT-B1087-AST2-
COMM
STEEL DIESEL FUEL 1087 AST 792 NO NO
LAK GENSPT-B1200-AST2-
FIRE DEPT
STEEL DIESEL FUEL 1200 AST 925 NO NO
LAK GENSPT-B1212-AST1 STEEL DIESEL FUEL 1212 AST 1479 NO NO
LAK
GENSPT-B1243-AST1-
REMOTE
MONITORING FAC
STEEL DIESEL FUEL 1243 AST 2510 NO NO
LAK GENSPT-B1275-AST2 STEEL DIESEL FUEL 1275 AST 330 NO NO
LAK GENSPT-B1283-AST1 STEEL DIESEL FUEL 1283 AST 396 NO NO
LAK GENSPT-B1302-AST1-
HANGAR 6
STEEL DIESEL FUEL 1304 AST 1479 NO NO
LAK GENSPT-B1381-AST1 STEEL DIESEL FUEL 1381 AST 7397 NO NO
LAK GENSPT-B1387-AST1-
WWTP
STEEL DIESEL FUEL 1387 AST 3566 NO NO
LAK GENSPT-B1464-AST2 STEEL DIESEL FUEL 1464 AST 396 NO NO
LAK HEAT-B1003-AST1 STEEL DIESEL FUEL 1003 AST 11091 NO NO
LAK HEAT-B1009-AST1.2 STEEL DIESEL FUEL 1009 AST 1532 NO NO
LAK HEAT-B1011-AST1 STEEL DIESEL FUEL 1011 AST 3598 NO NO
LAK HEAT-B1017-AST1 STEEL DIESEL FUEL 1017 AST 721 NO NO
LAK HEAT-B1019-AST1 STEEL DIESEL FUEL 1019 AST 720 NO NO
LAK HEAT-B1027-AST2 STEEL DIESEL FUEL 1027 AST 721 NO NO
LAK HEAT-B1032-AST1 STEEL DIESEL FUEL 1032 AST 1070 NO NO
LAK HEAT-B1035-AST1 STEEL DIESEL FUEL 1035 AST 5997 NO NO
LAK HEAT-B1040-AST1 STEEL DIESEL FUEL 1040A AST 20000 NO NO
LAK HEAT-B1040-AST2 STEEL DIESEL FUEL 1040B AST 20000 NO NO
LAK HEAT-B1040-AST3 STEEL DIESEL FUEL 1040C AST 20000 NO NO
LAK HEAT-B1070-AST1 STEEL DIESEL FUEL 1070 AST 204 NO NO
LAK HEAT-B1071-AST1.2 STEEL DIESEL FUEL 1071 AST 2510 NO NO
LAK HEAT-B1081-AST1 STEEL DIESEL FUEL 1081 AST 5548 NO NO
LAK HEAT-B1082-AST1- TEMP STEEL DIESEL FUEL 1082 AST 793 NO NO
LAK HEAT-B1084-UST1 STEEL DIESEL FUEL 1084 UST 951 NO NO
LAK HEAT-B1087-AST1 STEEL DIESEL FUEL 1087 AST 5284 NO NO
LAK HEAT-B1100-AST1 PLASTIC DIESEL FUEL 1100 AST 5092 NO NO
LAK HEAT-B1100-AST2 STEEL DIESEL FUEL 1100 AST 1984 NO NO
LAK HEAT-B1106-AST1 STEEL DIESEL FUEL 1106 AST 1189 NO NO
LAK HEAT-B1108-UST1 STEEL DIESEL FUEL 1108 AST 2646 NO NO
LAK HEAT-B1119-AST1 STEEL DIESEL FUEL 1119 AST 2381 NO NO
LAK HEAT-B1120-AST1 STEEL DIESEL FUEL 1120 AST 926 NO NO
LAK HEAT-B1125-AST1 STEEL DIESEL FUEL 1125 AST 926 NO NO
APPENDIX A-2 RAF LAKENHEATH TANK INVENTORY
LAK HEAT-B1127-AST1 STEEL DIESEL FUEL 1127 AST 714 NO NO
LAK HEAT-B1138-AST1 STEEL DIESEL FUEL 1138 AST 660 NO NO
LAK HEAT-B1145-AST1 STEEL DIESEL FUEL 1145 AST 476 NO NO
LAK HEAT-B1200-AST1 STEEL DIESEL FUEL 1200 AST 1849 NO NO
LAK HEAT-B1210-AST1 STEEL DIESEL FUEL 1210 AST 1189 NO NO
LAK HEAT-B1212-AST2 STEEL DIESEL FUEL 1212 AST 5997 NO NO
LAK HEAT-B1212-AST3 STEEL DIESEL FUEL 1212C AST 5997 NO NO
LAK HEAT-B1215-AST1 STEEL DIESEL FUEL 1215 AST 5020 NO NO
LAK HEAT-B1217-AST1 STEEL DIESEL FUEL 1217 AST 4756 NO NO
LAK HEAT-B1219-AST1 STEEL DIESEL FUEL 1219 AST 20000 NO NO
LAK HEAT-B1219-AST2 STEEL DIESEL FUEL 1219 AST 20000 NO NO
LAK HEAT-B1219-AST3 STEEL DIESEL FUEL 1219 AST 2985 NO NO
LAK HEAT-B1220-AST1 STEEL DIESEL FUEL 1220-1 AST 7926 NO NO
LAK HEAT-B1220-AST2 STEEL DIESEL FUEL 1220-2 AST 7926 NO NO
LAK HEAT-B1223-AST1 STEEL DIESEL FUEL 1223 AST 619 NO NO
LAK HEAT-B1225-AST1 STEEL DIESEL FUEL 1225 AST 5997 NO NO
LAK HEAT-B1227-AST1 STEEL DIESEL FUEL 1227 AST 924 NO NO
LAK HEAT-B1234-AST1 STEEL DIESEL FUEL 1234 AST 872 NO NO
LAK HEAT-B1235-AST1 STEEL DIESEL FUEL 1235 AST 725 NO NO
LAK HEAT-B1273-AST1 STEEL DIESEL FUEL 1273 AST 343 NO NO
LAK HEAT-B1280-AST1 STEEL DIESEL FUEL 1280-1 AST 1585 NO NO
LAK HEAT-B1280-AST2 STEEL DIESEL FUEL 1280-2 AST 3962 NO NO
LAK HEAT-B1286-AST1 STEEL DIESEL FUEL 1286 AST 646 NO NO
LAK HEAT-B1292-AST1 STEEL DIESEL FUEL 1292 AST 1488 NO NO
LAK HEAT-B1304-AST1 STEEL DIESEL FUEL 1304 AST 19549 NO NO
LAK HEAT-B1307-AST1 STEEL DIESEL FUEL 1307 AST 1200 NO NO
LAK HEAT-B1313-AST1 STEEL DIESEL FUEL 1313 AST 396 NO NO
LAK HEAT-B1319-AST1 STEEL DIESEL FUEL 1319 AST 14255 NO NO
LAK HEAT-B1319-AST2 STEEL DIESEL FUEL 1319 AST 14255 NO NO
LAK HEAT-B1319-AST3 STEEL DIESEL FUEL 1319 AST 14255 NO NO
LAK HEAT-B1320-AST1 STEEL DIESEL FUEL 1320 AST 1058 NO NO
LAK HEAT-B1325-AST1 STEEL DIESEL FUEL 1325 AST 924 NO NO
LAK HEAT-B1332-AST1 STEEL DIESEL FUEL 1332 AST 925 NO NO
LAK HEAT-B1339-AST1 STEEL DIESEL FUEL 1339 AST 12490 NO NO
LAK HEAT-B1345-AST1 PLASTIC DIESEL FUEL 1345 AST 1243 NO NO
LAK HEAT-B1346-AST1 STEEL DIESEL FUEL 1346 AST 3611 NO NO
LAK HEAT-B1355-AST1 STEEL DIESEL FUEL 1355 AST 19997 NO NO
LAK HEAT-B1359-AST1 STEEL DIESEL FUEL 1359 AST 6506 NO NO
LAK HEAT-B1362-AST1 STEEL DIESEL FUEL 1362 AST 15714 NO NO
LAK HEAT-B1370-AST1 STEEL DIESEL FUEL 1370 AST 5433 NO NO
LAK HEAT-B1370-AST2 STEEL DIESEL FUEL 1370 AST 5433 NO NO
LAK HEAT-B1379-AST1 STEEL DIESEL FUEL 1379 AST 5357 NO NO
LAK HEAT-B1384-AST1 STEEL DIESEL FUEL 1384 AST 661 NO NO
LAK HEAT-B1389-AST1 STEEL DIESEL FUEL 1389 AST 2114 NO NO
LAK HEAT-B1391-AST1 STEEL DIESEL FUEL 1391 AST 286 NO NO
LAK HEAT-B1392-AST1 STEEL DIESEL FUEL 1392 AST 924 NO NO
LAK HEAT-B1395-AST1 STEEL DIESEL FUEL 1395 AST 6340 NO NO
LAK HEAT-B1473-AST1 STEEL DIESEL FUEL 1473 AST 500 NO NO
LAK HEAT-B1492-AST1 STEEL DIESEL FUEL 1492 AST 725 NO NO
LAK HEAT-B1495-AST1 STEEL DIESEL FUEL 1495 AST 3725 NO NO
LAK HEAT-B1509-AST1 STEEL DIESEL FUEL 1509 AST 1025 NO NO
LAK HEAT-B1511-AST1 STEEL DIESEL FUEL 1511 AST 3078 NO NO
LAK HEAT-B1690-AST1 STEEL DIESEL FUEL 1690 AST 14415 NO NO
LAK HEAT-B1690-AST2 STEEL DIESEL FUEL 1690 AST 14415 NO NO
LAK HEAT-B1690-AST3 STEEL DIESEL FUEL 1690 AST 14415 NO NO
LAK HEAT-B431-AST1 STEEL #2 FUEL OIL 431 AST 924 NO NO
LAK HEAT-B439-AST1 STEEL #2 FUEL OIL 439 AST 1180 NO NO
LAK HEAT-B52-AST1 STEEL #2 FUEL OIL 52A AST 16216 NO NO
LAK HEAT-B52-AST3 STEEL DIESEL FUEL 52C AST 16216 NO NO
LAK HEAT-B650-AST1 STEEL DIESEL FUEL 650 AST 3439 NO NO
LAK HEAT-B651-AST1 STEEL DIESEL FUEL 651 AST 1502 NO NO
LAK HEAT-B657-AST1 STEEL DIESEL FUEL 657 AST 2381 NO NO
LAK HEAT-B670-AST1 STEEL DIESEL FUEL 670 AST 794 NO NO
LAK HEAT-B694-AST1 STEEL DIESEL FUEL 694 AST 3968 NO NO
LAK HEAT-B800-AST1 STEEL DIESEL FUEL 800 AST 10038 NO NO
LAK HEAT-B804-UST1 STEEL DIESEL FUEL 804 AST 919 NO NO
LAK HEAT-B826-AST1 STEEL DIESEL FUEL 826 AST 9590 NO NO
LAK HEAT-B833-AST1 STEEL DIESEL FUEL 833 UST 1206 NO NO
LAK HEAT-B834-AST1 STEEL DIESEL FUEL 834 AST 745 NO NO
LAK HEAT-B844-AST1 STEEL DIESEL FUEL 844 AST 15238 NO NO
LAK HEAT-B880-AST1 STEEL DIESEL FUEL 880 AST 9775 NO NO
LAK HEAT-B904-AST1 STEEL DIESEL FUEL 904A AST 10567 NO NO
LAK HEAT-B904-AST2 STEEL DIESEL FUEL 904B AST 10567 NO NO
LAK HEAT-B906-AST1 STEEL DIESEL FUEL 906 AST 1022 NO NO
LAK HEAT-B917-AST1 STEEL DIESEL FUEL 917A AST 7143 NO NO
LAK HEAT-B917-AST2 STEEL DIESEL FUEL 917B AST 7143 NO NO
LAK HEAT-B917-AST3 STEEL DIESEL FUEL 917C AST 7143 NO NO
LAK HEAT-B931-AST1 STEEL DIESEL FUEL 931A AST 24018 NO NO
LAK HEAT-B931-AST2 STEEL DIESEL FUEL 931B AST 24018 NO NO
LAK HEAT-B931-AST3 STEEL DIESEL FUEL 931C AST 12330 NO NO
LAK HEAT-B934-AST1 STEEL DIESEL FUEL 934 AST 6340 NO NO
LAK HEAT-B946-AST1 STEEL DIESEL FUEL 946 AST 1321 NO NO
LAK HEAT-B950-AST1 STEEL DIESEL FUEL 950 AST 4755 NO NO
LAK HEAT-B961-AST1 STEEL DIESEL FUEL 961 AST 3724 NO NO
LAK HEAT-B979A-AST1 STEEL DIESEL FUEL 979A AST 5231 NO NO
LAK HEAT-B979B-AST2 STEEL DIESEL FUEL 979B AST 5231 NO NO
LAK HEAT-B984-AST1 STEEL DIESEL FUEL 984 AST 530 NO NO
LAK HEAT-B989-AST1 STEEL DIESEL FUEL 989 AST 925 NO NO
LAK HEAT-B1100-AST2 PLASTIC DIESEL FUEL 1100 AST 1984 NO NO
Total AST RAFL = 124 Total UST RAFL = 2
Base Tank Identification Tank
Construct ion
Tank Contents BLDG AST / UST
Tank Volume
(GAL)
Monthly Inspection
Annual Inspection / Testing
FELT HEAT-B176-RAFF-AST1 STEEL DIESEL
FUEL
176 AST 3,170 NO NO
FELT HEAT-B202-AST1 STEEL DIESEL
FUEL
202 AST 27,474 NO NO
FELT HEAT-B202-AST2 STEEL DIESEL
FUEL
202 AST 27,474 NO NO
FELT HEAT-B215-AST1 STEEL DIESEL
FUEL
215A AST 2,500 NO NO
FELT HEAT-B230-RAFF-AST1-
TEMP
PLASTIC DIESEL
FUEL
230 AST 324 NO NO
FELT HEAT-B39-RAFF-AST1 STEEL DIESEL
FUEL
39A AST 18,492 NO NO
FELT HEAT-B39-RAFF-AST2 STEEL DIESEL
FUEL
39B AST 18,492 NO NO
FELT HEAT-B73-RAFF-AST1 STEEL DIESEL
FUEL
73A AST 10,038 NO NO
FELT HEAT-B80-RAFF-AST1 STEEL DIESEL
FUEL
80 AST 1,501 NO NO
FELT HEAT-B94-RAFF-AST1 STEEL DIESEL
FUEL
94 AST 5,000 NO NO
APPENDIX A-2 RAF FELTWELL TANK INVENTORY
Total RAFF AST = 10
APPENDIX A-3 RAF Mildenhall Tank Inventory
Base Above/Below
Ground Tank ID Bldg
Steel / Plastic
Tank Use Capacity (litres)
Mil Underground MI-0163-1-UST 163 Steel Gasoline 51,860
Mil Underground MI-0163-2-UST 163 Steel Gasoline 51,822
Mil Underground MI-0163-3-UST 163 Steel Gasoline 52,617
Mil Aboveground MI-0002-2-AST 2 Steel Generator Tank 750
Mil Aboveground MI-0655-1-AST 655 Steel Generator Tank 800
Mil Aboveground MI-1624-1-AST 1624 Steel Generator Tank 750
Mil Aboveground MI-1668-1-AST 1668 Steel Generator Tank 100
Mil Aboveground MI-1678-1-AST 1678 Steel Generator Tank 750
Mil Aboveground MI-2312-1-AST 2312 Steel Generator Tank 3,600
Mil Aboveground MI-0002-1-AST 2 Steel Heating Oil 2,500
Mil Aboveground MI-0104-1-AST 104 Steel Heating Oil 7,500
Mil Aboveground MI-0105-1-AST 105 Steel Heating Oil 20,000
Mil Aboveground MI-0160-1-AST 160 Steel Heating Oil 20,000
Mil Aboveground MI-0162-1-AST 162 Steel Heating Oil 2,500
Mil Aboveground MI-0163-1-AST 163 Steel Heating Oil 42,000
Mil Aboveground MI-0168-1-AST 168 Steel Heating Oil 2,500
Mil Aboveground MI-0172-1-AST 172 Steel Heating Oil 3,600
Mil Aboveground MI-0220-1-AST 220 Steel Heating Oil 8,000
Mil Aboveground MI-0288-1-AST 288 Steel Heating Oil 2,500
Mil Aboveground MI-0293-1-AST 293 Steel Heating Oil 4,600
Mil Aboveground MI-0431-1-AST 431 Steel Heating Oil 80,000
Mil Aboveground MI-0431-2-AST 431 Steel Heating Oil 80,000
Mil Aboveground MI-0442-1-AST 442 Steel Generator Tank 4.300
Mil Aboveground MI-0491-1-AST 491 Steel Heating Oil 25,000
Mil Aboveground MI-0491-2-AST 491 Steel Heating Oil 25,000
Mil Aboveground MI-0505-1-AST 505 Steel Heating Oil 3,600
Mil Aboveground MI-0528-1-AST 528 Steel Heating Oil 37,800
Mil Aboveground MI-0543-1-AST 543 Steel Heating Oil 3,600
Mil Aboveground MI-0556-1-AST 556 Steel Heating Oil 79,800
Mil Aboveground MI-0556-2-AST 556 Steel Heating Oil 79,800
Mil Aboveground MI-0570-1-AST 570 Steel Heating Oil 2,500
Mil Aboveground MI-0576-1-AST 576 Steel Heating Oil 3,600
Mil Aboveground MI-0589-1-AST 589 Steel Heating Oil 3,600
Mil Aboveground MI-0602-1-AST 602 Steel Heating Oil 14,200
Mil Aboveground MI-0610-1-AST 610 Steel Heating Oil 11,300
Mil Aboveground MI-0611-1-AST 611 Steel Heating Oil 945
Mil Aboveground MI-0613-1-AST 613 Steel Heating Oil 3,600
Mil Aboveground MI-0614-1-AST 614 Steel Heating Oil 2,200
Mil Aboveground MI-0617-1-AST 617 Steel Heating Oil 22,900
Mil Aboveground MI-0617-2-AST 617 Steel Heating Oil 22,900
Mil Aboveground MI-0621-1-AST 621 Steel Heating Oil 1,500
Mil Aboveground MI-0622-1-AST 622 Steel Heating Oil 2,500
Mil Aboveground MI-0631-1-AST 631 Steel Heating Oil 1,100
Mil Aboveground MI-0657-1-AST 657 Steel Heating Oil 28,000
Mil Aboveground MI-0670-1-AST 670 Steel Heating Oil 4,900
Mil Aboveground MI-0675-1-AST 675 Steel Heating Oil 13,200
Mil Aboveground MI-0678-1-AST 678 Steel Heating Oil 20,900
Mil Aboveground MI-0685-1-AST 685 Steel Heating Oil 750
Mil Aboveground MI-0701-1-AST 701 Steel Heating Oil 750
Mil Aboveground MI-0702-1-AST 702 Steel Heating Oil 2,500
Mil Aboveground MI-0705-1-AST 705 Steel Heating Oil 2,500
Mil Aboveground MI-0706-1-AST 706 Steel Heating Oil 1,800
Mil Aboveground MI-0707-1-AST 707 Steel Heating Oil 18,150
Mil Aboveground MI-0713-1-AST 713 Steel Heating Oil 1,800
Mil Aboveground MI-0714-1-AST 714 Steel Heating Oil 3,600
Mil Aboveground MI-0715-3-AST 715 Steel Heating Oil 2,500
Mil Aboveground MI-0715-4-AST 715 Steel Heating Oil 22,600
Mil Aboveground MI-0715-5-AST 715 Steel Heating Oil 22,600
Mil Aboveground MI-0754-1-AST 754 Steel Heating Oil 2,500
Mil Aboveground MI-0755-1-AST 755 Steel Heating Oil 22,600
Mil Aboveground MI-0763-1-AST 763 Steel Heating Oil 1,800
Mil Aboveground MI-0768-1-AST 768 Steel Heating Oil 17,000
Mil Aboveground MI-0768-2-AST 768 Steel Heating Oil 17,000
Mil Aboveground MI-0769-1-AST 769 Steel Heating Oil 18,900
Mil Aboveground MI-0769-2-AST 769 Steel Heating Oil 18,900
Mil Aboveground MI-0771-1-AST 771 Steel Heating Oil 52,900
Mil Aboveground MI-0771-2-AST 771 Steel Heating Oil 52,900
Mil Aboveground MI-0778-1-AST 778 Steel Heating Oil 2,500
Mil Aboveground MI-0782-1-AST 782 Steel Heating Oil 2,500
Mil Aboveground MI-0788-1-AST 788 Steel Heating Oil 5,000
Mil Aboveground MI-0789-1-AST 789 Steel Heating Oil 3,600
Mil Aboveground MI-0790-1-AST 790 Steel Heating Oil 3,600
Mil Aboveground MI-0796-1-AST 796 Steel Heating Oil 2,300
Mil Aboveground MI-0797-4-AST 797 Steel Heating Oil 3,600
Mil Aboveground MI-0798-1-AST 798 Steel Heating Oil 2,500
Mil Aboveground MI-0802-1-AST 802 Steel Heating Oil 12,500
Mil Aboveground MI-0802-2-AST 802 Steel Heating Oil 3,600
Mil Aboveground MI-0803-1-AST 803 Steel Heating Oil 20,000
Mil Aboveground MI-0809-1-AST 809 Steel Heating Oil 26,200
Mil Aboveground MI-0809-2-AST 809 Steel Heating Oil 26,200
Mil Aboveground MI-0812-1-AST 812 Steel Heating Oil 2,500
Mil Aboveground MI-0814-1-AST 814 Steel Heating Oil 29,200
Mil Aboveground MI-0814-2-AST 814 Steel Heating Oil 29,200
Mil Aboveground MI-0816-1-AST 816 Steel Heating Oil 3,900
Mil Aboveground MI-0818-1-AST 818 Steel Heating Oil 3,600
Mil Aboveground MI-0830-1-AST 830 Steel Heating Oil 9,450
Mil Aboveground MI-0840-1-AST 840 Steel Heating Oil 3,800
Mil Aboveground MI-0845-1-AST 845 Steel Heating Oil 8,690
Mil Aboveground MI-0849-1-AST 849 Steel Heating Oil 79,900
Mil Aboveground MI-0849-2-AST 849 Steel Heating Oil 79,900
Mil Aboveground MI-1381-1-AST 1381 Steel Heating Oil 3,780
Mil Aboveground MI-1522-1-AST 1522 Steel Heating Oil 8981
Mil Aboveground MI-1522-2-AST 1522 Steel Heating Oil 8981
Mil Aboveground MI-1541-1-AST 1541 Steel Heating Oil 10,200
Mil Aboveground MI-1546-1-AST 1546 Steel Heating Oil 12,000
Mil Aboveground MI-1546-2-AST 1546 Steel Heating Oil 3,600
Mil Aboveground MI-1566-1-AST 1566 Steel Heating Oil 2,500
Mil Aboveground MI-1616-1-AST 1616 Steel Heating Oil 3,600
Mil Aboveground MI-1626-1-AST 1626 Steel Heating Oil 2,500
Mil Aboveground MI-1635-1-AST 1635 Steel Heating Oil 1,800
Mil Aboveground MI-1637-1-AST 1637 Steel Heating Oil 1,800
Mil Aboveground MI-1791-1-AST 1791 Steel Heating Oil 3,600
Mil Aboveground MI-1792-1-AST 1792 Steel Heating Oil 3,600
Mil Aboveground MI-2275-1-AST 2275 Steel Heating Oil 3,600
Mil Aboveground MI-2631-1-AST 2631 Steel Heating Oil 11,300
Mil Aboveground MI-0240-1-AST 240 Plastic Used Oil 500 Mil Aboveground MI-1578-1-AST 1578 Steel Used Oil 15,000
Mildenhall AST’s = 104 Mildenhall UST’s = 3
Base Above/Below
Ground Tank ID Bldg
Steel / Plastic
Tank Use Capacity (litres)
Mil Aboveground MI-0539-FS1 539 Steel Fire Suppression 400 Mil Aboveground MI-0539-FS2 539 Steel Fire Suppression 400 Mil Aboveground MI-0539-FS3 539 Steel Fire Suppression 400 Mil Aboveground MI-0550-FS1 550 Steel Fire Suppression 400 Mil Aboveground MI-0550-FS2 550 Steel Fire Suppression 400 Mil Aboveground MI-0570-FS1 572 Steel Fire Suppression 400 Mil Aboveground MI-0711-FS1 711 Steel Fire Suppression 400 Mil Aboveground MI-0715-FS1 715 Steel Fire Suppression 1,100 Mil Aboveground MI-0715-FS2 715 Steel Fire Suppression 1,100 Mil Aboveground MI-0769-FS1 769 Steel Fire Suppression 400 Mil Aboveground MI-0772-FS1 772 Steel Fire Suppression 400 Mil Aboveground MI-0772-FS2 772 Steel Fire Suppression 400 Mil Aboveground MI-0772-FS3 772 Steel Fire Suppression 400 Mil Aboveground MI-0775-FS1 775 Steel Fire Suppression 400 Mil Aboveground MI-0775-FS2 775 Steel Fire Suppression 400 Mil Aboveground MI-0803-FS1 803 Steel Fire Suppression 400 Mil Aboveground MI-0803-FS2 803 Steel Fire Suppression 400 Mil Aboveground MI-0814-FS1 814 Steel Fire Suppression 400 Mil Aboveground MI-0814-FS2 814 Steel Fire Suppression 400
APPENDIX B-1 RAF Mildenhall Fire Diesel Tank Inventory
Mildenhall fire suppression diesel tanks = 19
Base Tank ID
APPENDIX C-3 RAF Mildenhall Line Testing Inventory
Test type
Mil MI-0707-1-AST
MI-0769-1-AST
MI-0796-1-AST
MI-0293-1-AST
MI-0220-1-AST
MI-1522-1-AST
MI-1522-2-AST
MI-0715-4-AST
MI-0715-5-AST
MI-0788-1-AST
MI-0809-1-AST
MI-0775-1-AST
MI-0160-1-AST
MI-0617-1-AST
MI-0611-1-AST
MI-0657-1-AST
MI-0631-1-AST
Mil
Mil Mil
Mil Mil
Mil Mil
Mil
Mil
Mil Mil
Mil Mil
Mil
Mil
Mil
Mil
MI-0105-1-AST
primary and secondary supply line
Supply Line Supply Line
Supply Line and return line Supply Line and return line
Supply Line
Supply Line
Supply Line
2x supply lines 2x supply lines primary and secondary supply line
2x primary and secondary supply line
Supply Line
Supply Line
Supply Line
Supply Line
Supply Line
2x Supply Line and return line
UFC 3-460-03
10 November 2017
Change 2, 24 August 2023
TANK INSPECTION CHECKLISTS STI SP001
MONTHLY INSPECTION CHECKLIST
General Inspection Information:
Inspection Date: Prior Inspection Date: Retain Until Date:
Inspector Name (print): Title:
Inspector’s Signature:
Tanks Inspected (ID #’s):
Regulatory facility name and ID number (if applicable)
Inspection Guidance:
This checklist is intended as a model. Locally developed checklists are acceptable as long as they are substantially equivalent (as applicable). Inspections of multiple tanks may be captured on one form as long as the tanks are substantially the same.
For equipment not included in this Standard, follow the manufacturer recommended inspection/testing schedules and procedures.
The periodic AST Inspection is intended for monitoring the external AST condition and its containment structure. This visual inspection does not require a Certified Inspector. It must be performed by an owner’s inspector per paragraph 4.1.2 of the standard.
Upon discovery of water in the primary tank, secondary containment area, interstice, or spill container, remove promptly or take other corrective action. Inspect the liquid for regulated products or other contaminants and dispose of properly.
Non-conforming items important to tank or containment integrity require evaluation by an engineer experienced in AST design, a Certified Inspector, or a tank manufacturer who will determine the corrective action. Note the non-conformance and corresponding corrective action in the comment section.
Retain the completed checklists for at least 36 months.
After severe weather (snow, ice, wind storms) or maintenance (such as painting) that could affect the operation of critical components (normal and emergency vents, valves), an inspection of these components is required as soon as the equipment is safely accessible after the event.
ITEM STATUS COMMENTS/DATE CORRECTED
Tank and Piping
Is tank exterior (roof, shell, heads, bottom, connections, fittings, valves, etc.) free of visible leaks?
Note: If "No", identify tank and describe leak and actions taken.
Change 2, 24 August 2023
ITEM STATUS COMMENTS/DATE CORRECTED
Is the tank liquid level gauge legible and in good working condition?
Is the area around the tank (concrete surfaces, ground, containment, etc.) free of visible signs of leakage?
Is the primary tank free of water or has another preventative measure been taken? NOTE: Refer to paragraph 6.10 and 6.11 of the standard for alternatives for Category 1 tanks. N/A is only appropriate for these alternatives.
For double-wall or double bottom tanks or CE-ASTs, is interstitial monitoring equipment (where applicable) in good working condition?
For double-wall or double bottom tanks or CE-ASTs, is interstice free of liquid? Remove the liquid if it is found.
If tank product is found, investigate possible leak.
Equipment on Tank
If overfill equipment has a "test" button, does it activate the audible horn or light to confirm operation? If battery operated, replace battery if needed.
Is overfill prevention equipment in good working condition? If it is equipped with a mechanical test mechanism, actuate the mechanism to confirm operation.
Is the spill container (spill bucket) empty, free of visible leaks and in good working condition?
Are piping connections to the tank (valves, fittings, pumps, etc.) free of visible leaks? Note: If "No", identify location and describe leak.
Do the ladders/platforms/walkways appear to be secure with no sign of severe corrosion or damage?
Containment (Diking/Impounding)
Is the containment free of excess liquid, debris, cracks, corrosion, erosion, fire hazards and other integrity issues?
Are dike drain valves closed and in good working condition?
Change 2, 24 August 2023
ITEM STATUS COMMENTS/DATE CORRECTED
Are containment egress pathways clear and any gates/doors operable?
Concrete Exterior AST (CE-AST)
Inspect all sides for cracks in concrete. Are there any cracks in the concrete exterior larger than 1/16"?
Inspect concrete exterior body of the tank for cleanliness, need of coating, or rusting where applicable. Tank exterior in acceptable condition?
Visual inspect all tank top openings including nipples, manways, tank top overfill containers, and leak detection tubes. Is the sealant between all tank top openings and concrete intact and in good condition?
Other Conditions
Is the system free of any other conditions that need to be addressed for continued safe operation?
Additional Comments:
Change 2, 24 August 2023
Change 2, 24 August 2023
STI SP001 Annual Inspection Checklist
General Inspection Information:
Inspection Date: Prior Inspection Date: Retain Until Date:
Inspector Name (print): Title:
Inspector’s Signature:
Tanks Inspected (ID #’s):
Regulatory facility name and ID number (if applicable)
Inspection Guidance:
This checklist is intended as a model. Locally developed checklists are acceptable as long as they are substantially equivalent (as applicable).
For equipment not included in this Standard, follow the manufacturer recommended inspection/testing schedules and procedures.
The periodic AST Inspection is intended for monitoring the external AST condition and its containment structure. This visual inspection does not require a Certified Inspector. It must be performed by an owner’s inspector per paragraph 4.1.2 of the standard.
Remove promptly standing water or liquid discovered in the primary tank, secondary containment area, interstice, or spill container. Before discharge to the environment, inspect the liquid for regulated products or other contaminants and disposed of it properly.
In order to comply with EPA SPCC (Spill Prevention, Control and Countermeasure) rules, a facility should regularly test liquid level sensing devices to ensure proper operation (40 CFR 112.8(c)(8)(v)).
Non-conforming items important to tank or containment integrity require evaluation by an engineer experienced in AST design, a Certified Inspector, or a tank manufacturer who will determine the corrective action. Note the non-conformance and corresponding corrective action in the comment section.
Retain the completed checklists for at least 36 months.
Complete this checklist on an annual basis supplemental to the owner monthly-performed inspection checklists.
Note: If a change has occurred to the tank system or containment that may affect the SPCC plan, the condition should be evaluated against the current plan requirement by a Professional Engineer knowledgeable in SPCC development and implementation.
ITEM STATUS COMMENTS/DATE CORRECTED
Tank Foundation/Supports
1 Free of tank settlement or foundation washout? Yes No
2 Concrete pad or ring wall free of cracking and spalling? Yes No N/A
3 Tank supports in satisfactory condition? Yes No N/A
Change 2, 24 August 2023
ITEM STATUS COMMENTS/DATE CORRECTED
Is water able to drain away from tank if tank is resting on a foundation or on the ground?
Yes No N/A
Is the grounding strap between the tank and foundation/supports in good condition?
Yes No N/A
Tank Shell, Heads and Roof
6 Free of visible signs of coating failure? Yes No
Free of noticeable distortions, buckling, denting, or bulging?
Yes No
8 Free of standing water on roof? Yes No N/A
9 Are all labels and tags intact and legible? Yes No
Tank Manways, Piping, and Equipment
Flanged connection bolts tight and fully engaged with no sign of wear or corrosion?
Yes No N/A
Tank Equipment
11 Normal and emergency vents free of obstructions? Yes No
Normal vent on tanks storing gasoline equipped with pressure/vacuum vent?
Yes No N/A
Are flame arrestors free of corrosion and are air passages free of blockage?
Yes No N/A
Is the emergency vent in good working condition and functional, as required by manufacturer? Consult manufacturer's requirements. Verify that components are moving freely (including long-bolt manways).
Yes No N/A
Is interstitial leak detection equipment in good condition? Are windows on sight gauges clear? Are wire connections intact? If equipment has a test function, does it activate to confirm operation?
Yes No N/A
Change 2, 24 August 2023
ITEM STATUS COMMENTS/DATE CORRECTED
Are all valves free of leaks, corrosion and other damage? Follow manufacturers' instructions for regular maintenance of these items. Check the following and verify (as applicable):
Anti-siphon valve Check Valve Gate Valve Pressure regulator valve Expansion relief valve Solenoid valve Fire valve Shear valve
Yes No N/A Yes No N/A Yes No N/A Yes No N/A Yes No N/A Yes No N/A Yes No N/A Yes No N/A
17 Are strainers and filters clean and in good condition? Yes No N/A
Insulated Tanks
Free of missing Insulation?
Insulation free of visible signs of damage?
Insulation adequately protected from water intrusion?
Yes No N/A
19 Insulation free of noticeable areas of moisture? Yes No N/A
20 Insulation free of mold? Yes No N/A
21 Free of visible signs of coating failure? Yes No N/A
Tank/Piping Release Detection
Is inventory control being performed and documented if required?
Yes No N/A
Is release detection being performed and documented if required?
Change 2, 24 August 2023
ITEM STATUS COMMENTS/DATE CORRECTED
Other Equipment
24 Are electrical wiring and boxes in good condition? Yes No N/A
Has the cathodic protection system on the tank been tested as required by the designing engineer?
PIPELINE PRESSURE TEST RECORD
A pressure test is required to confirm the proposed Maximum Allowable Operating Pressure (MAOP) and to discover all potentially hazardous leaks. This must be completed before placing in service or returning to service, any new segment, existing segment that has been replaced or relocated or a service line that has been disconnected for any reason. Records of each test must be made and retained for the life of the facility.
FACILITY NAME:
FACILITY ADDRESS: PHONE:( I
(lncllJde Ci1y)
LOCATION OF TEST SECTION:
LENGTH OF TEST SECTION:
PIPE MATERIAL:
PIPE SIZE:
TEST INFORMATION
TESTED WITH: NITROGEN AIR NATURAL GAS WATER OTHER
TEST DATE: I I TIME STARTED: . TIME ENDED: .
TEST PRESSURE AT START: TEST PRESSURE AT END:
REASON FOR ANY LINE LOSS THAT OCCURRED:
REPAIRS MADE TO CORRECT LEAKAGE
FOUND:
TEST CONDUCTED BY (Company Name):
OPERATOR
REPRESENTATIVE:
Attach sketch of piping layout or make one on reverse side of this form.
Change 2, 24 August 2023
Secondary Containment/Drainage System Integrity Testing UST Facility Person Conducting Test
Facility Name Facility ID# Tester's Name:
Physical Address Testing Company:
City State City State
Testing Requirements
Type of Test association or independent testing
Purpose of Test
Liquid Tight Test Procedure
IF adding water.
\2\ 4a. Fill all containments other than to minimum 1 inch water depth. /2/ and record with 1/16-
Test Data Table Test Date Containment Item ID No.
Test Start Time Test End Time
Comments:
Tester's Signature: ___________________________________ Date:_____________________
Containment Integrity Testing Checklist
Change 2, 24 August 2023
Secondary Containment Drainage System Integrity Testing
General Guidance Who must complete this form?
secondary
What sites must complete this testing?
-17: Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at Underground Storage Tank Facilities
Instructions for Completing the Fill-Port Containment Integrity Form:
UST Facility Information
Person Conducting the Test: Enter the tester's including the city and state from which they operate.
after repairs or replacement of parts connected to secondary containment.
test.
Tester's Signature: The person conducting the test must sign and date the test.
Hazardous Materials Authorization Request/Usage Report
POC Name/Number: PAGE _____of_________
Project/Contract Name: Date: _______________2022
Project or Facility Location/Building Number:
Usage Start Date:
Usage End Date:
***IMPORTANT! ATTACH A COPY OF THE SDS FOR EACH ITEM BELOW***
Item # Manufacturer
Name Product Trade
Name Container
Size Container
Type Quantity
Needed/Used
How Often Will The
Quantity be Used?
For HMMP Use Only
Example
Everbuild – A Sika Company
EVERBUILD®
404 Fungicidal Wash; 1ltr and 5ltr
Plastic Bottle total for entire contract
48 FW HAZMAT SPILL PLAN
CUI Mar 2023
CUI
ANNEX 2 TO 48 FW HAZMAT SPILL PLAN
48 FW HAZMAT Spill Report Form – must be completed for each spill
Instructions for this checklist are as follows: Complete Section 1 and 2 for all spills. Complete Section 3 for AFFF and Section 4 for PFOS/PFOA. Complete Section 5 for advanced information into EASIER.
For items highlighted in yellow, either/both require on scene attendance by CEIE member.
INITIAL INFORMATION
Spill release date/time:
Date/time reported to CEIE:
Unit/Location:
Sub location/parking spot:
Org POC and DSN:
Substance released:
For POL class I, II, III complete sec 2.
For AFFF complete sec 3.
For PFOS/PFOA complete sec 4.
If Spill is over 25 gallons, report to scene
Estimated quantity released:
Specify unit of measurement: US/UK gallons/lbs./Kg
Equipment type/Aircraft tail number:
Was the fire department notified:
If yes, state if they visited the release site (Date/Time)
Yes/No
Cause/description of release:
Spill surface: underline all that apply. Items underlined require on scene response
AIR / CONCRETE / ASPHALT / GRASS / BARE SOIL / SAND / GRAVEL / ROCK /
WATER / WOOD / CARPET / TILE / OTHER _____________________________
Did the release enter waterways:
If yes, explain type/Location
Damage to wildlife/vegetation:
If yes, specify
Yes/No
Human Injuries/deaths:
If yes, Date/time ER called
Yes/No
Is the Spill contained:
If no, explain why
Yes/No
SECTION 2. POL CLASS I, II, III
Class I POL spill is less than 2 feet in any direction and non-continuous (No need to attend scene) OR
Yes/No
Class II POL spill is no more than 10 feet across or 50 square feet and non-continuous. This spill could escalate to a class III if it becomes continuous. OR
Yes/No
Class III POL spill is one that has not been contained, is greater than 10 feet across and continuous in nature.
Yes/No
SECTION 3. AFFF
Did the release involve Aqueous Film Forming Foam (AFFF) Yes/No
Did the release involve AFFF concentrate exceeding 10 gallons? OR Yes/No
Did the release involve AFFF mixed foam exceeding 300 gallons? Yes/No
48 FW HAZMAT SPILL PLAN
CUI Mar 2023
CUI
SECTION 4. PFOS/PFOA
Did the release involve PFOS/PFOA or 1, 4-dioxane? Yes/No
SECTION 5. AFTER INCIDENT INFORMATION
Overall route cause?
Did the spill result in or cause loss of Aircraft/Equipment or Facility? Yes/No
Did the release interrupt flying operations? Yes/No
Did the release extend beyond installation boundaries? Yes/No
Did the release reach a body of water, storm drain or sewer and/or did it extend beyond a hard surface? If yes, please specify.
Yes/No
Did the release cause a film/sheen on the water surface? If yes, please specify.
Yes/No
Did the release involve sewage AND may cause an imminent and substantial threat to public health, safety or the environment? If yes, please state if any of the following were notified: DIO, EA or 48
FW/SEG.
Yes/No
Did the release result in political/host nation involvement? Yes/No
Does the release present a continuing threat to the environment? Yes/No
Do you anticipate the release to result in an Enforcement Action? Yes/No
Did the release cause an estimated financial impact exceeding $50K? Yes/No
Did the release receive or is it expected to receive media attention? Yes/No
Was an OPREP submitted? Yes/No
**Note** - All spills are reported in EASIER
Per AFI 32-7001 the following quantities will be reported to HAF or AFIMSC Det 4/CEIE for POL spills for assessment.
• All quantities of AFFF.
• Ethylene Glycol over 5000 lbs.
• Chlorine over 10lbs
Per FGS – UK, C18.2.8. See API.T1 list of HW-HM for further guidance
• POL or liquid/semi-liquid hazardous substance, over 110 US gallons
• Other solid hazardous material over 225 Kg (500 lbs.)
• Combination of POL and liquid, semi- liquid and solid hazardous substances over 340 Kg (750 lbs.)
Other considerations for reporting
• If the release contaminates a body of water or storm drain
• If the release involves 25 gallons or more of POL AND extends beyond a hard surface
• If the release involves POL and causes a film or sheen on a nearby water surface
RAF MILDENHALL POLLUTION INCIDENT SPILL RELEASE REPORT
DATE: _____________ LOCATION:_________________________________ TIME:___________
SPILL SURFACE(S): CIRCLE ALL THAT APPLY, ALL UNDERLINED ITEMS WILL NEED RESPONSE TO THE
SCENE.
Air Asphalt Bare soil Carpet Concrete Grass Gravel
Rock Sand Tile Water Wood Other: ______________
SPILL SURFACE LOCATION:
SUBSTANCE(S) RELEASED:
SUBSTANCE QUANTITY UNITS
SPILL CLASS:
CLASS I CLASS II
(<2� any direc�on) (>2 to 10� any direc�on)
CLASS III
(>10� any direc�on or continuous in nature)
ENTER WATERWAY? CIRCLE ONE.
YES / NO If yes, explain type: __________________________________________
DAMAGE? CHECK ALL THAT APPLY
WILDLIFE VEGETATION HUMAN INJURY HUMAN DEATH
MEDIA REACTION? CIRCLE ALL THAT APPLY
NEWSPAPER TV RADIO PUBLIC
REACTION
LEGAL
ACTION
OTHER: _________
Inside Outside Both
OPERATION BEING PERFORMED WHEN SPILL OCCURRED: ___________________
PLEASE CONTACT RAF MILDENHALL 100 CES/CEIE ENVIRONMENTAL SPILL PHONE ON +447768 057434
COMPLETED FORMS - SEND TO 100CES.CEIE.1@US.AF.MIL
MORE INFORMATION CAN BE FOUND IN THE 100 ARW HAZARDOUS MATERIALS SPILL PREVENTION
RESPONSE PLAN
RAF MILDENHALL POLLUTION INCIDENT SPILL RELEASE REPORT
EQUIPMENT INVOLVED
AIRCRAFT:_______________ MODEL:_____________ TAIL#____________ REG#_______
GOV/POV VEHICLE TYPE__________________ MODEL_________________ REG#_______
OTHER EQUIPMENT INVOLVED:____________________ MODEL_________ REG#_______
CAUSE OF SPILL: _____________________________________________________
SPILL CLEAN UP MATERIAL USED:
MATERIAL QUANTITY CONTAINER TYPE
ACKNOWLEDGEMENT OF RESPONSIBILITY
I affirm that this informa�on is true and correct to the best of my knowledge. I understand that contaminated absorbent materials are considered a HAZARDOUS WASTE product that must be handled and disposed of properly by the organiza�on/ individual causing the spill released to the environment. Any ques�ons concerning disposal instruc�ons, contact 100 CES/CEIE, DSN 314-238-5836 or 314-238-5828.
***PLEASE PRINT CLEARLY***
ORG/OFF SYMBOL ___________ PHONE _______ NAME/RANK ____________________
DATE: _____________________ SIGNATURE _________________________________________
SENIOR FIRE OFFICIAL (IF REQUIRED):_______________________________________________________
CEIE RESPONDER (IF REQUIRED):__________________________________________________________
BIO RESPONDER (IF REQUIRED):___________________________________________________________
PLEASE CONTACT RAF MILDENHALL 100 CES/CEIE ENVIRONMENTAL SPILL PHONE ON +447768 057434
COMPLETED FORMS - SEND TO 100CES.CEIE.1@US.AF.MIL
MORE INFORMATION CAN BE FOUND IN THE 100 ARW HAZARDOUS MATERIALS SPILL PREVENTION
RESPONSE PLAN
| Appendix A-1 Tank Inventory RAFL 20240405 |
| TANK CONTRACT RAFL |
| Appendix A-2 Tank Inventory RAFF 20240405 |
| TANK CONTRACT RAFF |
| Appendix A-3 Tank inventory RAFM 20250221 |
| Appx B - RAFM |
| Appendix B-1 Fire diesel Inventory RAFM 20250221 |
| Appx B - RAFM |
| Appendix C-1 Line Testing Inventory 20250221 RA |
| Appx B - RAFM |
| Appendix D Monthly Checklist STI 2P001 20250221 |
| Appendix E Annual Checklist STI SP001 20250221 |
| Appendix F Pipeline Pressure Testing Form 20250221 |
| Appendix G_UFC 3-460-30 Containment Integrity Test Checklist |
| Appendix H_HAZMAT Authorization Request - blank |
| Appendix I_48FW Hazmat Spill Report 2023 Template |
| Appendix J 100 ARW Spill Form |
| 20250731_RAFL Tanks Appendix A-1 Reformatted v1.pdf |
| Table 1 |
| 20250731_RAFL Tanks Appendix A-2 Reformatted v1.pdf |
| Table 1 |
| DATE: |
| LOCATION: |
| TIME: |
| Other: |
| SUBSTANCERow1: |
| QUANTITYRow1: |
| UNITSRow1: |
| SUBSTANCERow2: |
| QUANTITYRow2: |
| UNITSRow2: |
| SUBSTANCERow3: |
| QUANTITYRow3: |
| UNITSRow3: |
| OTHER: |
| OPERATION BEING PERFORMED WHEN SPILL OCCURRED 2: |
| Check Box1: Off |
| AIRCRAFT: |
| MODEL: |
| TAIL: |
| REG: |
| GOVPOV VEHICLE TYPE: |
| MODEL_2: |
| REG_2: |
| OTHER EQUIPMENT INVOLVED: |
| MODEL_3: |
| REG_3: |
| CAUSE OF SPILL 2: |
| MATERIALRow1: |
| QUANTITYRow1_2: |
| CONTAINER TYPERow1: |
| MATERIALRow2: |
| QUANTITYRow2_2: |
| CONTAINER TYPERow2: |
| MATERIALRow3: |
| QUANTITYRow3_2: |
| CONTAINER TYPERow3: |
| ORGOFF SYMBOL: |
| PHONE: |
| NAMERANK: |
| DATE_2: |
| SENIOR FIRE OFFICIAL IF REQUIRED: |
| CEIE RESPONDER IF REQUIRED: |
| BIO RESPONDER IF REQUIRED: |
File details come from the government source that posted it. Updated .